Puls SLR02 Data Sheet

When failure is not an option:
Single Redundancy Module
SLR02
• Easy set-up of N+1 redundancies on the DIN-Rail
• Decoupling diodes
• For use with 24...28V power sup­plies up to max. 35A
Data sheet
Short description
When failures might cause cost extensive downtimes, you should design a redundant power supply by using several (N+1) identical power sup­plies. The redundancy module SLR02 is designed to create an N+1 redundancy in combination with the PULS 24...28V power supplies units SL10, SL20 or SL30 or other 24...28V power supplies with an output current of up to 30A (max. 35A). One SLR02 is required for two power supply units. The module decouples the power supply outputs from each other, so that in case of failure one power supply unit cannot overload the other power
supply units. A relay-changeover contact, picked up under normal conditions and dropped in case of failure, indicates the status of each connected power supply unit. A Single Redundancy Module, the SLR01, is available to design a redun­dancy with one attached power supply unit and an output current of up to 40A (max. 50A). For smaller current values of 2.5A, 5A and 10A PULS also offers the SLR2, SLR5 and SLR10 power supplies with integrated re­dundancy modules.
Decoupling part
Voltage
• nominal value
• max. rated
Voltage drop V
V
in
out
Current per input
• nominal value
• max. rated
Output current
• nominal value
• max. rated
Parallel operation for increasing the power is only permissible if the to­tal output current cannot exceed the maximum rated value of 35A (danger of overloading).
Inverse battery protection
Connection
• Connector size range
Note: The GND connector on the module exclusively serves as intrinsic power supply
24 V DC 35 V, short-term 45 V
typ. 0.5 V
20-30 A 35 A
20-30 A 35 A
yes
via stable screw terminals solid: 0.5 - 6 mm
2
flexible: 0.5-4 mm
2
Construction / Mechanics*
Housing dimensions and Weight
•W x H x D
• Free space for ventilation
•Weight
Design advantages:
• All connection blocks are easy to reach as mounted at the front panel
Order information
48 mm x 124 mm x 102 mm (+ DIN Rail) above/below 10 mm recommended left/right 10 mm recommended 625 g
Relay contacts
Relay type
• relay picks up („ok“)
• relay drops out
Upper limit V
• hysteresis
Lower limit V
• guaranteed range
• preset
• hysteresis
Contact load 28 V DC / 1 A or 120 V AC / 0.5 A
Connection
• connector size range
LEDs on the front panel
• for inputs
• for output
Note:
• All relay contacts are potential-free.
• The SLR02 includes two of these relay contacts, each per input.
high
low
Changeover contact, picked-up during normal operation when V when V
30 V ± 5% fix appr. 0.7 V
adjustable
16...27 V 22 V ± 1% appr. 0.7 V
via stable screw terminals solid: 0.5 - 6 mm
green LED, when V green LED, when V
between V
in
< V
in
low
and V
low
or Vin > V
Not OK
OK
Not OK
2
flexible: 0.5-4 mm
between V
in
> appr. 2.5...3.5 V
out
high
high
low
Hysteresis
drops out30.7 V picks up30.0 V
picks up22.0 V drops out21.3 V
and V
2
high
Further information
Test voltage
• relay cont., V
•Vin, V
Ambient temperature range T
Efficiency > 97 %
*For further information see data sheets „The SilverLine“, „SilverLine Family Branches“
out
amb
, V
in
/ housing
500 V AC
out
500 V AC
Operation: -10°C...+70°C Storage: -25°C...+85°C
Order number Description
SLR02 SLZ02
slr02e / 040204 1/2
Single Redundancy Module (Screw mounting set, two needed per unit)
Power wiring SLR02
++––
SL20 or SL30
++––
Side view SLR02
GND +24V
SLR02SL20 or SL30
Vin12Vout GND
Front view SLR02 Bottom view SLR02
Further information, especially about EMC, Connections, Safety, Approvals, Mechanics and Mounting,
see page 2 of „The SilverLine“ data sheet.
Unless otherwise stated, specifications are valid for AC 230V input voltage, +25°C ambient temperature, and 5 min. run-in time. They are subject to change without prior notice.