30 A Single-Phase
SL30.100
• Input: AC 208-240V
• Output: 24...28V / 30A
• 92.5% efficiency
• Ideal for parallel operation
• Simple fusing
Data sheet
Input
Input voltage AC 208-240V
47-63 Hz
Note: DC operation not permissible
Rated tolerances
• Continuous operat. 180-276 V AC
Input current < 9A eff.
Inrush current < 33A at 276 V AC
Inrush current limiting done with a fixed 15R resistor (not a thermistor)
which is bridged after the unit is running, so losses are minimised. That
means no reset time even at a warm-start.
Fuse loading < 10 A
To be fused with a 10A, B-type ’circuit-breaker’ switch based on the
usual thermomagnetic overload sensing principle (used anyway to fuse
the input lines).
In addition, the unit contains an internal fuse (not accessible).
Transient
handling
Hold up time > 20 ms
Input voltage AC 208-240V
Efficiency, Reliability etc.*
Efficiency typ. 92.5 % (230 VAC , 24 V / 30 A)
Losses typ. 60 W (230 VAC, 24 V / 30 A)
Life cycle (electrolytics) The unit exclusively uses longlife electrolytics,
Efficiency typ. 92.5 % (230 VAC , 24 V / 30 A)
Note: S/P = Single/Parallel Mode
* For further information see data sheets „The SilverLine“, „SilverLine Family
Branches“ and mechanics data sheet
2
s
Active transient filter incorporated, so transient resistance acc.to VDE 0160 / W2 (750 V /
1.3 ms), for all load conditions.
at 230 VAC, 24 V / 30 A
47-63 Hz
specified for +105°C (cf. ’The SilverLine’, p.2).
High reliability and lifetime, as
• only 5 aluminum electrolytics and
• no small aluminum electrolytics are used.
EMC and
Low Volt.
Directive
UL60950 E137006
CUL/CSA-C22.2
No. 60950
UL508 LISTED
IND. CONT. EQ.
18 WM, 60°C
CB
scheme
IEC60950
Output
Output voltage 24...28 VDC, adjustable by (covered) front
panel potentiometer; prest: 24V ± 0.5%
Adjusting range guaranteed.
Output noise
suppression
Ambient temperature
range T
amb
Rated continuous loading with convection cooling
at T
=0°C - 60°C 24 V / 30 A (720 W) resp. 28 V / 26 A (728 W)
amb
Derating typ. 18 W/K (at T
Voltage regulation better than ±2% over all
Ripple
• Output charact. S
• Output charact. P
(see Note)
Over-voltage
protection
Front panel indicators:
• Green LED on, when V
below V
• Red LED on, when appr. 14 V < V
• Red LED flashes, when 0 V < V
Parallel operation Yes, up to five SL30 units
To achieve current sharing the output V/I characteristic can be altered
to be 'softer' (24.7 V at 0.4 A, 24.3 V at 30 A). This is done by repositioning a bridge connection (without opening the unit).
Power Back Immunity max. 30 V
adjusted (24V...28V)
out
Radiated EMI values below EN50081-1, even
when using long, unscreened output cables
Operation: 0°C...+70°C (> 60°C: Derating)
Storage: -25°C...+85°C
= +60°C....+70°C)
amb
(incl. spikes (20 MHz bandw.), 50 Ωmeasurem.)
< 50mV
< 100mV
< 150 mV
At 33 V ± 10%: switch to hiccup mode
(< 0,2 %)
PP
(In: 230VAC, Out: 24V/30A)
PP
(In: 184VAC, Out: 24V/30A)
PP
> UT, where UT is appr. 2 V
out
< U
out
T
< appr. 14 V
out
Construction / Mechanics *
Housing dimensions and Weight
•W x H x D
• Free space for
ventilation
•Weight
Design advantages:
• All connection blocks are easy to reach as mounted at the front panel.
• PVC insulated cable can be used for all connections, as the connection
blocks are mounted in the cooler area on the underside of the unit.
240 mm x 124 mm x 112 mm (+ DIN Rail)
above/below 70 mm recommended
left/right 25 mm recommended
2000 g
Order information
Order number Description
SL30.100
SLZ01 Screw mounting set, two needed per unit
sl30e100 / 040114 1/2
Data sheet
Start / Overload Behaviour
Startup delay typ. 0.3 s
Rise time appr. 10 ms, depending on load
Duration of switch-on attempts at
• Initial application
appr. 1.4 s
on mains
• Subsequent
appr. 0.5 s
attempts
Hiccup operation at V
Duration between
< appr. 14 V
out
appr. 1 s
switch-on attempts
Electronic current limiting, protects against overload and short circuit:
•V
< appr. 14 V: Periodical switch-on attempts (hiccup-mode).
out
•V
> appr. 14 V: The output current is continuous
out
The V/I characteristic of the supply is straight.
Advantages of the switch-on/overload behaviour:
• Safer switch-on into highly non-linear loads with large
starting currents.
• Short-term overloads result in current limiting and not in
an immediate shut-down.
• Parallel operation of several units possible.
Proper switch-on performance is obtained.
Further Information
For further information, especially about
•EMC
• Connections
• Safety, Approvals
• Mechanics und Mounting,
see page 2 of the „The SilverLine“ data sheet
For detailed dimensions
see SilverLine mechanics data sheet SL30
Output V/I characteristic (typ.)
32,00
24,00
16,00
Vout < appr. 14V: Hiccup mode
Output voltage Vout [V]
8,00
0,00
15,00 20,00 25,00 30,00 35,00 40,00
Vout range
Parallel mode
Single mode
Output current Iout [A]
Efficiency (typ.)
94,00
92,00
90,00
88,00
86,00
Efficiency [%]
84,00
180 195 210 225 240 255 270
94,00
92,00
90,00
88,00
Efficiency [%]
86,00
180 195 210 225 240 255 270
Out = 24V /30A
Out = 24V /20A
Out = 24V /10A
Input voltage VACi n [V]
Out = 28V/26 A
Out = 28V/18A
Out = 28V/9A
Input voltage VACi n [V]
Vin =
230 V AC
out = 24
out = 28
Hold-up time (min., at V
140
120
100
80
60
Hold-up time [ms]
40
20
0
180 190 200 210 220 230 240 250 260 270
Input voltage VACin [V]
out
=24V)
Iout = 5A
Iout = 10 A
Iout = 15 A
Iout = 20 A
Iout = 25 A
Iout = 30 A
Unless otherwise stated, specifications are valid for AC 230V input voltage, +25°C ambient temperature, and 5 min. run-in time. They are subject to change without prior notice.
Your partner in power supply:
European
Power Supply
Manufacturers
Association
Bayerns Best 50
Czech 100 Best
EuropeÕs 500
PULS GmbH
Arabellastraße 15
D-81925 München
Tel.: +49 89 9278-0
Fax: +49 89 9278-199
www.puls-power.com
2/2 sl30e100 / 040114