Pullin Evolution Solar PES190, PES300D, PES210D, PES190I, PES210I Installation And Servicing Instructions

...
1
1
UNVENTED MAINS PRESSURE SOLAR WATER HEATERS
100 TO 300 LITRE CAPACITY
DIRECT AND INDIRECT MODELS
INSTALLATION AND SERVICING INSTRUCTIONS
PACK CONTENTS
Factory fitted temperature/pressure relief valve l Cold water combination valve assembly l Expansion vessel
and mounting bracket l Tundish l Motorised valve (indirect models only) l Compression nuts and olives
Immersion heater spanner l Installation instructions
IMPORTANT: PLEASE READ ALL THESE INSTRUCTIONS BEFORE
COMMENCING INSTALLATION
PLEASE LEAVE THIS MANUAL WITH THE CUSTOMER FOR
FUTURE REFERENCE
NOTE: Prior to installation the unit should be stored in
an upright position in an area free from excessive damp or humidity.
INTRODUCTION
The Pullin Evolution Solar is a purpose designed unvented solar water heater. The unit has a stainless steel inner vessel, which ensures an excellent standard of corrosion resistance. The outer casing is a combination of resilient thermoplastic mouldings and corrosion proofed steel sheet. All products are insulated with CFC/HCFC free polyurethane foam to meet the latest European heat loss requirements (see Table 4).
The unit is supplied complete with all the necessary safety and control devices needed to allow connec­tion to the cold water mains. All these components are preset and not adjustable.
This appliance complies with the requirements of the CE marking directive and is Kiwa approved to show compliance with Building Regulations (Section G3).
The following instructions are offered as a guide to installation which must be carried out by a compe­tent plumbing and electrical installer in accordance with Building Regulation G3, The Building Standards (Scotland) Regulations 1990, or The Building Regula­tions (Northern Ireland).
2
Table 1: Unit weights
IMPORTANT NOTE:
THE PULLIN EVOLUTION SOLAR MUST BE INCOR­PORATED INTO A FULLY PUMPED SOLAR PRIMARY CIRCUIT. CONTROL OF THE SOLAR PRIMARY IS ACHIEVED BY THE USE OF EXTERNAL CONTROLS NOT SUPPLIED WITH THE UNIT. CONTROL MUST BE VIA A PURPOSE DESIGNED SOLAR HYDRAULIC STATION AND SOLAR DIFFERENTIAL TEMPERA­TURE CONTROLLER.
GENERAL REQUIREMENTS
SITING THE UNIT
The Pullin Evolution Solar must be installed vertically. Although location is not critical, the following points should be considered:
• The Pullin Evolution Solar should be sited to ensure minimum dead leg distances, particularly to the point of most frequent use.
• Avoid siting where extreme cold temperatures will be experienced. All exposed pipework should be insulated.
• The discharge pipework from the safety valves must have minimum fall of 1:200 from the unit and terminate in a safe and visible position.
• Access to associated controls and immersion heaters should be possible to allow for periodic servicing and maintenance.
• Ensure that the base chosen for the Pullin Evo­lution Solar is level and capable of permanently supporting the weight when full of water (see Table 1).
The Pullin Evolution Solar has an operating pressure of 3.5 bar that is controlled by the cold water combi­nation valve assembly. The cold water combination valve assembly can be connected to a maximum mains pressure of 16 bar. Wherever possible the mains supply pipe should be 22mm. We suggest the minimum supply requirements should be 1.5 bar pressure and 20 litres per minute flowrate. However, at these values outlet flow rates may be poor if several outlets are used simultaneously. The higher the available pressure and flow rate the better the system performance.
OUTLET/TERMINAL FITTINGS (TAPS, ETC.)
The Pullin Evolution Solar can be used with most types of terminal fittings. It is advantageous in many mixer showers to have balanced hot and cold water supplies. In these instances a balanced pressure cold water connection should be placed between the 2 pieces of the cold water combination valve assem­bly (see Fig. 1). Outlets situated higher than the Pullin Evolution Solar will give outlet pressures lower than that at the heater, a 10m height difference will
result in a 1 bar pressure reduction at the outlet.
LIMITATIONS
The Pullin Evolution Solar should not be used in association with any of the following:
• Solid fuel boilers or any other boiler in which the energy input is not under effective thermo­static control unless additional and appropriate safety measures are installed.
• Ascending spray type bidets or any other class 1 back syphonage risk requiring that a type A air gap be employed.
• Steam heating plants unless additional and ap­propriate safety devices are installed.
• Situations where maintenance is likely to be ne­glected or safety devices tampered with.
• Water supplies that have either inadequate pres­sure or where the supply may be intermittent.
• Situations where it is not possible to safely pipe away any discharge from the safety valves.
• In areas where the water consistently contains a high proportion of solids, e.g. suspended matter that could block the strainer, unless adequate fil­tration can be ensured.
OPERATIONAL SUMMARY
Maximum mains pressure 16 bar Operating pressure 3.5 bar Expansion vessel charge pressure 3.5 bar Expansion relief valve setting 6 bar T&P relief valve setting 90°C/10 bar Maximum primary circuit pressure (auxillary coil) (indirect only) 3 bar Maximum primary circuit pressure (solar coil) 6 bar Storage capacity See Table 1 Weight when full See Table 1
WATER SUPPLY
Bear in mind that the mains water supply to the prop­erty will be supplying both the hot and cold water re­quirements simultaneously. It is recommended that the maximum water demand is assessed and the water supply checked to ensure this demand can be satis­factorily met.
Note: A high mains water pressure will not always guarantee high flow rates.
Type
Model
reference
Nominal capacity
(litres)
Weight of
unit full
(kg)
DIRECT PES190D 190 235
PES210D 210 259 PES250D 250 302 PES300D 300 362
INDIRECT PES190I 190 240
PES210I 210 264 PES250I 250 308 PES300I 300 367
3
3
INSTALLATION – GENERAL (FIGS 3 & 5)
PIPE FITTINGS
All pipe fittings are made via 22mm compression fittings directly to the unit. The fittings are threaded 3/4”BSP male parallel should threaded pipe connec­tions be required.
COLD FEED
A 22mm cold water supply is recommended, how­ever if a 15mm (1/2”) supply exists which provides sufficient flow this may be used (although more flow noise may be experienced). A stopcock or servicing valve should be incorporated into the cold water supply to enable the Pullin Evolution Solar and its associated controls to be isolated and serviced.
COLD WATER COMBINATION VALVE ASSEMBLY (FIG 1)
The 2-piece cold water combination valve assembly can be located anywhere on the cold water mains supply prior to the expansion vessel (see Fig. 5) but the two pieces do not have to be installed together. The pressure reducing valve incorporates the pressure reducer & strainer and the expansion valve incorporates the expansion & check valves. Ensure that the valves are installed in the correct order and orientation. No other valves should be placed between the expansion valve and the Pullin Evolution Solar unit. A connection can be made between the expansion and pressure reducing valves to provide a balanced cold water connection. The expansion valve connection must not be used for any other purpose.
EXPANSION VESSEL
The expansion vessel accommodates expansion that results from heating the water inside the unit. The unit is pre-charged at 3.5 bar. The expansion vessel must be connected between the expansion valve (see Fig. 1) and the Pullin Evolution Solar (see Fig.
5). The location of the expansion vessel should allow access to recharge the pressure as and when necessary, this can be done using a normal car foot pump. It is recommended that the expansion vessel is adequately supported. An expansion vessel wall mounting bracket is supplied for this purpose.
NOTE: DO NOT USE THE POTABLE WATER EXPAN­SION VESSEL SUPPLIED WITH THE PULLIN EVOLUTION SOLAR FOR ANY OTHER PURPOSE. IT IS NOT SUITABLE FOR USE ON A SOLAR PRIMARY CIRCUIT.
SECONDARY CIRCULATION
If secondary circulation is required it is recommended that it be connected to the Pullin Evolution Solar as shown in Fig. 2. The secondary return pipe should be in 15mm pipe and incorporate a check valve to pre­vent backflow. A suitable WRAS approved bronze cir­culation pump will be required. On large systems, due to the increase in system water content, it may be necessary to fit an additional expansion vessel to the secondary circuit. This should be done if the capacity of the secondary circuit exceeds 10 litres. Pipe capacity (copper) 15mm o/d = 0.13 l/m (10 litres = 77m) 22mm o/d = 0.38 l/m (10 litres = 26m) 28mm o/d = 0.55 l/m (10 litres = 18m) Secondary circulation is NOT recommended for direct electric units being used on Off Peak electricity tariffs.
OUTLET
The hot water outlet is a 22mm compression fitting located at the top of the cylinder. Hot water distribu­tion pipework should be 22mm pipe with short runs of 15mm pipe to terminal fittings such as sinks and basins. Pipe sizes may vary due to system design.
DRAIN TAP
A suitable draining tap should be installed in the cold water supply to the Pullin Evolution Solar unit between the expansion valve (see Fig. 1) and the heater at as low a level as possible. It is recom­mended that the outlet point of the drain pipework be at least 1 metre below the level of the heater (this can be achieved by attaching a hose to the drain tap outlet spigot).
Fig. 1: Cold water combination valve assembly
Fig. 2: Secondary circulation connection
SECONDARY
CIRCULATION
PUMP
SECONDARY
RETURN
CHECK
VALV E
OUTLET
T&P RELIEF
VALV E
SECONDARY
RETURN
CONNECTION
INLET
OUTLET
EXPANSION
VALV E
OUTLET
PRESSURE REDUCING VALV E CARTRIDGE & STRAINER
DIRECTION OF FLOW
BALANCED COLD
WATER CONNECTION
(NOT SUPPLIED)
EXPANSION VALVE
PRESSURE REDUCING VALVE
CHECK
VALV E
4
Fig. 3: General Dimensions and features
190
9
1372 950 740 1019 1.1 110 115
190
9
1372 732 803 923 1019 1.1 110 0.61 11.9 20
210
9
1473 1000 759 1184 1.1 130 136
210
9
1473 892 808 1095 1184 1.1 130 0.68 15.2 20
250
9
1731 1072 773 1391 1.1 163 171
250
9
1731 1160 883 1258 1391 1.1 163 0. 79 15.2 23
300
9
2038 1409 870 1715 1.1 198 208
300
9
2038 1438 1023 1573 1715 1.1 198 0. 79 17.4 25
NOTES:
SOLAR SURFACE AREA (m²)
FE
NOMINAL
CAPACITY
(lit res)
TYPE DIMENSIONS (mm)
ABCD
2. Direct heating t imes as sume us e of lower element only and auxillary cy linder volume being heated
SURFACE AREA (m²)
RATING
(kW )
RECOVERY
(mins )
1. Recovery time based on heating 70% of auxillary volume through 45°C
AUXILLARY
VOLUME
(lit res)
AUXILLARY COIL HEATING
TIME DIRE CT
(mins )DIRECT INDIRE CT
370
433
D
C
B
A
29
412
E
F
SOLAR
PRIMARY
RETURN
SOLAR PRIMARY FLOW
AUX. BOILER RETURN
(INDIRECT ONLY)
AUX. BOILER RETURN
(INDIRECT ONLY)
AUX. BOILER FLOW
(INDIRECT ONLY)
T&P VALVE
SECONDARY RETURN
BOOST IMM. HTR. (DIRECT ONLY)
INLET AUX. CONTROL
HOUSING SOLAR CONTROL HOUSING
Ø550
20°
75°
90°
5
5
Worked example of discharge pipe sizing
The example below is for a G1/2 temperature relief valve with a discharge pipe (D2) having 4 No. elbows and length of 7m from the tundish to the point of discharge.
From Table 4: Maximum resistance allowed for a straight length of 22mm copper discharge pipe (D2) from a G1/2 temperature relief valve is 9.0m.
DISCHARGE PIPEWORK
It is a requirement of Building Regulation G3 that any discharge from an unvented system is conveyed to where it is visible, but will not cause danger to persons in or about the building. The tundish and discharge pipes should be fitted in accordance with the requirements and guidance notes of Building Regulation G3. The G3 Requirements and Guidance section 3.9 are reproduced in the following sections. Information Sheet No. 33 available from the British Board of Agrément gives further advice on discharge pipe installation. For discharge pipe arrangements not covered by G3 Guidance or BBA Info Sheet No.33 advice should be sought from your local Building Control Officer.
G3 REQUIREMENT
“...there shall be precautions...to ensure that the hot water discharged from safety devices is safely conveyed to where it is visible but will not cause danger to persons in or about the building.”
G3 GUIDANCE SECTION 3.9
The discharge pipe (D1) from the vessel up to and including the tundish is generally supplied by the manufacturer of the hot water storage system. Where otherwise, the installation should include the discharge pipe(s) (D1) from the safety device(s). In either case the tundish should be vertical, located in the same space as the unvented hot water storage system and be fitted as close as possible and within 500mm of the safety device e.g. the temperature relief valve. The discharge pipe (D2) from the tundish should terminate in a safe place where there is no risk to persons in the vicinity of the discharge, preferably be of metal and: a. be at least one pipe size larger than the nominal outlet size of the safety device unless its total equivalent hydraulic resistance exceeds that of a straight pipe 9m long i.e. discharge pipes between 9m and 18m equivalent resistance length should be at least two sizes larger than the nominal outlet size of the safety device, between 18 and 27m at least 3 sizes larger , and so on. Bends must be taken into account in calculating the flow resistance. Refer to Diagram 1, Table 1 and the worked example. An alternative approach for sizing dis­charge pipes would be to follow BS 6700:1987 Specification for design instal­lation, testing and maintenance of ser­vices supplying water for domestic use within buildings and their curtilages, Appendix E, section E2 and table 21. b. have a vertical section of pipe at least 300mm long, below the tundish before
any elbows or bends in the pipework. c. be installed with a continuous fall. d. have discharges visible at both the tundish and the final point of discharge but where this is not possible or is practi­cally difficult there should be clear visibility at one or other of these locations. Examples of acceptable discharge ar­rangements are:
i. ideally below a fixed grating and above the water seal in a trapped gully. ii. downward discharges at low level; i.e. up to 100mm above external surfaces such as car parks, hard standings, grassed areas etc. are acceptable pro­viding that where children may play or otherwise come into contact with dis­charges a wire cage or similar guard is positioned to prevent contact, whilst maintaining visibility. iii. discharges at high level; e.g. into a metal hopper and metal down pipe with the end of the discharge pipe clearly visible (tundish visible or not) or onto a roof capable of withstanding high tem­perature discharges of water and 3m from any plastics guttering system that would collect such discharges (tundish visible). iv. where a single pipe serves a number of discharges, such as in blocks of flats, the number served should be limited to not more than 6 systems so that any instalation discharging can be traced reasonably easily. The single common discharge pipe should be at least one pipe size larger than the largest indi­vidual discharge pipe (D2) to be con­nected. If unvented hot water storage systems are installed where discharges from safety devices may not be appar­ent i.e. in dwellings occupied by blind, infirm or disabled people, consideration should be given to the installation of an electronically operated device to warn when discharge takes place. Note: The discharge will consist of scalding water and steam. Asphalt, roof­ing felt and non-metallic rainwater goods may be damaged by such dis­charges.
6
Subtract the resistance for 4 No. 22mm elbows at
0.8m each = 3.2m
Therefore the permitted length equates to: 5.8m
5.8m is less than the actual length of 7m therefore calculate the next largest size.
Maximum resistance allowed for a straight length of 28mm pipe (D2) from a G1/2 temperature relief valves equates to 18m. Subtract the resistance of 4 No. 28mm elbows at
1.0m each = 4.0m Therefore the maximum permitted length equates to: 14m
As the actual length is 7m, a 28mm (D2) copper pipe will be satisfactory.
WARNINGS
• Under no circumstances should the factory fit­ted temperature/pressure relief valve be removed other than by a competent person. To do so will invalidate any guarantee or claim.
• The cold water combination valve assembly must be fitted to the mains water supply to the Pullin Evolution Solar unit.
• No control or safety valves should be tampered with.
• The discharge pipe should not be blocked or used for any other purpose.
• The tundish should not be located adjacent to any electrical components.
Valve outlet size
Min imum size of
discharge pipe
D1
Min imum size o f
discharge pipe
D2 from tundish
Ma ximum
resistance
allowed, expressed
as a length of
straight pipe (i.e.
no elbows or
bends)
Resistance
created by each
elbow or bend
G1/2 15mm
22mm 28mm 35mm
up to 9m up to 18m up to 27m
0.8m
1.0m
1.4m
G3/4 22mm
28mm 35mm 42mm
up to 9m up to 18m up to 27m
1.0m
1.4m
1.7m
G1 28mm
35mm 42mm 54mm
up to 9m up to 18m up to 27m
1.4m
1.7m
2.3m
Table 2: Sizing of copper discharge pipe (D2) for common temperature relief valve outlet sizes
Fixed grating
Discharge below fixed grating (Building Regulation G3 section 3.9d gives alternative points of discharge)
Trapped gully
Discharge pipe (D2) from tundish, with continuous fall. See Building Regulation G3 section 3.9d i-iv, Table 4 and worked example
300mm minimum
500mm maximum
Metal discharge pipe (D1) from Temperature relief valve to tundish
Tundish
Safety device (e.g. Temperature relief valve)
Fig.4: Typical discharge pipe arrangement (extract from Building Regulation G3 Guidance section)
Loading...
+ 14 hidden pages