Power Supply
Instruction Manual
Before operating the power supply, read this manual thoroughly and retain it for future reference! This device may only be
installed and put into operation by qualified personnel. If damage or malfunction should occur during operation,
immediately turn power off and send unit to the factory for inspection. The unit does not contain serviceable parts. The
tripping of an internal fuse is caused by an internal defect.
This power supply is designed for installation in an enclosure and is intended for general use such as in industrial control,
office, communication, and instrumentation equipment. Do not use this device in equipment, where malfunction may
cause severe personal injury or threaten human life.
Risk of electrical shock, fire, personal injury or death:
(1) Do not use the power supply without proper grounding (Protective Earth).
(2) Turn power off before working on the device. Protect against inadvertent re-powering.
(3) Make sure that the wiring is correct by following all local and national codes.
(4) Do not modify or repair the unit. The unit does not contain serviceable parts.
(5) Do not open the unit as high voltages are present inside.
(6) Use caution to prevent any foreign objects from entering the housing.
(7) Do not use in wet locations or in areas where moisture or condensation can be expected.
(8) Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.
Installation Notes
- Install the device on a DIN-rail according to EN 60715 with the input terminals on the bottom of the unit.
- Do not obstruct air flow as the unit is convection cooled.
Ventilation grid must be kept free of any obstructions (min. 40mm on top, 20mm on the bottom, 5mm left and right side).
- Do not place heat sources adjacent to the power supply.
- Do not use the device in pollution degree 3 environments.
- Do not use the device in parallel connection.
- The unit is tested and approved for branch circuits up to 30A (UL), 32A (IEC) without additional protection device.
If an external fuse is utilized, do not use breakers smaller than 10A (B- or C-Characteristic) to avoid nuisance tripping.
- Maximum surrounding air temperature: 70°C / 158°F.
- For use in CSA C22.2 No 107 areas: Provide an output disconnecting means and use only in controlled environments.
CE Declaration
The CE mark is in conformance with EMC directive 2004/108/EC, the low-voltage directive (LVD) 2006/95/EC and the
RoHS directive 2011/65/EU.
Headquarters: PULS GmbH, Arabellastrasse 15, 81925 Munich, Germany www.pulspower.com
Germany +49 89 9278 0 www.pulspower.de
China +86 512 62881820 www.pulspower.cn
France +33 478 668 941 www.pulspower.fr
Austria +43 27 64 32 13 www.pulspower.at
PIC120.241C
AC 200-240V / DC 24-28V 5A
PIC120.242C
PIC240.241C AC 200-240V / DC 24-28V 10A
Singapore +65 6684 2310 www.pulspower.sg
Switzerland +41 56 450 18 10 www.pulspower.ch
U.K. +44 1525 841001 www.pulspower.co.uk
U.S.A +1 630 587 9780 www.pulspower.us
![](/html/c3/c385/c38575d9eed07dfd8bd55d153128c0afd8823aa360c418cfa21d997ce7584329/bg2.png)
Technical Data
1)
PIC120.241C
PIC240.241C
PIC120.242C
Output Voltage nom. DC 24-28V DC 24-28V
Output Current nom. 5A at 24V, 4.3A at 28V 10A at 24V, 8.6A at 28V
Output Power nom. 120W 240W
Output Ripple & Noise Voltage
Input Voltage nom.
Input Frequency nom.
Input Current typ. 1.1A 2.2A
Power Factor typ. 0.54 0.52
Input Inrush Current
Efficiency / Power Losses typ. 90.5% / 12.6W 91.4% / 22.6W
Operational Temperature Range
Output Derating nom . 3W/°C from 55°C to +70°C 6W/°C from 55°C to +70°C
Storage Temperature Range nom. -40°C - +85°C -40°C - +85°C
5)
Terminals
AWG
Wire stripping length
Tightening torque
Stranded / solid wire
DC-OK Contact PIC120.241C: Yes
EMC Immunity Generic Standard IEC 61000-6-1/ -6-2 IEC 61000-6-1/ -6-2
EMC Emission Generic Standard
Radiated Emission
Conducted Emission
Harmonic Input Current
Dimensions (WxHxD, without DIN-rail) nom. 39x124x124mm 49x124x124mm
Weight max. 350g, 0.77lb 550g, 1.2lb
1) All parameters are specified at 230Vac, nominal output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
2) 50-Ohm measurement, bandwidth 20MHz
3) At 230Vac, 40°C ambient and cold start. The input inrush current is limited by a NTC and is temperature dependent.
4) The operational temperature range equals the surrounding air temperature measured 2cm below the unit.
5) Use appropriate copper cables, that are designed for a minimum operating temperature of 60°C for ambient temperatures up to 45°C, 75°C for
ambient temperatures up to 60°C and 90°C for ambient temperatures up to 70°C.
Follow national installation codes and regulations! Ensure that all strands of a stranded wire enter the terminal.
6) Contact ratings: 60Vdc 0.3A; 30Vdc 1A; 30Vac, 0.5A; resistive load, min. current 1mA.
PU-411.011.00-xxD
2)
max. 100mVpp 100mVpp
AC 200-240V
3)
typ. 28A peak 48A peak
4)
nom. -10°C - +70°C -10°C - +70°C
nom.
nom.
nom.
nom.
0.5-4mm2 / 0.5-6mm
PIC120.242C: No
IEC 61000-6-3 /-6-4
EN 55011/22 Class B
EN 55011/22 Class B
IEC 61000-3-2 Class A
The information presented in this document is believed to be accurate and may change without notice.
±10%
±6%
50-60Hz
20-10AWG
7mm, 0.28inch
1Nm, 9lb.in
AC 200-240V
50-60Hz
2
6)
0.5-4mm2 / 0.5-6mm
20-10AWG
7mm, 0.28inch
1Nm, 9lb.in
PIC240.241C: Yes
IEC 61000-6-4
EN 55011/22 Class B
EN 55011/22 Class B
±10%
±6%
2
6)
-