Typically, a load current is not constant. It varies over time. For pulse load compatibility, following rules must be met:
a) The pulse power demand must be below 150% of the nominal power.
b) The duration of the pulse power must be shorter than the allowed Bonus Time. (see output section)
c) The average (R.M.S.) output current must be below the specified continuous output current.
If the R.M.S. current is higher, the unit will respond with a thermal shut-down after a while. Use the max. duty
cycle curve (Fig. 27-2) to check if the average output current is below the nominal current.
d) For altitudes higher than 2000m reduce the pulse loading (30W/1000m) or the ambient temperature (5°C/1000m)
Jan. 2008 / Rev. 1.3 DS-QS20.241-EN
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
19/25
Q-Series
QS20.241, QS20.241-C1
24V, 20A, SINGLE PHASE INPUT
27.2. PEAK CURRENT CAPABILITY
Solenoids, contactors and pneumatic modules often have a steady state coil and a pick-up coil. The inrush current
demand of the pick-up coil is several times higher than the steady state current and usually exceeds the nominal
output current (including the Bonus Power®) The same situation applies, when starting a capacitive load.
Branch circuits are often protected with circuit breakers or fuses. In case of a short or an overload in the branch
circuit, the fuse needs a certain amount of over-current to trip or to blow. The peak current capability ensures the
safe operation of subsequent circuit breakers.
Assuming the input voltage is turned on before such an event, the built-in large sized output capacitors inside the
power supply can deliver extra current. Discharging this capacitor causes a voltage dip on the output. The following
two examples show typical voltage dips:
Fig. 27-3 Peak load 40A for 50ms, typ. Fig. 27-4 Peak load 80A for 5ms, typ.
24V
40A
Output
Voltage
19.0V
24V
80A17.5V
Output
Voltage
0A
10ms/DIV
Peak load 40A (resistive) for 50ms
Output voltage dips from 24V to 19.0V.
Output
Current
0A
Peak load 80A (nearly resistive) for 5ms
Output voltage dips from 24V to 17.5V.
1ms/DIV
Output
Current
Please note: The DC-OK relay triggers when the voltage dips more than 10% for longer than 1ms.
27.3. BACK-FEEDING LOADS
Loads such as decelerating motors and inductors can feed voltage back to the power supply. This feature is also called
return voltage immunity or resistance against Back- E.M.F. (E
lectro Magnetic Force).
This power supply is resistant and does not show malfunctioning when a load feeds back voltage to the power
supply. It does not matter, whether the power supply is on or off.
The maximum allowed feed back voltage is 34Vdc. The absorbing energy can be calculated according to the built-in
large sized output capacitor which is specified in chapter 8. If the feed back voltage gets higher than 34Vdc, the
power supply responds with a shut-down and a subsequent start-up attempt.
27.4. CHARGING OF BATTERIES
The power supply can be used for float-charging of lead-acid or maintenance free 24V VRLA batteries.
Instructions for charging batteries:
a) Set the output voltage, at disconnected load, very precisely to the end-of-charge voltage according to the
expected battery temperature.
End-of-charge voltage 27.8V 27.5V 27.15V 26.8V
Battery temperature 10°C 20°C 30°C 40°C
b) Use a 25A circuit breaker (or blocking diode ) between the power supply and the battery.
c) Ensure that the output current of the power supply is below the allowed charging current of the battery.
d) Use only matched batteries when putting 12V types in series.
e) The return current to the power supply is typ. 9mA at 25Vdcwhen the power supply is switched off.
Jan. 2008 / Rev. 1.3 DS-QS20.241-EN
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
20/25
Q-Series
QS20.241, QS20.241-C1
24V, 20A, SINGLE PHASE INPUT
27.5. OUTPUT CIRCUIT BREAKERS
Standard miniature circuit breakers (MCBs) can be used for branch protection. Ensure that the MCB is rated for DC
voltage, too. The following tests show which circuit breakers the power supply typically trips.
Circuit breakers have huge tolerances in their tripping behavior. Therefore, these typical tests can only be used as a
recommendation or for comparing two different power supplies. Furthermore, the loop impedance has a major
influence on whether a breaker trips or not. Two tests were performed, representing typical situations:
Test 1: Short circuit with S1 on the power supply end of the cable (loop impedance approx. 20mOhm)
Fig. 27-5 Branch protectors, test circuit 1
Circuit
Power
Supply
AC
DC
Breaker
I
+
S1
-
+
Load
-
Test 2: Short circuit with S1 on the load end (additional impedance included; represents longer load wire length).
Fig. 27-6 Branch protectors, test circuit 2
Circuit
Power
Supply
AC
DC
Breaker
I
+
-
R
+
S1Load
-
*) A list of the circuit breakers under test is available on request.
Example:
Which wire gauge must be used to trip a C-Characteristic circuit breaker with a rating of 8A? The load wire length is
19m.
Answer: A 8A C-Characteristic circuit breaker requires a loop impedance of less than 150mOhm (test results). The wire
length table shows that up to 20.9m wire with a cross section of 2.5mm
than 2.5mm
Tripping time shorter than 5s.
The following circuit breaker tripped during the test:
A- or Z- Characteristic:: ≤ 20A and R< 82mOhm *)
B- Characteristic: ≤ 13A and R< 120mOhm *)
C- Characteristic: ≤ 8A and R< 150mOhm *)
What does this resistance mean in wire length?
2
0.5mm
0.7mm2 1.0mm2 1.5mm2 2.5mm2 4.0mm2
2.3m 3.2m 4.6m 6.9m 11.4m 18.3m
3.3m 4.7m 6.7m 10.0m 16.7m 26.7m
4.2m 5.9m 8.4m 12.5m 20.9m 33.4m
2
are below 150mOhm. A wire not smaller
Jan. 2008 / Rev. 1.3 DS-QS20.241-EN
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
21/25
Loading...
+ 4 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.