Puls SL10.305 Data Sheet

48-52V, 3-phase, 240W
SL10.305
• Input: 2 AC 400-500V
• Output: 48-52V / 240W
• Switchable operating mode (single/ parallel)
• FUSE Mode / Continuous Mode
Data sheet
3 AC 380-500V
UL60950 E137006
CUL/CSA-C22.2
No 60950
UL508 LISTED IND. CONT. EQ.
18 WM, 60°C
EMC and Low Volt. Directive
This compact power supply unit is characterised by the variety of appli­cation possibilities and low system costs. The fact that the external fuses are no longer necessary is an advantage as it saves cost and space. The selectable FUSE Mode and the fully specified 2-phase operation make the SL10.305 the unit of choice.
Input 3-phase operation
(Input 2 phase operation and DC operation see page 2)
Nominal input voltage
• Voltage range
• Short-term (1 min.)
Frequency 50-60Hz ±6% (47...63Hz)
Input current 0,8A (3xAC 400V)
Power faktor 0,5 (3xAC 400V)
Inrush peak current electronically limited
Internal fused 3x T2A5 H.B.C
Compatible external fuse6A< Si < 32A Char. B or C or similar tripping
Hold-up time
3xAC 400V typ. 36ms; > 29ms (48V / 5A)
3xAC 480V typ. 56ms; > 45ms (48V / 5A)
Efficiency and Power dissipation
Efficiency 93,8% (48V / 5A / 3xAC 400V)
Power dissipation 16,0W (48V / 5A / 3xAC 400V)
No-load-losses 2,3W / 3W (3xAC 400V / 3xAC 480V)
3xAC 380-500V
3xAC 320...575V 3xAC 300...620V
0,7A (3xAC 480V)
0,47 (3xAC 480V)
2
< 15,4A; < 0,26A < 15,4A; < 0,4A
characteristic
93,9% (48V / 5A / 3xAC 480V)
15,7W (48V / 5A / 3xAC 480V)
s; < 3ms (3xAC 400V)
2
s; < 3ms (3xAC 480V)
At a competitive price, it also offers 6A power boost, 9-14A short cir­cuit current, output noise suppression, selectable Single Mode or Parallel Mode, small dimensions and easy installation. Due to its wide range input the unit can be connected to 3-phase electricity networks worldwide without switching.
Output
Rated voltage DC 48V
Rated voltage range 48...52V guaranteed
46...53V typ.
Preset 48V ±0,2V and “Parallel Use”
Rated current 0-5A (at 48V)
0-6A (< 1 minute per 10 minutes)
Short-circuit current min. 9A; max. 14A
Overload behaviour Continous Mode or FUSE Mode selectable (see
Overload Behaviour)
Output power 240W
Peak power 288W (< 1 minute per 10 minutes)
Ripple/Noise typ. 8mV
Static load regulation < 100,0mV in single operation
Dynamic load regulation
Power back immunity max. 60V
Over volt protection typ. 56V DC max. 60V DC
Parallel operation Yes, up to five SL10.305
To achieve current sharing:
• Protected against short-circuit, open circuit and overload.
< 2,5V in parallel operation
typ. ±300mV 500 µs Load step10% - 90% - 10%
• Plug jumper into 'Output parallel use'. This
• Missing jumper = 'Single Use', i.e. 'hard'
/ < 30mVSS (20MHz)
SS
alters the output V/I characteristic to be 'softer' (48V bei 0,5A, 46V bei 5A). The out­put voltage can still be adjusted.
characteristic
Order information
Order number Description
SL10.305 SLZ13 SLZ02
sl10e305 / 040907 1/4
Power supply unit Adapter for S7-300rail Wall mounting set, (two pcs. per package)
Data sheet
Input 2- phase operation
Random connection to L1, L2 or L
Nominal input voltage
Input voltage range 2xAC 340...575V
Short-term (1 min.) 2xAC 300...620V
Frequency 50-60Hz ±6% (47...63Hz)
Input current 1,2A (2xAC 400V)
Power factor 0,55 (2xAC 400V)
Inrush peak current < 15,4A; < 0,26A
Recommended external fuse
Hold-up time 2 phase operation
2xAC 400V typ. 32ms; > 26ms (48V / 5A)
2xAC 480V typ. 52ms; > 42ms (48V / 5A)
Efficiency and Power dissipation 2 phase operation
Efficiency 93,0% (48V / 5A / 2xAC 400V)
Power dissipation 18,0W (48V / 5A / 2xAC 400V)
No-load-losses 2,3W / 3W (2xAC 400V / 2xAC 480V)
2xAC 400-500V (TN, IT, TT-networks)
1A (2xAC 480V)
0,53 (2xAC 480V)
< 15,4A; < 0,4A
> 6A < 32A Char. B or C
93,2% (48V / 5A / 2xAC 480V)
17,5W (48V / 5A / 2xAC 480V)
3
2
2
s (2xAC 480V)
s (2xAC 400V)
Input DC operation
Random connection, consider PE (protected earth) terminal.
For further details regarding DC-operation please check out our technical note #25 on our webpage: www.puls-power.com, navigation “know how” and “technical notes”.
Nominal input voltage
Input voltage range
Short-term (1 min.) DC 400...890V
Threshold voltage:
• turn-on DC 350V (typ.)
• shut-down DC 260V (typ.)
Input current 0,5A (DC 600V)
Inrush peak current < 14A; < 0,3A
Recommended external fuse
DC 600V
DC 450...820V
2
s (DC 600V)
6A Littlefuse KLKD
Efficiency and Power dissipation DC operation
Efficiency 94,2% (48V / 5A / DC 600V)
Power dissipation 14,8W (48V / 5A / DC 600V)
No-load-losses 2,5W (DC 600V)
Operation and environmental data
Cooling natural convection,
no forced air-cooling necessary
Operating temperature range
Derating > 60 °C: 6W/K
Guaranteed startup -10 °C
Non-operating temperature range
0 °C...+70 °C
-40 °C...+85 °C
Electromagnetic Compatibility (EMC)
Emissions EN 61000-6-3 (also includes EN 61000-6-4)
Class B (EN 55011, EN 55022) EN 61000-3-2 and EN 61000-3-3
Immunity Electrostatic Discharge (ESD)
Electromagnetic radiated fields
Burst, coupled to: ACin lines DCout lines
Surge transients Differential mode (L→PE) Common mode (L
L2 , L2 → L
1
L
3→ L 1
Conducted noise immunity
Voltage dips EN 61000-4-11
Transient immunity
3
)
EN 61000-6-2 (also includes EN 61000-6-1) EN 61000-4-2, Level 4 (withstands 8 kV direct discharge, 15 kV air discharge)
EN 61000-4-3, Level 3 (10 V/m)
EN 61000-4-4 Level 4 (4 kV) Level 3 (2 kV)
EN 61000-4-5 Installation class 4 (4 kV)
Installation class 4 (2 kV)
;
EN 61000-4-6 Level 3 (10V, 150 kHz-80 MHz)
Transient resistance acc. to VDE 0160 / W2 over entire load range
Hold-up time DC operation
DC 600V typ. 43ms; > 35ms (48V/5A)
2/4 sl10e305 / 040907
Loading...
+ 2 hidden pages