Puls QS10.481, QS10.481-D1 Data Sheet

QS10.481, QS10.481-D1
Q-Series
POWER SUPPLY
AC 100-240V Wide-range Input Width only 60mm Efficiency up to 92% 150% (360W) Peak Load Capability Easy Fuse Tripping due to High Overload Current Active Power Factor Correction (PFC) Negligible low Inrush Current Surge Short-term Operation down to 60Vac and up to 300Vac Full Power Between -25°C and +60°C DC-OK Relay Contact Quick-connect Spring-clamp Terminals 3 Year Warranty
GENERAL DESCRIPTION
The most outstanding features of this Dimension Q­Series DIN-rail power supply are the high efficiency and the small size, which are achieved by a synchronous rectification and further novel design details. The Q­Series is part of the Dimension family, existing alongside the lower featured C-Series.
With short-term peak power capability of 150% and built-in large sized output capacitors, these features help start motors, charge capacitors and absorb reverse energy and often allow a unit of a lower wattage class to be used.
High immunity to transients and power surges as well as low electromagnetic emission makes usage in nearly every environment possible.
The integrated output power manager, a wide range input voltage design and virtually no input inrush current make installation and usage simple. Diagnostics are easy due to the dry DC-ok contact, a green DC-ok LED and red overload LED.
Unique quick-connect spring-clamp terminals allow a safe and fast installation and a large international approval package for a variety of applications makes this unit suitable for nearly every situation.
ORDER NUMBERS
Power Supply QS10.481 48-56V Power supply
Accessory ZM1.WALL Wall mount bracket ZM13.SIDE Side mount bracket YR2.DIODE Redundancy module UF20.481 Buffer unit
48V, 5A, SINGLE PHASE INPUT
SHORT-FORM DATA
Output voltage DC 48V Adjustment range 48 – 56V Output current 5 – 4.3A continuous
7.5 – 6.5A for typ. 4s Output power 240W continuous 360W for typ. 4s Output ripple < 100mVpp 20Hz to 20MHz Input voltage AC 100-240V ±15% Mains frequency 50-60Hz ±6% AC Input current 2.22 / 1.22A at 120 / 230Vac Power factor 0.98 / 0.92 at 120 / 230Vac AC Inrush current typ. 4 / 7A peak at 120 / 230Vac Efficiency 91.2 / 92.0% at 120 / 230Vac Losses 23.2 / 20.9W at 120 / 230Vac Temperature range -25°C to +70°C operational Derating 6W/°C +60 to +70°C Hold-up time typ. 27 / 28ms at 120 / 230Vac Dimensions 60x124x117mm WxHxD
MARKINGS
IND. CONT. EQ.
UL 508
UL 60950-1
Marine
Class I Div 2
EMC, LVD
Nov. 2011 / Rev. 2.1 DS-QS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
1/27
QS10.481, QS10.481-D1
Q-Series
48V, 5A, SINGLE PHASE INPUT
INDEX
Page Page
1.
Intended Use .......................................................3
2. Installation Requirements...................................3
3. AC-Input...............................................................4
4. DC-Input...............................................................5
5. Input Inrush Current ...........................................6
6. Output .................................................................7
7. Hold-up Time.......................................................9
8. DC-OK Relay Contact ..........................................9
9. Efficiency and Power Losses..............................10
10. Reliability...........................................................11
11. Functional Diagram...........................................12
12. Terminals and Wiring........................................12
13. Front Side and User Elements...........................13
14. EMC....................................................................14
15. Environment......................................................15
16. Protection Features ...........................................16
17. Safety Features ..................................................16
18. Dielectric Strength ............................................16
19. Approvals...........................................................17
20. Fulfilled Standards ............................................17
21. Used Substances ................................................18
22. Physical Dimensions and Weight......................18
The information presented in this document is believed to be accurate and reliable and may change without notice. No part of this document may be reproduced or utilized in any form without permission in writing from the publisher.
23. Accessories ........................................................ 19
23.1. ZM1.WALL Wall Mounting Bracket ....... 19
23.2. ZM13.SIDE Side Mounting Bracket ........ 19
23.3. UF20.481 Buffer Module .......................... 20
23.4. YR2.DIODE Redundancy Module.............20
24. Application Notes............................................. 21
24.1. Repetitive Pulse Loading..........................21
24.2. Peak Current Capability ...........................22
24.3. Back-feeding Loads ..................................22
24.4. External Input Protection.........................22
24.5. Charging of Batteries ...............................23
24.6. Output Circuit Breakers............................23
24.7. Parallel Use to Increase Output Power....24
24.8. Parallel Use for Redundancy ....................24
24.9. Daisy Chaining of Outputs ....................... 25
24.10. Series Operation .......................................25
24.11. Inductive and Capacitive Loads................25
24.12. Operation on Two Phases ........................26
24.13. Use in a Tightly Sealed Enclosure ............26
24.14. Mounting Orientations ............................27
TERMINOLOGY AND ABREVIATIONS
PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol .
Earth, Ground This document uses the term “earth” which is the same as the U.S. term “ground”.
T.b.d. To be defined, value or description will follow later.
AC 230V A figure displayed with the AC or DC before the value represents a nominal voltage with
standard tolerances (usually ±15%) included. E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V)
230Vac A figure with the unit (Vac) at the end is a momentary figure without any additional
tolerances included.
50Hz vs. 60Hz As long as not otherwise stated, AC 230V parameters are valid at 50Hz mains frequency.
may A key word indicating flexibility of choice with no implied preference.
shall A key word indicating a mandatory requirement.
should A key word indicating flexibility of choice with a strongly preferred implementation.
Nov. 2011 / Rev. 2.1 DS-QS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
2/27
QS10.481, QS10.481-D1
Q-Series
48V, 5A, SINGLE PHASE INPUT

1. INTENDED USE

This device is designed for installation in an enclosure and is intended for the general use such as in industrial control, office, communication, and instrumentation equipment.
Do not use this power supply in aircraft, trains, nuclear equipment or similar systems where malfunction may cause severe personal injury or threaten human life.
This device is designed for use in hazardous, non-hazardous, ordinary or unclassified locations.

2. INSTALLATION REQUIREMENTS

This device may only be installed and put into operation by qualified personnel. This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect. If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to
the factory for inspection. Mount the unit on a DIN-rail so that the output terminals are located on the top and the input terminals are located
on the bottom of the unit. For other mounting orientations see de-rating requirements in this document. See chapter
24.14. This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do
not cover ventilation grid (e.g. cable conduits) by more than 30%! Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are
recommended when the device is loaded permanently with more than 50% of the rated power. Increase this clearance to 15mm in case the adjacent device is a heat source (e.g. another power supply).
WARNING
- Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input block for earth connection and not one of the screws on the housing.
- Turn power off before working on the device. Protect against inadvertent re-powering.
- Make sure that the wiring is correct by following all local and national codes.
- Do not modify or repair the unit.
- Do not open the unit as high voltages are present inside.
- Use caution to prevent any foreign objects from entering the housing.
- Do not use in wet locations or in areas where moisture or condensation can be expected.
- Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.
Risk of electrical shock, fire, personal injury or death.
Nov. 2011 / Rev. 2.1 DS-QS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
3/27
QS10.481, QS10.481-D1
Q-Series
48V, 5A, SINGLE PHASE INPUT

3. AC-INPUT

AC input nom. AC 100-240V suitable for TN-, TT- and IT mains networks AC input range min. 85-276Vac continuous operation min. 60-85Vac full power for 200ms, no damage between 0 and 85Vac min. 276-300Vac < 500ms Allowed voltage L or N to earth max. 276Vac continuous, IEC 62103 Input frequency nom. 50–60Hz ±6% Turn-on voltage typ. 81Vac steady-state value, see Fig. 3-1 Shut-down voltage typ. 63Vac steady-state value, see Fig. 3-1 typ. 55Vac dynamic value
AC 100V AC 120V AC 230V Input current typ. 2.65A 2.22A 1.22A at 48V, 5A, see Fig. 3-3 Power factor *) typ. 0.99 0.98 0.92 at 48V, 5A, see Fig. 3-4 Crest factor **) typ. 1.65 1.67 1.85 at 48V, 5A Start-up delay typ. 800ms 650ms 340ms see Fig. 3-2 Rise time typ. 8ms 8ms 8ms 0mF, 48V, 5A, see Fig. 3-2 typ. 15ms 15ms 15ms 5mF, 48V, 5A, see Fig. 3-2 Turn-on overshoot max. 100mV 100mV 100mV see Fig. 3-2
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit. **) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, definitions
P
OUT
full
power
for
200ms
Shut-down
60V 300Vac276V
input range
Turn-on
85V
Rated
max.
500ms
V
IN
Input Voltage
Output Voltage
- 5%
Start-up
delay
Fig. 3-3 Input current vs. output load at 24V Fig. 3-4 Power factor vs. output load
2.8A
Input Current, typ.
2.4
2.0
1.6
1.2
0.8
0.4
0
0.5 1 1.5 2 2.5 3 3.5 4 4.5
Output Current
c
a
V
0
0
1
c
a
V
0
2
1
c
a
V
0
3
2
5A
Power Factor, typ.
1.0
0.95
0.9
0.85
0.8
0.75
0.5 1 1.5 2 2.5 3 3.5 4 4.5 5A
Rise
Time
100Vac
120Vac
0
3
2
Output Current
Overshoot
c
a
V
Nov. 2011 / Rev. 2.1 DS-QS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
4/27
QS10.481, QS10.481-D1
Q-Series

4. DC-INPUT

QS10.481:
DC input nom. DC 110-150V -20%/+25% DC input range min. 88-187Vdc continuous operation DC input current typ. 2.37A 110Vdc, at 24V, 10A
QS10.481-D1:
DC input nom. DC 110-300V -20%/+25% DC input range min. 88-375Vdc continuous operation DC input current typ. 2.37/ 0.85A 110/300Vdc, at 24V, 10A
All units:
Allowed Voltage L/N to Earth max. 375Vdc continuous, IEC 62103 Turn-on voltage typ. 80Vdc steady state value Shut-down voltage typ. 55Vdc steady state value
Fig. 4-1 Wiring for DC Input
Battery
+
Power Supply
AC
L
N
PE
+
-
Load
Instructions for DC use:
a) Use a battery or similar DC source.
For other sources contact PULS b) Connect +pole to L and –pole to N. c) Connect the PE terminal to a earth wire or to the machine
ground.
48V, 5A, SINGLE PHASE INPUT
-
Nov. 2011 / Rev. 2.1 DS-QS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
DC
5/27
QS10.481, QS10.481-D1
Q-Series
48V, 5A, SINGLE PHASE INPUT

5. INPUT INRUSH CURRENT

An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage and after short input voltage interruptions.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
Inrush current max. 10A typ. 5A Inrush energy max. 4A
AC 100V AC 120V AC 230V
10A
peak
4A
peak
2
s 4A2s 4A2s over entire temperature range
10A
peak
7A
peak
peak
peak
Inrush delay (A) typ. 650ms 520ms 250ms see (A) in Fig. 5-1
Fig. 5-1 Input inrush current, typical behavior
A
Input Current
A…. Inrush delay
Input: 230Vac Output: 48V, 5A
Input Voltage
Ambient: 25°C Upper curve: Input current 2A / DIV
Middle curve: Input voltage 500V / DIV
Output Voltage
Lower curve: Output voltage 40V / DIV Time basis: 100ms / DIV
over entire temperature range
over entire temperature range
Nov. 2011 / Rev. 2.1 DS-QS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
6/27
QS10.481, QS10.481-D1
Q-Series
48V, 5A, SINGLE PHASE INPUT

6. OUTPUT

Output voltage nom. 48V Adjustment range min. 48-56V guaranteed max. 58V Factory setting typ. 48.0V ±0.2%, at full load, cold unit Line regulation max. 10mV 60-300Vac Load regulation max. 100mV static value, 0A Æ 5A Ripple and noise voltage max. 100mVpp 20Hz to 20MHz, 50Ohm Output current nom. 5A continuously available at 48V, see Fig. 6-1 nom. 4.3A continuously available at 56V, see Fig. 6-1
nom. 7.5A
nom. 6.5A
Output power nom. 240W continuously available nom. 360W BonusPower® time typ. 4s duration until the output voltage dips, see Fig. 6-2 min. 3s max. 5s
®
BonusPower
recovery time typ. 7s overload free time to reset power manager, see Fig. 6-3 Overload behaviour cont. current Short-circuit current min. 3A max. 7A min. 5A max. 15A max. 7.5A Output capacitance typ. 3 000μF included inside the power supply
*) BonusPower®, short term power capability (up to typ. 4s)
The power supply is designed to support loads with a higher short-term power requirement without damage or shutdown. The short­term duration is hardware controlled by an output power manager. This BonusPower® is repeatedly available. Detailed information can be found in chapter 24.1. If the power supply is loaded longer with the BonusPower Fig. 6-2), the max. output power is automatically reduced to 240W.
**) Discharge current of output capacitors is not included.
***) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not
guaranteed value which can be achieved. The typical value is about 56.8V.
Peak current capability (up to several milliseconds)
The power supply can deliver a peak current which is higher than the specified short term current. This helps to start current demanding loads or to safely operate subsequent circuit breakers.
The extra current is supplied by the output capacitors inside the power supply. During this event, the capacitors will be discharged and causes a voltage dip on the output. Detailed curves can be found in chapter 24.2.
Peak current voltage dips typ. from 48V to 42V at 10A for 50ms, resistive load typ. from 48V to 42V at 20A for 2ms, resistive load typ. from 48V to 36V at 20A for 5ms, resistive load
***)
at clockwise end position of potentiometer
*)
short term available BonusPower
at 48V, for typical 4s, see Fig. 6-1
*)
short term available BonusPower
at 56V, for typical 4s, see Fig. 6-1
*)
short term available BonusPower
**)
continuous, load impedance 200mOhm, see Fig. 6-1
**)
continuous, load impedance 200mOhm, see Fig. 6-1
**)
during BonusPower
**)
during BonusPower
**)
continuous, load impedance <10mOhm, see Fig. 6-1
® *)
, load impedance 200mOhm
® *)
, load impedance 200mOhm
®
than shown in the Bonus-time diagram (see
® *)
® *)
® *)
,
,
Nov. 2011 / Rev. 2.1 DS-QS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
7/27
QS10.481, QS10.481-D1
Q-Series
Fig. 6-1 Output voltage vs. output current,
Output Voltage
60V
50
40
30
20
10
56V
48V
typ.
c o
n t
i
n u o u s
Adjustment
Range
0
02 6810
4
s
h
o
r
t
-
t
e
r
m
Output Current
12A
Fig. 6-2 Bonus time vs. output power
Bonus Time
10s
9 8 7 6 5 4 3 2 1 0
110 120 130 140 150
Fig. 6-3 BonusPower® recovery time
Limitation by
Power Demand
100%
Output Voltage
Bonus
Time
Power Manager
Recovery Time
Bonus Power disabled
t
t
48V, 5A, SINGLE PHASE INPUT
m
a
x
m
i
n
Output Power
typ
160%
The BonusPower
®
is available as soon as power comes on and immediately after the end of an output short circuit or
output overload.
Fig. 6-4 BonusPower® after input turn-on Fig. 6-5 BonusPower® after output short
Input Voltage
Short of
Output
Output Voltage
Output Voltage
Output Power
100%
150%
Bonus Power
Output Power
150%
100%
Bonus Power
Nov. 2011 / Rev. 2.1 DS-QS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
8/27
QS10.481, QS10.481-D1
Q-Series
48V, 5A, SINGLE PHASE INPUT

7. HOLD-UP TIME

AC 100V AC 120V AC 230V Hold-up Time typ. 51ms 53ms 55ms at 48V, 2.5A, see Fig. 7-1 typ. 26ms 27ms 28ms at 48V, 5A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions
Hold-up Time
50ms
,
V
8
4
,
V
8
40
30
20
4
V
8
4
V
8
4
10
0
Input Voltage
85 120 155 190 230Vac
.
yp
t
,
A
.
5
2
.
n
i
m
,
A
.
5
2
.
p
ty
,
A
5
,
.
n
i
m
,
A
5
,
Input Voltage
Output Voltage
Zero Transition
- 5%
Hold-up Time

8. DC-OK RELAY CONTACT

This feature monitors the output voltage, which is produced by the power supply itself. It is independent of a back-fed voltage from a unit connected in parallel to the power supply output.
Contact closes As soon as the output voltage reaches the adjusted output voltage level. Contact opens As soon as the output voltage dips more than 10% below the adjusted output voltage.
Short dips will be extended to a signal length of 250ms. Dips shorter than 1ms will be ignored. Contact re-closes As soon as the output voltage exceeds 90% of the adjusted voltage. Contact ratings max 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A resistive load min 1mA at 5Vdc min. permissible load Isolation voltage See dielectric strength table in section 18.
Fig. 8-1 DC-ok relay contact behavior
V
= V
OUT
ADJ
10%
open openclosed closed
Note: The DC-ok feature requires that the output voltage reaches the nominal (=adjusted) level after turn-on in order to function according
to specification. If this level cannot be achieved, the overload lamp will be on and the DC-ok contact will be open. The overload signal will only shut off as soon as the adjusted voltage is reached. This is an important condition to consider particularly, if the load is a battery, the power supply is used in parallel or the power supply is used for N+1 redundant systems.
1ms
<
>
1ms
250ms
0.9* V
ADJ
Nov. 2011 / Rev. 2.1 DS-QS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
9/27