DC/DC Converter 48V/48V, 5A, 240W
DC/DC CONVERTER
▪ 48V DC-Input
▪ Isolated 48Vdc Output
▪ Efficiency 95.1%
▪ Width only 42mm
▪ 20% Output Power Reserves
▪ Full Power Between -25°C and +60°C
▪ Soft-start Function
▪ Minimal Inrush Current Surge
▪ Reverse Input Polarity Protection
▪ 3 Year Warranty
The CD10.482 is a DIN-rail mountable DC/DC converter of the
Derate between +60°C and +70°C
DIMENSION series which provides a floating, stabilized and
galvanically separated SELV/PELV output voltage.
The CD-Series is part of the DIMENSION power supply family.
The most outstanding features of CD10.482 are the high
efficiency, the small size and the wide operational temperature
range.
The CD-Series includes all the essential basic functions. The
devices have a power reserve of 20% included, which may even
be used continuously at temperatures up to +45°C.
High immunity to transients and power surges as well as low
electromagnetic emission and a large international approval
package for a variety of applications makes this unit suitable for
nearly every situation.
DC/DC Converter
Mechanical Accessory
Jun 2020 / Rev. 1.0 DS-CD10.482-EN All values are typical figures specified at 48Vdc input voltage 48V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
For details or a complete approval list see section 18.
CD10.482
ZM2.WALL Wall/panel mount bracket
ZM12.SIDE Side mount bracket
DC/DC Converter 48V/48V, 5A, 240W
Page Page
TERMINOLOGY AND ABREVIATIONS
1. Intended Use ................................................................ 3
2. Installation Instructions ................................................ 3
3. DC-Input ....................................................................... 4
4. Input Inrush Current ..................................................... 6
5. Soft-start Feature ......................................................... 6
6. Output .......................................................................... 7
7. Hold-up Time ................................................................ 8
8. Efficiency and Power Losses ......................................... 9
9. Functional Diagram .................................................... 10
10. Front Side and User Elements .................................... 10
11. Connection Terminals ................................................ 11
12. Lifetime Expectancy ................................................... 12
13. MTBF .......................................................................... 12
14. EMC ............................................................................ 13
15. Environment ............................................................... 14
16. Safety and Protection Features .................................. 15
17. Dielectric Strength ...................................................... 15
18. Approvals ................................................................... 16
The information given in this document is correct to the best of our knowledge and experience at the time of publication. If not
expressly agreed otherwise, this information does not represent a warranty in the legal sense of the word. As the state of our
knowledge and experience is constantly changing, the information in this data sheet is subject to revision. We therefore kindly ask you
to always use the latest issue of this document (available under www.pulspower.com).
No part of this document may be reproduced or utilized in any form without our prior permission in writing.
19. Other Fulfilled Standards ........................................... 16
20. Physical Dimensions and Weight ............................... 17
21. Accessories................................................................. 18
21.1. ZM2.WALL – Wall/Panel Mount Bracket .......... 18
21.2. ZM12.SIDE - Side Mount Bracket ..................... 19
21.3. YRM2.DIODE - Redundancy Module ................ 20
21.4. UF20.481 - Buffer Module ................................ 20
22. Application Notes....................................................... 21
22.1. Peak Current Capability .................................... 21
22.2. Output Circuit Breakers .................................... 22
22.3. Charging of Batteries ........................................ 22
22.4. Series Operation ............................................... 23
22.5. Parallel Use to Increase Output Power ............ 23
22.6. Parallel Use for Redundancy ............................ 24
22.7. Use in a Tightly Sealed Enclosure ..................... 25
22.8. Mounting Orientations ..................................... 26
PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol .
Earth, Ground This document uses the term “earth” which is the same as the U.S. term “ground”.
T.b.d. To be defined, value or description will follow later.
DC 48V A figure displayed with the AC or DC before the value represents a nominal voltage with standard tolerances
included.
E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V)
48Vdc A figure with the unit (Vac) at the end is a momentary figure without any additional tolerances included.
may A key word indicating flexibility of choice with no implied preference.
shall A key word indicating a mandatory requirement.
should A key word indicating flexibility of choice with a strongly preferred implementation.
Jun 2020 / Rev. 1.0 DS-CD10.482-EN All values are typical figures specified at 48Vdc input voltage 48V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
DC/DC Converter 48V/48V, 5A, 240W
This device is designed for installation in an enclosure and is intended for commercial use, such as in industrial control, process control,
2. INSTALLATION INSTRUCTIONS
monitoring and measurement equipment or the like.
Do not use this device in equipment where malfunction may cause severe personal injury or threaten human life.
Risk of electrical shock, fire, personal injury or death.
- Turn power off before working on the device. Protect against inadvertent re-powering.
- Do not modify or repair the unit.
- Do not open the unit as high voltages may present inside.
- Use caution to prevent any foreign objects from entering the housing.
- Do not use in wet locations or in areas where moisture or condensation can be expected.
- Do not touch during power-on, and immediately after power-off. Hot surface may cause burns.
Obey the following installation requirements:
Install device in an enclosure providing protection against electrical, mechanical and fire hazards.
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the device. Other mounting
orientations require a reduction in output current.
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper cables that are designed for a
minimum operating temperature of 60°C for ambient temperatures up to +45°C, 75°C for ambient temperatures up to +60°C and 90°C
for ambient temperatures up to +70°C.
Ensure that all strands of a stranded wire enter the terminal connection. Unused screw terminals should be securely tightened.
The device is designed for pollution degree 2 areas in controlled environments. No condensation or frost is allowed.
The enclosure of the device provides a degree of protection of IP20. The enclosure does not provide protection against spilled liquids.
The input can be powered from batteries or similar DC sources. The voltage between the input terminals and ground must not exceed
60Vdc continuously.
The input must be powered from a PELV or SELV source or an "Isolated Secondary Circuit" in order to maintain a SELV or PELV output.
Check for correct input polarity. The device will not operate when the voltage is reversed.
A disconnecting means shall be provided for the input of the device.
The device is designed as “Class of Protection I” equipment according to IEC 61140. Do not use without a proper PE (Protective Earth)
connection.
The device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation
grid!
The device is designed for altitudes up to 5000m (16400ft). See additional requirements in the product datasheet for use above 2000m
(6560ft).
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and right side. Increase the 5mm to
15mm in case the adjacent device is a heat source. When the device is permanently loaded with less than 50%, the 5mm can be reduced
to zero.
The device is designed, tested and approved for branch circuits up to 50A without additional protection device. If an external fuse is
utilized, do not use circuit breakers smaller than 10A B- or C-Characteristic to avoid a nuisance tripping of the circuit breaker.
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the same as the ambient or surrounding
air temperature and is defined 2cm below the device.
The device is designed to operate in areas between 5% and 95% relative humidity.
Jun 2020 / Rev. 1.0 DS-CD10.482-EN All values are typical figures specified at 48Vdc input voltage 48V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
DC/DC Converter 48V/48V, 5A, 240W
The input can be powered from batteries or similar DC sources and must be a PELV or SELV source or an "Isolated Secondary Circuit" in
Allowed voltage between input and
earth/ground
Continuous operation, according to IEC 62477-1
Allowed input ripple voltage
In the frequency range from 47 to 500Hz, the momentary input
voltage must always be within the specified limits.
Steady-state value, see Fig. 3-1
Steady-state value, see Fig. 3-1
At 48Vdc input and 48V, 5A output load, see Fig. 3-3
At 36Vdc input and 48V, 5A output load, see Fig. 3-3
At 48V, 5A constant current load, 0mF load capacitance, see Fig.
3-2
At 48V, 5A constant current load, 5mF load capacitance, see Fig.
3-2
Installed inside the device, external capacitors on the input are
allowed without any limitations.
External input protection
See recommendations in chapter 2.
Fig. 3-1 Input voltage range
Fig. 3-2 Turn-on behavior, definitions
Turn-on
17.5Vdc
V
IN
P
OUT
Shut-down
32.4Vdc
15.5Vdc
18.0Vdc
Rated input range
35.0Vdc
Start-up
delay
Rise
Time
Overshoot
-5%
Output
Voltage
Input
Voltage
Fig. 3-3 Input current vs. output load
6A
1
2 3
4
0
2
4
6
8A
5
Output Current
Input: 48Vdc
Input Current, typ.
Input: 36Vdc
order to maintain a SELV or PELV output.
Check for correct input polarity. The device will not operate when the voltage is reversed.
Jun 2020 / Rev. 1.0 DS-CD10.482-EN All values are typical figures specified at 48Vdc input voltage 48V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
DC/DC Converter 48V/48V, 5A, 240W
Requirements for the Supplying Source
Fig. 3-4 External input filter requirements to avoid filter
instabilities
1 mOhm
10 mOhm
100 mOhm
1 Ohm
0.1mH 1mH 10mH
Inductance of the supplying network
Resistance of the
supplying network
(a) max.
(b) typ.
(a)
(b)
In certain circumstances, the input filter of the DC/DC converter can show a resonant effect which is caused by the supplying network.
Especially when additional external input filters are utilized, a superimposed AC voltage can be generated on the input terminals of the
DC/DC converter which might cause a malfunction of the unit. Therefore, additional input filters are not recommended. To avoid the
resonant effects, the minimal resistance of the supplying network which depends on the inductance of the input network, shall be
above the boundary curve in Fig. 3-4.
Jun 2020 / Rev. 1.0 DS-CD10.482-EN All values are typical figures specified at 48Vdc input voltage 48V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
DC/DC Converter 48V/48V, 5A, 240W
An active inrush limitation circuit (inrush limiting NTC resistor which is bypassed by a MOSFET) limits the input inrush current after turn-
Fig. 4-1 Typical input inrush current behavior at nominal load and
25°C ambient
Input Current
Input Voltage
Output Voltage
Ipk 7A
Input: 48Vdc
Output: 48V, 5A, constant current load
Ambient: 25°C
Input current 2A / DIV
Input voltage 10V / DIV
Output voltage 10V / DIV
Time basis: 100ms / DIV
on of the input voltage.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
After the DC/DC converter is turned on, the internal output current rises slowly to its nominal value. This method charges the output
capacitors (internal and external capacitors) slowly and avoids high input currents during turn-on. High input currents can produce a
high voltage drop on the input wiring (especially with long and thin cables) which reduces the terminal voltage on the DC/DC converter.
If the terminal voltage is below the shut-down voltage, the DC/DC converter will turn-off and will make a new start-up attempt. This
effect is avoided with the integrated soft-start function. Please note that this function increases the rise time of the output voltage by a
small amount.
Jun 2020 / Rev. 1.0 DS-CD10.482-EN All values are typical figures specified at 48Vdc input voltage 48V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
DC/DC Converter 48V/48V, 5A, 240W
The output provides a SELV/PELV rated voltage, which is galvanically isolated from the input voltage and is designed to supply any kind
This is the maximum output voltage which can occur
at the clockwise end position of the potentiometer due to
tolerances. It is not a guaranteed value which can be achieved.
±0.2%, at full load, cold unit
Between 36 and 60Vdc input voltage variation
Between 0 and 5A load variation, static value
Bandwidth 20Hz to 20MHz, 50Ohm
At 48V and an ambient temperature below +45°C
At 48V and +60° ambient temperature
At 48V and +70° ambient temperature
At 56V and an ambient temperature below +45°
At 56V and +60° ambient temperature
At 56V and +70° ambient temperature
Overload/ short-circuit current
RMS current, short circuit impedance <90mOhm
Included inside the power supply
The unit is resistant and does not show malfunctioning when a
load feeds back voltage to the power supply. It does not matter
whether the power supply is on or off. The absorbing energy can
be calculated according to the built-in large sized output
capacitor.
Fig. 6-1 Output voltage vs. output current at 48Vdc input
voltage, typ.
Fig. 6-2 Current limitation vs. input voltage, (46V
constant voltage load), typ.
Output Voltage
0
0 2 4
8
16
24
56V
32
40
48
8A31 5 6 7
Adjustment
Range
Output Current
5.0
6.0
7.0A
30 35 45 50 60Vdc
Input Voltage
Output Current
6.5
55
5.5
40
of loads, including unlimited capacitive and inductive loads.
The output is electronically protected against overload, no-load and short-circuits. In case of a protection event, audible noise may
occur.
The input voltage must also fulfill the SELV/PELV requirements.
Jun 2020 / Rev. 1.0 DS-CD10.482-EN All values are typical figures specified at 48Vdc input voltage 48V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
DC/DC Converter 48V/48V, 5A, 240W
The input side of the DC/DC converter is equipped with a bulk capacitor which keeps the output voltage alive for a certain period of time
At 48Vdc input voltage, 48V, 2.5A output, see Fig. 7-1
At 48Vdc input voltage, 48V, 2.5A output, see Fig. 7-1
At 48Vdc input voltage, 48V,.5A output, see Fig. 7-1
At 48Vdc input voltage, 48V, 5A output, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage
0
3
9
12
18ms
36 40 44 48 56Vdc
Input Voltage
Hold-up Time
52
(a)
(b)
(c)
(d)
6
15
(a) 48V, 2.5A, typ.
(b) 48V, 2.5A, min.
(c) 48V, 5A, typ.
(d) 48V, 5A, min.
Fig. 7-2 Shut-down test setup
Fig. 7-3 Shut-down behavior, definitions
Load
+
-
DC/DC
Converter
DC
Source
+
-
Input
Output
+
-
CD10
S1
-5%
Hold-up Time
Output
Voltage
Intput
Voltage
S1 opens
when the input voltage dips or is removed. The bulk capacitor can be discharged by loading the DC/DC converter on the output side or
through a load which is parallel to the input. There is no protection in the DC/DC converter which prevents current from flowing back to
the input terminals. If prevention is needed, an external diode should be used.
At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is also on during this time.
Jun 2020 / Rev. 1.0 DS-CD10.482-EN All values are typical figures specified at 48Vdc input voltage 48V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.