Q-Series
12. FUNCTIONAL DIAGRAM
Fig. 12-1 Functional diagram
L
N
Input Fuse
Input Filter
Input Rectifier
Active Inrush Limiter
Temper-
ature
Shutdown
Output
Power
Manager
PFC
Converter
Output
Over-
Voltage
Protection
QS20.241, QS20.241-C1
24V, 20A, SINGLE PHASE INPUT
Output
Voltage
Power
Converter
Output
Voltage
Monitor
Regulator
Output
Filter
DC-ok
Relay
V
OUT
+
+
-
-
Overload
LED
DC-ok
LED
DC-ok
contact
13. FRONT SIDE AND USER ELEMENTS
Fig. 13-1 Front side
Output Terminals
Quick-connect spring-clamp
terminals, no tools required
+ Positive output pole
- Negative output pole
Dual pins per pole
DC ok Relay contact
(NO-contact)
480W Continuous power /
720W Peak power
Input Terminals
Quick-connect spring-clamp
terminals, no tools required
N … Neutral input
L … Line (hot) input
... PE (Protective Earth)
See chapter 14 “Terminals
and Wiring” to choose
appropriate wire gauges
*) Up to 4s of overloading, the power supply delivers continuous output current. After this, the output power is
reduced to nearly zero for approx. 17s before a new start attempt is automatically performed. If the overload has
been cleared, the device will operate normally. If the overload still exists, the output current will be delivered for 2 to
4s (depending on the overload) again followed by a 17s rest time. This cycle is repeated as long as the overload exists.
The red overload LED is permanently on when the overload current is continuously flowing. During the 17s rest
period, the red LED is flashing with a frequency of approx. 1.3Hz.
Output voltage potentiometer
(multi turn potentiometer)
Open the flap to tune the output voltage.
Factory setting: 24.1V
DC-ok LED (green)
Overload LED (red)
Normal mode OFF ON Closed
BonusPower® mode OFF ON Closed
Overload
> 90%)
(V
OUT
Overload
(V
< 90%)
OUT
Short-circuit
= ca. 0V)
(V
OUT
Over- temperature *) OFF
No input power OFF OFF Open
DC-ok LED and DC-ok contact
function synchronized
Overload
LED
OFF ON Closed
*) OFF Open
*) OFF Open
DC-ok
LED
DC-ok
contact
Open
Jan. 2008 / Rev. 1.3 DS-QS20.241-EN
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
10/25