AS-Interface
Power Supply with 2.8A
SLA3.100
• Input: AC 115V / 230V
• Output: 30.55V / 2.8A
• AS Interface data decoupling
• Infrared (IR) addressing mode
• For highly demanding industrial
applications
• NEC Class 2 Power Supply
Data sheet
Short description
Appr. No. 34301
EMC and
Low Volt.
Directive
UL508 LISTED
IND. CONT. EQ.
18 WM, 60°C
CB
scheme
IEC60950
Data and energy:
The primary switched mode DIN rail power supply SLA3.100 specifically
supplies AS Interface
logy allows to connect up to 62 participants to a control and to supply
them with energy with a single two-conductor cable. When connecting
slaves, the yellow AS-Interface cable offers the high degree of protection
IP67 in conjunction with the insulation displacement. The communication signals of the individual network participants are modulated onto
the supply voltage. For this purpose, specific power supply units with integrated data decoupling are required for AS-Interface systems.
Fast addressing of slaves:
The "IR addressing mode" selectable via jumper interrupts the data com-
®
systems with energy. The AS-Interface bus techno-
Input
Rated voltage AC100-120/220-240V
(selectable by front panel slide switch)
Rated current 2.0A (switch in 115V position)
0.9A (switch in 230V position)
Frequency 47...63 Hz (alternatively DC also possible)
Voltage range AC 85...132V/184...264V, DC 230...375V
Power factor >0.5
Harmonic current
emissions
Integrated internal
fuse
Inrush current
Peak current I
I2t
Hold-up time >26 ms @ AC 100V or 196V and rated load
pk
EN 61000-3-2 [PFC], Class A limits are fulfilled
T2A5 / 250V HBC (not accessible)
limited by NTC resistor
T
= +50°C, cold start (line impedance
amb
acc. EN 61000-3-3)
20A (AC 132V) / 38A (AC 264V)
2
1.5 A
s (AC 132V) / 1.8 A2s (AC 264V)
(also see diagram)
munication on the yellow AS-Interface cable. Participants with an infrared interface can then quickly be assigned a new ID address by means of
an infrared programming unit without the need to disconnect them
from the AS-Interface cable. Afterwards, the "Communication Mode"
can be selected again to re-start the data communication.
Fit for the world market:
The input voltage range of the unit can be selected on the front panel.
Thus, it can be operated worldwide on all usual single-phase line voltages. International (IEC 60950) and various national (CBscheme) approvals
allow for worldwide application.
Output
Rated voltage DC 30.55V ±3% (not adjustable)
Rated current 2.8A
Isolation Safe low voltage PELV (IEC364-4-41)
Current limitation >3.2 A
Overload behaviour Continuous current (also see diagram)
Short-circuit current min. 3.2A, max. 4.6A
Load regulation stat. <200mV (no load / full load)
Line regulation stat. <10mV (AC 85...132V/184...264V)
Ripple <50 mV
ohmic load)
Noise (Spikes) <100mV
ohmic load)
Over-voltage protection max. 55V
Operating indictor Green LED (extinguishes at overload)
Output is protected against short-circuit, open circuit and overload.
Use AS-Interface power supplies only together with AS-Interface lines.
(500kHz bandw., 50Ω measurem.,
PP
(20MHz bandw., 50Ω measurem.,
PP
SELV (IEC60950)
Order information
Order number Description
SLA3.100
SLZ11
SLZ02
sla3e100 / 040511 1/4
AS-Interface power supply unit
Adapter for S7-300 rail
Wall mounting set (two pcs. per package)

SLA3.100Data sheet
Efficiency, Reliability
Efficiency typ. 90.5% (AC 230V, 2.8A)
Power dissipation typ. 9.1W (AC 230V, 2.8A)
Operating and environmental data
Non-operating
temperature range
Operating
temperature range
Derating from 60°C 2W/K onwards, power reduction
Cooling natural convection,
Over-temperature
protection
Humidity protect from moisture and condensation
Vibration
• Sinus
•Random
Shock 15g (6ms), 10g (11ms), IEC 68-2-27
Degree of pollution 2 (EN 60950)
Overvoltage category II (IEC 60950)
-25°C...+85°C
-10°C...+70°C
(measured at 25mm below the unit)
necessary
no forced air-cooling necessary
not implemented
2 – 17.8Hz ±1.6mm (IEC 68-2-6)
17.8Hz – 500Hz 2g (IEC 68-2-6)
2...800Hz 0.5m
III (EN 50178)
2
(s3) (IEC 68-2-64)
Electromagnetic Compatibility (EMC)
Emissions EN 61000-6-3 (also includes EN 61000-6-4)
Immunity
• Electrostatic
Discharge (ESD)
• Electromagnetic
radiated fields
• Burst, coupled to:
– ACin lines
– DCout lines
• Surge transients
– Differential
mode (L→PE)
– Common mode
(L
→ N)
• Conducted noise
immunity
• Voltage dips EN 61000-4-11
•Transient
immunity
Class B (EN 55011, EN 55022)
EN 61000-3-2 and EN 61000-3-3
EN 61000-6-2 (also includes EN 61000-6-1),
EN 61000-4-2, Level 4
(withstands 8 kV direct discharge,
15 kV air discharge)
EN 61000-4-3, Level 3 (10 V/m)
ENV 50204 (10 V/m)
EN 61000-4-4,
Level 4 (4 kV)
Level 3 (2 kV)
EN 61000-4-5,
Installation class 4 (4 kV)
Installation class 4 (2 kV)
EN 61000-4-6,
Level 3 (10V, 150 kHz-80 MHz)
Transient resistance acc. to VDE 0160 / W2
over entire load range
Schematic
L
N
V
Transient-
Inrush- and
EMC- Filter
Input Rectifier
and Hold-up
Capacitor
DC
DC
DC to DC
Converter
AS-i
AS-Interface
Decoupling
Network
Infrared (IR)
Addressing
Mode
Mode Selector:
Communication/
IR Addressing
AS-i +
AS-i +
Shield
AS-i -
AS-i -
IR on
AS-i ok
2/4 sla3e100 / 040511