PULS DP153 User Manual

DP153 1 Output
DIN Rail Power Supply, 40 to 60 Watt
High efficiency: 87% (@ 24V)
ACin 115/230V manual switch
WxHxD = 40x130x120mm
Parallel mode automatic load sharing
(DP153.133)
Meets EMV standards
EN 50081-1 (EN 55022/B), EN 50082-2 EN 61000-4 and NAMUR
Design meets VDE 0551 (EN 60 742)
Data Sheet
DP153
The DP153 is a compact power supply for applications using controllers, sensors, and actuators in industrial plants and heavy machines. Output voltage is stable over the total load range, with excellent ripple and noi­se values of < 20mVpp @ 24V DC.
Low weight and small size allow quick single-handed installation on TS35 DIN rails. The parallel-mode current sharing of the DP153.133 can improve output current performance.
The DP153 withstands line voltage disturbances ac cor­ding to EN 61000-4; VDE 0160 pulses (class 2 for total load range!) are filtered and regulated, so the load is not disturbed. The unit is protected against over-volt­age and short-circuits. Isolation is equivalent to safety transformers according to VDE 0551, and meets VBG 4.
www.puls-power.de
Schematic:
See the web for current data sheet version:
Vout Iout Pout Features Order-No.
10V 4A 12V 4A 24V 2.5A
24V 2.5A
27.6V 2A
Warranty: 2 years from date of delivery.
40W OVP 48W OVP 60W OVP
60W OVP, parallel mode 56W OVP, Vout adjustable
DP153.110 DP153.111 DP153.131
DP153.133 DP153.141
Output
Voltage Vout fixed DP153.110, 111, 131, 133.
Vout adjustable min. ± 5% DP153.141 only. Accuracy Includes: production-adjustment, DP153.110, 111, 131 max. ± 2% line regulation, DP153.133 max. ± 5% and load regulation.
DP153.141 max. ± 0.5% Sense lines None Not available. Minimum load None Not necessary. Output power Pout max. 60W Mounting side by side possible.
only DP153.133 max. 48W Per unit (@ parallel operation). Noise, Ripple max. 20mVpp 20Hz...200kHz.
incl. spikes max. 25mVpp 20Hz...20MHz. Over-voltage protection typ. 1.15 x Vout Threshold accuracy ± 4%. Derating 1W/K +60° to +70°C Ta. Operating indicator 1 green LED On the front. Isolation Vout to Vin SELV EN 60 950, VDE 0805. The output is protected against open-circuit, short-circuit, and overload.
Mechanical: Al/Mg alloy housing, snap-on mounting for
Weight: App. 460g
Screw terminals: Input 1 terminal, max. 2.5/4mm
Tel.: 0049.(0)89.9278-244
Fax: 0049.(0)89.9278-199 www.puls-power.de
DIN rail TS35/7.5 (EN 50022), WxHxD = 40 x 130 x 120mm, the depth includes the DIN-rail mounting, see page 4.
2
output 2 terminals, each max. 2.5/4mm see page 4.
Specifications valid for Vin = 230 V AC, Tamb = +25°C, and 5 min run-in time, unless otherwise stated. They are subject to change without prior notice.
,
2
Input
Line input AC 1 100...127V AC Switch position 115V.
Range 88...132V AC Full spec.
80...150V AC Derated, see page 2.
Line input AC 2 220...240V AC Switch position 230V.
Range 187...264V AC Full spec.
150...300V AC Derated, see page 2. Line frequency 47...63Hz DC or 400Hz, see page 2. Input current rms. max. 1.3Aeff. / 0.7Aeff. @ 115 / 230V AC.
,
Noise suppression EN 55 022/B 10kHz...30MHz, conducted.
Data sheet DP153
10.Mar.99
PULS Munich
Page 1
DP153
1 Output ◆ DIN Rail Power Supply ◆ 40 to 60 Watt
Output (continued) DP153. .110 .111 .131 .133 .141
Voltage regulation:
Line regulation max. %
Load regulation stat.
Load regulation dyn.
Response time t Temperature coefficient typ. %/K
U
max. %
stat
U
max. %
dyn
max. ms 1 1 1 1 1
s
Ripple max. mVpp 20 20 20 20 20
incl. spikes max. mVpp 25 25 25 25 25
Current limitation
Threshold min/max. A 105% ... 120% of Iout
Characteristic See graph on page 3
Short-circuit max. A 180% of Iout
Start delay t Vout rise-up time t
typ. ms 5
Delay
typ. ms 42
Rise
On and off characteristic Power back immunity U
(continued)
Input
max. V 1.2 x Vout
Back
AC input range 1 / 2 V AC 88...132 / 187...264 DC input range V DC 250...300 Derated AC range 1 / 2 V AC 80...88 / 150...187, 150 / 300 for 0.5s Derated DC range V DC 176...250
V DC 300...370
Frequency range Hz 47...63 Derated frequency range Hz 63...400 In-rush current max. A 14
Hold-up time min. ms 34
min. ms 46
Power factor
λ
typ. 0.66 Internal fuse 5x20mm T2A/250V Input range selection Manual (230V AC set at factory)
±
0.2± 0.2 ± 0.2 ± 0.2 ± 0.2
±
1.0± 1.0± 0.5± 4.0± 0.5
±
1.0± 1.0± 0.5 ± 2.0± 0.5
±
0.01± 0.01± 0.01± 0.01± 0.01
(IEC127/2-5)
88...132V AC / 187...264V AC, Iout = 100%. Iout = 50%, ∆ Iout = ±50%.
Iout = 10%...90%...10%, rise time dt = typ. 20µs. Till ∆Vout is within < 0.5% of final value.
20Hz...200kHz, @ AC nom, Iout = 100%. 20Hz...20MHz, @ AC nom, Iout = 100%.
Fixed.
After switch on.
Approximately monotonic. Unit off/on.
Full spec. Full spec.
Power derating typ. 20% (no start below 196V). Full spec, but air- and leakage distances not longer than stated in VDE 0805. Full spec. Increased leakage currents. Wait min. 30s before switching on again (cold-start), NAMUR standard met (Ta = 25° C). @ 88V AC, Iout = 100%. @ 187V AC, Iout = 100%, see figure on page 3. @ 88V AC, Iout = 100%. To replace, see page 4. 115/230V switch, position see page 4.
95%
t
0
t
DelaytRise
90% 10%
100Hz
Vout
Logic Functions
Parallel operation, DP153.133 only units
Current distribution
Connection No additional wiring needed.
Vout adjustable, DP153.141 only min. %
Equal —
Electromagnetic Compatibility
Emissions according to EN 50081-1
Radio interference, EN 55011, EN 55022 Class B (EN 50081-1)
Class A (EN 50081-2)
Immunity according to EN 50082-2 No degradation of performance
Electrostatic discharge ESD 8kV direct discharge (level 4)
EN 61000-4-2 15kV air discharge (level 4) Radiated fields, EN 61000-4-3 10V/m (level 3)
Fast transients, EN 61000-4-4 4kV (level 4)
2kV level 3) 2kV (level 4) cap. coupling
Surge transients EN 61000-4-5 4kV (isolation class 4)
2kV (isolation class 4)
Conducted disturb., ENV 50141 (draft of IEC 801-6) 10V (level 3)
Immunity according to further standards
Transient voltage, IEC 255 5kV
NAMUR-prescription Satisfied
Transient resistance, VDE 0160 §5.3.1.1.2 750V / 1.3ms (class 2)
Over-voltage resistance (PULS standard) 150 / 300V AC / 0.5s
No limit of number of units for DP153.133, 134. Characteristic see page 3. Use equal-length output cables.
±
5
Trimmer position see page 4.
EN 50081-2 is also satisfied For conducted emissions, 10kHz...30MHz, for radiated emissions, 30MHz...1000MHz, EN 50082-1 is also satisfied
80MHz...1000MHz, ACin and Vout lines: l = 1m. Coupled to ACin line. Coupled to DCout line. Coupled to Vout lines. Common mode, unit on. Differential mode, unit on. 150kHz...80MHz.
Common mode, unit off.
Valid for total load range. Switch position 115 / 230V AC.
PULS Munich Data sheet DP153
Page 2
10.Mar.99
Specifications valid for Vin = 230 V AC, Tamb = +25°C, and 5 min run-in time, unless otherwise stated. They are subject to change without prior notice.
Arabellastrasse 15
D-81925 Munich
www.puls-power.de
1 Output ◆ DIN Rail Power Supply ◆ 40 to 60 Watt
DP153
Minimum Hold-Up Time
290 270 250 230 210 190 170 150 130 110
Hold-Up Time [ms]
90 70 50 30 10
80 85 90 95 100 105 110 115 120 125 130
40% Load
60% Load
80% Load
100% Load
Output Vol tage Range 1 [Vac]
Typ. Output Characteristic
125
100
75
DP153.131
50
Output Voltage Vout [%]
25
0
0 50 100 150 200
DP153.133
Output Current Iout [ %]
Typ. Derating over Temperature
70
60
50
40
30
Output Power Pout [W]
20
10
50 55 60 65 70 75
60 Watt 56 Watt 40 Watt
Temperatur e [ + °C]
Protection
Unit protection
Overload Yes See current limit.
Short-circuit proof Yes Automatic voltage recovery.
Open-circuit proof Yes
Over-temperature (OTP)
Reverse battery prot. Yes
ACin range selection Manual Switch for 115/230V AC.
Load protection
Over-voltage (OVP) Yes
Threshold typ. 12.2V DP153.110.
typ. 14.2V DP153.111. typ. 28.2V DP153.131, DP153.1 33 .
typ. 31.2V DP153.141. Accuracy max.± 4% Method Independent second regulator.
Safety
Electrical safety
Test voltage 3kV AC Primary / secondary.
according to EN 60 950 2.5kV AC Primary / PE. for t = 2sec 500V AC Secondary / PE. Air- and leakage distance 6.4 / 8mm Primary / secondary.
4mm Primary / PE.
Isolation resistance min. 5M
Protection class
PE resistance < 0.1
Protection system IP20 DIN 40050, IEC 529.
Leakage current max. 0.75mA EN 60 950 (47...63Hz line) .
Safe low voltage SELV EN 60 950, VDE 0805, VDE 0160.
Over-voltage class
Ι
ΙΙ
VDE 0551. VDE 0106 part 1, IEC 536 . VDE 0805.
VDE 0110 part 1, IEC 664.
Touch safety Finger test VDE 0100 §6, EN 60 950, VBG4. Penetration protection
> ∅
3mm e.g. screws, small parts etc.
Operation and Ambient Area
Application class KSF DIN 40040. Operation temperature max. 0° ... +70°C Ta (measured at 1cm distance).
Derated range +60° ... +70°C Derating, see diagram.
Storage temperature typ. –20° ... +100°C Ta. Humidity max. 95% Non-condensing. Mechanical usage Vertical See page 4.
Lateral spacing None No gap needed.
Cooling Normal convection Don’t obstruct air flow. Dirt protection level max. 2 VDE 0110 part 1. Vibration 0.075mm IEC 68-2-6 (10...60Hz). Shock 11ms / 15g IEC 68-2-27 (3 shocks). Operation height max. 2,000m Above sea level.
Typ. Efficiency
87
82
Efficiency [%]
77
72
20 40 60 80 100
Tel.: 0049.(0)89.9278-244
Fax: 0049.(0)89.9278-199 www.puls-power.de
Output Power [%]
Efficiency and Power Loss
DP153.110 typ. 83% / 8.2W @ 230V ACin, Iout = 100%. DP153.111 typ. 83% / 9.8W As above. DP153.131, 133 typ. 87% / 9.0W As above. DP153.141 typ. 87% / 8.2W As above.
Reliability and Lifetime
230Vac 187Vac
Specifications valid for Vin = 230 V AC, Tamb = +25°C, and 5 min run-in time, unless otherwise stated. They are subject to change without prior notice.
MTBF according to Siemens standard SN29500 typ. 300,000h 230VAC, Iout = 100%, +40°C Ta. Only long life (> 2,000h @105° C) electrolytic capacitors are used. Function test 100% Test certificate enclosed. In-circuit test Yes Run-in (burn-in) 24h Full load, Ta = +60° C,
on/off cycle.
PULS Munich
Data sheet DP153
10.Mar.99
Page 3
F I L T E R
OVP
Regulator
Flyback converter
typ. 100kHz
Vout Vout GND
Trimmer, DP153.141 only
PE L
N
Do not obstruct air flow!
GND
PE (internal) LED green (Vout)
115/230V switch
secondary side
primary side
1)
2)
Mounting for DIN rail TS35/7.5
DP153
1 Output ◆ DIN Rail Power Supply ◆ 40 to 60 Watt
Fuse
The PSU has electronic protection against external short-circuits. In case of an internal defect, a fuse disconnects the unit. It can only be replaced by opening the unit which should be done by the supplier.
Installation for Operating
Install DIN rail TS35/7.5 horizontally, ensuring correct orientation. For other installation considerations consult your representative. Ensure free air flow.
Dimensions and Connections
Fully enclosed Al/Mg alloy housing. All mechanical dimensions are in mm.
1) Do not remove PE screw.
2) Trimmer for adjustment of Vou t at DP153.1 41 (min. ± 5%).
Schematic
Screw terminals:
On the front side. These accept wire of up to 4mm cross section (single-core cable) or 2.5mm2 cross section (multi-core flex). Remove 9 to 15 mm of insulation from wire. Take care of standards which must be satisfied, e.g. VDE 0100 or EN 60950.
Caution:
Do not remove any screws on box, as internal safety connections could be disconnected!
Modifications (contact supplier)
Other output voltages. Other DC input voltages. Lower cost versions.
2
PULS Munich Data sheet DP153
Page 4
10.Mar.99
Specifications valid for Vin = 230 V AC, Tamb = +25°C, and 5 min run-in time, unless otherwise stated. They are subject to change without prior notice.
Arabellastrasse 15
D-81925 Munich
www.puls-power.de
Loading...