Puls UB10.245 Circuit Diagram

U–Series
DC-UPS, DUAL OUTPUT
UB10.245
10. EFFICIENCY AND POWER LOSSES
Efficiency typ. 97.5% Normal mode, 24V 10A, 12V 0A, battery fully charged typ. 96% Normal mode, 24V 7.0A, 12V 5A, battery fully charged Power losses typ. 3.4W Normal mode, no load, battery fully charged typ. 6W Normal mode, 24V 10A, 12V 0A, battery fully charged typ. 10W Normal mode, 24V 12.3A, 12V 5A, battery fully charged typ. 5.5W During battery charging, no load. typ. 19W Buffer mode, 24V 10A, 12V 0A typ. 23W Buffer mode, 24V 7.0A, 12V 5A
11. FUNCTIONAL DIAGRAM
Fig. 11-1 Functional diagram
DC-UPS Control Unit
Input Fuse
24V
Power
Supply
12V Battery
+
-
Input
Battery
+
-
+
-
&
Reverse
Polarity
Protection
Battery
Tester
Cut-off
Relay
*
Battery
Charger
Electronic
Step-up
Converter
Current
Limiter
Step-down
Converter
Controller
+
24V Output
Buffered
Load
-
+
12V Output
Buffered
Load
-
Status LED (green) Diagnosis LED (yellow)
Check Wiring LED (red) Buffer-time Limiter
10s, 30s, 1m, 3m, 10m,
End-of-charge Voltage
(7)
Inhibit +
(8)
Inhibit -
(1) (2)
Ready Contact
*) Return current protection; This feature utilizes a Mosfet instead of a diode in order to minimize the voltage drop and power
losses.
(3) (4)
Buffering Contact
(5) (6)
Replace Battery Contact
May. 2008 / Rev. 1.0 Datasheet DS-UB10.245-EN All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current.
www.pulspower.com Phone +49 89 9278 0 Germany
10/24