SL20 with 36...43V
SL20.112
• Input: AC 115/230V auto select
• Output: 36...43V / 480W
• 92% efficiency
• Ideal for parallel operation
CB
scheme
IEC60950
UL508 LISTED
IND. CONT. EQ.
18 WM, 60°C
UL60950 E137006
CUL/CSA-C22.2
No 60950
Type approval
acc. to:
• IEC / EN60950
• EN50178
Overvolt. cat. III
• EN60204
Data sheet
Datasheet
Input Output
Input voltage AC 100-120V/220-240V,
47-63Hz, auto select
Rated tolerances
• Continuous
operation
• Short-term (30s)
at 36V/13A
Input current I
Inrush current limiting with active bypass of the limiting resistor (NTC).
Inrush current I
Fuse loading I²t <5A
To be fused with a 16A, B-type 'circuit-breaker' switch based on the usual thermomagnetic overload sensing principle (used anyway to fuse the
input lines).
EN 61000-3-2 (harmonic current emissions [PFC]) is fulfilled
Transient
handling
Hold-up time 27ms at 36V/13A, AC 230V
n
pk
AC 85...132V resp. AC 184...264V
AC 85...140V resp. AC 175...280V
<10A (115V range)
<5A (230V range)
<18A @ AC 264V (T
<37A @ AC 264V (T
2
s (T
= +25°C, cold start)
amb
2
<8A
s (T
= +50°C, cold start)
amb
Transient resistance acc. to VDE 0160 / W2
(750V / 1.3ms), for all load conditions.
35ms at 36V/13A, AC 120V
15ms at 36V/13A, AC 100V
= +25°C, cold start)
amb
= +50°C, cold start)
amb
in
in
in
Output voltage DC 36...43V, adjustable by (covered) front
Output noise
suppression
Ambient temperature
range T
amb
Rated continuous loading with convection cooling:
•T
=0°C - 60°C
amb
short-term (<30s)
Derating 12W/K (at T
Voltage regulation better than 2% over all
Ripple
• Output charact. S
• Output charact. P
(S/P: Single/Parallel Mode)
Over-voltage protection At 49V ±10%: switch to hiccup mode
Front panel indicators:
• Green LED on, when V
• Red LED on, when V
Parallel operation Yes, up to ten SL20
To achieve current sharing the output V/I characteristic can be altered to
be 'softer' (36.6V at 0A, 35.2V at 13.3A). This is done by repositioning an
external bridge connection (without opening the unit).
Power Back Immunity max. 48V
EMC and
Low Volt.
Directive
panel potentiometer; preset: 36V ±0.5%
Adjustment range guaranteed
Radiated EMI values below EN50081-1, even
when using long, unscreened output cables.
Operation: 0°C...+70°C (> 60°C: Derating)
Storage: -25°C...+85°C
36V/13.3A resp. 43V/11.2A
36V/16.6A resp. 42V/14A
= 60-70°C)
amb
(incl. spikes (20 MHz bandw.), 50Ω measurem.
<30mV
<80mV
<100mV
out
(<0.09%)
PP
(In: AC 230V, Out: 36V/13A)
PP
(In: AC 184V, Out: 42V/13A)
PP
= V
out
out
adjusted
adjusted
out
< V
Construction / Mechanics
Housing dimensions and Weight
•W x H x D
• Free space for
ventilation
•Weight
Design advantages:
• All connection blocks are easy to reach as mounted on the front
panel.
• PVC insulated cable can be used for all connections, as the connection
Order information
Order number Description
SL20.112
SLZ02 (wall mounting set; contains 2 pcs.)
sl20e112 / 040114 1/2
blocks are mounted in the cooler area on the underside of the unit.
220mm x 124mm x 102mm (+ DIN rail)
above/below 70mm recommended
left/right 25mm recommended
2.5kg
Data sheet
Efficiency, Reliability etc.*
Efficiency typ. 92% (AC 230V, 36V/13.3A)
Losses typ. 42W (AC 230V, 36V/13.3A)
MTBF 519.000h acc. to Siemensnorm SN29500
(36V / 13A, 230V, T
amb
= 40°C)
Life cycle (electrolytics) The unit exclusively uses longlife electrolytics,
specified for +105°C (cf. ’The SilverLine’, p.2).
High reliability, as
• only five aluminium electrolytics and
• no small aluminium electrolytics are used.
* For further information see data sheets„The SilverLine“,
„SilverLine Family Branches“ and mechanics data sheet SL20
Start / Overload Behaviour
Startup delay typ. 0.55s
Rise time appr. 20-80ms, depending on load
Overload behaviour Puls Overload Design (see right-hand diagram)
Advantages:
• No disconnection/hiccup, thus overloading is possible also for a
longer period of time (load start-up), ideal for parallel operation.
• High overload/short-circuit current due to straight characteristic;
each bias point of the V/I characteristic extends 13A.
Advantage: Due to the high and continuously supplied overload current the unit starts reliably even with awkward loads (DC-DC converters, motors). No 'sticking' can occur as, for example, with fold-back
characteristics, and secondary fuses trigger more reliably.
Further information
Further information, especially about
•EMC
• Connections
• Safety, Approvals
• Mechanics and Mounting,
see page 2 of the „The SilverLine“ data sheet
For detailed dimensions
see SilverLine mechanics data sheet SL20
Output characteristic (typ.)
40
35
30
25
20
15
Output voltage Vout [V]
10
5
0
0 5 10 15 20 25
Efficiency (typ., at V
93
92
91
90
Efficiency [%]
89
88
87
3 6 9 12 15 18
36 V / Single
35.36 V / Parallel
Output c urrent Iout [ A]
=36V)
out
Output curren t Iou t [A]
100VAC
120VAC
230VAC
Hold-up time (min., at V
60
50
40
30
20
Hold-up time [ms
10
0
180 190 200 210 220 230 240
Unless otherwise stated, specifications are valid for AC 230V input voltage, +25°C ambient temperature, and 5 min. run-in time. They are subject to change without prior notice.
60% Load
100% Load
125% Load
Your partner in power supply:
=36V)
out
at AC 230V
Input Voltage VACin [V]
100
80
60
60% Load
100% Load
125% Load
40
20
Hold-up time [ms]
at AC 115V
0
85 90 95 100 105 110 115 120 125 130
Input volt age VACin [ V]
European
Power Supply
Manufacturers
Association
Bayerns Best 50
Czech 100 Best
Europe’s 500
PULS GmbH
Arabellastraße 15
2/2 sl20e112 / 040114
D-81925 München
Tel.: +49 89 9278-0
Fax: +49 89 9278-199