Puls Dimension C, Dimension CPS20.241, Dimension CPS20.241-C1 Series Manual

CPS20.241, CPS20.241-C1
C-Series
24V, 20A, SINGLE PHASE INPUT
POWER SUPPLY
PLUS
Overload Mode
Easy Fuse Breaking due to High Overload Current Active Power Factor Correction (PFC) Minimal Inrush Current Surge Full Power Between -25°C and +60°C DC-OK Relay Contact Current Sharing Feature for Parallel Use 3 Year Warranty
1/26
GENERAL DESCRIPTION
The Dimension C-Series are cost optimized power supplies without compromising quality, reliability and performance. The C-Series is part of the DIMENSION power supply family. The most outstanding features of CPS20.241 are the high efficiency, electronic inrush current limitation, active PFC, wide operational temperature range. The small size is achieved by a synchronous rectification and further technological design details.
The C-Series includes all the essential basic functions. The devices have a power reserve of 20% included, which may even be used continuously at temperatures up to +45°C. Additionally, the CPS20.241 can deliver about 4 times the nominal output current for 15ms which helps to trip fuses on faulty output branches.
High immunity to transients and power surges as well as low electromagnetic emission, a DC-OK relay contact and a large international approval package for a variety of applications makes this unit suitable for nearly every situation.
SHORT-FORM DATA
Output voltage DC 24V Adjustment range 24 - 28V Output current 20A at 24V, amb <60°C 24A at 24V, amb <45°C
17.1A at 28V, amb <60°C
20.6A at 28V, amb <45°C Output power 480W ambient <60°C 576W ambient <45°C Output ripple < 50mVpp 20Hz to 20MHz AC Input voltage AC 100-240V -15%/+10% Mains frequency 50-60Hz ±6% AC Input current 4.36 / 2.33A at 120 / 230Vac Power factor 0.99 / 0.95 at 120 / 230Vac AC Inrush current typ. 9 / 7A peak at 120 / 230Vac Efficiency 92.7 / 94.0% at 120 / 230Vac Losses 37.8 / 30.6W at 120 / 230Vac Temperature range -25°C to +70°C operational Derating *) 12W/°C +60 to +70°C Hold-up time typ. 26 / 26ms at 120 / 230Vac Dimensions 65x124x127mm WxHxD Weight 1000g / 2.2lb
*) between 100-85Vac see chapter 15
ORDER NUMBERS
Power Supply CPS20.241 24-28V Standard unit
CPS20.241-C1 Conformal coated unit
Accessory ZM2.WALL Wall mount bracket ZM13.SIDE Side mount bracket YR40.242 Redundancy module YR40.245 Redundancy module
MARKINGS
IND. CONT. E
Q.
UL 508
UL 60950-1
Marine
Class I Div 2
IECEx ATEX
II 3G Ex nA nC II T3 Gc
EMC, LVD, RoHS
Apr. 2014 / Rev. 1.6 DS-CPS20.241-EN All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
CPS20.241, CPS20.241-C1
C-Series
24V, 20A, SINGLE PHASE INPUT
INDEX
Page Page
1.
Intended Use .......................................................3
2. Installation Requirements...................................3
3. AC-Input...............................................................4
4. DC-Input...............................................................5
5. Input Inrush Current ...........................................5
6. Output .................................................................6
7. Hold-up Time.......................................................8
8. DC-OK Relay Contact ..........................................8
9. Efficiency and Power Losses................................9
10. Lifetime Expectancy and MTBF.........................10
11. Functional Diagram...........................................10
12. Terminals and Wiring........................................11
13. Front Side and User Elements...........................12
14. EMC....................................................................13
15. Environment......................................................14
16. Protection Features ...........................................15
17. Safety Features ..................................................15
18. Dielectric Strength ............................................16
19. Approvals...........................................................17
20. Physical Dimensions and Weight..................... 18
21. Accessories ........................................................ 19
21.1. ZM2.WALL - Wall Mounting Bracket.......19
21.2. ZM13.SIDE - Side Mounting Bracket........19
21.3. Redundancy Modules ...............................20
22. Application Notes............................................. 21
22.1. Peak Current Capability ...........................21
22.2. Back-feeding Loads ..................................22
22.3. External Input Protection.........................22
22.4. Output Circuit Breakers............................22
22.5. Parallel Use to Increase Output Power....23
22.6. Parallel Use for Redundancy .................... 23
22.7. Series Operation .......................................24
22.8. Inductive and Capacitive Loads................24
22.9. Charging of Batteries ...............................24
22.10. Operation on Two Phases ........................25
22.11. Use in a Tightly Sealed Enclosure ............25
22.12. Mounting Orientations ............................26
The information presented in this document is believed to be accurate and reliable and may change without notice. No part of this document may be reproduced or utilized in any form without permission in writing from the publisher.
TERMINOLOGY AND ABREVIATIONS
PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol .
Earth, Ground This document uses the term “earth” which is the same as the U.S. term “ground”.
T.b.d. To be defined, value or description will follow later.
AC 230V A figure displayed with the AC or DC before the value represents a nominal voltage with
standard tolerances (usually ±15%) included. E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V)
230Vac A figure with the unit (Vac) at the end is a momentary figure without any additional
tolerances included.
50Hz vs. 60Hz As long as not otherwise stated, AC 230V parameters are valid at 50Hz mains frequency.
may A key word indicating flexibility of choice with no implied preference.
shall A key word indicating a mandatory requirement.
should A key word indicating flexibility of choice with a strongly preferred implementation.
Apr. 2014 / Rev. 1.6 DS-CPS20.241-EN All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
2/26
CPS20.241, CPS20.241-C1
C-Series
24V, 20A, SINGLE PHASE INPUT
1. INTENDED USE
This device is designed for installation in an enclosure and is intended for the general professional use such as in industrial control, office, communication, and instrumentation equipment.
Do not use this power supply in equipment, where malfunction may cause severe personal injury or threaten human life.
This device is designed for use in hazardous, non-hazardous, ordinary or unclassified locations.
2. INSTALLATION REQUIREMENTS
This device may only be installed and put into operation by qualified personnel. This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect. If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to
the factory for inspection. Mount the unit on a DIN-rail so that the terminals are located on the bottom of the unit. For other mounting
orientations see de-rating requirements in this document. See chapter 24.13. This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do
not cover ventilation grid (e.g. cable conduits) by more than 15%! Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are
recommended when the device is loaded permanently with more than 50% of the rated power. Increase this clearance to 15mm in case the adjacent device is a heat source (e.g. another power supply).
A disconnecting means shall be provided for the output of the power supplies when used in applications according to CSA C22.2 No 107.1-01.
WARNING
Risk of electrical shock, fire, personal injury or death.
- Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input block for earth connection and not one of the screws on the housing.
- Turn power off before working on the device. Protect against inadvertent re-powering.
- Make sure that the wiring is correct by following all local and national codes.
- Do not modify or repair the unit.
- Do not open the unit as high voltages are present inside.
- Use caution to prevent any foreign objects from entering the housing.
- Do not use in wet locations or in areas where moisture or condensation can be expected.
- Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.
Notes for use in hazardous location areas:
The power supply is suitable for use in Class I Division 2 Groups A, B, C, D locations and for use in Group II Category 3 (Zone 2) environments and are evaluated according to EN 60079-0:2012 and EN 60079-15:2010.
WARNING EXPLOSION HAZARDS!
Substitution of components may impair suitability for this environment. Do not disconnect the unit or operate the voltage adjustment or S/P jumper unless power has been switched off or the area is known to be non-hazardous.
A suitable enclosure must be provided for the end product which has a minimum protection of IP54 and fulfils the requirements of the EN 60079-15:2010.
Apr. 2014 / Rev. 1.6 DS-CPS20.241-EN All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
3/26
CPS20.241, CPS20.241-C1
C-Series
24V, 20A, SINGLE PHASE INPUT
3. AC-INPUT
AC input nom. AC 100-240V suitable for TN-, TT- and IT mains networks AC input range min. 100-264Vac continuous operation min. 85-100Vac short term or with output derating (1%/V) or with
reduced ambient temperature, see Fig. 15-1,
no damage between 0 and 100Vac min. 264-300Vac < 500ms Allowed voltage L or N to earth max. 300Vac continuous, IEC 62103 Input frequency nom. 50–60Hz ±6% Turn-on voltage typ. 84Vac steady-state value, see Fig. 3-1 Shut-down voltage typ. 39Vac steady-state value at 5A load, see Fig. 3-1 typ. 53Vac steady-state value at 10A load, see Fig. 3-1 typ. 74Vac steady-state value at 20A load, see Fig. 3-1
AC 100V AC 120V AC 230V Input current typ. 5.25A 4.36A 2.33A at 24V, 20A, see Fig. 3-3 Power factor*) typ. 0.99 0.99 0.95 at 24V, 20A, see Fig. 3-4 Crest factor
**)
typ. 1.5 1.5 1.65 at 24V, 20A Start-up delay typ. 850ms 850ms 650ms see Fig. 3-2 Rise time typ. 85ms 85ms 85ms at 24V, 20A const. current load,
0mF load capacitance, see Fig. 3-2
typ. 150ms 150ms 150ms at 24V, 20A const. current load,
20mF load capacitance,, see Fig. 3-2
Turn-on overshoot max. 200mV 200mV 200mV see Fig. 3-2
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit. **) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, definitions
Turn-on
85V
Rated
input range
max.
500ms
V
IN
P
OUT
4/26
300Vac264V
Shut-down
Start-up Rise
delay Time
Overshoot
- 5%
Output Voltage
Input Voltage
Fig. 3-3 Input current vs. output load at 24V Fig. 3-4 Power factor vs. output load
24A
2 4 6 8 10 12 14 16 18
0
1
2
3
4
5
6A
Input Current, typ.
20 22
a) 100Vac b) 120Vac c) 230Vac
b
a
c
Output Current
Power Factor, typ.
2 4 6 8 10 12 14 16 18 24A
0.75
0.8
0.85
0.9
0.95
1.0
20 22
a) 100Vac b) 120Vac c) 230Vac
a, b
c
Output Current
Apr. 2014 / Rev. 1.6 DS-CPS20.241-EN All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
CPS20.241, CPS20.241-C1
C-Series
24V, 20A, SINGLE PHASE INPUT
4. DC-INPUT
Do not operate this power supply with DC-input voltage. Use the CPS20.241-D1 unit instead.
5. INPUT INRUSH CURRENT
An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage and after short input voltage interruptions.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
AC 100V AC 120V AC 230V
Inrush current
*)
max. 13A
peak
13A
peak
13A
peak
temperature independent
typ. 11A
peak
9A
peak
7A
peak
temperature independent
Inrush energy
*)
max. 2A2s 2.5A2s 0.5A2s temperature independent
Inrush delay typ. 935ms 935ms 735ms start-up delay plus rise time
*) Mains interruptions > 500ms
Fig. 5-1 Typical input inrush current
behaviour at nominal load and 25°C ambient
100mS/DIV
Output
Input
230Vac
24Vdc
Input Current 5A / DIV
Apr. 2014 / Rev. 1.6 DS-CPS20.241-EN All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/26
CPS20.241, CPS20.241-C1
C-Series
24V, 20A, SINGLE PHASE INPUT
6. OUTPUT
Output voltage nom. 24V Adjustment range min. 24-28V guaranteed max. 30V
****)
at clockwise end position of potentiometer Factory settings typ. 24.1V ±0.2%, at full load, cold unit, in “single use” mode typ. 24.1V ±0.2%, at full load, cold unit, in “parallel use” mode typ. 25.1V at no load, cold unit, in “parallel use” mode Line regulation max. 10mV 85-300Vac Load regulation max. 100mV in “single use” mode: static value, 0A Æ 20A;
see Fig. 6-1
typ. 1000mV in “parallel use” mode: static value, 0A Æ 20A,
see Fig. 6-2 Ripple and noise voltage max. 50mVpp 20Hz to 20MHz, 50Ohm Output current nom. 20A at 24V, ambient temperature <60°C, see Fig. 6-1 nom. 24A*) at 24V, ambient temperature <45°C, see Fig. 6-1 nom. 17.1A at 28V, ambient temperature <60°C, see Fig. 6-1 nom. 20.6A
*)
at 28V, ambient temperature <45°C, see Fig. 6-1
typ. 80A up to 15ms, output voltage stays above 20V, see Fig.
6-4, This peak current is available once every five
seconds. See chapter 22.1 for more peak current
measurements. Output power nom. 480W continuously available nom. 576W*) Power Boost
® *)
Overload behaviour cont. current output voltage > 13Vdc, see Fig. 6-1 Hiccup
PLUS
mode
**)
output voltage < 13Vdc, see Fig. 6-1
Short-circuit current min. 35A
***)
load impedance <10mOhm, see Fig. 6-3
max. 45A
***)
load impedance <10mOhm, see Fig. 6-3
max. 15A
***)
average (R.M.S.) current, load impedance 50mOhm,
see Fig. 6-3 min. 70A up to 15ms, load impedance <10mOhm, see Fig. 6-4 typ. 100A up to 15ms, load impedance <10mOhm, see Fig. 6-4 Output capacitance typ. 7 000μF included inside the power supply
*) Power Boost
This power/ current is continuously allowed up to an ambient temperature of 45°C. Above 45°C, do not use this power/ current longer than a duty cycle of 10% and/ or not longer than 1 minute every 10 minutes.
**) Hiccup
PLUS
Mode At heavy overloads (when output voltage falls below 13V), the power supply delivers continuous output current for 2s. After this, the output is switched off for approx. 18s before a new start attempt is automatically performed. This cycle is repeated as long as the overload exists. If the overload has been cleared, the device will operate normally. See Fig. 6-3
***) Discharge current of output capacitors is not included. ****) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not
guaranteed value which can be achieved. The typical value is about 28.5V (in “single use” mode).
Apr. 2014 / Rev. 1.6 DS-CPS20.241-EN All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
6/26
CPS20.241, CPS20.241-C1
C-Series
24V, 20A, SINGLE PHASE INPUT
Fig. 6-1 Output voltage vs. output current,
typ.
Fig. 6-2 Output voltage in “parallel use”
mode, typ.
Output Voltage
(Single Use, typ.)
0
025
4
8
12
28V
16
20
24
40A155 10 20 30 35
Adjustment
Range
Output Current
Continuous
current Factory setting
Hiccup
mode
Output Voltage
(Parallel Use, typ.)
22V
0816
23V
24V
25V
29V
26V
27V
28V
24A20124
Adjustment
Range
Factory setting
Output Current
Fig. 6-3 Short-circuit on output, Hiccup
PLUS
mode, typ. Fig. 6-4 Dynamic overcurrent capability, typ.
Output Current
7/26
0
42A
18s
18s
18s
2s
2s
2s
t
Short -circuit
Normal
operation
Normal
operation
Output Voltage
(dynamic behavior, < 15ms)
0
4
8
12
28V
16
20
24
0
100A4020 60 8010 30 50 70 90
Adjustment
Range
Output Current
Apr. 2014 / Rev. 1.6 DS-CPS20.241-EN All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
CPS20.241, CPS20.241-C1
C-Series
24V, 20A, SINGLE PHASE INPUT
7. HOLD-UP TIME
AC 100V AC 120V AC 230V Hold-up Time typ. 65ms 65ms 65ms at 24V, 10A, see Fig. 7-1 min. 54ms 54ms 54ms at 24V, 10A, see Fig. 7-1 typ. 26ms 26ms 26ms at 24V, 20A, see Fig. 7-1 min. 21ms 21ms 21ms at 24V, 20A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions
0
10
20
30
40
80ms
90 120 155 190 230Vac
Input Voltage
50
60
Hold-up Time
24V, 20A, typ.
24V, 10A, min.
24V, 10A, typ.
70
24V, 20A, min.
- 5%
Hold-up Time
Zero Transition
Output Voltage
Input Voltage
8. DC-OK RELAY CONTACT
This feature monitors the output voltage, which is produced by the power supply itself. It is independent of a back-fed voltage from a unit connected in parallel to the power supply output.
Contact closes As soon as the output voltage reaches 90% of the adjusted output voltage level. Contact opens As soon as the output voltage dips more than 10% below the adjusted output voltage.
Short dips will be extended to a signal length of 100ms. Dips shorter than 1ms will be ignored. Contact ratings max. 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A resistive load min. 1mA at 5Vdc min. permissible load Isolation voltage See dielectric strength table in section 18.
Fig. 8-1 DC-ok relay contact behavior
V
OUT
= V
ADJ
8/26
100ms
0.9* V
ADJ
<
1ms
10%
>
1ms
open openclosed closed
Apr. 2014 / Rev. 1.6 DS-CPS20.241-EN All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany