Puls SL20.110, SL20.111 Data Sheet

Data sheet
20A single phase
SL20.110/.111
• Input: AC 115/230V Auto Select
• Output: 24...28V / 480W (600W)
• 90% Efficiency
• Ideal for parallel operation
CB
scheme
IEC60950
UL508 LISTED IND. CONT. EQ.
18 WM, 60°C
UL60950 E137006
CUL/CSA-C22.2
No 60950
Type approval
acc. to:
• IEC / EN60950
• EN50178 Overvolt. cat. III
• EN60204
EMC and
Low Volt.
Directive
Input
Input voltage AC 100-120V/200-240V, 47-63Hz
Auto Select
Rated tolerances
• Continuous operation
• Short-term (1 min)
AC 85-132V resp. AC 184-264V
AC 85-140V resp. AC 170-280V
at 24V/20A
Input current I
n
<10A (115V range) <5A (230V range)
Inrush current limiting with active bypass of the limiting resistor (NTC).
Inrush current I
pk
<18A at AC 264V (T <37A at AC 264V (T
Fuse loading I²t <5A
<8A
2
s (T
= +25°C, cold start)
amb
2
s (T
= +50°C, cold start)
amb
= +25°C, cold start)
amb
= +50°C, cold start)
amb
To be fused with a 16A, B-type 'circuit-breaker' switch based on the usual thermomagnetic overload sensing principle (used anyway to fuse the input lines).
Harmonic current
emissions (PFC)
Transient handling
SL20.110: no SL20.111: acc. to EN 61000-3-2
Transient resistance acc. to VDE 0160 / W2 (750V / 1.3ms), for all load conditions.
Hold-up time 30ms at 24V/20A, AC 230Vin
30ms at 24V/20A, AC 120Vin 15ms at 24V/20A, AC 100Vin
Efficiency, Reliability etc.*
Efficiency typ. 90% (AC 230V, 24V/20A)
Losses typ. 53W (AC 230V, 24V/20A)
MTBF 519.000h acc. to Siemensnorm SN29500
(24V/20A, 230V, T
amb
= 40°C)
Life cycle (electrolytics) The unit exclusively uses longlife electrolytics,
specified for +105°C (cf. ’The SilverLine’, p.2). High reliability, as
• only five aluminium electrolytics and
• no small aluminium electrolytics are used.
* For further information see data sheets „The SilverLine“,
„SilverLine Family Branches“ and mechanics data sheet
Order information
Output
Output voltage DC 24...28V, adjustable by (covered) front
panel potentiometer. Adjust. range guaran­teed
Output noise suppression
Ambient temperature range T
amb
EN 61000-6-3 (class B) is fulfilled even when using long, unscreened output cabels
Operation: 0°C...+70°C (>60°C: Derating) Storage: -25°C...+85°C
Rated continuous loading with convection cooling:
=0°C - 60°C 24V/20A resp. 28V/18A
•T
amb
short-term (<30s) 24V/25A resp. 28V/22A
Derating 12W/K (at T
= 60-70°C)
amb
Voltage regulation better than 2% over all
Ripple
• Output charact. S
• Output charact. P
(S/P: Single/Parallel Mode)
(incl. spikes (20MHz bandw.), 50 measurem.) <20mV <40mV <100mV
(<0.1%)
PP
(In: AC 230V, Out: 24V/20A)
PP
(In: AC 184V, Out: 24V/20A)
PP
Over-voltage protection At 31V ± 3%: switch to hiccup mode
Front panel indicators:
• Green LED on, when V adjusted (24V...28V)
• Red LED on, when V
> UT, where UT is appr. 2V below V
out
< U
out
T
out
Parallel operation Yes, up to ten SL20
To achieve current sharing:
• Plug jumper into pos. 'Output parallel use'. This alters the output V/I characteristic to be 'softer' (25V at 0.4A, 24V at 20A). The out­put voltage can still be adjusted.
• Missing jumper = 'parallel use', i.e. 'soft' characteristic
Power back immunity max. 30V
Construction / Mechanics*
Housing dimensions and Weight
• W x H x D
• Free space for ventilation
•Weight
220mm x 124mm x 102mm (+ DIN rail) above/below 70mm recommended left/right 25mm recommended
1.8kg (SL20.110) resp.
2.5kg (SL20.111)
Design advantages:
• All connection blocks are easy to reach as mounted at the front panel.
• PVC insulated cable can be used for all connections, as the connec­tion blocks are mounted in the cooler area on the underside of the unit.
Order number
SL20.110 (without PFC)
Description
SLZ02 (wall mounting set; contains 2 pcs.)
SL20.111 (including PFC)
sl10e110 / 050318 1/2
Data sheet
V
Start / Overload Behaviour
Startup delay typ. 0.55s
Rise time appr. 20-80ms, depending on load
Overload behaviour (see characteristic on the right)
• Power Boost: Short-term (<30s) 125% output power without voltage drop.
• Electronic current limiting, protects from overload and short-circuit.
• High overload/short-circuit behaviour (V
<14V) switchable between PULS Over-
out
load Design and hiccup mode. Switching by jumper on bottom of the unit; it is not neces­sary to open the unit for this purpose.
PULS Overload Design™ (continuous current):
• No disconnection/hiccup, thus overloading is possible also for a longer period of time (load start-up), ideal for parallel operation.
• High overload/short-circuit current due to straight characteristic; each bias point of the V/I characteristic extends 20A.
Advantage: Due to the high and continuously supplied overload current the unit starts reliably even with awkward loads (DC-DC converters, mo­tors). No ’sticking’ such as can occur with fold-back characteristics, and secondary fuses trigger more reliably.
Hiccup mode:
• Unit switches off when high overload occurs (V with subsequent periodical switch-on attempts (hiccup mode):
< appr. 14V)
out
– Duration of switch-on attempts:
appr. 0.1s at short-chircuit or appr. 1s at overload
– Duration between switch-on attempts: appr. 1.5s
•V
> appr. 14V: The output current is continuous. The V/I charac-
out
teristic equals that of the PULS Overload Design™; each bias point of the V/I characteristic extends 20A.
Further information
Further information, especially about
•EMC
• Connections
• Safety, Approvals
• Mechanics und Mounting,
see page 2 of the „The SilverLine“ data sheet
For detailed dimensions
see SilverLine mechanics data sheet SL20
Output characteristic (typ.)
32
28
24
20
16
12
8
Output voltage Vout [
4
0
Efficiency (typ., at V
92
91
90
89
Efficiency [%]
88
87
Hold-up time (min., at V
80
60
40
20
Hold-up time [ms]
0
180 190 200 210 220 230 240
80
60
40
Vout < appr. 14V: Hiccup mode
28V / Parallel 24V / Parallel 24V / Single 28V / Single
0 5 10 15 20 25 30
5 10152025
Output current Iout [A]
=24V)
out
100 V AC 120 V AC 230 V AC
Output c urrent Iout [A]
out
60% Load 100% Load 125% Load
Input voltage VACin [V]
60% Load 100% Load 125% Load
SL20.110
=24V)
at 230V AC
20
Hold-up time [ms]
0
80 90 100 110 120 130
Unless otherwise stated, specifications are valid for AC 230V input voltage, +25°C ambient temperature, and 5 min. run-in time. They are subject to change without prior notice.
All data is valid for the SL20.110. Regarding the SL20.111 (including PFC) some values may differ (please contact us if necessary).
Input voltage VACin [V]
Your partner in power supply:
Manufacturers
at 115V AC
European
Power Supply
Association
Bayerns Best 50
Czech 100 Best
Europe’s 500
PULS GmbH
2/2 sl10e110 / 050318
Arabellastraße 15
D-81925 München
Tel.: +49 89 9278-0
Fax: +49 89 9278-199
www.puls-power.com
Loading...