PULS CD5.241, CD5.241-S1 User guide

CD–Series
1. GENERAL DESCRIPTION
The Dimension CD5-series offer DIN-rail DC/DC converters in the 120W output power range in a very compact housing.
These DC/DC converters are allowed to run from a battery, can also be used to refresh and stabilize the 24Vdc on the end of a long cable or to isolate specific loads from the 24V bus voltage.
The CD5.241 includes all the essential basic functions while the CD5.241-S1 is equipped with quick-connect spring clamp terminals, a DC-OK-contact which monitors the output and an input-low-relay-contact. Both devices have a power reserve of 20% and this extra power can be used continuously up to +45°C.
CD-Series
Related products
24V->24V
CD5.241
24V->24V
CD5.241-S1
24V->12V
CD5.121
48V->24V
CD5.242
Spring-clamp terminals, Input-low, DC-OK contacts
3. ORDER NUMBERS
DC/DC Converter
Accessories ZM1.WALL Wall mount bracket ZM11.SIDE Side mount bracket
YR2.DIODE Decoupling module
CD5.241
CD5.241-S1
YRM2.DIODE Redundancy module
Standard unit
Unit with signals and spring-clamp terminals
CD5.241, CD5.241-S1
DC/DC Converter; 24V, 5A
DC/DC CONVERTER
Wide Range DC Input (18-32.4Vdc)
Isolated 24Vdc Output
Efficiency up to 90.3%
Width only 32mm
20% Output Power Reserves
Full Output Power Between -25°C and +60°C
Soft Start Function Included
Minimal Inrush Current Surge
Reverse Input Polarity Protection
DC-OK and Input-low Relay Contact (CD5.241-S1)
3 Year Warranty
2. SHORT-FORM DATA
Output voltage DC 24V Adjustment range 23 - 28V
5 – 4.3A 6 – 5.1A
UL 60950-1
GL
Marine, pending
Ambient <60°C Ambient <45°C
(14 to 18Vdc with derating)
Class I Div 2,
pending
EMC, LVD
Output current
Output power 120W Ambient <60°C 144W Ambient <45°C Output ripple < 50mVpp 20Hz to 20MHz Input voltage DC 24V 18 to 32.4Vdc
Input current typ. 5.5A At 24Vdc input Input Inrush current typ. 1.2A peak Efficiency typ. 90.3% At 24Vdc input Losses typ. 12.9W At 24Vdc input Hold-up time typ. 6ms At 24Vdc input Temperature range -25°C to +70°C Operational Derating 3W/°C +60 to +70°C Dimensions 32x124x102mm WxHxD
4. MARKINGS
18WM
LISTED
IND. CONT. EQ.
UL 508
R
CUS
182790
pending
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
CDSeries
CD5.241, CD5.241-S1
DC/DC Converter; 24V, 5A
INDEX PAGE INDEX PAGE
1.
General Description ............................................1
2. Short-form Data ..................................................1
3. Order Numbers....................................................1
4. Markings..............................................................1
5. Input Voltage ......................................................3
6. Soft-start and Input Inrush Current Surge .........4
7. Output .................................................................5
8. Hold-up Time.......................................................6
9. Efficiency and Power Losses................................7
10. Functional Diagram.............................................8
11. Reliability.............................................................8
12. Front Side and User Elements.............................9
13. Terminals and Wiring..........................................9
14. DC-OK Relay Contact (CD5.241-S1) ..................10
15. Input-low Relay Contact (CD5.241-S1) .............10
16. EMC....................................................................11
17. Environment......................................................12
18. Protection Features...........................................12
19. Safety .................................................................13
20. Dielectric Strength ............................................13
21. Approvals...........................................................14
22. Fulfilled Standards............................................ 14
23. Used Substances ............................................... 14
24. Physical Dimensions and Weight..................... 15
25. Installation and Operation Instructions .......... 15
26. Accessory........................................................... 16
27. Application Notes............................................. 17
27.1. Peak Current Capability......................... 17
27.2. Back-feeding Loads................................ 17
27.3. Inductive and Capacitive Loads ............. 17
27.4. Output Circuit Breakers ......................... 18
27.5. Series Operation..................................... 19
27.6. Parallel Use to Increase Output Power . 19
27.7. Daisy Chaining of Outputs..................... 19
27.8. Parallel Use for 1+1 Redundancy........... 20
27.9. Charging of Batteries............................. 20
27.10. Requirements for the Supplying Source 21
27.11. External Input Protection....................... 21
27.12. Use in a Tightly Sealed Enclosure .......... 21
27.13. Mounting Orientations.......................... 22
INTENDED USE
The DC/DC converter shall only be installed and put into operation by qualified personnel. This DC/DC converter is designed for installation in an enclosure and is intended for the general use, such as in
industrial control, office, communication, and instrumentation equipment. Do not use this device in aircraft, trains and nuclear equipment, where malfunctioning of the DC/DC converter may cause severe personal injury or threaten human life.
TERMINOLOGY AND ABREVIATIONS
PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol .
Earth, Ground This document uses the term “earth” which is the same as the U.S. term “ground”.
T.b.d. To be defined, value or description will follow later.
DC 24V A figure displayed with the AC or DC before the value represents a nominal voltage with
standard tolerances included. E.g.: DC 12V describes a 12V battery regardless whether it is full (13.7V) or flat (10V)
24Vac A figure with the unit (Vdc) at the end is a momentary figure without any additional
tolerances included.
DISCLAIMER
The information presented in this document is believed to be accurate and reliable and may change without notice. Some parts of this unit are patent by PULS (US patent No 091662,063, Des. 424,529, …). No part of this document may be reproduced or utilized in any form without permission in writing from PULS GmbH.
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
CDSeries
CD5.241, CD5.241-S1
DC/DC Converter; 24V, 5A
5. INPUT VOLTAGE
Input Input voltage range
14.0-18.0Vdc Max. 60 seconds or with de-rating see Fig. 5-2
Allowed voltage between input and earth (ground)
Allowed input ripple voltage
Turn-on voltage typ. 17.5Vdc Steady-state value, see Fig. 5-1 Shut-down voltage typ. 14.0Vdc Steady-state value, see Fig. 5-1
Input current Start-up delay typ. Rise time typ. 80ms 0mF, 24V, constant current load 5A, see Fig. 5-3
Turn-on overshoot Input capacitance typ.
External capacitors on the input voltage bus are allowed without any limitations.
Fig. 5-1 Input voltage range
P
OUT
Shut-down
14.0Vdc
Rated input range
Turn-on
17.5Vdc
18.0Vdc
Fig. 5-3 Turn-on behavior, definitions Fig. 5-4 Input current vs. output load
Intput Voltage
Output Voltage
- 5%
Start-up
delay
Rise
Time
nom. DC 24V nom. 18.0-32.4Vdc Continuous operation
max. 36.0Vdc Absolute maximum continuous input voltage with no
damage to the DC/DC converter.
max. 60Vdc or
42.4Vac
max. 5Vpp 47Hz-40kHz, the momentary input voltage must always be
within the specified limits.
typ. 35Vdc Steady-state value, see Fig. 5-1 typ. 5.5A At 24Vdc input and output 24V, 5A, see Fig. 5-4
650ms
See Fig. 5-3
typ. 150ms 5mF, 24V, constant current load 5A, see Fig. 5-3
32.4Vdc
500mV 3 000µF
V
IN
35.0Vdc
Overshoot
See Fig. 5-3
Fig. 5-2 Allowable output current below 18V
Output Current
6A
5
4
3
2
1
0
14 16 18 20 24Vdc
Input
8A
Current, typ.
6
4
2
0
1
1.5 2 3
input voltage
)
a
(
)
b
(
(a) Ambient < 45°C (b) Ambient < 60°C
Input Voltage
Output Current
3.5
2.5
u
p
n
I
n
I
4
:
t
p
4.5
22
c
d
V
8
1
V
4
2
:
t
u
5
d
5.5
c
6A
max.
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
CDSeries
CD5.241, CD5.241-S1
DC/DC Converter; 24V, 5A
6. SOFT-START AND INPUT INRUSH CURRENT SURGE
Inrush current limitation
An active inrush limitation circuit (inrush limiting resistor which is bypassed by a relay contact) limits the input inrush current after turn-on of the input voltage.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
Inrush current
max. 1.6A typ. 1.2A Inrush energy
typ. negligible -25°C to +70°C
Fig. 6-1 Input inrush current, typical behavior
Input Current
Input Voltage
Input 24Vdc
-25°C to +70°C
peak
-25°C to +70°C
peak
Input: 24Vdc Output: 24Vdc, 5A, constant current load Ambient: 25°C
Upper curve: Input current 2A / DIV Middle curve: Input voltage 20V / DIV Lower curve: Output voltage 20V / DIV Time scale: 100ms / DIV
Output Voltage
Soft-start function:
After the DC/DC converter is turned on, the internal output current rises slowly to its nominal value. This method charges the output capacitors (internal and external capacitors) slowly and avoids high input currents during turn-on. High input currents can produce a high voltage drop on the input wiring (especially with long and thin cables) which reduces the terminal voltage on the DC/DC converter. If the terminal voltage is below the shut-down voltage, the DC/DC converter will turn-off and will make a new start-up attempt. This effect is avoided with the integrated soft­start function. Please note, that this function increases the rise time of the output voltage by a small amount.
Fig. 6-2 Soft-start behavior
Input: 24Vdc Output: 24Vdc, 5A, constant current load Ambient: 25°C No additional external capacitors
Input Current
Upper curve: Input current 2A / DIV Lower curve: Output voltage 10V / DIV Time scale: 20ms / DIV
Output Voltage
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
A
CDSeries
CD5.241, CD5.241-S1
DC/DC Converter; 24V, 5A
7. OUTPUT
Output voltage Adjustment range max. 30V At clockwise end position of potentiometer Factory setting Line regulation Load regulation max. 100mV CD5.241; static value, 0A Æ 5A Æ 0A
Ripple and noise voltage Output capacitance typ. Output current nom. 6A At 24V, ambient < 45°C, see Fig. 7-1 nom. 5A
Output power nom. 144W Ambient < 45°C nom. 120W Short-circuit current max. 10A Load impedance 200mOhm, see Fig. 7-1
Fig. 7-1 Output voltage vs. output current,
typ. (24Vdc input voltage)
nom. 24V min. 23-28V Guaranteed
max.
24.1V 25mV
±0.2%, at full load, cold unit
Input variations between 18 to 32.4Vdc
max. 150mV CD5.241-S1; static value, 0A Æ 5A Æ 0A max.
50mVpp 2200µF
20Hz to 20MHz, 50Ohm
At 24V, ambient < 60°C, see
Fig. 7-1
nom. 5.1A At 28V, ambient < 45°C, see Fig. 7-1 nom. 4.3A
At 28V, ambient < 60°C, see
Fig. 7-1
Ambient < 60°C
min. 7A Load impedance 200mOhm, see Fig. 7-1
Fig. 7-2 Current limitation vs. input voltage,
typ. (23V constant voltage load)
Output Voltage
28V
24
20
16
12
8
4 0
Adjustment
Range
Output Current
048
1062
12
Output Current
6.6A
6.5
6.4
6.3
6.2
6.1
6.0
5.9
5.8 15 21 27
Input Voltage
33Vdc302418
Peak current capability (up to several ms)
The DC/DC converter can deliver a peak current which is higher than the specified short term current. This helps to start current demanding loads or to safely operate subsequent circuit breakers.
The extra current is supplied by the output capacitors inside the DC/DC converter. During this event, the capacitors will be discharged and cause a voltage dip on the output. Detailed curves can be found in chapter 27.1.
Peak current voltage dips typ. from 24V to 15V
typ. from 24V to 18V At 10A for 50ms, resistive load
At 20A for 2ms, resistive load
typ. from 24V to 11.5V
At 20A for 5ms, resistive load
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
CDSeries
CD5.241, CD5.241-S1
DC/DC Converter; 24V, 5A
8. HOLD-UP TIME
The input side of the DC/DC converter is equipped with a bulk capacitor which keeps the output voltage alive for a certain period of time when the input voltage dips or is removed. The bulk capacitor can be discharged by loading the DC/DC converter on the output side or through a load which is parallel to the input. There is no protection in the DC/DC converter which prevents current from flowing back to the input terminals. If prevention is needed, an external diode should be used.
Input 24Vdc
Hold-up Time typ. 11.8ms Input 24Vdc, output: 24Vdc, 2.5A, see Fig. 8-1 typ. 6ms Input 24Vdc, output: 24Vdc, 5A, see Fig. 8-1
Fig. 8-1 Hold-up time vs. input voltage
Hold-up Time
12ms
10
8
6
4
2
0
Input Voltage
18 20 22 24 28Vdc
(
a
)
)
(
b
)
c
(
)
(
d
(a) 24V, 2.5A, typ. (b) 24V, 2.5A, min. (c) 24V, 5A, typ. (d) 24V, 5A, min.
26
Fig. 8-2 Shut-down test setup Fig. 8-3 Shut-down behavior, definitions
DC/DC
Converter
S1
Input
Output
CD5
+
+
Load
-
-
DC
Source
+
-
Intput Voltage
Output Voltage
S1 opens
- 5%
Hold-up Time
Note: At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is also on during this time.
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
A
A
c
c
CDSeries
CD5.241, CD5.241-S1
DC/DC Converter; 24V, 5A
9. EFFICIENCY AND POWER LOSSES
Input 24Vdc
Efficiency typ. 90.3% 5A, 24V Power losses typ. 0.7W CD5.241 at no output load
1.1W CD5.241-S1 at no output load typ. 6.2W 2.5A, 24V typ. 12.9W 5A, 24V typ. 16.3W 6A, 24V
Fig. 9-1 Efficiency vs. output current at 24V Fig. 9-2 Losses vs. output current at 24V
Efficiency
91%
90
89
88
87
86
85
Output Current
1
245
3
6
Power Losses
18W
15
12
9
6
3
0
012 456
Fig. 9-3 Efficiency vs. input voltage, 24V, 5A Fig. 9-4 Losses vs. input voltage, 24V, 5A
Efficiency
91%
90.5
90.0
89.5
89.0
88.5
88.0 18 20 22 26 28 32
Input Voltage
24 30
Vd
Power Losses
18W
15
12
9
6
3
0
18 20 24 26 28 32
Output Current
3
Input Voltage
22 30
Vd
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
CDSeries
10. FUNCTIONAL DIAGRAM
Fig. 10-1 Functional diagram CD5.241
+
Fig. 10-2 Functional diagram CD5.241-S1
Chassis
Ground
-
+
-
Chassis
Ground
Input Fuse & Input Filter
Input Fuse & Input Filter
Reverse Polarity Protection & Inrush Limiter
Over-
Temperature
Protection
Reverse Polarity Protection & Inrush Limiter
Over-
Temperature
Protection
Output
Over-
Voltage
Protection
Output
Over-
Voltage
Protection
Power
Converter
Power
Converter
CD5.241, CD5.241-S1
DC/DC Converter; 24V, 5A
Output
Voltage
Output Voltage Monitor
Input Voltage Monitor
Regulator
Output
Filter
Output
Voltage
Regulator
Output
Filter
DC-ok Relay
Input low Relay
V
OUT
+ +
-
-
DC ok
V
OUT
+ +
-
-
DC ok
14
13
12
11
Input low
11. RELIABILITY
CD5.241 CD5.241-S1
Lifetime expectancy min. 183 000h 180 000h 40°C, 24V, 2.5A min. 65 000h 60 000h 40°C, 24V, 5A min. 37 000h 33 000h 40°C, 24V, 6A min. 185 000h 169 000h 25°C, 24V, 5A MTBF SN 29500, IEC 61709 1 178 000h 1 048 000h 40°C, 24V, 5A 1 932 000h 1 719 000h 25°C, 24V, 5A MTBF MIL HDBK 217F 625 000h 602 000h 40°C, 24V, 5A, Ground Benign GB40 838 000h 807 000h 25°C, 24V, 5A, Ground Benign GB25
The Lifetime expectancy shown in the table indicates the operating hours (service life) and is determined by the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours. Lifetime expectancy is calculated according to the capacitor’s manufacturer specification. The prediction model allows a calculation of up to 15 years from date of shipment.
MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
CDSeries
12. FRONT SIDE AND USER ELEMENTS
Fig. 12-1
Front side CD5.241
Fig. 12-2
Front side CD5.241-S1
CD5.241, CD5.241-S1
DC/DC Converter; 24V, 5A
A Output Terminals Screw terminals (Spring-clamp terminals on the CD5.241-S1)
Dual terminals per pole + Positive output
- Negative (return) output
Input Terminals
B Screw terminals (Spring-clamp terminals on the CD5.241-S1) + Positive input
- Negative (return) input Chassis ground can be used to bond the housing to PE Ground this terminal to minimize high-frequency emissions.
Signal Terminals
C Plug Connector for DC-OK and Input-low relay contact
D
Output voltage potentiometer
Open the flap to set the output voltage. Factory set: 24.1V
E DC-OK LED (green) See also chapter 14
CD5.241: On when the voltage on the output terminals is > 21V CD5.241-S1: Monitors the output voltage, which is produced by the power supply itself and is on when the voltage is higher than 90% of the adjusted output voltage. DC-OK lamp and DC-OK contact functions are synchronized
Input-low LED (yellow) See also chapter 15
F On when the input voltage is between 4Vdc and 20Vdc..
Input-low LED and Input-low contact functions are synchronized
13. TERMINALS AND WIRING
Type Screw terminals Spring-clamp terminals Plug-connector (screws) Solid wire 0.5-6mm2 0.5-6mm2 0.2-1.5mm2 Stranded wire 0.5-4mm2 0.5-4mm2 0.2-1.5mm2 American wire gauge 20-10 AWG 20-10 AWG 22-14 AWG Recommended tightening torque 1Nm, 9lb.in - 0.4Nm / 3.5lb.in Wire stripping length 7mm / 0.275inch 10mm / 0.4inch 6mm / 0.25inch
Instructions:
a) Use appropriate copper cables that are designed for an operating temperature of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum. b) Follow local and national installation codes and regulations! c) Ensure that all strands of a stranded wire enter the terminal connection! d) Up to two stranded wires with the same cross section are permitted in one connection point. e) Ferrules are allowed but not required f) In order to fulfill GL requirements, unused terminal spaces must be closed.
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
Input and output CD5.241
www.pulspower.com Phone +49 89 9278 0 Germany
Input and output CD5.241-S1
Signals CD5.241-S1
CDSeries
CD5.241, CD5.241-S1
DC/DC Converter; 24V, 5A
14. DC-OK RELAY CONTACT (CD5.241-S1)
This feature is only available on the model CD5.241-S1 and monitors the output voltage, which is produced by the DC/DC converter itself. It is independent of a back-fed voltage from a unit which is connected in parallel to the DC/DC converter output. It is a “Normally Open” contact.
Contact closes As soon as the output voltage reaches the adjusted output voltage. Contact opens As soon as the output voltage dips more than 10% below the adjusted output voltage.
Contact re-closes As soon as the output voltage exceeds 90% of the adjusted voltage. Contact ratings max 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A Resistive load min 1mA at 5Vdc Minimum permissible load Isolation voltage See dielectric strength table in section 20
Fig. 14-1 DC-ok relay contact behavior
V
=
V
OUT
ADJ
90%
V
ADJ
open
<
1ms
Short dips will be extended to a signal length of 250ms. Dips shorter than 1ms will be ignored.
Note:
The DC-ok feature requires that the output voltage
10%
reaches the nominal (=adjusted) level after turn-on in order to function according to specification. If this level cannot be achieved, the overload lamp will be on and
>
1ms
250ms
the DC-ok contact will be open. The overload signal will only shut off as soon as the adjusted voltage is reached. This is an important condition to consider particularly, if the load is a battery, the DC/DC converter is used in
openclosed closed
parallel or the DC/DC converter is used for N+1 redundant systems.
15. INPUT-LOW RELAY CONTACT (CD5.241-S1)
This feature monitors the input voltage of the DC/DC converter. It is a “Normally Closed” contact.
Contact is closed Contact opens Contact ratings max 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A Resistive load min 1mA at 5Vdc Minimum permissible load Isolation voltage See dielectric strength table in section 20
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
When the input voltage falls below 19.5Vdc (typ.) As soon as the input voltage reaches 20.5 Vdc (typ.)
www.pulspower.com Phone +49 89 9278 0 Germany
10/22
CDSeries
CD5.241, CD5.241-S1
DC/DC Converter; 24V, 5A
16. EMC
The CE mark indicates conformance with EMC directive 89/336/EC, 93/68/EC and 2004/108/EC and the low-voltage directive (LVD) 73/23/EC, 93/68/EC, 2006/95/EC. A detailed EMC Report is available on request.
EMC Immunity
Electrostatic discharge EN 61000-4-2 Contact discharge
Electromagnetic RF field EN 61000-4-3 80MHz-2.7GHz 10V/m Criterion A
Fast transients (Burst) EN 61000-4-4 Input lines
Surge voltage on input EN 61000-4-5 + Æ -
Surge voltage on output EN 61000-4-5 + Æ -
Conducted disturbance EN 61000-4-6 0,15-80MHz 10V Criterion A
Criterions:
A: DC/DC converter shows normal operation behavior within the defined limits. C: Temporary loss of function is possible. DC/DC converter might shut-down and restarts by itself. No damage or hazards will occur
to the DC/DC converter.
EMC Emission
Conducted emission CISPR 16-1-2, CISPR 16-2-1 Input / output lines (Limits for DC power ports) Radiated emission EN 55011, EN 55022 Class B
This device complies with FCC Part 15 rules. Operation is subjected to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Switching frequency
EN 61000-6-2, EN 61000-6-1
Air discharge
Output lines Signal lines
+ / - Æ chassis ground
+ / - Æ chassis ground
EN 61000-6-3, EN 61000-6-4 Generic standards
90kHz to 135kHz (Output current > 0.5A) Input voltage and output current
Generic standards 8kV
15kV
4kV 2kV 2kV
1kV 2kV
500V 500V
dependent
Criterion A Criterion A
Criterion A Criterion A Criterion A
Criterion A Criterion A
Criterion A Criterion A
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
11/22
C
CDSeries
CD5.241, CD5.241-S1
DC/DC Converter; 24V, 5A
17. ENVIRONMENT
Operational temperature -25°C to +70°C (-13°F to 158°F) Reduce output power according to Fig. 17-1 Output de-rating 1.6W/°C 45-60°C (113°F to 140°F), see Fig. 17-1 3W/°C 60-70°C (140°F to 158°F), see Fig. 17-1 Storage temperature -40 to +85°C (-40°F to 185°F) During storage and transportation
Humidity 5 to 95% r.H. IEC 60068-2-30
Vibration sinusoidal 2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
Shock 30g 6ms, 20g 11ms
2 hours / axis
3 bumps / direction, 18 bumps in total
Altitude 0 to 6000m (0 to 20000ft) Reduce output power or ambient
Output de-rating (for altitude) 7.5W/1000m or 5°C/1000m Above 2000m (6500ft), see Fig. 17-2 Over-voltage category III EN 50178, altitudes up to 2000m II Altitudes from 2000m to 6000m Degree of pollution 2 EN 50178, non conductive
Fig. 17-1 Output current vs. ambient temp. Fig. 17-2 Output current vs. altitude, 24V
Allowable Output Current at 24V
6A
5
4
3
2
1
0
-25 0 20 40 70°
c
n
o
n
i
t
u
o
u
s
Ambient Temperature
60
s
h
r
o
t
t
e
r
m
Allowable Output Current at 24V
6A
5
4
3
2
1
0
The ambient temperature is defined 2cm below the unit.
Do not energize while condensation is present
IEC 60068-2-6
IEC 60068-2-27
temperature above 2000m sea level.
h
s
r
o
t
t
e
m
r
C
B
A
.
A
.
a
.
T
b
m
<
6
C
°
B
.
.
.
T
C
.
.
.
T
0 2000 4000
0
a
b
m
5
<
C
°
0
a
b
m
4
<
C
°
0
Altitude
6000m
18. PROTECTION FEATURES
Output protection Electronically protected against overload, no-load and short-circuits Output over-voltage protection typ. 31Vdc
max. 32Vdc
Reverse input polarity protection Included Unit does not start when input voltage is reversed Output over-current protection electronically limited See Fig. 7-1 Degree of protection IP 20 EN/IEC 60529 Penetration protection > 3.5mm E.g. screws, small parts Over-temperature protection Yes Output shut-down with automatic restart Input transient protection MOV Metal Oxide Varistor Internal input fuse T10A H.B.C. Not user replaceable
An audible noise may be heard during a no load, overload or short circuit event.
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
In case of an internal DC/DC converter fault, a redundant circuit limits the maximum output voltage. The output shuts down and automatically attempts to restart.
12/22
CDSeries
CD5.241, CD5.241-S1
DC/DC Converter; 24V, 5A
19. SAFETY
Input / output separation SELV IEC/EN 60950-1 PELV EN 60204-1, EN 50178, IEC 60364-4-41
Double or reinforced insulation,
Max. allowed voltage between any input pin and ground: 60Vdc or 42.4Vac Class of protection II PE (Protective Earth) connection not required Isolation resistance > 5MOhm Input to output, 500Vdc Chassis Ground resistance < 0.1Ohm Between housing and Chassis Ground terminal
Touch current (leakage current) The leakage current which is produced by the DC/DC converter itself depends on
the input voltage ripple and need to be investigated in the final application.
For a smooth DC input voltage, the produced leakage current is less than 100µA.
20. DIELECTRIC STRENGTH
The output voltage is floating and has no ohmic connection to ground. To fulfill the PELV requirements according to EN60204-1 § 6.4.1, it is recommend that either the + pole, the – pole or
any other part of the output circuit shall be connected to the protective earth system. This helps to avoid situations in which a load starts unexpectedly or can not be switched off any more when an unnoticed earth faults occur.
CD5.241:
CD5.241-S1:
Fig. 20-1 Dielectric strength
Input
+
-
A
Chassis ground
Fig. 20-2 Dielectric strength
Input Signals
+
-
A
Chassis ground
B
Output
C
B
B
C
D
Output
A B C
Type test 60s 1500Vac 1500Vac 500Vac
Factory test 5s 1500Vac 1500Vac 500Vac
Field test 5s 1000Vac 1000Vac 500Vac
+
-
Type tests and factory tests: Conducted by the manufacturer. Do not repeat test in field! Rules for field test: Use appropriate test equipment which applies the voltage with a slow ramp! Connect all input poles together as well as all output poles.
A B C D
Type test 60s 1500Vac 1000Vac 500Vac 500Vac
Factory test 5s 1500Vac 1000Vac 500Vac 500Vac
Field test 5s 1000Vac 1000Vac 500Vac 500Vac Type tests and factory tests:
Conducted by the manufacturer. Do not repeat test in field! Rules for field test:
+
-
Use appropriate test equipment which applies the voltage with a slow ramp! Connect all input poles together as well as all output poles.
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
13/22
CDSeries
CD5.241, CD5.241-S1
DC/DC Converter; 24V, 5A
21. APPROVALS
IEC 60950-1
IECEE
CB SCHEME
UL 508
UL 60950-1
UL 1604
pending
The unit is suitable for use in Class I Division 2 Groups A, B, C, D locations as well as for Class I
CSA pending
Marine
pending
Zone 2 Groups IIA, IIB and IIC locations. Substitution of components may impair suitability for Class I Division 2 environment. Do not disconnect equipment unless power has been switched off. Wiring must be in accordance with Class I, Division 2 wiring methods of the National Electrical Code, NFPA 70, and in accordance with other local or national codes.
18WM
LISTED
IND. CONT. EQ.
R
CUS
182790
GL
ABS
CB Scheme, Information Technology Equipment
LISTED E198865 Industrial Control Equipment
RECOGNIZED E137006 recognized for the use in U.S.A. (UL 60950-1) and Canada (C22.2 No. 60950) Information Technology Equipment, Level 3
RECOGNIZED E246877 recognized for use in U.S.A. (UL 1604) and Canada (C22.2 No. 213-M1987) Hazardous Location Class I Div 2 T4 Groups A,B,C,D and Class I Zone 2 Groups IIA, IIB and IIC
CSA approval for Canada CAN/CSA C22.2 No 107-1; CAN/ CSA 60950-1-03; UL60950-1
GL (Germanischer Lloyd) classified and ABS (American Bureau for Shipping) PDA for marine and offshore applications.
Environmental category: C, EMC2
22. FULFILLED STANDARDS
EN 61558-2-17 Safety of Power Transformers
EN/IEC 60204-1 Safety of Electrical Equipment of Machines
EN/IEC 61131-2 Programmable Controllers
EN 50178, IEC 62103 Electronic Equipment in Power Installations
23. USED SUBSTANCES
The unit does not release any silicone and is suitable for the use in paint shops.
The unit conforms to the RoHS directive 2002/96/EC
Electrolytic capacitors included in this unit do not use electrolytes such as Quaternary Ammonium Salt Systems.
Plastic housings and other molded plastic materials are free of halogens, wires and cables are not PVC insulated.
The materials used in our production process do not include the following toxic chemicals: Polychlorinated Biphenyl (PCB), Pentachlorophenol (PCP), Polychlorinated naphthalene (PCN), Polybrominated Biphenyl (PBB), Polybrominated Biphenyl Oxide (PBO), Polybrominated Diphenyl Ether (PBDE), Polychlorinated Diphenyl Ether (PCDE), Polybrominated Diphenyl Oxide (PBDO), Cadmium, Asbestos, Mercury, Silica
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
14/22
CDSeries
CD5.241, CD5.241-S1
DC/DC Converter; 24V, 5A
24. PHYSICAL DIMENSIONS AND WEIGHT
Weight 425g / 0.94lb CD5.241 450g / 0.99lb CD5.241-S1 DIN-Rail Use 35mm DIN-rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm.
The DIN-rail height must be added to the depth (102mm) to calculate the total required installation depth.
Electronic files with mechanical data can be downloaded at www.pulspower.com
Fig. 24-1
CD5.241
Front view
Fig. 24-2
CD5.241
Side view
Fig. 24-3 CD5.241-S1 Front view
Fig. 24-4
CD5.241-S1
Side view
25. INSTALLATION AND OPERATION INSTRUCTIONS
Mounting:
Output terminal must be located on top and input terminal on the bottom. For other orientations see chapter 27.13. An appropriate electrical and fire end-product enclosure should be considered in the end use application.
Cooling:
Convection cooled, no forced cooling required. Do not cover ventilation grill (e.g. cable conduits) by more than 30%!
Installation clearances:
40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance are recommended.
Risk of electrical shock, fire, personal injury or death!
Turn power off before working on the DC/DC converter. Protect against inadvertent re-powering. Make sure the wiring is correct by following all local and national codes. Do not open, modify or repair the unit. Use caution to prevent any foreign objects from entering into the housing. Do not use in wet locations or in areas where moisture or condensation can be expected.
Supplying source, supplying network:
The inductance and resistance of the supplying network shall be below in Fig. 27-9 in chapter 27.10 to avoid resonant effects on the input terminals. Please also check chapter 27.10.
Service parts: The unit does not contain any service parts. The tripping of an internal fuse is caused by an internal fault. If damage or malfunctioning should occur during operation, immediately turn power off and send unit to the factory for inspection!
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
15/22
CDSeries
CD5.241, CD5.241-S1
DC/DC Converter; 24V, 5A
26. ACCESSORY
ZM1.WALL Wall mounting bracket This bracket is used to mount specific Dimension units onto a flat surface without utilizing a DIN-Rail. The two
aluminum brackets and the black plastic slide of the unit have to be removed, so that the two steel brackets can be mounted.
(Please note: Picture shows a different unit)
Fig. 26-1 ZM1.WALL Wall Mounting Bracket Fig. 26-2 Assembled Wall Mounting Bracket
ZM11.SIDE Side mounting bracket This bracket is used to mount specific Dimension units sideways with or without utilizing a DIN-Rail. The two
aluminum brackets and the black plastic slide of the unit have to be removed, so that the steel bracket can be mounted.
For sideways DIN-rail mounting, the removed aluminum brackets and the black plastic slide need to be reinstalled on the steel bracket.
(Please note: Pictures show a different unit)
Fig. 26-3 ZM11.SIDE Side Mounting Bracket Fig. 26-4 Side Mounting with DIN-rail brackets
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
16/22
CDSeries
CD5.241, CD5.241-S1
DC/DC Converter; 24V, 5A
27. APPLICATION NOTES
27.1. PEAK CURRENT CAPABILITY
Solenoids, contactors and pneumatic modules often have a steady state (sealed) coil and a pick-up coil. The inrush current demand of the pick-up coil is several times higher than the steady state current and usually exceeds the nominal output current (including the PowerBoost) The same situation applies, when starting a capacitive load.
Branch circuits are often protected with circuit breakers or fuses. In case of a short or an overload in the branch circuit, the fuse needs a certain amount of over-current to trip or to blow. The peak current capability ensures the safe operation of subsequent circuit breakers.
Assuming the input voltage is turned on before such an event, the built-in large sized output capacitors inside the DC/DC converter can deliver extra current. Discharging this capacitor causes a voltage dip on the output. The following two examples show typical voltage dips:
Fig. 27-1 Peak load 10A for 50ms, typ. Fig. 27-2 Peak load 20A for 5ms, typ.
24V
10A
Output Voltage
18V
24V
Output Voltage
20A
11.5V
0A
10ms/DIV
Peak load 10A (resistive) for 50ms
Output voltage dips from 24V to 18V.
Output Current
0A
Peak load 20A (resistive) for 5ms
Output voltage dips from 24V to 11.5V.
1ms/DIV
Output Current
27.2. BACK-FEEDING LOADS
Loads such as decelerating motors and inductors can feed voltage back to the DC/DC converter. This feature is also called return voltage immunity or resistance against Back- E.M.F. (E
This DC/DC converter is resistant and does not show malfunctioning when a load feeds back voltage to the DC/DC converter. It does not matter, whether the DC/DC converter is on or off.
The maximum allowed feed back voltage is 30Vdc. The absorbing energy can be calculated according to the built-in large sized output capacitor which is specified in chapter 7.
lectro Magnetic Force).
27.3. INDUCTIVE AND CAPACITIVE LOADS
The unit is designed to supply any kind of load, including unlimited capacitive and inductive loads.
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
17/22
CDSeries
CD5.241, CD5.241-S1
DC/DC Converter; 24V, 5A
27.4. OUTPUT CIRCUIT BREAKERS
Standard miniature circuit breakers (MCBs or UL1077 circuit breakers) can be used for branch circuit protection. Ensure that the MCB is also rated for DC voltage. The following tests show which circuit breakers the DC/DC converter typically trips.
Circuit breakers have huge tolerances in their tripping behavior, therefore, these typical tests can only be used as a recommendation or for comparing two different DC/DC converters. Furthermore, the loop impedance has a major influence on whether a breaker trips or not. Two tests were performed, representing typical situations:
Test 1: Short circuit with S1 on the DC/DC converter end of the cable (loop impedance approx. 20mOhm)
Fig. 27-3 Branch protectors, test circuit 1
Circuit
Breaker
I
+
S1
-
+
Load
-
DC/DC
Converter
Input
DC
Test 2: Short circuit with S1 on the load end (additional impedance included; represents longer load wire length).
Fig. 27-4 Branch protectors, test circuit 2
Circuit
DC/DC
Converter
AC
DC
Breaker
I
+
-
R
+
S1 Load
-
*) A list of the circuit breakers under test is available on request.
Example: Which wire gauge must be used to trip a C-Characteristic circuit breaker with a rating of 3A? The load wire length is 21m.
Answer: A 3A C-Characteristic circuit breaker requires a loop impedance of less than 270mOhm (test results). The wire length table shows that up to 23m wire with a cross section of 1.5mm
2
1.5mm
shall be used.
180mOhm 270mOhm
Parameters: Input voltage: 24Vdc, load current: 0A
The following circuit breaker tripped during the test:
A- or Z- Characteristic:: equal or smaller 8A *) B- Characteristic: no tripping 6A *)
no breaker available < 6A C- Characteristic: equal or smaller 3A *)
Parameters: Input voltage: 24Vdc, load current: 0A
The following circuit breaker tripped during the test:
A- or Z- Characteristic:: 6A and R= 180mOhm *) B- Characteristic: no tripping 6A *)
no breaker available < 6A C- Characteristic: ≤ 3A and R= 270mOhm *)
What does this resistance mean in wire length?
2
0.5mm
0.7mm2 1.0mm2 1.5mm2 2.5mm2 4.0mm2
5.0m 7.0m 10m 15m 25m 40m
7.5m 10.5m 15m 23m 38m 60m
2
are below 270mOhm. A wire not smaller than
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
18/22
CDSeries
27.5. SERIES OPERATION
DC/DC converters can be connected in series to increase the output voltage.
Fig. 27-5 Schematic for series operation
Unit A
Input
Unit B
Input
Output
+
-
+
Output
-
+
Load
-
Earth (see notes)
Instructions for use in series:
a) It is possible to connect as many units in series as needed,
providing the sum of the output does not exceed 150Vdc.
b) Voltages with a potential above 60Vdc are not SELV any more
and can be dangerous. Such voltages must be installed with a
protection against touching. c) For serial operation use DC/DC converters of the same type. d) Earthing of the output is required when the sum of the output
voltage is above 60Vdc. e) Keep an installation clearance of 15mm (left/right) between
two DC/DC converters and avoid installing the DC/DC
converters on top of each other. Note:
Avoid return voltage (e.g. from a decelerating motor or
battery) which is applied to the output terminals.
CD5.241, CD5.241-S1
DC/DC Converter; 24V, 5A
27.6. PARALLEL USE TO INCREASE OUTPUT POWER
Several DC/DC converter can be paralleled to increase the output power.
Fig. 27-6 Schematic for parallel operation
Unit A
Input
Output
Unit B
Input
Output
Fuse
+
-
Fuse
+
-
*)
+
*)
Load
-
Instructions for parallel use:
a) Use only DC/DC converters from the same series (C-Series) or
consult PULS. b) Adjust the output voltages of all power supplies to
approximately the same value (±200mV). c) A fuse (or diode) on the output is only required if more than
three units are connected in parallel. d) Do not load terminals with more than 25A. Follow wiring
instructions according to chapter 27.7 e) Ensure that the ambient temperature of the power supply does
not exceed 45°C.
27.7. DAISY CHAINING OF OUTPUTS
Daisy chaining (jumping from one power supply output to the next) is allowed as long as the maximum current through one terminal pin does not exceed 25A. If the current is higher, use a separate distribution terminal block.
Fig. 27-7 Daisy chaining of outputs
max 25A!
Output
+ +
- -
DC/DC
Converter
Output
+ +
- -
DC/DC
Converter
+
Load
-
Fig. 27-8 Using distribution terminals
Output
+ +
- -
DC/DC
Converter
Output
+ +
- -
DC/DC
Converter
+
Load
-
Input
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
Input
www.pulspower.com Phone +49 89 9278 0 Germany
Input
Input
Distribution Terminals
19/22
CDSeries
CD5.241, CD5.241-S1
DC/DC Converter; 24V, 5A
27.8. PARALLEL USE FOR 1+1 REDUNDANCY
DC/DC converters can be paralleled for 1+1 redundancy to gain a higher system availability. Redundant systems require a certain amount of extra power to support the load in case one DC/DC converter unit fails. The simplest way is to put two DC/DC converters in parallel. In case one converter fails, the other one is automatically able to support the load current without any interruption.
Furthermore, redundant systems can be built by using a DC/DC converter powered from a battery and a power supply with AC input.
- Use the decoupling module YR2.DIODE in combination with two CD5.241-S1 and use the DC-OK signals of the DC/DC converter to monitor a faulty unit or input voltage.
- Use the redundancy module YRM2.DIODE in combination with two CD5.241 and use the DC-OK signals of the redundancy module to monitor a faulty unit or input voltage.
Recommendations for building redundant power systems: a) Use separate input fuses for each DC/DC converter. b) Monitor the individual voltage sources of a redundant system. A DC-ok lamp and a DC-ok contact is included in
the redundancy module YRM2.DIODE and the DC/DC converter CD5.241-S1. This feature reports a faulty unit.
c) When possible, connect each DC/DC converter to different power sources.
27.9. CHARGING OF BATTERIES
The power supply can be used for float-charging of lead-acid or maintenance free 24V VRLA batteries.
Instructions for charging batteries:
a) Ensure that the ambient temperature of the power supply does not exceed 50°C. b) Set the output voltage on a disconnected load, very precisely to the end-of-charge voltage according to the
expected battery temperature.
End-of-charge voltage 27.8V 27.5V 27.15V 26.8V Battery temperature 10°C 20°C 30°C 40°C
c) Use a 6A or 10A circuit breaker (or blocking diode ) between the power supply and the battery. d) Ensure that the output current of the power supply is below the allowed charging current of the battery. e) Use only matched batteries when putting 12V types in series. f) The return current to the power supply is typ. 26.4mA at 25Vdc when the power supply is switched off (except in
case a blocking diode is utilized).
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
20/22
CDSeries
CD5.241, CD5.241-S1
DC/DC Converter; 24V, 5A
27.10. REQUIREMENTS FOR THE SUPPLYING SOURCE
In certain circumstances, the input filter of the DC/DC converter can show a resonant effect which is caused by the supplying network. Especially when additional external input filters are utilized, a superimposed AC voltage can be generated on the input terminals of the DC/DC converter which might cause a malfunction of the unit. Therefore, additional input filters are not recommended. To avoid the resonant effects, the minimal resistance of the supplying network which depends on the inductance of the input network, shall be above the boundary curve in Fig. 27-9.
Fig. 27-9 Requirements for an input filter
Resistance of the supplying network
1 Ohm
100 mOhm
stability
10 mOhm
1 mOhm
0.1mH 1mH 10mH
Inductance of the supplying network
)
a
(
(
b
)
(a) max. (b) typ.
27.11. EXTERNAL INPUT PROTECTION
The unit is tested and approved for branch circuits up to 50A. External protection is only required if the supplying branch has an ampacity greater than this. In some countries local regulations might apply so check local codes and local requirements.
If an external fuse is necessary or utilized, a minimum value is required to avoid undesired tripping of the fuse.
B-Characteristic C-Characteristic
Ampacity max.
min.
50A 50A 10A 8A
27.12. USE IN A TIGHTLY SEALED ENCLOSURE
When the DC/DC converter is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher than the outside. The inside temperature defines the ambient temperature for the DC/DC converter.
Results from such an installation: DC/DC converter is placed in the middle of the box, no other heat producing equipment inside the box Enclosure: Rittal Type IP66 Box PK 9516 100, plastic, 110x180x165mm
Load: 24V, 4A; (=80%) load is placed outside the box Input: 24Vdc Temperature inside the box: 42.8°C (in the middle of the right side of the DC/DC converter with a distance of 2cm) Temperature outside the box: 24.0°C Temperature rise: 28.8K
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
21/22
CDSeries
CD5.241, CD5.241-S1
DC/DC Converter; 24V, 5A
27.13. MOUNTING ORIENTATIONS
Mounting orientations other than input terminals on the bottom and output on the top requires a reduction in continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction influences the lifetime expectancy of the DC/DC converter. Therefore, two different derating curves for continuous operation can be found below:
Curve A1 Recommended output current. Curve A2 Max allowed output current (results approx. in half the lifetime expectancy of A1).
Fig. 27-10
Mounting Orientation A
Standard Orientation
Fig. 27-11
Mounting Orientation B (Upside down)
OUTPUT
DC/DC
Converter
INPUT
INPUT
Converter
DC/DC
OUTPUT
Fig. 27-12
Mounting Orientation C
(Table-top mounting)
Fig. 27-13
Mounting Orientation D
(Horizontal cw)
Converter
INPUT
OUTPUT
DC/DC
Fig. 27-14
Mounting Orientation E
(Horizontal ccw)
OUTPUT
DC/DC
INPUT
Converter
Output Current
6A
5 4 3 2 1
0
10 20 30
Output Current
6A
5 4 3 2 1
0
10 20 30
Output Current
6A
5 4 3 2 1
0
10 20 30
Output Current
6A
5 4 3 2 1
0
10 20 30
Output Current
6A
5 4 3 2 1
0
10 20 30
Ambient Temperature
40
50
Ambient Temperature
40
A
2
A
1
Ambient Temperature
40
A
2
A
1
Ambient Temperature
40
Ambient Temperature
40
50
50
50
50
A
1
60°C
A
2
A
1
60°C
60°C
60°C
A
2
A
1
60°C
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.