More Power: 30 A
SL30.300
• Input: 3 AC 400...500V
• Output: 24...28V / 720W
• 92.5% efficiency
• Ideal for parallel operation
• Simple fusing
Data sheet
Input
Input voltage 3 AC 400...500 V, ± 15 %
47-63 Hz,
Suitable for IT power systems
Rated Tolerances
• Continuous
operation
• Short term (1 min)
at 24 V/30 A
Input current 3 x 2.0 A
Inrush current < 17 A bei 576 V AC
Inrush current limiting done with a fixed 47R resistor (not a thermistor)
which is bridged after the unit is running, so losses are minimised. That
means no reset time even at a warm-start.
Fuse loading < 2 A
To be fused with a 3 x 10A, B-type 'circuit-breaker' switch based on the
usual thermomagnetic overload sensing principle (used anyway to fuse
the input lines; unit has no internal fuses).
Harmonic current
emissions (PFC)
Transient
handling
Hold up time > 10 ms
340-576 V AC resp.
450-820 V DC
300-620 V AC resp.
420-890 V DC
2
s
acc. EN 61000-3-2
Active transient filter incorporated, so transient resistance acc.to VDE 0160 / W2 (1560 V /
1.3 ms), for all load conditions.
at 400 V AC, 24 V / 30 A
EMC and
Low Volt.
Directive
UL60950 E137006
CUL/CSA-C22.2
No. 60950
UL508 LISTED
IND. CONT. EQ.
18 WM, 60°C
CB
scheme
IEC60950
Output
Output voltage 24...28 V DC, adjustable by (covered) front
panel potentiometer. Adj. range guaranteed
Output noise
suppression
Ambient temperature
range T
amb
Rated continuous loading with convection cooling
at T
=0°C - 60°C 24 V / 30 A (720 W) resp. 28 V / 26 A (728 W)
amb
Derating typ. 18 W/K (at T
Voltage regulation better than 2% over all
Ripple
• Output charact. S
• Output charact. P
(S/P Single/Parallel Mode)
Over-voltage protectionAt 32 V ± 10%: switch to hiccup mode
Front panel indicators: • Green LED on, when V
Parallel operation Yes, up to ten SL30 units
To achieve current sharing the output V/I characteristic can be altered
to be 'softer' (25V at 0.4A, 24V at 30A). This is done by repositioning a
bridge connection (without opening the unit).
Power Back Immunity 35 V
EN 61000-6-3 (class B) is fulfilled even when
using long, unscreened output cabels
Operation: 0°C...+70°C (>60°C: Derating)
Storage: -25°C...+85°C
=+60°C...+70°C)
amb
(incl. spikes (20 MHz bandw.), 50 Ω measurem.)
< 20 mV
< 40 mV
< 100 mV
• Red LED on, when 10 V < V
• Red LED flashes, when 0 V < V
(< 0.1 %)
PP
(In: 230VAC, Out: 24V/30A)
PP
(In: 184VAC, Out: 24V/30A)
PP
> UT, where UT is
ca. 2 V below Vout adjusted (24V...28V)
out
out
< U
out
T
< 10 V
Efficiency, Reliability etc. *
Construction / Mechanics *
Efficiency typ. 92.5 % (400 VAC, 24 V / 30 A)
Losses typ. 60 W (400 VAC, 24 V / 30 A)
MTBF 425,000 h @ 400 VAC, 360,000 h @ 480 VAC
(Siemensnorm SN 29500 (Release 07.97),
24 V/30 A, T
Life cycle (electrolytics) The unit exclusively uses longlife electrolytics,
specified for +105°C (cf. ’The SilverLine’, p.2).
High reliability and lifetime, as
• only four aluminium electrolytics and
• no small aluminium electrolytics are used.
= +40 °C)
amb
Housing dimensions and Weight
•W x H x D
• Free space for
ventilation
•Weight
Design advantages:
• All connection blocks are easy to reach as mounted at the front panel.
• PVC insulated cable can be used for all connections, as the connection
blocks are mounted in the cooler area on the underside of the unit.
240 mm x 124 mm x 112 mm (+ DIN rail)
above/below 70 mm recommended
left/right 25 mm recommended
2.0 kg
* For further information see data sheets „The SilverLine“,
„SilverLine Family Branches“ and mechanics data sheet
Order information
Order number Description
SL30.300
SLZ01 Screw mounting set, two needed per unit
sl30e300 / 050318 1/2
Data sheet
Start / Overload Behaviour
Startup delay typ. 0.2 s
Rise time ca. 20-80 ms, depending on load
Duration of switch-on attempts at
• Initial application
ca. 1.4 s
on mains
• Subsequent
ca. 0.5 s
attempts
Hiccup operation at V
Duration between
out
ca. 1 s
< ca. 10 V
switch-on attempts
Electronic current limiting, protects against overload and short circuit:
•V
< ca. 10 V: Periodical switch-on attempts (hiccup-mode).
out
•V
> ca. 10 V: The output current is continuous.
out
The V/I characteristic of the supply is straight.
Advantages of the switch-on/overload behaviour:
• Safer switch-on into highly non-linear loads with large
starting currents
• Short-term overloads result in current limiting and not in
an immediate shut-down.
• Parallel operation of several units possible.
Proper switch-on performance is obtained.
Further Information
For further information, especially about
•EMC
• Connections
• Safety, Approvals
• Mechanics und Mounting,
see page 2 of the „The SilverLine“ data sheet.
For detailed dimensions
see SilverLine mechanics data sheet SL30
Output V/I characteristic (typ.)
32,00
24,00
16,00
Output Voltage Uout / V
8,00
0,00
15,00 20,00 25,00 30,00 35,00 40,00
Vout range
Parallel mode
Single mode
Vout < ca. 10V: Hiccup mode
Output Current Iout [A]
Vin =
380 V AC
Efficiency (typ.)
94,00
92,00
90,00
88,00
86,00
Efficiency [%]
84,00
350 400 450 500 550
94,00
92,00
90,00
88,00
Efficiency [%]
86,00
350 400 450 500 550
Out = 24V/30A
Out = 24V/20A
Out = 24V/10A
Input voltage VACin [ V]
Out = 28V/26 A
Out = 28V/18A
Out = 28V/9A
Input voltage VACin [V]
Vin =
460 V AC
Vout = 24V
Vout = 28V
Hold-up time (min., at V
60
100% Load
50
40
30
Hold-up time [ms]
20
10
0
330 370 410 450 490 530
80% Load
60% Load
40% Load
Input voltage VACin [V]
out
=24V)
Specifications valid for 3 x AC 400V input voltage, +25°C ambient temperature, and 5 min run-in time, unless otherwise stated. They are subject to change without prior notice.