Single-Phase Power
SL20.100
CB
scheme
IEC60950
UL508 LISTED
IND. CONT. EQ.
18 WM, 60°C
• Input: AC 230V
• Output: 24-28V / 480W (600W)
• 91% efficiency
• Ideal for parallel operation
• Simple fusing
Data sheet
Input
Input voltage AC 230V, +15%, – 20%
Rated Tolerances
• Continuous
operation
• Short term (1 min)
at 24 V/20 A
Input current 5A
Inrush current typ. 33A at AC 264V
Inrush current limiting done with a fixed 15R resistor (not a thermistor)
which is bridged after the unit is running, so losses are minimised. That
means no reset time even at a warm-start.
Fuse loading <10A
Unit is internally fused (fuse not accessible). For external fusing of unit
and for input line protection, use circuit breaker with B-characteristic
10A or slower action, or alternatively T10A HBC fuse.
Harmonic current
emissions (PFC)
Transient
handling
Hold up time >20ms
Efficiency, Reliability etc.*
Efficiency typ. 91% (AC 230V, 24V/20A)
Losses typ. 48W (AC 230V, 24V/20A)
MTBF 310.000h acc. to Siemensnorm SN 29500
Life cycle (electrolytics) The unit exclusively uses longlife electrolytics,
47...63Hz
(SL20.300/.301: 3 AC 400/480V,
see separate data sheet)
AC 184...264V resp.
DC 270...370V
AC 170...280V resp.
DC 250...400V
2
s
SL20.100 on request
SL20.101 acc. to EN61000-3-2
Active transient filter incorporated, so transient resistance acc.to VDE 0160 / W2 (750V/
1.3ms), for all load conditions.
at AC 230V, 24V/20A
(24V/20A, AC 230V, T
specified for +105°C (cf. ’The SilverLine’, p.2).
High reliability, as
• only four aluminium electrolytics and
• no small aluminium electrolytics are used.
amb
= +40°C)
* For further information see data sheets „The SilverLine“,
„SilverLine Family Branches“ and mechanics data sheet
Order information
UL60950 E137006
CUL/CSA-C22.2
No 60950
EMC and
Low Volt.
Directive
Output
Output voltage DC 24-28V adjustable by (covered) front panel
Output noise
suppression
Ambient temperature
range T
amb
Rated continuous loading with convection cooling
=0°C - 60°C
•T
amb
•T
=0°C - 45°C
amb
Derating typ. 12W/K (at T
Voltage regulation better than 2% over all
Ripple
• Output charact. S
• Output charact. P
(S/P: Single/Parallel Mode)
Over-voltage
protection
Front panel indicators: • Green LED on, when V
Parallel operation Yes, up to ten SL20 units
To achieve current sharing the output V/I characteristic can be altered
to be 'softer' (25V at 0.4A, 24V at 20A). This is done by repositioning a
bridge connection (without opening the unit).
Power Back Immunity >30V
Construction / Mechanics *
Housing dimensions and Weight
• W x H x D
• Free space for
ventilation
•Weight
Design advantages:
• All connection blocks are easy to reach as mounted at the front
panel.
• PVC insulated cable can be used for all connections, as the connection blocks are mounted in the cooler area on the underside of the
unit.
potentiometer, preset: 24.0V ±0.5%
Adjustment range guaranteed
Radiated EMI values below EN61000-6-3, even
when using long, unscreened output cables.
Operation: 0°C...+70°C (>60°C: Derating)
Storage: -25°C...+85°C
24V/20A (480W) resp. 28V/18A (504W)
24V/25A (600W) resp. 28V/22A (616W)
short-term also at 60°C
= +60°C...+70°C)
amb
(incl. spikes (20MHz bandw.), 50Ω measurem.)
<20mV
<40mV
<100mV
At 33V ±10%: switch to hiccup mode
• Red LED on, when 14V < V
• Red LED flashes, when 0V < V
(<0.1%)
PP
(In: AC 230V, Out: 24V/20A)
PP
(In: AC 184V, Out: 24V/20A)
PP
> UT, where UT
is ca. 2 V below Vout adjusted (24V...28V)
220mm x 124mm x 102mm (+ DIN rail)
above/below 70mm recommended
left/right 25mm recommended
SL20.100: 1800g SL20.101: 2400g
out
out
< U
out
T
< 14V
Order number Description
SL20.100 (Basic version*),
SLS20.100 (Safety Cover*),
SLZ01
sl20e100 / 050923 1/2
including PFC: SL20.101
including PFC: SLS20.101
Screw mounting set,two needed per unit
Start / Overload Behaviour
Data sheet
Startup delay typ. 0.5s
Rise time ca. 20-80ms, depending on load
Duration of switch-on attempts at
• Initial application
ca. 1.4s
on mains
• Subsequent attempts
ca. 0.5s
Electronic current limiting, protects against overload and short circuit:
•V
< ca. 14V: Periodical switch-on attempts (hiccup-mode).
out
Advantages of the switch-on/overload behaviour:
• Safer switch-on into highly non-linear loads with large
starting currents
• Short-term overloads result in current limiting and not in
an immediate shut-down.
• Parallel operation of several units possible.
Proper switch-on performance is obtained.
Hiccup operation at V
Duration between switch-on at-
out
ca. 4s
< ca. 14V
tempts
Functional diagrams
Output characteristic (typ.) Efficiency (typ., at V
32
24
16
Vout < ca. 14V : Hic cup mode
8
Output voltage Vout [V]
0
0 5 10 15 20 25 30 35 40
24V / Single
24V / Parallel
28V /Singl e
28V / Parallel
Output current Iout [A]
95
94
93
92
91
90
89
88
Efficiency [%]
87
86
85
84
5 10152025
=24V)
out
184V AC
230V AC
264 V AC
Output current Iout [ A]
Hold-up time (min., at V
100
80
60
40% Load
60% Load
80% Load
100% Load
125% Load
out
=24V)
Further information
For further information, especially about
40
Hold-up time [ms]
•EMC
• Connections
20
•Safety, Approvals
• Mechanics und Mounting,
see page 2 of the „The SilverLine“ data sheet
For detailed dimensions
see SilverLine mechanics data sheet SL20
Unless otherwise stated, specifications are valid for AC 230V input voltage, +25°C ambient temperature, and 5 min. run-in time. They are subject to change without prior notice.
0
185 205 225 245 265
Input voltage VACin [V]
All data is valid for SL20.100. Regarding the SL20.101 (including PFC) some values may differ.
Your partner in power supply:
European
Power Supply
Manufacturers
Association
Bayerns Best 50
Czech 100 Best
Europe’s 500
PULS GmbH
Arabellastraße 15
D-81925 München
Tel.: +49 89 9278-0
Fax: +49 89 9278-199
www.puls-power.com
2/2 sl20e100 / 050923