This compact power supply unit is characterised by the variety of application possibilities and low system costs. The fact that the externalfuses are no longer necessary is an advantage as it saves cost and
space. The selectable FUSE Mode and the fully specified 2-phase operation make the SL10.305 the unit of choice.
Input 3-phase operation
(Input 2 phase operation and DC operation see page 2)
Nominal input
voltage
• Voltage range
• Short-term (1 min.)
Frequency50-60Hz ±6% (47...63Hz)
Input current0,8A (3xAC 400V)
Power faktor0,5 (3xAC 400V)
Inrush peak currentelectronically limited
Internal fused3x T2A5 H.B.C
Compatible external fuse6A< Si < 32A Char. B or C or similar tripping
Hold-up time
3xAC 400Vtyp. 36ms; > 29ms (48V / 5A)
3xAC 480Vtyp. 56ms; > 45ms (48V / 5A)
Efficiency and Power dissipation
Efficiency93,8% (48V / 5A / 3xAC 400V)
Power dissipation16,0W (48V / 5A / 3xAC 400V)
No-load-losses2,3W / 3W (3xAC 400V / 3xAC 480V)
3xAC 380-500V
3xAC 320...575V
3xAC 300...620V
0,7A (3xAC 480V)
0,47 (3xAC 480V)
2
< 15,4A; < 0,26A
< 15,4A; < 0,4A
characteristic
93,9% (48V / 5A / 3xAC 480V)
15,7W (48V / 5A / 3xAC 480V)
s; < 3ms (3xAC 400V)
2
s; < 3ms (3xAC 480V)
At a competitive price, it also offers 6A power boost, 9-14A short circuit current, output noise suppression, selectable Single Mode or
Parallel Mode, small dimensions and easy installation. Due to its wide
range input the unit can be connected to 3-phase electricity networks
worldwide without switching.
Output
Rated voltageDC 48V
Rated voltage range48...52V guaranteed
46...53V typ.
Preset48V ±0,2V and “Parallel Use”
Rated current0-5A (at 48V)
0-6A (< 1 minute per 10 minutes)
Short-circuit currentmin. 9A; max. 14A
Overload behaviourContinous Mode or FUSE Mode selectable (see
Overload Behaviour)
Output power240W
Peak power288W (< 1 minute per 10 minutes)
Ripple/Noisetyp. 8mV
Static load regulation< 100,0mV in single operation
Dynamic load
regulation
Power back immunity max. 60V
Over volt protectiontyp. 56V DC max. 60V DC
Parallel operation Yes, up to five SL10.305
To achieve current
sharing:
• Protected against short-circuit, open circuit and overload.
< 2,5V in parallel operation
typ. ±300mV 500 µs
Load step10% - 90% - 10%
• Plug jumper into 'Output parallel use'. This
• Missing jumper = 'Single Use', i.e. 'hard'
/ < 30mVSS (20MHz)
SS
alters the output V/I characteristic to be
'softer' (48V bei 0,5A, 46V bei 5A). The output voltage can still be adjusted.
characteristic
Order information
Order numberDescription
SL10.305
SLZ13
SLZ02
sl10e305 / 0409071/4
Power supply unit
Adapter for S7-300rail
Wall mounting set, (two pcs. per package)
Data sheet
Input 2- phase operation
Random connection to L1, L2 or L
Nominal input
voltage
Input voltage range 2xAC 340...575V
Short-term (1 min.) 2xAC 300...620V
Frequency50-60Hz ±6% (47...63Hz)
Input current1,2A (2xAC 400V)
Power factor0,55 (2xAC 400V)
Inrush peak current < 15,4A; < 0,26A
Recommended
external fuse
Hold-up time 2 phase operation
2xAC 400Vtyp. 32ms; > 26ms (48V / 5A)
2xAC 480Vtyp. 52ms; > 42ms (48V / 5A)
Efficiency and Power dissipation 2 phase operation
Efficiency93,0% (48V / 5A / 2xAC 400V)
Power dissipation18,0W (48V / 5A / 2xAC 400V)
No-load-losses2,3W / 3W (2xAC 400V / 2xAC 480V)
2xAC 400-500V (TN, IT, TT-networks)
1A (2xAC 480V)
0,53 (2xAC 480V)
< 15,4A; < 0,4A
> 6A < 32A Char. B or C
93,2% (48V / 5A / 2xAC 480V)
17,5W (48V / 5A / 2xAC 480V)
3
2
2
s (2xAC 480V)
s (2xAC 400V)
Input DC operation
Random connection, consider PE (protected earth) terminal.
For further details regarding DC-operation please check out our
technical note #25 on our webpage: www.puls-power.com, navigation
“know how” and “technical notes”.
Nominal input
voltage
Input
voltage range
Short-term (1 min.) DC 400...890V
Threshold voltage:
• turn-onDC 350V (typ.)
• shut-downDC 260V (typ.)
Input current0,5A (DC 600V)
Inrush peak current < 14A; < 0,3A
Recommended
external fuse
DC 600V
DC 450...820V
2
s (DC 600V)
6A Littlefuse KLKD
Efficiency and Power dissipation DC operation
Efficiency94,2% (48V / 5A / DC 600V)
Power dissipation14,8W (48V / 5A / DC 600V)
No-load-losses2,5W (DC 600V)
Operation and environmental data
Coolingnatural convection,
no forced air-cooling necessary
Operating temperature
range
Derating> 60 °C: 6W/K
Guaranteed startup-10 °C
Non-operating
temperature range
0 °C...+70 °C
-40 °C...+85 °C
Electromagnetic Compatibility (EMC)
EmissionsEN 61000-6-3 (also includes EN 61000-6-4)
Class B (EN 55011, EN 55022)
EN 61000-3-2 and EN 61000-3-3
Immunity
Electrostatic
Discharge (ESD)
Electromagnetic
radiated fields
Burst, coupled to:
ACin lines
DCout lines
Surge transients
Differential
mode (L→PE)
Common mode
(L
→ L2 , L2 → L
1
L
3→ L 1
Conducted noise
immunity
Voltage dipsEN 61000-4-11
Transient
immunity
3
)
EN 61000-6-2 (also includes EN 61000-6-1)
EN 61000-4-2, Level 4
(withstands 8 kV direct discharge,
15 kV air discharge)
EN 61000-4-3, Level 3 (10 V/m)
EN 61000-4-4
Level 4 (4 kV)
Level 3 (2 kV)
EN 61000-4-5
Installation class 4 (4 kV)
Installation class 4 (2 kV)
;
EN 61000-4-6
Level 3 (10V, 150 kHz-80 MHz)
Transient resistance acc. to VDE 0160 / W2
over entire load range
Higher current for a short period of time (< 1 minute
or even longer with forced ventilation) without voltage breaking down. Optimum fit to peak load requirements and oversizing of power supplies is not needed
anymore.
Overload Design
TM
:
Extended output characteristic curve with a high short current at
a gradually reduced output voltage. Unit does not switch off,
when the rated current is exeeded. The high short current reliably
starts heavy loads such as DC-motors or capacitive loads and blows
branch fuses.
Two different operating mode options, switchable by plugging the frontpanel jumper. If the jumper is missing, the unit is set to FUSE Mode. The
unit is preset to Continuous Mode at shipment.
a) FUSE Mode (Switch-off after typ. 5s):
• Jumper is in the 'OVL FUSE mode' position.
• When overload or short-circuit occurs for more than typ. 5s, the
unit switches off the output.
• Definition of overload or short-circuit: The set output voltage in
each case can no longer be maintained.
• Power Boost and Overload Design™ remain unchanged during the
typ. 5s delay time.
• Red LED flashes at switch-off.
b) Continuous Mode (continuous current):
• Jumper is in the 'OVL cont. mode' position.
• When overload or short-circuit occurs, the unit continuously supplies current (see. diag. 1), no Hiccup.
Re-start:
• by pushing the reset button on the unit’s front panel
• by disconnection from mains and re-start of the unit after > 1 min.
or as soon as the red LED stops flashing
• With some applications, the FUSE Mode can replace the usual fusing on the secondary side. The FUSE Mode has closer tolerances
than thermal trips.The tripping delay time of typ. 5s enables heavy
loads to start and thereby avoids unneccassary service activities.
Overtemperature Protection
Continuous ModeSwitch-off and automatic re-start after cooling.
FUSE ModeUnit remains switched off after overheating until
restart (also see ’Re-start’ above).
Start Behaviour
Startup delay
Rise time
typ. 200ms
appr. 5-20ms, depending on load
Connectors and terminals
TerminalsProofed terminals with captive screws for 5.5
mm slotted screwdriver or Philips cross-recessed
screwdriver No. 2. Input terminals are equipped
with an additional protection
cover.
PositionEasy to reach terminals on the front panel;
Specifications valid for 3 x AC 400V input voltage, +25°C ambient temperature, and 5 min run-in time, unless otherwise stated. They are subject to change
without prior notice.
This datasheet and other documents regarding this power supply are available online through our webpage: www.puls-power.com/SL10.305
Your partner in power supply:
• observe national regulations
• “external” fusing recommended, please
refer to input section, page 1.
above / below 25mm recommended
left / right 15mm recommended
European
Power Supply
Manufacturers
Association
Bayerns Best 50
Czech 100 Best
EuropeÕs 500
PULS GmbH
Arabellastraße 15
D-81925 München
Tel.: +49 89 9278-0
Fax: +49 89 9278-299
www.puls-power.com
4/4sl10e305 / 040907