All-rounder
SL20.303
EMC and
Low Volt.
Directive
• Input: 3 AC 400V
• Output: 48...56V / 480W (600W)
• 92% efficiency
• Ideal for parallel operation
• Simple fusing
Data sheet
Input
Input voltage 3 AC 400 V, – 15 %, + 20 %
47-63 Hz, suitable for IT power systems
Rated tolerances
• Continuous
operation
• Short-term (1 min)
at 48 V/10 A
Input current 3 x 1.5 A
Inrush current < 15 A at 440 V AC
Inrush current limiting done with a fixed 47R resistor (not a thermistor)
which is bridged after the unit is running, so losses are minimised. That
means no reset time even at a warm-start.
Fuse loading < 2 A
To be fused with a 3 x 10A, B-type 'circuit-breaker' switch based on the
usual thermomagnetic overload sensing principle (used anyway to fuse
the input lines; unit has no internal fuses).
Harmonic current
emissions (PFC)
Transient
handling
Hold-up time > 11 ms
340-479 V AC or 450-700 V DC
300-550 V AC or 370-790 V DC
2
s
acc. to EN 61000-3-2
Active transient filter incorporated, so transient resistance acc.to VDE 0160 / W2 (1300 V /
1.3 ms), for all load conditions.
at 48 V/10 A, 400 V AC
Efficiency, Reliability etc.*
Efficiency typ. 92 % (48 V/10 A, 400 V AC)
Losses typ. 42 W (48 V/10 A, 400 V AC)
MTBF 310.000 h acc. to Siemensnorm SN 29500
(48 V/10 A, 400 V AC, T
Life cycle (electrolytics) The unit exclusively uses longlife electrolytics,
specified for +105°C (cf. ’The SilverLine’, p.2).
High reliability and lifetime, as
• only four aluminum electrolytics and
• no small aluminum electrolytics are used.
* For further information see data sheets „The SilverLine“,
„SilverLine Family Branches“ and mechanics data sheet
= +40 °C)
amb
UL60950 E137006
CUL/CSA-C22.2
No. 60950
UL508 LISTED
IND. CONT. EQ.
18 WM, 60°C
CB
scheme
IEC60950
Output
Output voltage 48...56 V DC, adjustable by (covered) front
Output noise
suppression
Ambient temperature
range T
amb
Rated continuous loading with convection cooling
•T
=0°C - 60°C
amb
•T
=0°C - 45°C
amb
Derating typ. 12 W/K (at T
Voltage regulation better than 2 % over all
Ripple < 50 mV
Over-voltage protect. At 61V ± 7%: switch to hiccup mode
Front panel indicators:
• Green LED on, when V
appr. 4 V below Vout adjusted (48 V...56 V).
• Red LED on, when appr. 28 V < V
• Red LED flashes, when 0 V < V
Parallel operation Yes, up to ten SL20 units
To achieve current sharing the output V/I characteristic can be altered to
be 'softer' (48.8 V at 0.1 A, 48 V at 10 A). This is done by repositioning a
bridge connection (without opening the unit).
Power Back Immunity < 63 V
panel potentiometer, preset: 48.1V ±0.5%
Adjusting range guaranteed
Radiated EMI values below EN50081-1, even
when using long, unscreened output cables.
Operation: 0°C...+70°C (>60°C: Derating)
Storage: -25°C...+85°C
48 V / 10 A (480 W) resp. 56 V / 9 A (504 W)
48 V / 12.5 A (600 W) resp. 56 V / 11 A (616 W)
short-term (< 1 min.) also at 60°C permissible
=+60°C...+70°C)
amb
(i.e. < 0.1 %) incl. spikes
PP
20 MHz bandwidth, 50 Ω measurement
> UT, where UT is
out
< U
out
T.
< appr. 28 V.
out
Construction / Mechanics*
Housing dimensions and Weight
•W x H x D
• Free space for
ventilation
•Weight
Design advantages:
• All connection blocks are easy to reach as mounted at the front panel.
• PVC insulated cable can be used for all connections, as the connection
blocks are mounted in the cooler area on the underside of the unit.
220 mm x 124 mm x 102 mm (+ DIN rail)
above/below 70 mm recommended
right/left 25 mm recommended
1.8 kg
Order information
Order number Description
SL20.303
SLZ02
sl20e303 / 030924 1/2
Screw mounting set, two needed per unit
Data sheet
Start / Overload Behaviour
Startup delay typ. 0.2 s
Rise time appr. 20-80 ms, depending on load
Duration of switch-on attempts at
• Initial application
on mains
• Subsequent
attempts
Hiccup operation at V
Duration between
switch-on attempts
Electronic current limiting, protects against overload and short circuit:
•V
< appr. 28 V: Periodical switch-on attempts (hiccup mode).
out
•V
> appr. 28 V: The output current is continuous.
out
The V/I characteristic of the supply is straight.
Advantages of the switch-on/overload behaviour:
• Safer switch-on into highly non-linear loads with large
starting currents.
• Short-term overloads result in current limiting and not in
an immediate shut-down.
• Parallel operation of several units possible.
Proper switch-on performance is obtained.
Further information
For further information, especially about
•EMC
• Connections
• Safety, Approvals
• Mechanics und Mounting,
see page 2 of the „The SilverLine“ data sheet.
For detailed dimensions
see SilverLine mechanics data sheet SL20
appr. 1.4 s
appr. 0.5 s
< appr. 28 V
out
appr. 4 s
Output V/I characteristic (typ.)
64
56
48
40
32
Vout < ca. 28V: Hiccup mode
24
Output voltage Vout [V
16
8
0
0 2 4 6 81012141618
Efficiency (typ., at V
95
94
93
92
91
90
89
88
Efficiency [%]
87
86
85
84
24681012
Hold-up time (min., at V
56V / Parallel
56V / Single
48V / Parallel
48V / Single
Output current Iout [A]
=48V)
out
Output current I out [A]
out
340 V AC
400 V AC
480 V AC
=48V)
60
40% Load
50
40
30
20
Hold-up time [ms]
10
0
Specifications valid for 3 x AC 400V input voltage, +25°C ambient temperature, and 5 min run-in time, unless otherwise stated. They are subject to change without prior notice.
Your partner in power supply:
60% Load
80% Load
100% Load
125% Load
340 360 380 400 420 440 460 480
Input voltage V ACin [ V]
European
Power Supply
Manufacturers
Association
Bayerns Best 50
Czech 100 Best
Europe’s 500
PULS GmbH
Arabellastraße 15
D-81925 München
Tel.: +49 89 9278-0
Fax: +49 89 9278-199
www.puls-power.com
2/2 sl20e303 / 030924