AC 100-240V Wide-range Input
Width only 39mm
Built-in Decoupling Mosfet for 1+1 and n+1 Redundancy
Efficiency up to 94.7%
20% Output Power Reserves
Safe Hiccup
Easy Fuse Breaking – 3 times nominal current for 12ms
Active Power Factor Correction (PFC)
Minimal Inrush Current Surge
Full Power Between -25°C and +60°C
DC-OK Relay Contact
Current Sharing Feature Included
3 Year Warranty
PLUS
Overload Mode
GENERAL DESCRIPTION
The Dimension CP-Series are cost optimized power
supplies without compromising quality, reliability and
performance. The most outstanding features of the
CP10.241–R1/-R2/-R3 units are the high efficiency,
electronic inrush current limitation, active PFC, wide
operational temperature range and the extraordinary
small size. The units include a decoupling MOSFET for
building 1+1 or n+1 redundant power supply systems.
These redundancy power supplies come with three
connection terminal options; screw terminals, springclamp terminals or plug connector terminals which
allows replacement on an active application.
CP10.242-R2 version feature an enhanced DC input
voltage range.
With high immunity to transients and power surges, low
electromagnetic emission, a DC-OK signal contact for
remote monitoring, and a large international approval
package, makes this unit suitable for nearly every
application.
CP10.241-R3 With screw terminals
CP10.242-R2 Enhanced DC-Input
Mechanical Accessory
ZM4.WALL Wall/panel mount bracket
ZM12.SIDE Side mount bracket
SHORT-FORM DATA
Output voltage DC 24V 0%/+6%
Adjustment range -
Output current 12A Below +45°C ambient
10A At +60°C ambient
7.5A At +70°C ambient
Derate linearely between +45°C and +70°C
AC Input voltage AC 100-240V -15%/+10%
Mains frequency 50-60Hz ±6%
AC Input current 2.17 / 1.14A At 120 / 230Vac
Power factor 0.99 / 0.97 At 120 / 230Vac
Input voltage DC DC 110-150V
DC 110-300V
Input current DC 2.35A / 0.84A At 110 / 300Vdc
AC Inrush current 6 / 9Apk At 120 / 230Vac
Efficiency 93.0 / 94.7% At 120 / 230Vac
Losses 18.1 / 13.4W At 120 / 230Vac
Hold-up time 37 / 37ms At 120 / 230Vac
Temperature range -25°C to +70°C
Size (w x h x d) 39x124x117mm Without DIN-rail and
Weight 600g / 1.32lb
±20%
For CP10.241-Rx
±20%
For CP10.242-R2
plug connectors
MARKINGS
For details or a complete approval list see section 20.
Feb. 2018 / CP10.241-R2 Rev0.3-EN - All values are typical figures specified at 230Vac, 50Hz input voltage, 24V, 10A output
load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
1/31
P R E L I M I N A R Y
CP10.241-R1, CP10.241-R2,
CP10.241-R3,CP10.242-R2
INDEX
Page Page
1. Intended Use .......................................................4
The information given in this document is correct to the best of our knowledge and experience at the time of
publication. If not expressly agreed otherwise, this information does not represent a warranty in the legal sense of the
word. As the state of our knowledge and experience is constantly changing, the information in this data sheet is
subject to revision. We therefore kindly ask you to always use the latest issue of this document.
No part of this document may be reproduced or utilized in any form without our prior permission in writing.
Feb. 2018 / CP10.241-R2 Rev0.3-EN - All values are typical figures specified at 230Vac, 50Hz input voltage, 24V, 10A output
load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
2/31
P R E L I M I N A R Y
CP10.241-R1, CP10.241-R2,
CP10.241-R3,CP10.242-R2
TERMINOLOGY AND ABREVIATIONS
PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol .
Earth, Ground This document uses the term “earth” which is the same as the U.S. term “ground”.
T.B.D. To be defined, value or description will follow later.
AC 230V A figure displayed with the AC or DC before the value represents a nominal voltage with
230Vac A figure with the unit (Vac) at the end is a momentary figure without any additional
50Hz vs. 60Hz As long as not otherwise stated, AC 230V parameters are valid at 50Hz mains frequency.
may A key word indicating flexibility of choice with no implied preference.
shall A key word indicating a mandatory requirement.
should A key word indicating flexibility of choice with a strongly preferred implementation.
1+1 Redundancy Use of two identical power supplies in parallel to provide continued operation following most
N+1 Redundancy Use of three or more identical
CP-Series
24V,10A,240W,SINGLE PHASE
standard tolerances (usually ±15%) included.
E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V)
tolerances included.
failures in a single power supply. The two power supply outputs should be isolated from each
other by utilizing diodes or other switching arrangements. E.g. two 10A power supplies are
needed to achieve a 10A
redundant system.
power supplies in parallel to
provide continued operation
AC
CP10-Rx
AC
CP10-Rx
N+1
Redundancy
AC
AC
CP10-Rx
CP10-Rx
AC
CP10-Rx
AC
CP10-Rx
Redundancy
AC
CP10-Rx CP10-Rx
following most failures in a
DC
DC
DC
DC
DC
DC
single power supply. All power
supply outputs should be
isolated from each other by
utilizing diodes or other
switching arrangements.
+
Load
-
E.g.: To achieve a 40A redundant system, five 10A power supplies are needed in a N+1
redundant system.
DC
1+1
+
Load
AC
-
DC
Feb. 2018 / CP10.241-R2 Rev0.3-EN - All values are typical figures specified at 230Vac, 50Hz input voltage, 24V, 10A output
load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
3/31
P R E L I M I N A R Y
CP10.241-R1, CP10.241-R2,
CP10.241-R3,CP10.242-R2
1. INTENDED USE
This device is designed for installation in an enclosure and is intended for the general professional use such as in
industrial control, office, communication, and instrumentation equipment.
Do not use this power supply in equipment, where malfunction may cause severe personal injury or threaten human
life.
2. INSTALLATION REQUIREMENTS
WARNING
- Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input block for
earth connection and not one of the screws on the housing.
- Turn power off before working on the device. Protect against inadvertent re-powering.
- Make sure that the wiring is correct by following all local and national codes.
- Do not modify or repair the unit.
- Do not open the unit as high voltages are present inside.
- Use caution to prevent any foreign objects from entering the housing.
- Do not use in wet locations or in areas where moisture or condensation can be expected.
- Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.
Obey the following installation requirements:
- This device may only be installed and put into operation by qualified personnel.
- Install the device in an enclosure providing protection against electrical, mechanical and fire hazards.
- The device is designed for use in pollution degree 2 areas in controlled environments.
- The enclosure of the device provides a degree of protection of IP20 according to IEC 60529.
- Mount the unit on a DIN-rail so that the input terminals are located on the bottom of the unit. For other mounting
orientations see de-rating requirements in this document.
- The device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do
not cover ventilation grid (e.g. cable conduits) by more than 15%!
- Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are
recommended when the device is loaded permanently with more than 50% of the rated power. Increase this
clearance to 15mm in case the adjacent device is a heat source (Example: another power supply).
- Make sure that the wiring is correct by following all local and national codes. Use appropriate copper cables that are
designed for a minimum operating temperature of 60°C for ambient temperatures up to +45°C, 75°C for ambient
temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. Ensure that all strands of a stranded wire
enter the terminal connection. Check also local codes and local requirements. In some countries local regulations
might apply.
- This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect. If
damage or malfunction should occur during installation or operation, immediately turn power off and send the
device to the factory for inspection.
- The device is designed, tested and approved for branch circuits up to up to 30A (UL) or 32A (IEC) without additional
protection device. If an external fuse is utilized, do not use circuit breakers smaller than 10A B- or C-Characteristic to
avoid a nuisance tripping of the circuit breaker.
- A disconnecting means shall be provided for the input of the power supply.
CP-Series
Risk of electrical shock, fire, personal injury or death.
24V,10A,240W,SINGLE PHASE
Feb. 2018 / CP10.241-R2 Rev0.3-EN - All values are typical figures specified at 230Vac, 50Hz input voltage, 24V, 10A output
load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
4/31
P R E L I M I N A R Y
CP10.241-R1, CP10.241-R2,
CP10.241-R3,CP10.242-R2
3. AC-INPUT
The device is suitable to be supplied from TN-, TT- and IT mains networks with AC voltage. For suitable DC supply
voltages see chapter 4.
AC input Nom. AC 100-240V
AC input range Min. 85-264Vac Continuous operation
Min. 264-300Vac For maximal 500ms (occasional)
Allowed voltage L or N to earth Max. 300Vac Continuous, according to IEC 60664-1
Input frequency Nom. 50–60Hz ±6%
Turn-on voltage Typ. 80Vac Steady-state value, see Fig. 3-1
Shut-down voltage Typ. 70Vac Steady-state value, see Fig. 3-1
Typ. 55Vac Dynamic value (max. 250ms)
External input protection See recommendations in chapter 2.
Input current Typ. 2.63A 2.17A 1.14A At 10A, see Fig. 3-3
Power factor Typ. 0.99 0.99 0.97 At 10A, see Fig. 3-4
Crest factor Typ. 1.5 1.5 1.65 At 10A, The crest factor is the
Start-up delay Typ. 300ms 290ms 240ms See Fig. 3-2
Rise time Typ. 30ms 30ms 30ms At 10A const. current load, 0mF
Typ. 75ms 75ms 75ms At 10A const. current load, 20mF
Turn-on overshoot Max. 200mV 200mV 200mV See Fig. 3-2
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, definitions
P
OUT
input range
CP-Series
Rated
AC 100VAC 120VAC 230V
max.
500ms
24V,10A,240W,SINGLE PHASE
mathematical ratio of the peak
value to RMS value of the input
current waveform.
load capacitance, see Fig. 3-2
load capacitance,, see Fig. 3-2
Input
Voltage
Turn-on
Shut-down
a) 100Vac
b) 120Vac
c) 230Vac
85V
Output Current
Fig. 3-3 Input current vs. output current Fig. 3-4 Power factor vs. output current
Input Current, typ.
6A
5
4
3
2
1
0
24681012141618
Feb. 2018 / CP10.241-R2 Rev0.3-EN - All values are typical figures specified at 230Vac, 50Hz input voltage, 24V, 10A output
load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
300Vac264V
20 22
V
24A
IN
a
b
c
Output
Voltage
Power Factor, typ.
1.0
0.95
0.9
0.85
0.8
0.75
2 4 6 8 101214161824A
- 5%
Start-up
delay
Rise
Time
a) 100Vac
b) 120Vac
c) 230Vac
Output Current
20 22
a, b
Overshoot
c
5/31
P R E L I M I N A R Y
CP10.241-R1, CP10.241-R2,
CP10.241-R3,CP10.242-R2
4. DC-INPUT
The device is suitable to be supplied from a DC input voltage. Use a battery or a similar DC source. A supply from the
intermediate DC-bus of a frequency converter is not recommended and can cause a malfunction or damage the unit.
Connect +pole to L, –pole to N and the PE terminal to an earth wire or to the machine ground.
DC input Nom. DC 110-150V ±20% for CP10.241-Rx
Nom. DC 110-300V ±20% for CP10.242-R2
DC input range Min. 88-180Vdc Continuous operation for CP10.241-Rx
88-360Vdc Continuous operation for CP10.242-R2
DC input current Typ. 2.35A At 110Vdc and 10A load current
Typ. 0.84A At 300Vdc and 10A load current
Allowed Voltage (+) or (-) input
to Earth
Turn-on voltage Typ. 80Vdc Steady state value
Shut-down voltage Typ. 70Vdc Steady state value
Typ. 55Vdc Dynamic value (max. 250ms)
Fig. 4-1 Wiring for DC Input
Battery
+
CP-Series
Power Supply
AC
L
N
PE
+
24V,10A,240W,SINGLE PHASE
Max. 360Vdc Continuous according to IEC 60664-1
Load
-
-
Feb. 2018 / CP10.241-R2 Rev0.3-EN - All values are typical figures specified at 230Vac, 50Hz input voltage, 24V, 10A output
load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
DC
6/31
P R E L I M I N A R Y
CP10.241-R1, CP10.241-R2,
CP10.241-R3,CP10.242-R2
5. INPUT INRUSH CURRENT
An active inrush limitation circuit (NTCs, which are bypassed by a relay contact) limits the input inrush current after
turn-on of the input voltage.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
Inrush current Max. 11A
Typ. 9A
Typ. 9A
Inrush energy Max. 0.1A²s 0.1A²s 0.4A²s At 40°C, cold start
Fig. 5-1 Typical turn-on behaviour at nominal
load, 120Vac input and 25°C ambient
Input current
2A/DIV
50ms/DIV
CP-Series
24V,10A,240W,SINGLE PHASE
AC 100VAC 120VAC 230V
7A
peak
6A
peak
6A
peak
11A
peak
6A
peak
9A
peak
Fig. 5-2 Typical turn-on behaviour at nominal
load, 230Vac input and 25°C ambient
6A
peak
peak
peak
50ms/DIV
Input current
2A/DIV
At 25°C, cold start
At 40°C, cold start
At 40°C, cold start
Input voltage
250V/DIV
Output voltage 20V/DIV
6A
Input voltage
500V/DIV
Output voltage 20V/DIV
Feb. 2018 / CP10.241-R2 Rev0.3-EN - All values are typical figures specified at 230Vac, 50Hz input voltage, 24V, 10A output
load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
7/31
P R E L I M I N A R Y
CP10.241-R1, CP10.241-R2,
CP10.241-R3,CP10.242-R2
6. OUTPUT
The output provides a SELV/PELV/ES1 rated voltage, which is galvanically isolated from the input voltage. The output
of the devices includes a decoupling MOSFET for building 1+1 or n+1 redundant power supply systems.
The device is designed to supply any kind of loads, including capacitive and inductive loads. If extreme large
capacitors, such as EDLCs (electric double layer capacitors or “UltraCaps”) with a capacitance larger than 1.5F are
connected to the output, the unit might charge the capacitor in the Hiccup
The device is featured with a “soft output regulation characteristic” in order to achieve current share between
multiple devices when they are connected in parallel. The “soft output regulation characteristic” regulates the output
voltage in such a manner that the voltage at no load is approx. 4% higher than at nominal load.
Output voltage Nom. DC 24V 23.8 - 25.2V
Adjustment range See chapter 24.2
Factory settings typ. 24.1V ±0.2%, at 10A, cold unit (results to typ. 23.9V
Line regulation Max. 10mV 85-300Vac
Load regulation Typ. 1000mV Static value, 0A Æ 10A; see Fig. 6-1
Ripple and noise voltage Max. 50mVpp 20Hz to 20MHz, 50Ohm
Output current Nom. 12A1) Below 45°C ambient temperature, see Fig. 17-1
Nom. 10A At 60°C ambient temperature, see Fig. 17-1
Nom. 7.5A At 70°C ambient temperature, see Fig. 17-1
Fuse breaking current2) Typ. 30A Up to 12ms once every five seconds, see Fig. 6-3.
Overload protection Included Electronically protected against overload, no-load
Overload behaviour Continuous current Output voltage >13Vdc, see Fig. 6-1
Intermitted current3) Output voltage <13Vdc, see Fig. 6-1
Overload/ short-circuit current Max. 15.5A Continuous current, see Fig. 6-1
Typ. 14A Intermitted current peak value for typ. 2s
Max. 5A Intermitted current average value (R.M.S.)
Output capacitance Typ. 4 400μF Included inside the power supply
Back-feeding loads
1) This current is also available for temperatures up to +70°C with a duty cycle of 10% and/ or not longer than 1 minute every 10 minutes.
2) The fuse braking current is an enhanced transient current which helps to start heavy loads or to trip fuses on faulty output branches. The
output voltage stays above 20V. See chapter 24.1 for additional measurements.
3) At heavy overloads (when output voltage falls below 13V), the power supply delivers continuous output current for 2s. After this, the
output is switched off for approx. 18s before a new start attempt is automatically performed. This cycle is repeated as long as the overload
exists. If the overload has been cleared, the device will operate normally. See Fig. 6-2.
CP-Series
24V,10A,240W,SINGLE PHASE
PLUS
mode.
12A and typ. 25.1V
and short-circuits. In case of a protection event,
audible noise may occur.
Load impedance 10mOhm, see Fig. 6-2.
Discharge current of output capacitors is not included.
Load impedance 10mOhm, see Fig. 6-2.
Max. 35V The unit is resistant and does not show
malfunctioning when a load feeds back voltage to
the power supply. It does not matter whether the
power supply is on or off. The absorbing energy can
be calculated according to the built-in large sized
output capacitor.
±0.2%
at no load)
±0.2%
at
Feb. 2018 / CP10.241-R2 Rev0.3-EN - All values are typical figures specified at 230Vac, 50Hz input voltage, 24V, 10A output
load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
8/31
P R E L I M I N A R Y
CP10.241-R1, CP10.241-R2,
CP10.241-R3,CP10.242-R2
Fig. 6-1 Output voltage vs. output current, typ. Fig. 6-2 Short-circuit on output, Hiccup
Output Voltage
28V
24
20
16
12
A: continuous current
8
B: intermitted current
4
0
012.5
Fig. 6-3 Dynamic overcurrent capability, typ.
Output Voltage
28V
24
20
16
12
8
4
0
0
CP-Series
(dynamic behavior, < 12ms)
A
B
Output
Current
Output
Current
20A7.52.5 51015 17.5
50A201030405 15253545
24V,10A,240W,SINGLE PHASE
Output
Current
Normal
operation
14A
0
2s
18s
Short -circuit
2s
18s
PLUS
mode, typ.
2s
18s
Normal
operation
t
7. HOLD-UP TIME
AC 100VAC 120VAC 230V
Hold-up Time Typ. 73ms 73ms 73ms At 5A, see Fig. 7-1
Min. 55ms 55ms 55ms At 5A, see Fig. 7-1
Typ. 37ms 37ms 37ms At 10A, see Fig. 7-1
Min. 28ms 28ms 28ms At 10A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions
Hold-up Time
80ms
70
60
50
40
30
20
10
0
90120155190230Vac
Feb. 2018 / CP10.241-R2 Rev0.3-EN - All values are typical figures specified at 230Vac, 50Hz input voltage, 24V, 10A output
load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
a) At 5A typ.
b) At 5A min.
Input Voltage
c) At 10A typ.
d) At 10A min.
a
b
c
d
Input
Voltage
Output
Voltage
Zero Transition
- 5%
Hold-up Time
9/31
P R E L I M I N A R Y
CP10.241-R1, CP10.241-R2,
CP10.241-R3,CP10.242-R2
8. DC-OKRELAY CONTACT
This feature monitors the output voltage of the power supply in front of the decoupling device (see also chapter 12).
Contact closes As soon as the output voltage reaches typically 22Vdc.
Contact opens As soon as the output voltage dips below 22Vdc.
Switching hysteresis 1V
Contact ratings Maximal 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, resistive load
Minimal permissible load: 1mA at 5Vdc
Isolation voltage See dielectric strength table in chapter 19.
Fig. 8-1 DC-ok relay contact behavior
22Vdc
CP-Series
Short dips will be extended to a signal length of 100ms. Dips shorter than 1ms will be ignored.
24V,10A,240W,SINGLE PHASE
<
openopenclosedclosed
1ms
>
1...4ms
100ms
Feb. 2018 / CP10.241-R2 Rev0.3-EN - All values are typical figures specified at 230Vac, 50Hz input voltage, 24V, 10A output
load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
10/31