Puls SL5.300 Data Sheet

3-phase 5 A
SL5.300
EMV und
Nied.-Spg.
Richtlinie
• Input: 3 AC 400–500 V
• Output: 24...28V / 120 W
UL60950 E137006
CUL/CSA-C22.2
No. 60950
• Power boost up to 144 W
• High overload current, no switch-off
UL508 LISTED IND. CONT. EQ.
18 WM, 60°C
• Robust mechanics and EMC
CB
scheme
Data sheet
Input
Input voltage 3 AC 400–500 V, ± 15 %
47-63 Hz, suitable for IT power systems
Rated tolerances
• Continuous operat.
• Short term (1 min.)
Even if one phase fails, the unit’s operation with nominal current can be continued (limitations: EN 61000-3-2 (harmonic current emissions) is then not fulfilled, the unit has noise suppression level A instead of level B and the hold-up time is shorter). Continued operat. with two phases is also permissible; however, it reduces the unit’s reliability and lifetime.
Input current 3 x 0.5 A
Inrush current typ. <25A at 575 V AC and cold-start
To be fused with a 3 x 10A, B-type 'circuit-breaker' switch based on the usual thermomagnetic overload sensing principle (used anyway to fuse the input lines; unit has no internal fuses).
Harmonic current emissions (PFC)
Hold-up time >16 ms (3 phase op. at 400 VAC, 24 V / 5 A)
(at 24V/5A)
340...576 V AC resp. 450...820 V DC
300...620 V AC resp. 420...890 V DC
acc. to EN 61000-3-2
>10 ms (2 phase op. at 400 VAC, 24 V / 5 A)
Efficiency, Reliability etc.*
Efficiency typ. 89% (3 AC 400V, 24 V / 5 A)
Losses typ. 15 W (3 AC 400V, 24 V / 5 A)
MTBF 410.000 h acc. to Siemensnorm 29500
(24 V/5 A, 3 AC 400V, T
Life cycle (electrolytics) The unit exclusively uses longlife electrolytics,
specified for +105°C (cf. ’The SilverLine’, p.2).
* For further information see data sheets „The SilverLine“, „SilverLine Family
Branches“ and mechanics data sheet (mechanical design equals that of the SL20.100).
= 40 °C)
U
Start / Overload Behaviour
Startup delay typ. 0.1 s
Rise time ca. 5-20 ms, depending on load
Overload Behaviour
• Special PULS Over­load Design (see diagram overleaf)
• 20% power boost
Advantages:
• High short-circuit current, giving large ’start-up window’: unit starts reliably even with awkward loads such as DC-DC converters.
• Secondary fuses operate more reliably
sl5e300 / 050318 1/2
no disconnection, no hiccup if overloaded high overload current (up to typ. 2⋅ I is reduced with increasing current. 6 A short-term continuous
, at 45°C or forced cooling even
Nom
), Vout
Output
Output voltage 24...28 V DC, adjustable by (covered) front
panel potentiometer, preset: 24.5 V ± 0.5% Adjusting range guaranteed
Output noise suppression
Ambient temperature range T
amb
Rated continuous loading with con­vection cooling Output is protected against short-circuit, open circuit and over­load
Derating Voltage regulation Ripple / Noise
Overvolt. protection typ. 33 V
Serial connection Parallel operation Power back immunity
Front panel indicator green LED off, at V
EN 61000-6-3 (class B) is fulfilled even when using long, unscreened output cabels
Operation: -10°C...+70°C (>60°C: Derating) Storage: -25°C...+85°C
Input T 3-phase -10°C...+60°C 5 A 4,3 A
2-phase -10...+60 5 A 4,3 A DC in -10...+60 5 A 4,3 A
* * short-term (< 1 min) or with forced air-cooling
typ. 6W/K (at T better than 2% Vout overall < 25 mV
not allowed yes; current sharing available on request 34 V; inapplicable for inductive loads
amb
-10°C...+45°C 6 A* 5,1 A*
-10°C...+45°C 6 A* 5,1 A*
also at 60°C admissible
, (20 MHz bandw., 50 Ω measurem.)
PP
I
out
=+60°C...+70°C)
amb
<20V
out
@ 24V I
Construction / Mechanics
Housing dimensions and Weight
•W x H x D
• Free space for ventilation
•Weight
Design advantages:
• All connection blocks are easy to reach as mounted at the front pan­el.
• Input and output are strictly apart from each other and so cannot be mixed up (Input below, output above).
* For further information see data sheets "the SilverLine", "SilverLine Family
Branches" and mechanics data sheet
Order information
Order number Description
SL5.300 SLZ01
73 mm x 124 mm x 117 mm (+ DIN rail) above/below 50 mm recommended left/right 15 mm recommended 730 g
Screw mounting set, two needed per unit
IEC60950
out
@ 28V
Data sheet
Hold-up time, 3-phase
(min., at V
out
=24V)
50
3-phase
40
30
20
Hold-up time [ms]
10
0
320 360 400 440 480 520 560
Input voltage [VACin] 3-phase
Hold-up time, 2-phase
(min., at V
out
=24V)
50
2-phase
40
Iout = 2A Iout = 3A Iout = 4A Iout = 5A
Output characteristic (min.)
32
T
= 60°C / 45°C / 25°C / 0°C
28
amb
Vout range
24
20
Vin = 3 AC 400V
16
12
8
Output Voltage Vout [V]
4
0
0 2 4 6 8 10 12 14
Output Current Iout [A]
Efficiency (typ.,
at V
out
=24V
)
90
88
86
30
20
Hold-upt time [ms]
10
Iout = 2A Iout = 3A Iout = 4A Iout = 5A
84
82
Efficiency [%]
80
3 x 400 VACin 3 x 500 VACin
78
0
320 360 400 440 480 520 560
Input voltage [VACin] 2-phase
For further information, especially about
•EMC
• Connections
• Safety, Approvals
• Mechanics und Mounting, see page 2 of the „The SilverLine“ data sheet. For detailed dimensions see SilverLine mechanics data sheet SL2.5/ SL5/ SL10
Specifications valid for 3AC 400V input voltage, +25°C ambient temperature, and 5 min run-in time, unless otherwise stated. They are subject to change without prior notice.
Your partner in power supply:
76
123456
Output current Iout [A]
European Power Supply Manufacturers Association
Bayerns Best 50 Czech 100 Best EuropeÕs 500
PULS GmbH
Arabellastraße 15
D-81925 München
Tel.: +49 89 9278-0
Fax: +49 89 9278-199
www.puls-power.com
2/2 sl5e300 / 050318