AS-Interface
Power Supply with 4A
SLA4.100
• Input: AC 115V / 230V
• Output: 30.5V / 4A
• AS Interface data decoupling
• Infrared (IR) addressing mode
• For highly demanding industrial
applications
• Ground Fault (GF) detector with
signal output
Data sheet
Short description
Appr. No. 41801
UL60950 E137006
CUL/CSA-C22.2
No 60950
UL508 LISTED
IND. CONT. EQ.
18 WM, 60°C
EMC and
Low Volt.
Directive
Data and energy:
The primary switched mode DIN rail power supply SLA4.100 specifically
supplies AS Interface
nology allows to connect up to 62 participants to a control and to supply
them with energy with a single two-conductor cable. When connecting
slaves, the yellow AS-Interface cable offers the high degree of protection
IP67 in conjunction with the insulation displacement. The communication signals of the individual network participants are modulated onto
the supply voltage. For this purpose, specific power supply units with integrated data decoupling are required for AS-Interface systems.
Fast addressing of slaves:
The "IR addressing mode" selectable via jumper interrupts the data communication on the yellow AS-Interface cable. Participants with an infrared interface can then quickly be assigned a new ID address by means of
an infrared programming unit without the need to disconnect them
from the AS-Interface cable. Afterwards, the "Communication Mode"
can be selected again to restart the data communication.
®
systems with energy. The AS-Interface bus tech-
Input
Rated voltage AC100-120/220-240V
(selectable by front panel slide switch)
Rated current 2.7A (switch in 115V position)
1.3A (switch in 230V position)
Frequency 47...63 Hz (alternatively DC also possible)
Voltage range AC 85...132V/184...264V, DC 240...300V
Harmonic current
emissions
Integrated internal
fuse
Inrush current limited by NTC resistor
Peak current I
2
t <3.7A2s <4.6A2s<2.5A2s<3.3A2s
I
Hold-up time >30ms @ AC 100V or 196V and rated load
pk
EN 61000-3-2 [PFC], Class A limits are fulfilled
T3A15/250V HBC (not accessible)
T
= +50°C, cold start
amb
(line impedance acc. EN 61000-3-3)
AC 120V AC 132V AC 230V AC 264V
<44.7A <49.3A <49.7A <57.5A
(also see diagram)
Worldwide operation:
This compact primary switched-mode built-in power supply can be operated on all usual single-phase line voltages. Its design corresponds to international standards. The CE-Declaration allows for industrial and office
application.
Ground fault detector:
Acc. to EN60204 part 1 and DIN VDE0113 respectively, ground faults in
control circuits must neither cause a machine to start inadvertently or to
dangereously move nor prevent a controlled shutdown. The internal
SLA4 ground fault dectector makes external ground fault detector modules redundant. The AS-Interface network is monitored by the power
supply unit via the AS-Interface cable connected to the various participants. Detected ground faults are stored and signalled via front panel
LEDs and relay contacts. The ground fault detector may be manually
checked using the test/reset button.
Output
Rated voltage DC 30.5V ±3% (not adjustable)
Rated current 4.0A
Isolation Safe low voltage PELV (IEC 60364-4-41)
SELV (IEC 60950)
Current limitation >4.2 A
Overload behaviour Continuous current (also see diagram)
Short-circuit current >4.2A, <6.5A
Load regulation stat. <250mV (no load / full load)
Line regulation stat. <10mV (AC 85...132V/184...264V)
Ripple <50 mV
ohmic load)
Noise (Spikes) <150mV
ohmic load)
Over-voltage protection max. 55V
Operating indictor Green LED (extinguishes at overload)
Output is protected against short-circuit, open circuit and overload.
Use AS-Interface power supplies only together with AS-Interface lines.
(500kHz bandw., 50Ω measurem.,
PP
(20MHz bandw., 50Ω measurem.,
PP
Order information
Order number Description
SLA4.100
SLZ13
SLZ02
sla4e100 / 061020 1/4
AS-Interface power supply unit
Adapter for S7-300 rail
Wall mounting set (two pcs. per package)
SLA4.100Data sheet
Ground fault detector
The ground fault detector monitors ground faults on the AS-Interface
lines and includes a self-test feature. The ground fault feature consists
of the LED 'Ground Fault (GF)', a 'Test/Reset' push-button and a relay
output. In case of failure, the output voltage will not switch off. For
proper functioning, it is essential to connect the shield terminal to PE
or machine ground. The AS-Interface network must not contain any
other ground fault detectors or insulation monitoring devices.
LED 'Ground Fault (GF)' displays a current or stored ground fault
push-button 'Reset/test'
• push <2s
• push >2s
Ground fault relay
•max. V
•max. I
switch
switch
to start test function
to reset stored ground fault
normally closed contact (NC); opens in the
event of ground fault
AC 25V or DC 60V
0.5A
Operating and environmental data
Non-operating
temperature range
Operating
temperature range
Derating from 60°C onwards 3W/K power reduction
Cooling natural convection,
Over-temperature
protection
Humidity protect from moisture and condensation
Vibration
• Sinus
•Random
Shock 15g (6ms), 10g (11ms), IEC 60068-2-27
Degree of pollution 2 (EN 60950)
Overvoltage category II (IEC 60950; IEC 60664), III (EN 50178)
-25°C...+85°C
-10°C...+70°C
(measured at 25mm below the unit)
necessary (see diagram)
no forced air-cooling necessary
not implemented
2 – 17.8Hz ±1.6mm (IEC 60068-2-6)
17.8Hz – 500Hz 2g (IEC 60068-2-6)
2...800Hz 0.5m
2
(s3) (IEC 60068-2-64)
Electromagnetic Compatibility (EMC)
Emissions EN 61000-6-3 (also includes EN 61000-6-4)
Immunity
• Electrostatic
Discharge (ESD)
• Electromagnetic
radiated fields
• Burst, coupled to:
– ACin lines
– DCout lines
– Signal lines
• Surge transients
– Differential
mode (L→PE,
N→PE)
– Common mode
(L
→ N)
• Conducted noise
immunity
• Voltage dips EN 61000-4-11
•Transient
immunity
Efficiency, Reliability
Efficiency typ. 90% (AC 230V, 4A)
Power dissipation typ. 13.5W (AC 230V, 4A)
Class B (EN 55011, EN 55022)
EN 61000-3-2 and EN 61000-3-3
EN 61000-6-2 (also includes EN 61000-6-1),
EN 61000-4-2, Level 4
(withstands 8 kV direct discharge,
15 kV air discharge)
EN 61000-4-3, Level 3 (10 V/m)
EN 61000-4-4,
Level 4 (4 kV)
Level 3 (2 kV)
Level 3 (1 kV)
EN 61000-4-5,
Installation class 4 (4 kV)
Installation class 4 (2 kV)
EN 61000-4-6,
Level 3 (10V, 150 kHz-80 MHz)
Transient resistance acc. to VDE 0160 / W2
over entire load range
Schematic
2/4 sla4e100 / 061020