Puls SL10.305 Data Sheet

48-52V, 3-phase, 240W
SL10.305
• Input: 2 AC 400-500V
• Output: 48-52V / 240W
• Switchable operating mode (single/ parallel)
• FUSE Mode / Continuous Mode
Data sheet
3 AC 380-500V
UL60950 E137006
CUL/CSA-C22.2
No 60950
UL508 LISTED IND. CONT. EQ.
18 WM, 60°C
EMC and Low Volt. Directive
This compact power supply unit is characterised by the variety of appli­cation possibilities and low system costs. The fact that the external fuses are no longer necessary is an advantage as it saves cost and space. The selectable FUSE Mode and the fully specified 2-phase operation make the SL10.305 the unit of choice.
Input 3-phase operation
(Input 2 phase operation and DC operation see page 2)
Nominal input voltage
• Voltage range
• Short-term (1 min.)
Frequency 50-60Hz ±6% (47...63Hz)
Input current 0,8A (3xAC 400V)
Power faktor 0,5 (3xAC 400V)
Inrush peak current electronically limited
Internal fused 3x T2A5 H.B.C
Compatible external fuse6A< Si < 32A Char. B or C or similar tripping
Hold-up time
3xAC 400V typ. 36ms; > 29ms (48V / 5A)
3xAC 480V typ. 56ms; > 45ms (48V / 5A)
Efficiency and Power dissipation
Efficiency 93,8% (48V / 5A / 3xAC 400V)
Power dissipation 16,0W (48V / 5A / 3xAC 400V)
No-load-losses 2,3W / 3W (3xAC 400V / 3xAC 480V)
3xAC 380-500V
3xAC 320...575V 3xAC 300...620V
0,7A (3xAC 480V)
0,47 (3xAC 480V)
2
< 15,4A; < 0,26A < 15,4A; < 0,4A
characteristic
93,9% (48V / 5A / 3xAC 480V)
15,7W (48V / 5A / 3xAC 480V)
s; < 3ms (3xAC 400V)
2
s; < 3ms (3xAC 480V)
At a competitive price, it also offers 6A power boost, 9-14A short cir­cuit current, output noise suppression, selectable Single Mode or Parallel Mode, small dimensions and easy installation. Due to its wide range input the unit can be connected to 3-phase electricity networks worldwide without switching.
Output
Rated voltage DC 48V
Rated voltage range 48...52V guaranteed
46...53V typ.
Preset 48V ±0,2V and “Parallel Use”
Rated current 0-5A (at 48V)
0-6A (< 1 minute per 10 minutes)
Short-circuit current min. 9A; max. 14A
Overload behaviour Continous Mode or FUSE Mode selectable (see
Overload Behaviour)
Output power 240W
Peak power 288W (< 1 minute per 10 minutes)
Ripple/Noise typ. 8mV
Static load regulation < 100,0mV in single operation
Dynamic load regulation
Power back immunity max. 60V
Over volt protection typ. 56V DC max. 60V DC
Parallel operation Yes, up to five SL10.305
To achieve current sharing:
• Protected against short-circuit, open circuit and overload.
< 2,5V in parallel operation
typ. ±300mV 500 µs Load step10% - 90% - 10%
• Plug jumper into 'Output parallel use'. This
• Missing jumper = 'Single Use', i.e. 'hard'
/ < 30mVSS (20MHz)
SS
alters the output V/I characteristic to be 'softer' (48V bei 0,5A, 46V bei 5A). The out­put voltage can still be adjusted.
characteristic
Order information
Order number Description
SL10.305 SLZ13 SLZ02
sl10e305 / 040907 1/4
Power supply unit Adapter for S7-300rail Wall mounting set, (two pcs. per package)
Data sheet
Input 2- phase operation
Random connection to L1, L2 or L
Nominal input voltage
Input voltage range 2xAC 340...575V
Short-term (1 min.) 2xAC 300...620V
Frequency 50-60Hz ±6% (47...63Hz)
Input current 1,2A (2xAC 400V)
Power factor 0,55 (2xAC 400V)
Inrush peak current < 15,4A; < 0,26A
Recommended external fuse
Hold-up time 2 phase operation
2xAC 400V typ. 32ms; > 26ms (48V / 5A)
2xAC 480V typ. 52ms; > 42ms (48V / 5A)
Efficiency and Power dissipation 2 phase operation
Efficiency 93,0% (48V / 5A / 2xAC 400V)
Power dissipation 18,0W (48V / 5A / 2xAC 400V)
No-load-losses 2,3W / 3W (2xAC 400V / 2xAC 480V)
2xAC 400-500V (TN, IT, TT-networks)
1A (2xAC 480V)
0,53 (2xAC 480V)
< 15,4A; < 0,4A
> 6A < 32A Char. B or C
93,2% (48V / 5A / 2xAC 480V)
17,5W (48V / 5A / 2xAC 480V)
3
2
2
s (2xAC 480V)
s (2xAC 400V)
Input DC operation
Random connection, consider PE (protected earth) terminal.
For further details regarding DC-operation please check out our technical note #25 on our webpage: www.puls-power.com, navigation “know how” and “technical notes”.
Nominal input voltage
Input voltage range
Short-term (1 min.) DC 400...890V
Threshold voltage:
• turn-on DC 350V (typ.)
• shut-down DC 260V (typ.)
Input current 0,5A (DC 600V)
Inrush peak current < 14A; < 0,3A
Recommended external fuse
DC 600V
DC 450...820V
2
s (DC 600V)
6A Littlefuse KLKD
Efficiency and Power dissipation DC operation
Efficiency 94,2% (48V / 5A / DC 600V)
Power dissipation 14,8W (48V / 5A / DC 600V)
No-load-losses 2,5W (DC 600V)
Operation and environmental data
Cooling natural convection,
no forced air-cooling necessary
Operating temperature range
Derating > 60 °C: 6W/K
Guaranteed startup -10 °C
Non-operating temperature range
0 °C...+70 °C
-40 °C...+85 °C
Electromagnetic Compatibility (EMC)
Emissions EN 61000-6-3 (also includes EN 61000-6-4)
Class B (EN 55011, EN 55022) EN 61000-3-2 and EN 61000-3-3
Immunity Electrostatic Discharge (ESD)
Electromagnetic radiated fields
Burst, coupled to: ACin lines DCout lines
Surge transients Differential mode (L→PE) Common mode (L
L2 , L2 → L
1
L
3→ L 1
Conducted noise immunity
Voltage dips EN 61000-4-11
Transient immunity
3
)
EN 61000-6-2 (also includes EN 61000-6-1) EN 61000-4-2, Level 4 (withstands 8 kV direct discharge, 15 kV air discharge)
EN 61000-4-3, Level 3 (10 V/m)
EN 61000-4-4 Level 4 (4 kV) Level 3 (2 kV)
EN 61000-4-5 Installation class 4 (4 kV)
Installation class 4 (2 kV)
;
EN 61000-4-6 Level 3 (10V, 150 kHz-80 MHz)
Transient resistance acc. to VDE 0160 / W2 over entire load range
Hold-up time DC operation
DC 600V typ. 43ms; > 35ms (48V/5A)
2/4 sl10e305 / 040907
Diagramme
Data sheet
t [ms]
Output characteristic (min. at V
56
[V]
48
out
40
=400VAC3Ph)
0ut
3
32
1
24
Output voltage V
16
8
0
024681012
2
Output current I
out
Hold-up time 2-phase Hold-up time 3-phase
[A]
1 Jumper-setting “single use” (fixed characteristic)
2 Jumper-setting “parallel use” (inclined characteristic)
3 Power Boost:
Higher current for a short period of time (< 1 minute or even longer with forced ventilation) without volta­ge breaking down. Optimum fit to peak load require­ments and oversizing of power supplies is not needed anymore.
Overload Design
TM
:
Extended output characteristic curve with a high short current at a gradually reduced output voltage. Unit does not switch off, when the rated current is exeeded. The high short current reliably starts heavy loads such as DC-motors or capacitive loads and blows branch fuses.
t [ms]
Output Current I
Power dissipation 2xAC 400V & 2xAC 500V
[W]
loss
P
Vin [VAC]
[A]
out
Efficiency 3xAC 400V & 3xAC 500VEfficiency 2xAC 400V & 2xAC 500V
Output current I
Power dissipation 3xAC 400V & 3xAC 500V
[W]
loss
P
out
Vin [V
[A]
AC
]
Output current I
out
[A]
Output current I
out
[A]
sl10e305 / 040907 3/4
Data sheet
Overload Behaviour
Two different operating mode options, switchable by plugging the front­panel jumper. If the jumper is missing, the unit is set to FUSE Mode. The unit is preset to Continuous Mode at shipment.
a) FUSE Mode (Switch-off after typ. 5s):
• Jumper is in the 'OVL FUSE mode' position.
• When overload or short-circuit occurs for more than typ. 5s, the unit switches off the output.
• Definition of overload or short-circuit: The set output voltage in each case can no longer be maintained.
• Power Boost and Overload Design™ remain unchanged during the typ. 5s delay time.
Red LED flashes at switch-off.
b) Continuous Mode (continuous current):
• Jumper is in the 'OVL cont. mode' position.
• When overload or short-circuit occurs, the unit continuously supp­lies current (see. diag. 1), no Hiccup.
Re-start:
• by pushing the reset button on the unit’s front panel
• by disconnection from mains and re-start of the unit after > 1 min. or as soon as the red LED stops flashing
• With some applications, the FUSE Mode can replace the usual fu­sing on the secondary side. The FUSE Mode has closer tolerances than thermal trips.The tripping delay time of typ. 5s enables heavy loads to start and thereby avoids unneccassary service activities.
Overtemperature Protection
Continuous Mode Switch-off and automatic re-start after cooling.
FUSE Mode Unit remains switched off after overheating until
restart (also see ’Re-start’ above).
Start Behaviour
Startup delay Rise time
typ. 200ms appr. 5-20ms, depending on load
Connectors and terminals
Terminals Proofed terminals with captive screws for 5.5
mm slotted screwdriver or Philips cross-recessed screwdriver No. 2. Input terminals are equipped
with an additional protection cover.
Position Easy to reach terminals on the front panel;
input and output clearly separate from each other
Tightening torque 0,8Nm
Wire gauge
• flexible cable
solid cable
Ferrules admissible
Stripping length 7mm
0,5 - 4mm 0,5 - 6mm
Front elements
PE terminal
L1, L2, L3 Input phase 1 to 3.
Construction / Mechanics
Degree of protectionIP20
Dimensions
Width Height Depth
Weight 1040g
Random connection to L DC-operation.
089 mm
124 mm 117 mm (without DIN rail)
2
(20-10 AWG)
2
(20-10 AWG)
, L2 or L3 at
1
Installation notes
External fusing • not necessary (internal fuse)
Mounting position vertical; input below, output above
Free space for cooling
Specifications valid for 3 x AC 400V input voltage, +25°C ambient temperature, and 5 min run-in time, unless otherwise stated. They are subject to change without prior notice. This datasheet and other documents regarding this power supply are available online through our webpage: www.puls-power.com/SL10.305
Your partner in power supply:
• observe national regulations
“external” fusing recommended, please
refer to input section, page 1.
above / below 25mm recommended left / right 15mm recommended
European Power Supply Manufacturers Association
Bayerns Best 50 Czech 100 Best EuropeÕs 500
PULS GmbH
Arabellastraße 15
D-81925 München
Tel.: +49 89 9278-0
Fax: +49 89 9278-299
www.puls-power.com
4/4 sl10e305 / 040907