Baby SilverLine with 2.5 A
SL2.5
EMC and
Low Volt.
Directive
• Input: AC 230V / 115V
• Output: 24V / 2.5A
• High overload current, no switch-off
• Quasi-Wide-Range Input
• Robust mechanics and EMC
• NEC Class 2 Power Supply
Data sheet
Data sheet
Input
Input voltage AC100-120/220-240 V (switchable), 47-63 Hz
(85-132 VAC / 176-264 VAC, 160-375 VDC, see
also „Output: Continuous Loading“)
Quasi-Wide-Range Input: With the switch in the 230V position the power-supply unit operates at low and moderate loads at any input voltage
between 95 and 264 V AC (see ’Output’ at the right side).
Note: At DC input, always leave the switch in the 230V position
Input current < 1.3 A (switch in 115V position)
DC input current
at open output
Inrush current typ. 25 A at 264 V AC and cold start
To be fused with a 10A, B-type 'circuit-breaker' switch based on the usual thermomagn. overload sensing principle (used anyway to fuse the input lines). In addition, the unit contains an internal fuse (not accessible)
EN 61000-3-2 (harmonic current emissions) is fulfilled
Transient
handling
Hold up time > 20 ms at 196 VAC, 24 V / 2.5 A
< 0.7 A (switch in 230V position)
typ. 5.3 mA at 110 VDC, 3.9 mA at 300 VDC
(preserves battery sources)
Transient resistance acc. to VDE 0160 / W2
(750 V / 1.3 ms), for all load conditions.
(see Diagram overleaf)
Efficiency, Reliability etc.*
Efficiency typ. 87.5 % (230 VAC, 24 V / 2.5 A)
Losses typ. 8.6 W (230 VAC, 24 V / 2.5 A)
MTBF 740,000 h acc. to Siemensnorm SN 29500
(24 V/2.5 A, 230 VAC, T
Life cycle (electrolytics) The unit exclusively uses longlife electrolytics,
specified for +105°C (cf. ’The SilverLine’, p.2).
= +40 °C)
amb
UL60950 E137006
CUL/CSA-C22.2
No. 60950
UL508 LISTED
IND. CONT. EQ.
18 WM, 60°C
CB
scheme
IEC60950
Output
Output voltage 24 V DC +5% –1% (12V on request)
Output noise
suppression
Ambient temperature
range T
amb
Continuous loading
(at T
= -10°C...+60°C,
amb
onvection cooling),
ee also Diagram overleaf.
For start at T
low input voltage, please
contact PULS.
* For start with DC input >
95 V DC needed
Output protected against short circuit, open circuit and overload
Derating typ. 1.5 W/K (at T
Voltage regulation better than 2% Vout overall
Ripple / Noise < 25 mV
Overvolt. protection typ. 32 V
Parallel operation yes; current sharing available on request
Power back immunity 26 V
Front panel indicator Green LED, goes out at V
amb
<0°C and
Radiated EMI values below EN 61000-6-3, even
when using long, unscreened output cables.
Operation: -10°C...+70°C (>60°C: Derating)
Storage: -25°C...+85°C
Switch AC/DCin Iout
230V 176-264 V ACin 2,5 A
95-176 V ACin 1,5 A
160-375 V DCin 2,5 A
120-160 V DCin 2,0 A
115V 85-132 V ACin 2.5 A
80*-120 V DCin 1,5 A
=+60°C...+70°C)
amb
, (20 MHz bandw., 50 Ω measurem.)
PP
< 18V
out
Start / Overload Behaviour
Startup delay typ. 0.1 s
Rise time ca. 5-20 ms, depending on load
Overload Behaviour
• Special PULS Over-
load Design (see
diagram overleaf)
Advantages:
• High short-circuit current, giving large ’start-up window’: unit starts
reliably even with awkward loads (DC-DC converters, motors).
• No ’sticking’ such as can occur with fold-back characteristics
• Secondary fuses operate reliably
– no disconnection, no hiccup if overloaded
– high overload current (up to 1.5 I
is gradually reduced with increasing current.
Nom
), Vout
Order information
Order number Description
sl2e100 / 040128 1/2
SL2.100
SLR2.100
SLZ01
(Basic version*)
(N+1 redundancy*)
(Screw mounting set, two needed per unit)
Data sheet
Construction / Mechanics*
Housing dimensions and Weight
•W x H x D
• Free space for
ventilation
•Weight
Design advantages:
• All connection blocks are easy to reach as mounted at the front panel.
• Input and output are strictly apart from each other and so cannot
be mixed up (Input below, output above).
* *For further information see data sheets „The SilverLine“,
„SilverLine Family Branches“ and mechanics data sheet
For further information, especially about
•EMC
• Connections
• Safety, Approvals
• Mechanics und Mounting,
see page 2 of the „The SilverLine“ data sheet.
For detailed dimensions
see SilverLine mechanics data sheet SL2.5/ SL5/ SL10
49 mm x 124 mm x 102 mm (+ DIN rail)
above/below 25 mm recommended
right 10 mm recommended (front view)
460 g
Output Current over Input Voltage (min.)
3
2
1
>95 VDC for start
80 375160
100 200 300 400
Input voltage VDCin [V]
3
Output current Iout [A]
2
1
85
switch at 115V
switch
95
100 200 300 400
176
132 264
Input voltage VACin [V]
Output characteristic (min.)
28
24
20
16
Tamb = 60°C / 45°C / 25°C / 0°C
DCin
ACin
12
8
Output voltage Vout [V]
4
0
0123456
Output c urrent Iout [A]
Hold-up time (min.)
100
90
DCin
80
70
60
50
40
30
Hold-up time [ms]
20
10
0
80 120 160 200 240 280 320
Input voltage VDCin [V]
Iout= 1,0
Iout= 1,5
Iout= 2,5
Unless otherwise stated, specifications are valid for AC 230V input voltage, +25°C ambient temperature, and 5 min. run-in time. They are subject to change without prior notice.
Your partner in power supply:
100
ACin
90
Hold-up time [ms]
80
70
60
50
40
30
20
10
0
Iout= 1,5
Iout=2,5
90 120 150 180 210 240
Switch pos.
115V
Switch pos
Inpu t volta ge VACin [V]
230V
European
Power Supply
Manufacturers
Association
Iout=1,0
Iout=1,5
Iout=2,5
Bayerns Best 50
Czech 100 Best
Europe’s 500
PULS GmbH
Arabellastraße 15
D-81925 München
Tel.: +49 89 9278-0
Fax: +49 89 9278-199
www.puls-power.com
2/2 sl2e100 / 040128