The MiniLine-2 series covers the lower power
requirements in the range from 15W to 120W. These
units in their rugged plastic housing and large screw
terminals are highly efficient, very compact, easy to
install and are extremely reliable. Besides the standard
24V power supplies, many other output voltages are
also available as well as units rated down to -40°C.
More DIN-Rail power supplies in rugged plastic housings
can be found in the MiniLine family which is equipped
with quick-connect spring-clamp terminals. These units
come in power ranges from 25W to 100W and a variety
of output voltages.
The ML120 units are highly immune against electrical
disturbances on the mains and provides reliable output
power. This offers superior protection for equipment
which is connected to the public mains network or is
exposed to a critical industrial environment.
Besides the cost optimized ML120.244, two additional
units are available in the ML120 series. The
ML120.CLASS2 fulfills the NEC Class 2 requirements and
the ML120.241 is the standard product with an autoselect 100-120/220-240V input.
The supplementary MiniLine-2 redundancy module
MLY10.241 allows building of redundant systems or
protecting against back-feeding voltages.
ORDER NUMBERS
Power Supply ML120.244 24V Standard unit
Accessory MLY10.241 Redundancy module
YRM2.DIODE Redundancy module
with alarm contacts
UF20.241 Buffer Module
24V,5A,SINGLE PHASE INPUT
OWER SUPPLY
P
AC 200-240V Regional Input
Efficiency up to 90.3%
Compact Design, Width only 72.5mm
Full Power between -10°C and +60°C
Large International Approval Package
Cost / Performance Optimized
3 Year Warranty
SHORT-FORM DATA
Output voltage DC 24V
Adjustment range 24V
Output current 5A
Output power 120W
Output ripple < 50mVpp 20Hz to 20MHz
Input voltage AC 200-240V -15% / +10%
Mains frequency 50-60Hz ±6%
AC Input current 1.07A
Power factor 0.54
AC Inrush current typ. 31A peak value at
230Vac 40°C and
cold start
DC Input -
Efficiency 90.3%
Losses 12.9W
Temperature range -10°C to +70°C operational
Derating 3W/°C +60 to +70°C
Hold-up time typ. 35ms
Dimensions 72.5x75x103mm WxHxD
Weight 360g / 0.8lb
MARKINGS
Ind. Cont. Eq.
UL 508, pending
Class I Div 2, pend.
UL 60950-1
pending
Marine, pending
EMC, LVD, RoHS
Apr. 2013 / Rev. 1.1 DS-ML120.244-EN
All parameters are specified at 24V, 5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
1/21
ML120.244
MiniLine-2
24V,5A,SINGLE PHASE INPUT
INDEX
Page Page
1.
Intended Use .......................................................3
The information presented in this document is believed to be accurate and reliable and may change without notice.
The housing is patent by PULS (US patent No US D442,923S).
No part of this document may be reproduced or utilized in any form without permission in writing from the publisher.
20. Physical Dimensions and Weight..................... 15
PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol .
Earth, Ground This document uses the term “earth” which is the same as the U.S. term “ground”.
T.B.D. To be defined, value or description will follow later.
AC 230V A figure displayed with the AC or DC before the value represents a nominal voltage with
standard tolerances (usually ±15%) included.
E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V)
230Vac A figure with the unit (Vac) at the end is a momentary figure without any additional
tolerances included.
50Hz vs. 60HzAs long as not otherwise stated, AC 100V and AC 230V parameters are valid at 50Hz and AC
120V parameters are valid at 60Hz mains frequency.
may A key word indicating flexibility of choice with no implied preference.
shall A key word indicating a mandatory requirement.
should A key word indicating flexibility of choice with a strongly preferred implementation.
Apr. 2013 / Rev. 1.1 DS-ML120.244-EN
All parameters are specified at 24V, 5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
2/21
ML120.244
MiniLine-2
24V,5A,SINGLE PHASE INPUT
1. INTENDED USE
This device is designed for installation in an enclosure and is intended for the general use such as in industrial control,
office, communication, and instrumentation equipment.
Do not use this power supply in equipment, where malfunction may cause severe personal injury or threaten human
life.
2. INSTALLATION REQUIREMENTS
This device may only be installed and put into operation by qualified personnel.
This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect.
If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to
the factory for inspection.
Mount the unit on a DIN-rail so that the output terminals are located on top and input terminal on the bottom. For
other mounting orientations see de-rating requirements in this document.
This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do
not cover ventilation grid (e.g. cable conduits) by more than 15%!
Keep the following installation clearances:
- on top 40mm
- on the bottom 20mm
- Left and right: 0mm (or 15mm in case the adjacent device is a heat source; in example another power supply, …).
WARNING
- Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input block for
earth connection.
- Turn power off before working on the device. Protect against inadvertent re-powering.
- Make sure that the wiring is correct by following all local and national codes.
- Do not modify or repair the unit.
- Do not open the unit as high voltages are present inside.
- Use caution to prevent any foreign objects from entering into the housing.
- Do not use in wet locations or in areas where moisture or condensation can be expected.
- Do not touch during power-on, and immediately after power-off. Hot surface may cause burns.
Notes for use in hazardous location areas:
The power supply is suitable for use in Class I Division 2 Groups A, B, C, D locations.
WARNING EXPLOSION HAZARDS!
Substitution of components may impair suitability for this environment. Do not disconnect the unit or operate the
voltage adjustment unless power has been switched off or the area is known to be non-hazardous.
A suitable enclosure must be provided for the end product which has a minimum protection of IP54 and fulfils the
requirements of the EN 60079-15:2010.
Risk of electrical shock, fire, personal injury or death.
Apr. 2013 / Rev. 1.1 DS-ML120.244-EN
All parameters are specified at 24V, 5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
3/21
ML120.244
MiniLine-2
24V,5A,SINGLE PHASE INPUT
3. AC-INPUT
AC input nom. AC 200-240V -15% / +10%
Allowed mains networks TN/ TT/ IT-mains
AC input range 170-264Vac continuously allowed
0-170Vac no damage to the unit
264–300Vac < 0.5s
Allowed voltage L or N to earth max. 300Vac continuously allowed, IEC 62103
Input frequency nom. 50–60Hz ±6%
Input current (rms) typ. 1.07A at 24V, 5A see Fig. 3-3
Power factor*) typ. 0.54 at 24V, 5A see Fig. 3-4
Crest factor
Start-up delay typ. 80ms see Fig. 3-2
Rise time typ. 65ms at 24V, 5A const. current load, 0mF load
175ms at 24V, 5A const. current load, 5mF load
Turn-on overshoot max. 200mV see Fig. 3-2
Turn-on voltage typ. 158Vac steady-state value, see Fig. 3-1
Shut-down voltage typ. 134Vac steady-state value, see Fig. 3-1
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, definitions
**)
typ. 4.0 at 24V, 5A
capacitance, Fig. 3-2
capacitance
P
OUT
Rated input range
Input
Voltage
Turn-on
Shut-down
V
IN
170V
264Vac
Output
Voltage
- 5%
Start-up
delay
Rise
Time
Overshoot
Fig. 3-3 Input current vs. output load at 24V Fig. 3-4 Power factor vs. output load at 24V
Input Current, typ.
1.4A
1.2
1.0
0.8
0.6
0.4
0.2
0
0.5 1 1.5 2 2.5 3 3.5 4 4.5
Output Current
5A
Power Factor, typ.
0.65
0.60
0.55
0.50
0.45
0.40
0.5 1 1.5 2 2.5 3 3.5 4 4.5 5A
Output Current
Apr. 2013 / Rev. 1.1 DS-ML120.244-EN
All parameters are specified at 24V, 5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/21
ML120.244
MiniLine-2
24V,5A,SINGLE PHASE INPUT
4. INPUT INRUSH CURRENT
A NTC limits the input inrush current after turn-on of the input voltage. The inrush current is input voltage and
ambient temperature dependent.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
Inrush current max. 37A
typ. 28A
typ. 23A
Inrush energy typ. 1A
Fig. 4-1 Input inrush current, typical behavior
230Vac input, 24V 5A output, 25°C ambient
Input
Current
10A/DIV
Input Voltage
- 500V/DIV
Fig. 4-2 Input inrush current, zoom into first peak 230Vac input, 24V 5A output, 25°C ambient
40°C ambient, cold start
peak
40°C ambient, cold start
peak
25°C ambient, cold start
peak
2
s 40°C ambient, cold start
Ipeak = 23A
Output
Voltage
20V/DIV
40ms/DIV
Input Current
1ms/DIV
- 5A/DIV
5. DC-INPUT
Do not operate this power supply with DC-input voltage. Use the ML120.241 unit instead.
Apr. 2013 / Rev. 1.1 DS-ML120.244-EN
All parameters are specified at 24V, 5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/21
ML120.244
MiniLine-2
24V,5A,SINGLE PHASE INPUT
6. OUTPUT
Output voltage nom. 24V
Adjustment range min. fixed no adjustment included
Factory setting 24.5V ±3%, at full load, cold unit
Line regulation max. 10mV 85-264Vac
Load regulation max. 100mV static value, 0A Æ 5A
Ripple and noise voltage max. 50mVpp 20Hz to 20MHz, 50Ohm
Output capacitance typ. 3 000μF
Output current nom. 5A at 24V, see Fig. 6-1
nom. 4.3A at 28V, see Fig. 6-1
peak 25A The full output voltage cannot be maintained and the
output voltage will drip to lower values. Detailed
curves can be found in chapter22.1.
Output power nom. 120W
Short-circuit current min. 7.8A load impedance 200mOhm, see Fig. 6-1
max. 9.2A load impedance 200mOhm, see Fig. 6-1
max. 8.5A load impedance <10mOhm, see Fig. 6-1
Fig. 6-1 Output voltage vs. output current,
Output Voltage
28V
24
20
16
12
8
4
0
024
typ.
Output Current
8A53167
Apr. 2013 / Rev. 1.1 DS-ML120.244-EN
All parameters are specified at 24V, 5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
6/21
ML120.244
MiniLine-2
24V,5A,SINGLE PHASE INPUT
7. HOLD-UP TIME
Hold-up Time typ. 71ms at 24V, 2.5A, see Fig. 7-1
min. 60ms at 24V, 2.5A, see Fig. 7-1
typ. 35ms at 24V, 5A, see Fig. 7-1
min. 30ms at 24V, 5A, see Fig. 7-1
Note: At no load, the hold-up time can be up to several seconds. The green DC-on LED is also on during this time
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions
Hold-up Time
90ms
75
60
45
30
15
0
200 210230 240260Vac
Input Voltage
220
a
a) 24V 2.5A typ.
b) 24V 2.5Amin.
c) 24V 5A typ.
d) 24V 5A min.
250
b
c
d
Input
Voltage
Output
Voltage
Zero Transition
Hold-up Time
- 5%
Apr. 2013 / Rev. 1.1 DS-ML120.244-EN
All parameters are specified at 24V, 5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
7/21