Intelligent Power Control™ IPC34XX-NET Series
Enclosure Power Distribution Units (ePDU™)
IPC3401-NET Rear
Front
IPC3402-NET Rear
IPC3402-2756 Rear
• Remote access via WAN/LAN, TCP/IP, Modem, or Direct RS-232:
Prevent costly site visits with remote-reboot and power management.
• Sequence power up and down with Pulizzi’s®patented Multiple Time DelayTMcircuitry:
Prevent inrush current problems such as system lock-ups and automatically control the order in which equipment within your network powers up or down.
• Strap up to 10 IPC34XX systems together for control of 80 outlets:
Use one IPC34XX-NET unit as the main system and strap (nine) less expensive IPC34XX (non-NET) units together to save money and increase overall control of your network equipment.
Ethernet Strapping Switch
• 100-240VAC / 15A or 20A input (IPC3401 or IPC3401-NET):
One unit to purchase, stock and utilize worldwide.
• Remote access disable and Local on/off control:
When you need to work locally with the IPC34XX systems, the push of a button will prevent anyone from coming in remotely and the individual outlet on/off switches are also located on the front panel.
• Cross platform compatible with Telnet and Browser Control:
You can easily access and control the IPC34XX with either PC, Mac, Linux or Unix platforms running Telnet or via your web browser.
RS485 Strapping Connectors RS232 Serial (DB9 Connector)
Network
www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999
© 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.
Equipment
Equipment
Rear
Modem
Modem
Up To 10 IPC
Units Can Be Stacked
Together
2
CHASSIS
• 19” x 1.72” (1U) x 9.5”
• Weight approximately 12 lbs.
• Weight approximately 15 lbs.
& IPC2930)
(IPC3401 & 02) (IPC3402-2756
• Detachable mounting brackets allow for several mounting options
NEMA or IEC 320 OUTLETS
• IPC3401 has 8 IEC 60320 Type C13 – Rated by UL/CSA 125V~/15A – Rated by UL/CSA/VDE 250V~/10A
• IPC3402 has 8 NEMA 5-15R
• IPC3402-A2 has 8 NEMA 5-20R
• IPC3402-2756 has 4 NEMA 5-20R and 4 NEMA 5-15R
• IPC3402-2930 has 8 NEMA 5-15R
(11) INDICATOR LIGHTS
• Main power to system-CB “on”
• Individual power “on” to outlets 1-8
• Data acquisition and remote disable
REMOTE or LOCAL CONTROL
• Serial RS232 port (DB9 Male) for direct computer or modem connection
• RS485 input/output for strapping up to 10 systems together over CAT.5 cable
• Local: one on/off switch for each outlet
• -NET SYSTEMS ONLY: RJ45 for network connections (Ethernet)
REMOTE DISABLE
• With the push of a button, disable remote access to the IPC when needed
POWER SUPPLY
• The IPC3401 series features a full range power supply for operation at 100-240VAC input/output
BAUD RATE
• Default: 9600 baud
EMI/RFI FILTERING
• Common Mode - Line to Ground
• Differential Mode - Line to Line
• Filtered inlet isolates noise before entering the system
• IPC3402-2756 and IPC3402-2930 do not have filtering
SPIKE/SURGE SUPPRESSION (TVSS)
• Line to Line
• Multi-stage, both MOVs and SAPs
BRANCH CIRCUIT PROTECTION
• UL498 Listed Main Disconnect Breaker and guard, with a long time delay curve provides manual on/off switching and trips in an overload condition
POWER INPUT
• IEC 60320 Type C20 EMI/RFI Filtered Inlet
• Mating power cables must be ordered separately
• IPC3402-2756: attached 10’ cable and NEMA L5-30P
OUTLET STATUS
• Query the IPC for Outlet and Watch Dog status, i.e. outlets are “on” or “off”
STRAPPING
• Strapping allows up to 10 IPCs (80 outlets) to be controlled at one address
• Units are connected together via the RS485 “IN” and “OUT” connectors
UNIT NAME / PASSWORD
• The IPC comes with a default name @@@@, which can be changed to any four alphanumeric characters
• Optional 3 character password
MULTIPLE TIME DELAYTM(MTDTM)
• Sequence power up and power down to outlets with a one second time delay (factory set)
• User Programmable: – Set power “on” sequence to any
combination of outlets
– Set the MTD
TM
timing from 1 second
to 999 seconds, i.e. 009 = 9 seconds
AUTO-EVENT COMMAND RESPONSE
• The IPC will automatically update the status of outlets (“on” or “off”) via serial or telnet
SOFTWARE CONTROLS
• Multi-platform compatible
• Control via Terminal Emulation Software
• Web interface for browser control
COMMANDS AVAILABLE
• All outlets on/off
• Specific outlets on/off
• Set up and Sequence on/off all outlets
• Create password and unit address
• Outlet naming (8 characters)
• Set up, enable or disable Watchdog
Display outlet and Watchdog Timer status
• Automatically receive update outlet status whenever there’s a change
• Auto-reboot outlet 1 with a five second delay on restart
SPECIFICATIONS: IPC3401 IPC3401-NET IPC3402 IPC3402-NET IPC3402-A2 IPC3402-A2-NET IPC3402-2756 IPC3402-2930
Approvals UL/cUL, CE, GS, FCC UL/cUL, FCC UL/cUL, FCC UL/cUL, FCC UL/cUL, FCC UL/cUL UL/cUL
Voltage (50/60Hz) 100-240V~ 100-240V~ 120V~ 120V~ 120V~ 120V~ 120V~ 120V~
Current Input 20A @ 120V~
16A @ 240V~
Current Output
16A 16A 16A 16A 16A 16A 24A 24A
Full Load VA 1920VA @ 120V~
3840VA @ 240V~
Outlets (IEC or NEMA) Type C13 Type C13
20A @ 120V~ 16A @ 240V~
1920VA @ 120V~ 3840VA @ 240V~
20A 20A 20A 20A
30A 30A
1920VA 1920VA 1920VA 1920VA 2880VA 2880VA
5-15R 5-15R 5-20R 5-20R (4) 5-20R, (4) 5-15R (8) 5-15R
Circuit Breaker 20/20A 20/20A 20A 20A 20A 20A 20/10A 20/10A
EMI/RFI Filter 20A 20A 20A 20A 20A 20A
N/A N/A
Surge Suppression 270V 270V 270V 270V 270V 270V 270V 270V
Power Input Type C20 Inlet Type C20 Inlet Type C20 Inlet Type C20 Inlet Type C20 Inlet Type C20 Inlet
L5-30P L5-30P
Power Cord Power cables must be ordered separately. 10/3AWG 10’ 10/3AWG 10’
Ethernet Control
NO YES NO YES NO YES YES YES
Serial Control (RS232) YES YES YES YES YES YES YES YES
www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999
© 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.
3
TVSS (Transient Voltage Surge Suppression)
MOV SPECIFICATIONS
Continuous AC Voltage 150VAC 270VAC 320VAC
Continuous DC Voltage 200VDC
Max. DC Leakage 200µA 200µA 200µA
Low Varistor Voltage Limit 212VDC
High Varistor Voltage Limit 243VDC
Nominal Varistor Voltage 236VDC 424VDC
Current For Varistor Voltage
Max. Clamp Voltage 8x20µs
Max. Clamp Voltage Test Current
Peak Current Rating (1 Pulse) 12000A
Peak Current Rating (2 Pulse)
Energy Rating (10x1000µs)
Energy Rating (8x20µs)
Capacitance 1700pF 970pF 820pF
Impulse Response Time
1mA 1mA 1mA
360V 680V 810V
100A 100A 100A
9000A 6500A 6500A
170J 325J 385J
170J 325J 385J
50ns 50ns 50ns
360VDC 420VDC
389VDC 462VDC
453VDC 540VDC
503VDC
10000A 10000A
EMI/RFI FILTERING COMMON MODE INSERTION LOSS
Mhz. .01 1 10 20 50 100
dB. 8 2940506840
DIFFERENTIAL INSERTION LOSS
Mhz. .01 1 10 20 50 100
dB. 8 2345583228
Environmental
Operating Temperature is 0 to 50 C Storage Temperature is -40 to 70 C Altitude Maximum 10,000 ft. Relative Humidity is 95% Max Non-Condensing
www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999
© 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.
4
Accessories
Optional Cable Restraint and Management
KIT-CABLRES-01
• Prevent downtime and accidental disconnection
• Secure cables/plugs to Power Distribution Unit
• Cable ties provide highest level of retention
Adjustable Mounting Options
TRANSVERSE MOUNTING
010-9334: C19 to NEMA 5-15P 125V, 15A Straight Blade 8 foot, 14AWG/3wire
Mounting Brackets
Are Detachable With
Several Mounting
Options Shown
Rear Flush
Front Flush
Front Recessed
Rack Mounting Hole Specification Table
19.00 Y
Z
HOLE SPECIFICATION TABLE
AYZ
1.75 .25 1.25
010-9335:
Center Mount
Optional
Zero-U
Bracket
(001-1928-1)
A
C19 to NEMA 5-20P 125V, 20A Straight Blade 8 foot, 12AWG/3wire
010-9339: C19 to NEMA L5-20P 125V, 20A Twist-Lock 8 foot, 12AWG/3wire
010-9341: C19 to NEMA L6-20P 250V, 20A Twist-Lock 8 foot, 12AWG/3wire
010-9343: CEE7-7 to C19 250V, 16A EUROPE (Schuko)
2.5M, 1.5mm/3wire Harmonized
010-0025: 8 foot C13 to C14 Harmonized, 1mm/3wire 100-240V rated
5
www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999
© 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.
Drawings are
not shown to scale
Dimensions
are in inches
IPC3401
www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999
© 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.
IPC3402
6
Loading...