PULS PIC120.241D, PIC240.241D User guide

EN
PIC-02 Power Supply Instruction Manual
Before operating the power supply, read this manual thoroughly and retain it for future reference! This device may only be installed and put into operation by qualified personnel. If damage or malfunction should occur during operation, immediately turn power off and send unit to the factory for inspection. The unit does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect.
This power supply is designed for installation in an enclosure and is intended for general use such as in industrial control, office, communication, and instrumentation equipment. Do not use this device in equipment, where malfunction may cause severe personal injury or threaten human life.
Risk of electrical shock, fire, personal injury or death:
(1) Do not use the power supply without proper grounding (Protective Earth). (2) Turn power off before working on the device. Protect against inadvertent re-powering. (3) Make sure that the wiring is correct by following all local and national codes. (4) Do not modify or repair the unit. The unit does not contain serviceable parts. (5) Do not open the unit as high voltages are present inside. (6) Use caution to prevent any foreign objects from entering the housing. (7) Do not use in wet locations or in areas where moisture or condensation can be expected. (8) Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.
Installation Notes
- Install the device on a DIN-rail according to EN 60715 with the input terminals on the bottom of the unit.
- Do not obstruct air flow as the unit is convection cooled. Ventilation grid must be kept free of any obstructions (min. 40mm on top, 20mm on the bottom, 5mm left and right side).
- Do not place heat sources adjacent to the power supply.
- Do not use the device in pollution degree 3 environments.
- Do not use the device in parallel connection.
- The unit is tested and approved for branch circuits up to 32A without additional protection device. If an external fuse is utilized, do not use breakers smaller than 10A B- or 6A C-Characteristic to avoid nuisance tripping.
- Maximum surrounding air temperature: 70°C / 158°F.
- For use in CSA C22.2 No 107 areas: Provide an output disconnecting means and use only in controlled environments.
CE Declaration
The CE mark is in conformance with EMC directive and the low-voltage directive (LVD).
Headquarters: PULS GmbH, Elektrastr. 6, 81925 Munich, Germany www.pulspower.com
Germany +49 89 9278 0 www.pulspower.de China +86 512 62881820 www.pulspower.cn France +33 478 668 941 www.pulspower.fr Austri a +43 27 64 32 13 www.pulspower.at
PIC120.241D AC 100-120V/ 200-240V
DC 24-28V 5A 120W
PIC240.241D AC 100-240V
Singapore +65 6684 2310 www.pulspower.sg Switzerland +41 56 450 18 10 www.pulspower.ch U.K. +44 1525 841001 www.pulspower.co.uk U.S.A +1 630 587 9780 www.pulspower.us
Technical Data
1)
PIC120.241D PIC240.241D
Output Voltage nom. DC 24-28V DC 24-28V Output Current nom. 5A at 24V, 4.3A at 28V 10A at 24V, 8.6A at 28V Output Ripple & Noise Voltage Input Voltage nom. Autoselect, AC 100-120/ 200-240V
Input Frequency nom. Input Current (120/ 230Vac) typ. 1.71A/ 1.05A 2.2A/ 1.21A Power Factor (120/ 230Vac) typ. 0.64/ 0.54 0.97/ 0.91 Input Inrush Current Efficiency / Power Losses typ. 91.2% / 11.6W at 120Vac
Operational Temperature Range Output Derating nom. 3W/°C from 55°C to +70°C
Storage Temperature Range nom. -40°C - +85°C -40°C - +85°C
5)
Terminals
AWG Wire stripping length Tightening torque
Stranded / solid wire
DC-OK Contact Yes EMC Immunity Generic Standard IEC 61000-6-1/ -6-2 IEC 61000-6-1/ -6-2 EMC Emission Generic Standard
Radiated Emission Conducted Emission Harmonic Input Current
Dimensions (WxHxD, without DIN-rail) nom. 39x124x124mm 49x124x124mm Weight max. 370g, 0.81lb 540g, 1.2lb
1) All param eters are specified at 230Vac, nominal output c urrent, 25°C ambient and after a 5 minutes run-in t ime unless otherwise noted.
2) 50-Ohm measurement, bandwidth 20MHz
3) At 120/ 230 Vac, 40°C ambient and cold start. The input inr ush current is temperature dependent.
4) The operat ional temperature range equals the surroun ding air temperature measured 2cm below the u nit.
Observe required output derating above + 50°C / +55°C
5) Use appropr iate copper cables, that are designed for a m inimum operating temperature of 75°C for am bient temperatures up to 55°C and
90°C for ambient temperatures up to 70°C. Follow national installation c odes and regulations! Ensure that all strands of a stranded wire enter the terminal.
6) Contact ratin gs: 60Vdc 0.3A; 30Vdc 1A; 30Vac, 0.5A; re sistive load, min. current 1mA.
7) for AC 110-1 20 / 220-240V mains systems
8) for AC 100 / 200V mains systems
PU-415.010.00-xxC
2)
max. 100mVpp 100mVpp
50-60Hz
3)
typ. 22A/ 33A peak 14A/ 26A peak
4)
nom. -10°C - +70°C -25°C - +70°C
92.3% / 10.0W at 230Vac
3W/°C from 50°C to +70°C
nom. nom. nom. nom.
The information presented in this docum ent is believed to be accurate and may change without notice.
0.5-4mm2 / 0.5-6mm 20-10AWG
7mm, 0.28inch
1Nm, 9lb.in
IEC 61000-6-3/ -6-4 EN 55011/22 Class B EN 55011/22 Class B
IEC 61000-3-2 Class A
Wide range AC 100-240V
±10%
±6%
93.6% / 16.4W at 120Vac
94.8% / 13.2W at 230Vac
7)
6W/°C from 55°C to +70°C
8)
2
0.5-4mm2 / 0.5-6mm
7mm, 0.28inch
6)
IEC 61000-6-4 EN 55011/22 Class A EN 55011/22 Class B
IEC 61000-3-2 Class A
50-60Hz
20-10AWG
1Nm, 9lb.in
Yes
±10%
±6%
2
6)