Puls SLA4.100 Data Sheet

AS-Interface
Power Supply with 4A
SLA4.100
• Input: AC 115V / 230V
• Output: 30.5V / 4A
• AS Interface data decoupling
• For highly demanding industrial applications
• Ground Fault (GF) detector with signal output
Data sheet
Short description
Appr. No. 41801
UL60950 E137006
CUL/CSA-C22.2
No 60950
UL508 LISTED IND. CONT. EQ.
18 WM, 60°C
EMC and
Low Volt.
Directive
Data and energy:
The primary switched mode DIN rail power supply SLA4.100 specifically supplies AS Interface nology allows to connect up to 62 participants to a control and to supply them with energy with a single two-conductor cable. When connecting slaves, the yellow AS-Interface cable offers the high degree of protection IP67 in conjunction with the insulation displacement. The communica­tion signals of the individual network participants are modulated onto the supply voltage. For this purpose, specific power supply units with in­tegrated data decoupling are required for AS-Interface systems.
Fast addressing of slaves:
The "IR addressing mode" selectable via jumper interrupts the data com­munication on the yellow AS-Interface cable. Participants with an infra­red interface can then quickly be assigned a new ID address by means of an infrared programming unit without the need to disconnect them from the AS-Interface cable. Afterwards, the "Communication Mode" can be selected again to restart the data communication.
®
systems with energy. The AS-Interface bus tech-
Input
Rated voltage AC100-120/220-240V
(selectable by front panel slide switch)
Rated current 2.7A (switch in 115V position)
1.3A (switch in 230V position)
Frequency 47...63 Hz (alternatively DC also possible)
Voltage range AC 85...132V/184...264V, DC 240...300V
Harmonic current emissions
Integrated internal fuse
Inrush current limited by NTC resistor
Peak current I
2
t <3.7A2s <4.6A2s<2.5A2s<3.3A2s
I
Hold-up time >30ms @ AC 100V or 196V and rated load
pk
EN 61000-3-2 [PFC], Class A limits are fulfilled
T3A15/250V HBC (not accessible)
T
= +50°C, cold start
amb
(line impedance acc. EN 61000-3-3)
AC 120V AC 132V AC 230V AC 264V <44.7A <49.3A <49.7A <57.5A
(also see diagram)
Worldwide operation:
This compact primary switched-mode built-in power supply can be oper­ated on all usual single-phase line voltages. Its design corresponds to in­ternational standards. The CE-Declaration allows for industrial and office application.
Ground fault detector:
Acc. to EN60204 part 1 and DIN VDE0113 respectively, ground faults in control circuits must neither cause a machine to start inadvertently or to dangereously move nor prevent a controlled shutdown. The internal SLA4 ground fault dectector makes external ground fault detector mod­ules redundant. The AS-Interface network is monitored by the power supply unit via the AS-Interface cable connected to the various partici­pants. Detected ground faults are stored and signalled via front panel LEDs and relay contacts. The ground fault detector may be manually checked using the test/reset button.
Output
Rated voltage DC 30.5V ±3% (not adjustable)
Rated current 4.0A
Isolation Safe low voltage PELV (IEC 60364-4-41)
SELV (IEC 60950)
Current limitation >4.2 A
Overload behaviour Continuous current (also see diagram)
Short-circuit current >4.2A, <6.5A
Load regulation stat. <250mV (no load / full load)
Line regulation stat. <10mV (AC 85...132V/184...264V)
Ripple <50 mV
ohmic load)
Noise (Spikes) <150mV
ohmic load)
Over-voltage protection max. 55V
Operating indictor Green LED (extinguishes at overload)
Output is protected against short-circuit, open circuit and overload.
Use AS-Interface power supplies only together with AS-Interface lines.
(500kHz bandw., 50Ω measurem.,
PP
(20MHz bandw., 50Ω measurem.,
PP
Order information
Order number Description
SLA4.100 SLZ13 SLZ02
sla4e100 / 061020 1/4
AS-Interface power supply unit Adapter for S7-300 rail Wall mounting set (two pcs. per package)
SLA4.100Data sheet
Ground fault detector
The ground fault detector monitors ground faults on the AS-Interface lines and includes a self-test feature. The ground fault feature consists of the LED 'Ground Fault (GF)', a 'Test/Reset' push-button and a relay output. In case of failure, the output voltage will not switch off. For proper functioning, it is essential to connect the shield terminal to PE or machine ground. The AS-Interface network must not contain any other ground fault detectors or insulation monitoring devices.
LED 'Ground Fault (GF)' displays a current or stored ground fault
push-button 'Reset/test'
• push <2s
• push >2s
Ground fault relay
•max. V
•max. I
switch
switch
to start test function to reset stored ground fault
normally closed contact (NC); opens in the event of ground fault AC 25V or DC 60V
0.5A
Operating and environmental data
Non-operating temperature range
Operating temperature range
Derating from 60°C onwards 3W/K power reduction
Cooling natural convection,
Over-temperature protection
Humidity protect from moisture and condensation
Vibration
• Sinus
•Random
Shock 15g (6ms), 10g (11ms), IEC 60068-2-27
Degree of pollution 2 (EN 60950)
Overvoltage category II (IEC 60950; IEC 60664), III (EN 50178)
-25°C...+85°C
-10°C...+70°C (measured at 25mm below the unit)
necessary (see diagram)
no forced air-cooling necessary
not implemented
2 – 17.8Hz ±1.6mm (IEC 60068-2-6)
17.8Hz – 500Hz 2g (IEC 60068-2-6)
2...800Hz 0.5m
2
(s3) (IEC 60068-2-64)
Electromagnetic Compatibility (EMC)
Emissions EN 61000-6-3 (also includes EN 61000-6-4)
Immunity
• Electrostatic Discharge (ESD)
• Electromagnetic radiated fields
• Burst, coupled to: – ACin lines – DCout lines – Signal lines
• Surge transients – Differential
mode (L→PE, NPE)
– Common mode
(L
N)
• Conducted noise immunity
• Voltage dips EN 61000-4-11
•Transient immunity
Efficiency, Reliability
Efficiency typ. 90% (AC 230V, 4A)
Power dissipation typ. 13.5W (AC 230V, 4A)
Class B (EN 55011, EN 55022) EN 61000-3-2 and EN 61000-3-3
EN 61000-6-2 (also includes EN 61000-6-1), EN 61000-4-2, Level 4 (withstands 8 kV direct discharge, 15 kV air discharge)
EN 61000-4-3, Level 3 (10 V/m)
EN 61000-4-4, Level 4 (4 kV) Level 3 (2 kV) Level 3 (1 kV)
EN 61000-4-5, Installation class 4 (4 kV)
Installation class 4 (2 kV)
EN 61000-4-6, Level 3 (10V, 150 kHz-80 MHz)
Transient resistance acc. to VDE 0160 / W2 over entire load range
Schematic
2/4 sla4e100 / 061020