Puls SLA4.100 Data Sheet

AS-Interface
Power Supply with 4A
SLA4.100
• Input: AC 115V / 230V
• Output: 30.5V / 4A
• AS Interface data decoupling
• For highly demanding industrial applications
• Ground Fault (GF) detector with signal output
Data sheet
Short description
Appr. No. 41801
UL60950 E137006
CUL/CSA-C22.2
No 60950
UL508 LISTED IND. CONT. EQ.
18 WM, 60°C
EMC and
Low Volt.
Directive
Data and energy:
The primary switched mode DIN rail power supply SLA4.100 specifically supplies AS Interface nology allows to connect up to 62 participants to a control and to supply them with energy with a single two-conductor cable. When connecting slaves, the yellow AS-Interface cable offers the high degree of protection IP67 in conjunction with the insulation displacement. The communica­tion signals of the individual network participants are modulated onto the supply voltage. For this purpose, specific power supply units with in­tegrated data decoupling are required for AS-Interface systems.
Fast addressing of slaves:
The "IR addressing mode" selectable via jumper interrupts the data com­munication on the yellow AS-Interface cable. Participants with an infra­red interface can then quickly be assigned a new ID address by means of an infrared programming unit without the need to disconnect them from the AS-Interface cable. Afterwards, the "Communication Mode" can be selected again to restart the data communication.
®
systems with energy. The AS-Interface bus tech-
Input
Rated voltage AC100-120/220-240V
(selectable by front panel slide switch)
Rated current 2.7A (switch in 115V position)
1.3A (switch in 230V position)
Frequency 47...63 Hz (alternatively DC also possible)
Voltage range AC 85...132V/184...264V, DC 240...300V
Harmonic current emissions
Integrated internal fuse
Inrush current limited by NTC resistor
Peak current I
2
t <3.7A2s <4.6A2s<2.5A2s<3.3A2s
I
Hold-up time >30ms @ AC 100V or 196V and rated load
pk
EN 61000-3-2 [PFC], Class A limits are fulfilled
T3A15/250V HBC (not accessible)
T
= +50°C, cold start
amb
(line impedance acc. EN 61000-3-3)
AC 120V AC 132V AC 230V AC 264V <44.7A <49.3A <49.7A <57.5A
(also see diagram)
Worldwide operation:
This compact primary switched-mode built-in power supply can be oper­ated on all usual single-phase line voltages. Its design corresponds to in­ternational standards. The CE-Declaration allows for industrial and office application.
Ground fault detector:
Acc. to EN60204 part 1 and DIN VDE0113 respectively, ground faults in control circuits must neither cause a machine to start inadvertently or to dangereously move nor prevent a controlled shutdown. The internal SLA4 ground fault dectector makes external ground fault detector mod­ules redundant. The AS-Interface network is monitored by the power supply unit via the AS-Interface cable connected to the various partici­pants. Detected ground faults are stored and signalled via front panel LEDs and relay contacts. The ground fault detector may be manually checked using the test/reset button.
Output
Rated voltage DC 30.5V ±3% (not adjustable)
Rated current 4.0A
Isolation Safe low voltage PELV (IEC 60364-4-41)
SELV (IEC 60950)
Current limitation >4.2 A
Overload behaviour Continuous current (also see diagram)
Short-circuit current >4.2A, <6.5A
Load regulation stat. <250mV (no load / full load)
Line regulation stat. <10mV (AC 85...132V/184...264V)
Ripple <50 mV
ohmic load)
Noise (Spikes) <150mV
ohmic load)
Over-voltage protection max. 55V
Operating indictor Green LED (extinguishes at overload)
Output is protected against short-circuit, open circuit and overload.
Use AS-Interface power supplies only together with AS-Interface lines.
(500kHz bandw., 50Ω measurem.,
PP
(20MHz bandw., 50Ω measurem.,
PP
Order information
Order number Description
SLA4.100 SLZ13 SLZ02
sla4e100 / 061020 1/4
AS-Interface power supply unit Adapter for S7-300 rail Wall mounting set (two pcs. per package)
SLA4.100Data sheet
Ground fault detector
The ground fault detector monitors ground faults on the AS-Interface lines and includes a self-test feature. The ground fault feature consists of the LED 'Ground Fault (GF)', a 'Test/Reset' push-button and a relay output. In case of failure, the output voltage will not switch off. For proper functioning, it is essential to connect the shield terminal to PE or machine ground. The AS-Interface network must not contain any other ground fault detectors or insulation monitoring devices.
LED 'Ground Fault (GF)' displays a current or stored ground fault
push-button 'Reset/test'
• push <2s
• push >2s
Ground fault relay
•max. V
•max. I
switch
switch
to start test function to reset stored ground fault
normally closed contact (NC); opens in the event of ground fault AC 25V or DC 60V
0.5A
Operating and environmental data
Non-operating temperature range
Operating temperature range
Derating from 60°C onwards 3W/K power reduction
Cooling natural convection,
Over-temperature protection
Humidity protect from moisture and condensation
Vibration
• Sinus
•Random
Shock 15g (6ms), 10g (11ms), IEC 60068-2-27
Degree of pollution 2 (EN 60950)
Overvoltage category II (IEC 60950; IEC 60664), III (EN 50178)
-25°C...+85°C
-10°C...+70°C (measured at 25mm below the unit)
necessary (see diagram)
no forced air-cooling necessary
not implemented
2 – 17.8Hz ±1.6mm (IEC 60068-2-6)
17.8Hz – 500Hz 2g (IEC 60068-2-6)
2...800Hz 0.5m
2
(s3) (IEC 60068-2-64)
Electromagnetic Compatibility (EMC)
Emissions EN 61000-6-3 (also includes EN 61000-6-4)
Immunity
• Electrostatic Discharge (ESD)
• Electromagnetic radiated fields
• Burst, coupled to: – ACin lines – DCout lines – Signal lines
• Surge transients – Differential
mode (L→PE, NPE)
– Common mode
(L
N)
• Conducted noise immunity
• Voltage dips EN 61000-4-11
•Transient immunity
Efficiency, Reliability
Efficiency typ. 90% (AC 230V, 4A)
Power dissipation typ. 13.5W (AC 230V, 4A)
Class B (EN 55011, EN 55022) EN 61000-3-2 and EN 61000-3-3
EN 61000-6-2 (also includes EN 61000-6-1), EN 61000-4-2, Level 4 (withstands 8 kV direct discharge, 15 kV air discharge)
EN 61000-4-3, Level 3 (10 V/m)
EN 61000-4-4, Level 4 (4 kV) Level 3 (2 kV) Level 3 (1 kV)
EN 61000-4-5, Installation class 4 (4 kV)
Installation class 4 (2 kV)
EN 61000-4-6, Level 3 (10V, 150 kHz-80 MHz)
Transient resistance acc. to VDE 0160 / W2 over entire load range
Schematic
2/4 sla4e100 / 061020
Data sheet
Operating indicators and elements
Plastic slider:
• Mounting: Place the unit onto the DIN-rail and push it downwards and against the lower front edge until it snaps into place.
• Detachment: Push downwards and detach the unit from its DIN-rail mounting bracket.
DIN-rail mouting bracket
Ground fault relay output:
Closed: no ground fault
Open: ground fault
Green LED:
ON: AS-Interface volt-
age is within the limits
OFF: at overload
or missing input voltage
Plug-in jumper:
Pos. 1-2: regular AS-In-
terface communication
Pos. 2-3: Data commu-
nication is interrupted.
IR-addressing can be
carried out
Red LED:
ON: Jumper position 2-3
OFF: Jumper position 1-2
Button:
Push <2s: test function
Push >2s: ground fault is reset
Output terminals:
Dual terminals for AS-Interface + and AS-Interface –
SLA4.100
Plastic slider
Machine ground connection
Connectors and terminals
Terminals Fingertouch-proof terminals with captive
screws for 5.5mm slotted screwdriver or Philips cross-recessed screwdriver No. 2
Position Easy to reach terminals on the front panel;
input and output clearly separate from each other
Tightening torque 0.8Nm
Wire gauge
• flexible cable
• solid cable
Ferrules admissible
Stripping length 7mm
0.5-4mm
0.5-6mm
2
(20-10AWG)
2
(20-10AWG)
Front elements
PE teminal
N Input neutral
L Input phase
GF ok Ground Fault (GF) output (twice); normally
closed contact relay type, signals ground fault
brown
blue
Shield Connection of machine ground
Positive AS-Interface output voltage (twice)
Negative AS-Interface output voltage (twice)
(Functional earth for balancing the AS-Inter­face output. Connection is recommended for EMC)
Red LED:
ON: ground fault or stored
ground fault
OFF: faultless operation
115/230V switch:
Slide switch to select the
input voltage range
Construction / Mechanics
Housing Robust metal housing for built-in installation
Degree of protection IP20 (EN 60529)
Class of protection 1 (IEC 60536);
Width w Height h Depth d
Weight 650g
Installation notes
External fusing • not necessary (internal fuse)
Mounting position vertical; input below, output above
Free space for cooling above / below 25mm recommended
Always connect PE before operating the unit!
Operation without AS-Interface: This AS-Interface PSU has an in­ductive output. When operating without AS-Interface structure (e.g. in a laboratory test) you should connect a 470µF / 35V capacitor between AS-Interface + and AS-Interface – as commercial electronic loads in combination with the data decoupling often tend to oscillate, and the oscillation may exceed the permitted modulation voltage. Otherwise, equipment may be destroyed.
Input terminals
do not use without protective earth (PE)
73 mm 124 mm 102 mm (without DIN rail)
• observe national regulations
• circuit breaker with B-characteristic min. 6A or slower action, or alternatively 6A HBC fuse
left / right 15mm recommended
sla4e100 / 061020 3/4
Functional diagrams
]
Data sheet
SLA4.100
Start behaviour
U
Out
30.6V
115V
65 Vac
switch pos.
81 Vac
118 Vac
switch pos.
160 Vac
Efficiency / Power dissipation
92
90
88
86
84
82
Efficiency [%]
80
78
76
230 V
position
Efficien cy Power los s
00,40,81,21,622,42,83,23,64
Output current Iout [A]
230V
16
14
12
10
8
6
4
2
0
U
In
[W]
loss
Power loss P
Hold-up time
115 V
150
position
130
110
90
70
Hold-up time [ms
50
30
10
70 95 120 145 170 195 220 245 270
typ.
min.
d a
o
l
typ.
%
0
5
min.
d
a
o
l
l
l
u
f
Input voltage V ACin [V]
230 V
position
Output characteristic / Overload behaviour
35
30
25
20
15
10
Output voltage Vout [V]
5
0
01234567
AC 230V min ma x.
Output current Iout [A]
Insulation diagram
Derating
GF
L
N
2.500Vac
ac
00V
0
3.
3
.
0
0
0
V
a
c
c
a
V
0
0
5
5
0
V
a
c
GF
500Vac
AS-i +
AS-i -
50Vac
Shield
Unless otherwise stated, specifications are valid for AC 230V input voltage, +25°C ambient temperature, and 5 min. run-in time. They are subject to change without prior notice.
Your partner in power supply:
I
3A
max
4A
(P
)
max
T
amb
0°C
10°C
20°C
30°C
40°C
50°C
60°C
-10°C
European Power Supply Manufacturers Association
70°C
Bayerns Best 50 Czech 100 Best Europe’s 500
PULS GmbH
Arabellastraße 15
4/4 sla4e100 / 061020
D-81925 München
Tel.: +49 89 9278-0
Fax: +49 89 9278-199