Modern machines typically use maintenance-free ACmotors which are controlled by frequency converters
or servo amplifiers. Such devices have an
intermediate DC-bus where all individual drives are
connected.
The QTD20 power supply can be connected directly
to the intermediate DC-bus. In case of a mains
failure, the QTD20 utilizes the kinetic energy from
the motor and the DC-bus capacitors to keep the
controls and other important peripheral equipment
operational until the motor is in a complete stop
position. With the QTD20 mains failure can be
handled with no problems.
Intermediate DC-buses are not usually filtered and
have high EMI noise superimposed. The QTD20 has a
very robust input stage and an appropriate input
filter included.
L1
L2
L3
PE
+
PE
f
f
QTD
+
-
PE
+
-
DC Load,
Controller
Additionally, the
Motor
QTD20 is UL 508
approved and is
equipped with
Motor
input fuses which
are rated and
tested for 600V
applications.
QTD20.241
24V, 20A, DC INPUT
POWER SUPPLY
• 600Vdc Input Voltage
• Optimized for Intermediate DC-busses of Drive Systems
• Two Input Fuses for 600Vdc Included
• Efficiency up to 95%
• Width only 65mm
• 125% Peak Load Capability
• Active Input Transient Filter
• Full Power Between -25°C and +60°C
• Minimal Inrush Current
• DC-OK Relay Contact
• Quick-connect Spring-clamp Terminals
• 3 Year Warranty
2. SHORT-FORM DATA
Output voltage DC 24V
Adjustment range 24-28V
Output current 20A continuous, 24V
25A for typ. 4s, 24V
Output power 480W continuous, 24V
600W for typ. 4s, 24V
Output ripple < 100mVpp 20Hz to 20MHz
Input voltage DC 600V
480-840Vdc continuous
Input current 0.85A 600Vdc, 24V, 20A
Inrush current typ. 1.5A peak
Efficiency 95.0% at 600Vdc
Losses 25.5W at 600Vdc
Temperature range -25°C to +70°C operational
Derating 12W/°C +60 to +70°C
Hold-up time typ. 22ms at 600Vdc
Dimensions 65x124x127mm wxhxd
360-480Vdc
840-900Vdc
< 1 minute
or with reduced
output current
3. ORDER NUMBERS
Power Supply
Accessory ZM1.WALL Wall mount bracket
ZM14.SIDE Side mount bracket
YR2.DIODE Decoupling module
UF20.241 Buffer unit
Jan. 2007 / Rev. 1.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
QTD20.241
600VÆ24V Converter
www.pulspower.com Phone +49 89 9278 0 Germany
4. MARKINGS
LISTED
IND. CONT. EQ.
UL 508, pending
18WM
EMC, LVD
1/22
Q-Series
QTD20.241
24V, 20A, DC INPUT
INDEX PAGE INDEX PAGE
1.
General Description ............................................1
2. Short-form Data ..................................................1
3. Order Numbers....................................................1
The power supply shall only be installed and put into operation by qualified personnel.
This power supply is designed for installation in an enclosure and is intended for the general use, such as in industrial
control, office, communication, and instrumentation equipment. Do not use this device in aircraft, trains and nuclear
equipment, where malfunctioning of the power supply may cause severe personal injury or threaten human life.
TERMINOLOGY AND ABREVIATIONS
PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol .
Earth, Ground This document uses the term “earth” which is the same as the U.S. term “ground”.
T.b.d. To be defined, value or description will follow later.
DC 600V A figure displayed with the AC or DC before the value represents a nominal voltage with
standard tolerances (usually ±15%) included.
E.g.: DC 12V describes a 12V battery regardless whether it is charged (13.7V) or discharged
(10V)
600Vdc A figure with the unit (Vdc) at the end is a value which is used during testing without any
additional tolerances included.
DISCLAIMER
The information presented in this document is believed to be accurate and reliable and may change without notice.
Jan. 2007 / Rev. 1.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
2/22
Q-Series
QTD20.241
24V, 20A, DC INPUT
5. INPUT
Input
Input voltage range
360-480Vdc max. 60 seconds or with de-rating according to Fig. 7-2
Allowed voltage between input
and earth (ground)
max. ±900V peak value, allowed for transients
Slew rate for voltage between
input and earth (ground)
Allowed input ripple voltage max. 50Vpp 50Hz-40kHz
Turn-on voltage typ. 450Vdc Steady-state value, see Fig. 5-1
Shut-down voltage typ. 325Vdc Steady-state value, see Fig. 5-1
Input current
Start-up delay typ. 350ms See Fig. 5-2
Rise time typ. 70ms 0mF, 24V, 20A, see Fig. 5-2
Turn-on overshoot
External capacitors on the input voltage bus are allowed without any limitations.
Fig. 5-1 Input voltage range
nom. DC 600V
nom. 480-840Vdc continuous operation
840-900Vdc max. 60 seconds or with de-rating according to Fig. 7-21000Vdc Absolute maximum input voltage with no damage to the
power supply. Above 900Vdc, the output will switch off
and will turn-on again when the voltage falls below 850V.
max. 600V R.M.S. continuously allowed
max. 1000V/µs
typ. 0.85A At 600Vdc input, 24V, 20A, see Fig. 5-3
typ. 110ms 20mF, 24V, 20A, see Fig. 5-2
max. 500mV See Fig. 5-2
P
OUT
BA
B
A: continuously allowed
: < 60s or with derating
Shut-down
325Vdc
360Vdc
B
Turn-on
450Vdc
480Vdc
V
IN
900Vdc
840Vdc
Fig. 5-2 Turn-on behavior, definitions Fig. 5-3 Input current at 600Vdc vs. output load
Intput
Voltage
Output
Voltage
Jan. 2007 / Rev. 1.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
- 5%
Start-up
delay
Rise
Time
Overshoot
www.pulspower.com Phone +49 89 9278 0 Germany
1.0A
0.8
0.6
0.4
0.2
0
2 4 6 8 10 12 14 16 18
Input Current, typ.
Output Current
20A
3/22
Q-Series
QTD20.241
24V, 20A, DC INPUT
6. INPUT INRUSH CURRENT
An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage and after short
input voltage interruptions.
The charging current into the EMI suppression capacitors is disregarded for the first millisecond after switch-on.
Inrush current max. 3A
typ. 1.5A
Inrush energy
Inrush delay
max. 1A2s -25°C to +70°C
typ. 350ms
Fig. 6-1 Input inrush current, typical behavior
Input Voltage
Output Voltage
A
Input Current
600Vdc
-25°C to +70°C
peak
-25°C to +70°C
peak
A: Inrush delay
Input: 600Vdc
Output: 24V, 20A
Ambient: 25°C
Upper curve: Input voltage 100V / DIV
Medium curve: Output voltage 5V / DIV
Lower curve: Input current 1A / DIV
Time basis: 100ms / DIV
Jan. 2007 / Rev. 1.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/22
Q-Series
QTD20.241
24V, 20A, DC INPUT
7. OUTPUT
Output voltage
Adjustment range
max. 30V at clockwise end position of potentiometer
Factory setting
Line regulation
Load regulation max. 100mV static value, 0A Æ 20A Æ 0A
Ripple and noise voltage
Output capacitance
Continuous output power capability
Output current
Output power
Short-circuit current min. 20A load impedance 50mOhm, see Fig. 7-1max. 23A load impedance 50mOhm, see Fig. 7-1
nom. 24V
min. 24-28V guaranteed, multi turn potentiometer
max. 10mV 480Vdc Æ 840Vdc Æ 480Vdc, 24V, 20A
max. 100mVpp 20Hz to 20MHz, 50Ohm
typ. 1 000µF The energy of the bulk capacitor on the input side will be
nom. 20A at 24V see Fig. 7-1,
nom. 17.5A
nom. 480W at 24-28V, between 480Vdc and 840Vdc
24.1V
±0.2%, at full load, cold unit
transferred to the output to supply short load peaks.
Note: derating below 480Vdc and above 840Vdc, see Fig. 7-2
at 28V see
a derating is required below 480Vdc and above 840Vdc
Note: derating below 480Vdc and above 840Vdc, see
Fig. 7-1,
Fig. 7-2
BonusPower®, short term output power capability (up to typ. 4s)
The power supply is designed to support loads with a higher short-term power requirement without damage or
shutdown. The short-term duration is hardware controlled by an output power manager. The BonusPower
repeatedly available. Detailed information can be found in chapter 26.1 .
Once BonusPower® has been stopped by the output power limiter, a timer disables the next BonusPower® capability.
This timer (recovery time) will start as soon as the output voltage reaches the adjusted value again, which usually
happens after the load has been reduced.
Output current
Output power
Short-circuit current min. 25A load impedance 50mOhm, see Fig. 7-1max. 28A load impedance 50mOhm, see Fig. 7-1
Bonus time
min 3.5s see Fig. 7-3
BonusPower® recovery time
nom. 25A at 24V, between 480Vdc and 840Vdc, see Fig. 7-1
Note: derating below 480Vdc and above 840Vdc, see
nom. 21.4A
nom. 600W 24-28V, short term
typ. 4s at 24V, > 25A, duration until the output voltage dips,
max. 4.5s
typ. 7s Overload free time to reset power manager, see Fig. 7-4
at 28V, between 480Vdc and 840Vdc, see
a derating is required below 480Vdc and above 840Vdc
Fig. 7-1
®
is
Fig. 7-2
Jan. 2007 / Rev. 1.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/22
Q-Series
QTD20.241
24V, 20A, DC INPUT
Fig. 7-1 Output voltage vs. output current, typ. Fig. 7-2 Output current vs. input voltage
Output Voltage
28V
24
20
16
12
8
4
0
Adjustment
Range
c
o
n
t
i
n
u
o
u
s
Output Current
05102025
1530A
s
h
o
r
t
-
t
e
r
m
Allowed Output
Current at 24V
25A
20
<
0
15
6
10
5
0
360
480
Vdc
Vdc
s
f
o
r
t
y
.
p
s
4
c
o
n
t
i
u
n
u
o
Input Voltage
s
Fig. 7-3 Bonus time vs. output power
Bonus Time
5s
4
3
m
x
a
.
m
i
n
.
2
1
0
105110115120125
Output Power
130%
Fig. 7-4 BonusPower® recovery time
Limitation by
Power
Demand
<125%
Bonus
Time
Power Manager
Recovery Time
Bonus Power disabled
Output
Voltage
100%
Bonus Power
®
is available as soon as power comes on and immediately after the end of an output short circuit.
Fig. 7-5 BonusPower® after input turn-on
Fig. 7-6 BonusPower® after output short
6
<
840
Vdc
s
0
900
Vdc
100%
Short of
Output
125%
Bonus
Power
Intput
Voltage
Output
Voltage
100%
125%
Bonus
Power
Output
Voltage
Output
Power
Output
Power
Jan. 2007 / Rev. 1.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
6/22
Q-Series
QTD20.241
24V, 20A, DC INPUT
8. HOLD-UP TIME
600Vdc
Hold-up Time typ. 22ms 20A, 24V, see
typ. 44ms 10A, 24V, see Fig. 8-1
Fig. 8-1 Hold-up time vs. input voltage Fig. 8-2 Shut-down behavior, definitions
Hold-up Time
50ms
40
V,
4
2
V,
4
2
.
p
y
t
,
A
0
1
.
n
i
m
,
A
0
1
30
.
p
y
t
,
A
20
0
2
,
V
4
2
.
i
n
m
,
A
0
2
,
V
4
2
10
0
400500600700800Vdc
Input Voltage
Fig. 8-1
Intput
Voltage
Output
Voltage
Hold-up Time
- 5%
9. DC-OK RELAY CONTACT
This feature monitors the output voltage, which is produced by the power supply itself. It is independent of a back-
fed voltage from a unit which is connected in parallel to the power supply output.
Contact closes As soon as the output voltage reaches the adjusted output voltage.
Contact opens As soon as the output voltage dips more than 10% below the adjusted output voltage.
Contact re-closes As soon as the output voltage exceeds 90% of the adjusted voltage.
Isolation voltage See dielectric strength table in section 19
Fig. 9-1 DC-ok relay contact behavior
V
=
V
OUT
ADJ
90%
V
ADJ
open
<
1ms
Short dips will be extended to a signal length of 250ms. Dips shorter than 1ms will be ignored.
Note:
The DC-ok feature requires that the output voltage
10%
reaches the nominal (=adjusted) level after turn-on in
order to function according to specification. If this level
cannot be achieved, the overload LED will be on and
>
1ms
250ms
the DC-ok contact will be open. The overload signal will
only shut off as soon as the adjusted voltage is reached.
This is an important condition to consider particularly, if
the load is a battery, the power supply is used in
openclosedclosed
parallel or the power supply is used for N+1 redundant
systems.
Jan. 2007 / Rev. 1.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
Fig. 10-1 Efficiency vs. output current at 24V Fig. 10-2 Losses vs. output current at 24V
Efficiency
96%
95
94
93
92
91
90
89
88
4 6 8 101214161820
Output Current
Fig. 10-3 Efficiency vs. input voltage, 24V, 20A Fig. 10-4 Losses vs. input voltage, 24V, 20A
Efficiency
95.5%
95.0
94.5
94.0
93.5
93.0
92.5
350450650750850
Input Voltage
550
Vd
Power Losses
30W
25
20
15
10
5
0
0246810121420
Power Losses
35W
33.0
31.0
29.0
27.0
25.0
23.0
350450550650850
Output Current
Input Voltage
750
16 18
Vd
Jan. 2007 / Rev. 1.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
8/22
Q-Series
11. FUNCTIONAL DIAGRAM
Fig. 11-1 Functional diagram
+
-
Input
Fuses
(in + and pole)
Temper-
ature
Shutdown
Input Filter
Inrush Current
Limiter
Transient Filter
Output
Power
Manager
Output
Over-
Voltage
Protection
Power
Converter
Output
Voltage
Monitor
Output
Voltage
Regulator
Output
Filter
DC ok
Relay
QTD20.241
24V, 20A, DC INPUT
V
OUT
+
+
-
-
Overload
DC
ok
DC
ok
12. FRONT SIDE AND USER ELEMENTS
Fig. 12-1 Front side
Output Terminals
Quick-connect spring-clamp
terminals, no tools required
+ Positive output
- Negative (return) output
Dual pins per pole
DC ok Relay contact
(NO-contact)
Input Terminals
Quick-connect spring-clamp
terminals, no tools required
+ - Power input
PE (Protective Earth) input
See chapter 13 “Terminals and
Wiring” to choose appropriate
wire gauges
Output voltage potentiometer
(multi turn potentiometer)
Open the flap to set the output voltage.
Factory setting: 24.1V
DC-ok LED (green)
Overload LED (red)
Normal mode OFF ON Closed
BonusPower®
mode
Overload
< 90%)
(V
OUT
Short-circuit
= ca. 0V)
(V
OUT
Overtemperature
No input power OFF OFF Open
Overload
LED
OFF ON Closed
ON OFF Open
ON OFF Open
ON OFF
DC-ok
LED
DC-ok
contact
Open
The DC-ok LED and the DC-ok contact
functions are synchronized
Jan. 2007 / Rev. 1.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
9/22
Q-Series
QTD20.241
24V, 20A, DC INPUT
13. TERMINALS AND WIRING
Type Bi-stable, quick-connect spring clamp terminals. IP20 Finger safe construction.
Suitable for field- and factory installation. Shipped in open position.
Solid wire 0.5-6mm
Stranded wire 0.5-4mm2
American wire gauge 20-10 AWG
Ferrules Allowed, but not required
Wire stripping length 10mm / 0.4inch
Pull-out force 10AWG:80N, 12AWG:60N, 14AWG:50N, 16AWG:40N (according to UL486E)
Fig. 13-1 Connecting a wire
1.
Insert the wire
To disconnect wire:
reverse the procedure
2.
Close the lever
2
Instructions:
a) Use appropriate copper cables that are designed
for an operating temperature of:
Input: 60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum.
Output: 75°C for ambient up to 40°C and
95°C for ambient up to 60°C minimum.
b) Follow local and national installation codes and
installation regulations!
c) Ensure that all strands of a stranded wire enter
the terminal connection!
d) Up to two stranded wires with the same cross
section are permitted in one connection point
(except PE wire).
The Lifetime expectancy shown in the table above indicates the operating hours (service life) and is determined by
the lifetime expectancy of the built-in electrolytic capacitors.
Lifetime expectancy is specified in operational hours and is calculated according to the capacitor’s manufacturer
specification. The prediction model allows a calculation of up to 15 years from date of shipment.
MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates
reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily
represent the life of a product.
Jan. 2007 / Rev. 1.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
600Vdc
www.pulspower.com Phone +49 89 9278 0 Germany
10/22
Q-Series
QTD20.241
24V, 20A, DC INPUT
15. EMC
The power supply is suitable for applications in industrial environments without any restrictions. The CE mark is in
conformance with EMC guideline 89/336/EEC and 93/68/EEC and the low-voltage directive (LVD) 73/23/EEC. A detailed
EMC Report is available upon request
EMC Immunity
Electrostatic discharge EN 61000-4-2 Contact discharge
Electromagnetic RF field EN 61000-4-3 80MHz-1GHz 10V/m Criterion A
Fast transients (Burst) EN 61000-4-4 Input lines
Surge voltage on input EN 61000-4-5 + Æ - 1000V Criterion A
Surge voltage on input EN 61000-4-5 + Æ PE, - Æ PE 4kV Criterion A
Surge voltage on output EN 61000-4-5 + Æ -
Conducted disturbance EN 61000-4-6 0.15-80MHz 10V Criterion A
Criteria:
A: Power supply shows normal operation behavior within the defined limits.
EMC Emission
Conducted emission EN 55011, EN 55022 N/A *)
Radiated emission EN 55011, EN 55022 Class A
*) There are no mandatory requirements in the generic standard EN 61000-6-4 for conducted emission on DC lines (input and
output). For the assessment of the conducted emission, the input filter of the frequency converter or servo amplifier need to be
taken into account.
Switching Frequencies
Switching frequency 1 100kHz Nearly constant
Switching frequency 2 30kHz to 90kHz Input voltage and load dependent
Switching frequency 3 17kHz to 120kHz Input voltage and load dependent
EN 61000-6-1, EN 61000-6-2, EN-61800-3
Air discharge
Output lines
+ / - Æ PE
EN 61000-6-4, EN-61800-3 Generic and product standards
The power supply has three converters with three different switching frequencies
included. One is nearly constant. The other two are input voltage and load dependent.
Generic and product standards
8kV
15kV
2kV
2kV
500V
500V
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Jan. 2007 / Rev. 1.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
11/22
C
Q-Series
QTD20.241
24V, 20A, DC INPUT
16. ENVIRONMENT
Operational temperature -25°C to +70°C (-13°F to 158°F) Reduce output power above +60°C
Output de-rating 12W/°C 60-70°C (140°F to 158°F), see Fig. 16-1
Storage temperature -40 to +85°C (-40°F to 185°F) Storage and transportation
Humidity 5 to 95% r.H. IEC 60068-2-30
Vibration sinusoidal 2-17.8Hz: ±1.6mm;
17.8-500Hz: 2g
2 hours / axis
2(s3
Vibration random
0.5m
2 hours / axis
)
Shock 30g 6ms, 20g 11ms
3 bumps / direction,
18 bumps in total
Altitude 0 to 6000m (0 to 20 000ft) Reduce output power or ambient temperature
Output de-rating (for altitude) 30W/1000m or 5°C/1000m above 2000m, see Fig. 16-2
Over-voltage category III EN 50178, altitudes up to 2000m
II Altitudes from 2000m to 6000m
Degree of pollution 2 EN 50178, non conductive
Fig. 16-1 Output current vs. ambient temp., Fig. 16-2 Output current vs. altitude
Allowed Output
Current at 24V
30A
25
20
15
10
5
0
-2502040
Ambient Temperature
f
r
o
t
y
p
4
.
s
c
o
i
t
n
u
n
u
o
s
70°
60
The ambient temperature is defined as the air temperature 2cm below the unit.
Do not energize while condensation is present
IEC 60068-2-6
IEC 60068-2-64
IEC 60068-2-27
above 2000m sea level.
Allowed Output
Current at 24V
30A
f
25
20
15
10
5
0
020004000
4
s
.
p
y
t
r
o
C
c
o
n
t
i
u
n
s
u
o
.
A
.
a
.
T
b
m
<
6
C
°
B
.
.
.
T
C
.
.
.
T
0
a
b
m
<
5
C
°
0
a
b
m
<
4
C
°
0
A
Altitude
B
6000m
Jan. 2007 / Rev. 1.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
12/22
Q-Series
QTD20.241
24V, 20A, DC INPUT
17. PROTECTION FEATURES
Output protection Electronically protected against overload, no load and short circuits *)
Output over-voltage protection typ. 32Vdc
max. 35Vdc
Degree of protection IP 20 EN/IEC 60529
Penetration protection > 3.5mm e.g. screws, small parts
Over-temperature protection yes Output shut-down with automatic restart
Input transient protection MOV (Metal Oxide Varistor) and active transient filter
Internal input fuse 5A, midget size
*) An audible noise may be heard during a no load, overload or short circuit event.
fast acting type
2 times
(+ line and - line)
In case of an internal power supply fault, a redundant
circuit limits the maximum output voltage. The output
shuts-down and automatically attempts to restart.
The unit is equipped with two internal input fuses which
protect the unit against internal short circuits and ground
faults. The fuses are not user accessible. A tripping of an
internal fuse is caused by an internal fault.
18. SAFETY
Input / output separation SELV IEC/EN 60204-1
PELV EN 60204-1, EN 50178, IEC 60364-4-41
double or reinforced insulation
Class of protection I PE (Protective Earth) connection required
Isolation resistance > 5MOhm Input to output, 500Vdc
PE resistance < 0.1Ohm Between housing and PE terminal
Touch current (leakage current) The leakage current which is produced by the power supply itself depends on the
input voltage ripple and need to be investigated in the final application.
For a smooth DC input voltage, the produced leakage current is less than 100µA.
19. DIELECTRIC STRENGTH
Fig. 19-1 Dielectric strength
InputDC-ok
+
-
A
Earth
B
B
C
D
Output
+
-
Type test 60s 2500Vac 3000Vac 500Vac 500Vac
Factory test 5s 2500Vac 2500Vac 500Vac 500Vac
Field test 5s 2000Vac 2000Vac 500Vac 500Vac
Type tests and factory tests:
Conducted by the manufacturer. Do not repeat test in field!
Rules for field test:
Use appropriate test equipment which applies the voltage
with a slow ramp! Connect L1, L2 and L3 together as well as
all output poles.
A B C D
The output voltage is floating and has no ohmic connection to ground.
To fulfill the PELV requirements according to EN60204-1 paragraph 6.4.1, PULS recommend that either the + pole or
the – pole shall be connected to the protective earth system. This helps to avoid situations in which a load starts
unexpectedly or cannot be switched off when an unnoticed ground fault occurs.
Jan. 2007 / Rev. 1.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
13/22
Q-Series
24V, 20A, DC INPUT
20. APPROVALS
UL 508
pending
18WM
LISTED
IND. CONT. EQ.
LISTED E198865
Industrial Control Equipment
21. FULFILLED STANDARDS
EN 61558-2-17 Safety of Power Transformers
EN/IEC 60204-1 Safety of Electrical Equipment of Machines
EN/IEC 61131-2 Programmable Controllers
EN 50178, IEC 62103 Electronic Equipment for Use in Power Installations
EN 61800-5 Adjustable speed electrical power drive systems, Safety requirements
QTD20.241
22. USED SUBSTANCES
The unit does not release any silicone and is suitable for the use in paint shops.
Electrolytic capacitors included in this unit do not use electrolytes such as Quaternary Ammonium Salt Systems.
Plastic housings and other molded plastic materials are free of halogens, wires and cables are not PVC insulated.
The materials used in our production process do not include the following toxic chemicals:
Polychlorinated Biphenyl (PCB), Polychlorinated Biphenyl (PCB), Pentachlorophenol (PCP), Polychlorinated naphthalene
(PCN), Polybrominated Biphenyl (PBB), Polybrominated Biphenyl Oxide (PBO), Polybrominated Diphenyl Ether (PBDE),
Polychlorinated Diphenyl Ether (PCDE), Polybrominated Diphenyl Oxide (PBDO), Cadmium, Asbestos, Mercury, Silica
Jan. 2007 / Rev. 1.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
14/22
Q-Series
QTD20.241
24V, 20A, DC INPUT
23. PHYSICAL DIMENSIONS AND WEIGHT
Weight 890g / 1.96lb
DIN-Rail Use 35mm DIN-rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm.
The DIN-rail height must be added to the depth (127mm) to calculate the total required
installation depth.
CAD files with mechanical data can be downloaded at www.pulspower.com
Fig. 23-1 Front view Fig. 23-2 Side view
24. INSTALLATION AND OPERATION INSTRUCTIONS
Mounting and installation:
Output terminal must be located on top and input terminal on the bottom. For other orientations see section 26.10.
An appropriate electrical and fire end-product enclosure should be considered in the end use application.
Cooling:
Convection cooled, no forced cooling required. Do not cover ventilation grill (e.g. cable conduits) by more than 30%!
Installation clearances:
40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently
with full power. If the adjacent device is a heat source, 15mm clearance is recommended.
Risk of electrical shock, fire, personal injury or death!
Do not use the unit without proper earth connection (Protective Earth). Use the pin on the terminal block for earth
connection and not one of the screws on the housing.
Turn power off before working on the power supply. Protect against inadvertent re-powering.
Make sure the wiring is correct by following all local and national codes.
Do not open, modify or repair the unit.
Use caution to prevent any foreign objects from entering into the housing.
Do not use in wet locations or in areas where moisture or condensation can be expected.
Service parts:
The unit does not contain any serviceable parts. The tripping of an internal fuse is caused by an internal fault. If
damage or malfunctioning should occur, immediately turn power off and send the unit back to the factory for
inspection!
Jan. 2007 / Rev. 1.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
15/22
Q-Series
QTD20.241
24V, 20A, DC INPUT
25. ACCESSORIES
ZM1.WALL Wall mounting bracket
This bracket is used to mount Dimension units onto a flat surface without utilizing a DIN-Rail. The two aluminum
brackets and the black plastic slide of the unit have to be removed, so that the two steel brackets can be mounted.
ZM14.SIDE Side mounting bracket
This bracket is used to mount specific Dimension units sideways with or without utilizing a DIN-Rail. The two
aluminum brackets and the black plastic slide of the unit have to be detached, so that the steel brackets can be
mounted.
For sideways DIN-rail mounting, the removed aluminum brackets and the black plastic slide need to be mounted on
the steel bracket.
Fig. 25-3 ZM14.SIDE Side Mounting Bracket
Panel Mount
Fig. 25-4 ZM14.SIDE Side Mounting Bracket
DIN-Rail Mount
Jan. 2007 / Rev. 1.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
16/22
Q-Series
QTD20.241
24V, 20A, DC INPUT
26. APPLICATION NOTES
26.1. REPETITIVE PULSE LOADING
Typically, a load current is not constant as it varies over time. For pulse load compatibility the following rules must be
met:
a) The pulse power demand must be below 125% of the nominal power.
b) The duration of the pulse power must be shorter than the allowed Bonus Time. (see output section)
c) The average (R.M.S.) output current must be below the specified continuous output current.
If the R.M.S. current is higher, the unit will respond with a thermal shut-down after a period of time. Use the
"Max. Duty Cycle Curve" (
d) The duty cycle must be below 0.75.
e) For altitudes higher than 2000m reduce the pulse loading (15W/1000m) or the ambient temperature (5°C/1000m)
Jan. 2007 / Rev. 1.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
17/22
Q-Series
QTD20.241
24V, 20A, DC INPUT
26.2. BACK-FEEDING LOADS
Loads such as decelerating motors and inductors can feed voltage back to the power supply. This feature is also called
return voltage immunity or resistance against Back- E.M.F. (Electro Magnetic Force).
This power supply is resistant and does not show adverse effects when a load feeds back voltage to the power supply.
It does not matter, whether the power supply is on or off.
The maximum allowed feed back voltage is 34Vdc. The absorbing energy can be calculated according to the built-in
large sized output capacitor which is specified in chapter 7.
CHARGING OF BATTERIES
The power supply can be used to charge lead-acid or maintenance free batteries. (Two 12V batteries in series)
Instructions for charging batteries:
a) Set output voltage (measured at the battery) very precisely to the end-of-charge voltage.
End-of-charge voltage 27.8V 27.5V 27.15V 26.8V
Battery temperature 10°C 20°C 30°C 40°C
b) Use a 25A circuit breaker (or blocking diode ) between the power supply and the battery.
c) Ensure that the output current of the power supply is below the allowed charging current of the battery.
d) Use only matched batteries when putting 12V types in series.
e) The return current to the power supply is typ. 16mA at 25Vdcwhen the power supply is switched off (except in
case a blocking diode is utilized).
Jan. 2007 / Rev. 1.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
18/22
Q-Series
QTD20.241
24V, 20A, DC INPUT
26.3. OUTPUT CIRCUIT BREAKERS
Standard miniature circuit breakers (MCBs or UL1077 circuit breakers) can be used for branch protection. Ensure that
the MCB is rated for DC voltage, too. The following tests show which circuit breakers the power supply typically trips.
Circuit breakers have huge tolerances in their tripping behavior. Therefore, these typical tests can only be used as a
recommendation or for comparing two different power supplies. Furthermore, the loop impedance has a major
influence on whether a breaker trips or not. Two tests were performed, representing typical situations:
Test 1: Short circuit with S1 on the power supply end of the cable (loop impedance approx. 20mOhm)
Fig. 26-3 Branch protectors, test circuit 1
Circuit
Power
Supply
AC
DC
Breaker
I
+
S1
-
+
Load
-
Test 2: Short circuit with S1 on the load end (additional impedance included; represents longer load wire length).
Fig. 26-4 Branch protectors, test circuit 2
Circuit
Power
Supply
AC
DC
Breaker
I
+
-
R
+
S1Load
-
*) A list of the circuit breakers under test is available on request.
Example:
Which wire gauge must be used at a length of 15m before a B-Characteristic circuit breaker with 10A will trip?
Answer: A 10A B-Characteristic circuit breaker requires a loop impedance of less than 120mOhm based on the test
results. The wire length table shows that a length of 16.7m wire with a cross section of 2.5mm
120mOhm. A wire not smaller than 2.5mm
Tripping time shorter than 5s.
The following circuit breaker tripped during the test:
A- or Z- Characteristic:: ≤ 10A and R< 120mOhm *)
B- Characteristic: ≤ 10A and R< 120mOhm *)
C- Characteristic: ≤ 8A and R<= 150mOhm *)
What does this resistance mean in wire length?
2
0.5mm
0.7mm2 1.0mm2 1.5mm2 2.5mm2 4.0mm2
3.3m 4.7m 6.7m 10.0m 16.7m 26.7m
4.2m 5.9m 8.4m 12.5m 20.9m 33.4m
2
is measured at
Jan. 2007 / Rev. 1.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
19/22
Q-Series
26.4. PARALLEL USE TO INCREASE OUTPUT POWER
Power supplies can be paralleled to increase the output power.
Fig. 26-5 Schematic for parallel operation
Unit A
Input
Output
Unit B
Input
Output
Fuse
+
-
Fuse
+
-
*)
+
*)
Load
-
Instructions for parallel use:
a) Use only power supplies from the same series (Q-Series).
b) Adjust the output voltages of all power supplies to
approximately the same value (±500mV).
Otherwise, the DC-ok signal might not work properly.
c) A fuse (or diode) on the output is only required if more
than three units are connected in parallel.
d) Keep an installation clearance of 15mm (left / right)
between two power supplies and avoid installing the
power supplies on top of each other.
26.5. PARALLEL USE FOR REDUNDANCY
QTD20.241
24V, 20A, DC INPUT
Power supplies can be paralleled for redundancy to gain a higher system availability. Redundant systems require a
certain amount of extra power to support the load in case one power supply unit fails. The simplest way is to put two
Q-Series power supplies in parallel. This is called a 1+1 redundancy. In case one power supply unit fails, the other one
is automatically able to support the load current without any interruption. Redundant systems for a higher power
demand are usually built in a N+1 method. E.g. Five power supplies, each rated for 10A are paralleled to build a 40A
redundant system.
Please note: This simple way to build a redundant system does not cover failures such as an internal short circuit on
the secondary side of the power supply. In such cases, the defect unit becomes a load for the other power supplies
and the output voltage can not be maintained any more. This can only be avoided by utilizing decoupling diodes
which are included in the decoupling module YR2.DIODE. (One module per power supply)
Recommendations for building redundant power systems:
a) Use separate input fuses for each power supply.
b) Monitor the individual power supply units. A DC-ok LED and a DC-ok contact is already included in the units This
feature reports a faulty unit.
c) When possible, connect each power supply to different phases or circuits.
d) It is desirable to set the output voltages of all power supplies to the same value to avoid a false DC-ok signal.
26.6. DAISY CHAINING OF OUTPUTS
Daisy chaining (jumping from one power supply output to the next) is allowed as long as the maximum current
through one terminal pin does not exceed 25A. If the current is higher, use a separate distribution terminal block.
Fig. 26-6 Daisy chaining of outputs
max 25A!
Fig. 26-7 Using distribution terminals
+
-
+ +
- -
Power
Supply
Input
Jan. 2007 / Rev. 1.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
+ +
- -
Power
Supply
Input
+ +
Load
www.pulspower.com Phone +49 89 9278 0 Germany
- -
Power
Supply
Input
+ +
Power
Supply
- -
Input
+
Load
Distribution
Terminals
-
20/22
Q-Series
26.7. SERIES OPERATION
The power supply can be put in series to increase the output voltage.
Fig. 26-8 Schematic for series operation
Unit A
Input
Output
Unit B
Input
Output
+
-
+
Load
+
-
-
Earth
(see notes)
Instructions for use in series:
a) It is possible to connect as many units in series as needed,
providing the sum of the output voltage does not exceed
150Vdc.
b) Voltages with a potential above 60Vdc are not considered
SELV any longer and can be dangerous. Such voltages must
be installed with a protection against touching.
c) For serial operation use power supplies of the same type.
d) Earthing of the output is required when the sum of the
output voltage is above 60Vdc.
e) Keep an installation clearance of 15mm (left/right) between
two power supplies and avoid installing the power supplies
on top of each other.
Avoid return voltage (e.g. from a decelerating motor or
Note:
battery) which is applied to the output terminals.
QTD20.241
24V, 20A, DC INPUT
26.8. INDUCTIVE AND CAPACITIVE LOADS
The unit is designed to supply any kind of load, including unlimited capacitive and inductive loads.
26.9. USE IN A TIGHTLY SEALED ENCLOSURE
When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher
than the outside. The inside temperature defines the ambient temperature for the power supply.
Results from such an installation:
Power supply is placed in the middle of the box, no other heat producing equipment inside the box
Enclosure: Rittal Typ IP66 Box PK 9519 100, plastic, 180x180x165mm
Load: 24V, 16A (=80% of the rated load); load is placed outside the box
Input: 600Vdc
Temperature inside enclosure: 54.9°C (in the middle of the right side of the power supply with a distance of 2cm)
Temperature outside enclosure: 22.6°C
Temperature rise: 32.3K
Jan. 2007 / Rev. 1.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
21/22
C
C
C
C
C
Q-Series
QTD20.241
24V, 20A, DC INPUT
26.10. MOUNTING ORIENTATIONS
Mounting orientations other than input terminals on the bottom and output on the top requires a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:
Curve A1 Recommended output current.
Curve A2 Max allowed output current (results approx. in half the lifetime expectancy of A1).
Fig. 27-12
Mounting
Orientation A
Standard
Orientation
Fig. 27-13
Mounting
Orientation B
(Upside down)
OUTPUT
Power
Supply
INPUT
INPUT
Supply
Power
OUTPUT
Fig. 27-14
Mounting
Orientation C
(Table-top
mounting)
Fig. 27-15
Mounting
Orientation D
(Horizontal cw)
Supply
INPUT
OUTPUT
Power
Fig. 27-16
Mounting
Orientation E
(Horizontal ccw)
OUTPUT
Power
INPUT
Supply
Output Current
20A
16
12
8
4
0
Ambient Temperature
10203040
Output Current
20A
16
12
8
4
0
Ambient Temperature
10203040
Output Current
20A
16
12
8
4
0
Ambient Temperature
10203040
Output Current
20A
16
12
8
4
0
Ambient Temperature
10203040
Output Current
20A
16
12
8
4
0
Ambient Temperature
10203040
A
1
60°
50
A
2
A
1
50
A
2
A
1
50
A
2
A
1
50
A
2
A
1
50
60°
60°
60°
60°
Jan. 2007 / Rev. 1.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
22/22
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.