Caution. Consult this manual in all cases where
this symbol is used.
Caution. Risk of electric shock
Alternating current
Alternating current (a.c.) or direct current (d.c.)
Double or Reinforced insulation
Functional earth terminal not relied on for safety
WARNING: Death, serious injury, or fire hazard could result from improper connection or
operation of this instrument. Carefully read and understand manual before connecting this
instrument.
AVERTISSEMENT: Si l'instrument est mal connecté, la mort, des blessures graves, ou un
danger d'incendie peuvent s'en suivre. Lisez attentivement le manuel avant de connecter
l'instrument.
WARNUNG: Der falsche Anschluß dieses Gerätes kann Tod, schwere Verletzungen oder
Feuer verursachen. Bevor Sie dieses Instrument anschließen, müssen Sie die Anleitung lesen und
verstanden haben.
ADVERTENCIA: Una conexión incorrecta de este instrumento puede producir la muerte,
lesiones graves y riesgo de incendio. Lea y entienda el manual antes de conectar.
If this equipment is used in a manner not specified by the manufacturer, the protection provided
by the equipment may be impaired. Installation, service, and maintenance of your PQube must
only be done by an expert for electrical installations.
Standards Laboratory. “PQube” is a registered trademark of Power Standards Lab. “Windows”
“Excel”, and “PowerPoint” are registered trademarks of Microsoft Corporation.
The information contained in this document is subject to change without notice.
PSL MAKES NO WARRANTY OF ANY KIND WITH REGARD TO THIS MATERIAL, INCLUDING, BUT NOT
LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
USE.
PSL shall not be liable for errors contained herein or for incidental or consequential damages in
connection with the furnishing, performance, or use of this material. If you do not accept this
limitation on liability, please return the product to PSL prior to use.
Produced in the United States of America.
First Release: July 2012
Page 2 of 113
PQube User Manual 2.1
Table of Contents
Table of Contents 3
Introduction 6
What Can Your PQube Do? .......................................................................................................... 6
How Is Your PQube Different? ..................................................................................................................................... 7
Measure Current, Power, and Energy ......................................................................................................................... 9
Remote Communication .............................................................................................................................................. 9
XCT5 and ETH1 combined into 1 module .................................................................................................................... 9
Power your PQube from 100~240Vac ....................................................................................................................... 10
Measure Temperature and Humidity ........................................................................................................................ 10
DC Monitoring ............................................................................................................................................................ 10
General Installation ................................................................................................................... 13
Mount your PQube securely ...................................................................................................................................... 13
PQube instrument power .......................................................................................................................................... 14
Connecting the wires ................................................................................................................................................. 14
Using your PQube with external Potential Transformers ......................................................................................... 16
Include overcurrent protection and a disconnecting device .................................................................................... 17
Protect the operator from the hazardous terminals ................................................................................................ 17
Protect antenna terminals from lightning ................................................................................................................. 18
Installing Your ETH1 Ethernet Module ...................................................................................................................... 18
Installing Your PS1 or PS2 Power Supply Module ..................................................................................................... 19
Installing Current Modules ........................................................................................................................................ 19
Overview of connections and controls ...................................................................................................................... 27
Disconnect mains prior to servicing ........................................................................................................................... 27
Page 3 of 113
PQube User Manual 2.1
Calibration Information for Your PQube .................................................................................... 27
Setting up your PQube 28
Setting the Date and Time ......................................................................................................................................... 28
Setting Your Languages .............................................................................................................................................. 28
Check your Power Configuration ............................................................................................................................... 28
Setting Your Potential Transformer Ratio ................................................................................................................. 28
Potential Transformers with Calibrated Ratios ......................................................................................................... 29
Setting up Your Optional Current Module ................................................................................. 30
Setting Current Transformer Ratio ............................................................................................................................ 30
Inverting Current Channels ........................................................................................................................................ 30
Calculating Current With a Missing CT ...................................................................................................................... 30
Fix installation errors, simply and easily .................................................................................... 31
Setting Relays for Triggering on Events ...................................................................................... 31
Setting up Your Optional ETH1 Ethernet Module ...................................................................... 32
Web Server Setup ...................................................................................................................................................... 35
DC Monitoring ........................................................................................................................... 38
Individual Ratios for each Analog channel ................................................................................................................ 38
DC Power and Energy ................................................................................................................................................. 38
Swap AN1 and AN2 in software................................................................................................................................. 38
Customize your Analog channels ............................................................................................................................... 38
User Guide 39
Using Your PQube ...................................................................................................................... 39
Your PQube’s Display and User Interface .................................................................................................................. 39
Inserting and Removing Your SD Card ....................................................................................... 44
What Channels Does My PQube Measure? ............................................................................... 44
Standard PQube Channels ......................................................................................................................................... 44
Additional Channels Available With Optional Current Module ............................................................................... 48
Temperature and Humidity ....................................................................................................................................... 49
Manually Trigger Snapshots or Daily Trends ............................................................................................................. 61
User Counter .............................................................................................................................................................. 61
Getting Data Into and Out of Your PQube ................................................................................. 62
Upgrading Your PQube’s Firmware ........................................................................................................................... 65
Turning Off Your PQube ............................................................................................................................................. 65
Replacing your PQube’s battery ................................................................................................................................ 65
A brief introduction to Modbus ................................................................................................................................. 71
Setting up your Trends and Statistics ...................................................................................................................... 101
Appendix 3 – Ride-Through Curves 105
STANDARD ............................................................................................................................................................... 105
Samsung Power Vaccine .......................................................................................................................................... 106
Your PQube® is an instrument for monitoring electric power systems.
It is convenient to think of it as a combination of a power disturbance monitor, a power meter, a
power recorder, and a digital camera – it combines the best features of all four.
Your PQube records disturbances on the mains circuit: sags/dips, swells, interruptions, frequency
variations, and disturbances on two analog input channels. It also records impulses, waveform
snapshots, unbalance, flicker, and THD, and trend data (strip charts and cumulative statistics).
When equipped with an optional current sensing module,
your PQube also records current waveforms, RMS amps,
power and carbon. It measures watts, watt-hours, VAR’s,
power factor, and other power-related parameters.
You don’t need any software from PSL to use
your PQube. It records all data on a SD
memory card, which can be read by any
computer. No special software is required –
just open the GIF picture files with standard image programs, or even Microsoft
Word® and Microsoft PowerPoint®, or open the CSV files with any spreadsheet
program such as Microsoft Excel® (or OpenOffice.org Calc if you prefer something
free). Configure your PQube with our free PQube Configurator program, or by
editing a text file on the SD card.
It can monitor single-phase or three-phase circuits, at up to 690 VAC phase-to-phase (400 VAC
phase-to-earth), at 50 Hz, 60 Hz, and 400 Hz.
It includes channels for measuring auxiliary voltages – typically 24V AC or 48V DC.
It also has a general-purpose digital input, which you can control with switch contacts or a logic
signal, and a relay contact output, which opens for at least 3 seconds whenever your PQube
detects an event.
It can be directly powered from 24V AC or 24~48V DC, or it can be equipped with an optional PS1
power supply that operates from 100V ~ 240V, 50/60 Hz.
Your PQube also measures and triggers on temperature and humidity at up to two locations, using
optional TH1 temperature-humidity probes.
When equipped with an optional ETH1 Ethernet module, your PQube can automatically send you
e-mails whenever it detects an event. You can send your PQube a new setup file, or even update its
firmware via e-mail. The Ethernet module also includes a web server, an FTP server, and MODBUS
over TCP, giving you even more ways to communicate with your PQube.
Page 6 of 113
PQube User Manual 2.1
How Is Your PQube Different?
There are many power quality meters, energy meters, and energy recorders available. What
makes the PQube stand out from other products?
No software. No rental fees. Open data. -- You don’t need any software from PSL to use
the PQube. Do you have a web browser? A text editor? A spreadsheet program like
Microsoft Excel®? That’s all you need! All the data that the PQube records are in open
formats that are easy to understand. You don’t have to buy or lease software from Power
Standards Lab, you don’t have to pay us to see your data, and the files are easy to pass on
to third parties.
Friendly data. – When you look at information about your electric power, you don’t want
to spend a lot of time learning to use software to get the view that you want. You simply
want your data organized and presented to your in a format you can understand. Your
PQube presents power quality events, trends, and statistics in formats you can easily use
and lays the data out in a way that’s understandable. Your PQube knows what’s
important.
Free firmware updates – From time to time, we offer firmware updates to add new
features to your PQube. Other instrument manufacturers charge for firmware updates, we
don’t.
Works out of the box, or configure everything to work for you – With our patent-pending
auto configuration, you can connect your PQube to the power that you want to measure
and the PQube will immediately start recording data. If you don’t like the default settings
you can change almost any setting in the PQube Configurator program, or by editing a text
file on the SD card.
Works with or without a network – Do you have an Ethernet network? Use an optional
ETH1 module and get emails when an event occurs, browse the recorded events and
trends with your web browser, or integrate it into your Modbus system. Don’t have a
network? No problem, just walk up to the PQube and take the SD card. You can look at all
the files on any computer (you don’t need software). You don’t need a sophisticated
centralized data collection system to get started. Just connect a PQube and start getting
data right away.
Store years of data on standard SD cards. – Your PQube comes with a 4GB SD card which
will store about 2 years’ worth of data.
Small size – The PQube is tiny (a little bit bigger than your fist), and that makes it easier to
integrate into your product.
Low cost – At Power Standards Lab, we’re experts at building power sensor electronics.
We know how to do it right, and we know how to do it inexpensively. The PQube costs far
less than comparable instruments.
It’s everything you need. – Power quality data: dips, swells, frequency variation, and high-
frequency impulses. Energy data: kWh, kVAh, and carbon. Trend data: daily, weekly, and
monthly strip charts, cumulative probability and load duration. Why buy multiple meters
when the PQube can do it all?
Page 7 of 113
PQube User Manual 2.1
1
Applications
Your PQube is ideal for reducing your service costs on sensitive equipment, such as semiconductor
manufacturing equipment and sophisticated medical scanners. By detecting and recording power
disturbances, you can easily and quickly separate intermittent power problems from other
intermittent problems: software bugs, user errors, supply stock problems, etc.
And your PQube is an excellent choice for monitoring the power that feeds industrial controls, such
as automated machinery, robotics, and elevator/lift controls.
You can use your PQube in dozens of other applications: monitoring the power quality at key
accounts, doing national surveys of power quality, safely recording power data for research
projects, understanding why your wind turbine drops off line unexpectedly, and many other
purposes.
Choosing Modules
Your PQube records events, trends, and statistics by monitoring your AC mains voltages. It also
measures two analog input channels for additional signals (for example, the output of a power
supply), a digital input channel, an output relay, and a full color display. Your PQube records all
information to a standard SD memory card.
IMPORTANT: Installation, service, and maintenance of your PQube must only be done by an
expert for electrical installations.1
Page 8 of 113
PQube User Manual 2.1
Your PQube clicks together with several optional modules to provide extra features. To choose
modules for your application, you’ll need to answer four simple questions:
Are you interested in measuring current, power, or energy?
Do you want to power your PQube from 100~240Vac (50/60Hz)?
Are you interested in any of the following: email, a web server, an FTP server, or Modbus
over TCP?
Do you want to record the temperature and humidity in addition to everything about the
electric power?
Measure Current, Power, and Energy
Are you interested in measuring current, power, or energy? If so, you’ll need a PQube current
module. There are three versions; please pick the one that is best for you.
XCT4 – External CTs with current secondary outputs
If you already have CTs (Current Transformers) with current outputs, you
can use an XCT4. This module accepts 1-Amp or 5-Amp CT secondaries.
For more information, see the XCT4 Current Module section (page 19).
XCT5 - External CTs with voltage secondary outputs
If you already have CTs with voltage output, or you purchase them from
Power Standards Lab, you can use an XCT5. This module accepts 0.333 Volt,
1 Volt, 5 Volt, or 10 Volt secondaries. This module comes with five current
channels, allowing you to measure all three phase currents, neutral current,
and earth current simultaneously!
CT4 – Current Sensing Module
If you don’t want to use CTs, the CT4 current module might be right for
you. This module comes in 20Amp and 100Amp versions and has the
CTs built in already. Just pass the conductors through. For more
information, see the CT4 Current Module section (page 20).
Remote Communication
ETH1
Are you interested in any of the following: email, a web server, an FTP
server, or Modbus over TCP? If you need any of these features, you
need an ETH1 Ethernet module. For more information, see the ETH1
section (page 62).
XCT5 and ETH1 combined into 1 module
CTE1
Are you interested in having network capability and measuring current,
but don’t have the space for both an ETH1 module and XCT5 module? Use
a CTE1 module to take advantage of the ETH1 and XCT5 functionality in a
single compact module.
Page 9 of 113
PQube User Manual 2.1
Power your PQube from 100~240Vac
PS1
Do you want to power your PQube from 100~240Vac (50/60Hz)? If you have
24~48Vdc or 24Vac, you can use your PQube’s internal power supply (just
connect to the power supply screw terminals). If you want to use
100~240Vac, you’ll need an optional PS1 Power supply module.
PS2
In addition to powering your PQube from 100 ~ 240VAC (50/60Hz), you can
power external accessories with the PS2’s 24VDC output.
Measure Temperature and Humidity
TH1
Do you want to record the temperature and humidity in addition to
everything about the electric power? You can use up to two TH1
Temperature/Humidity sensors. Measure the local environment or
connect a second sensor with an extension cable and measure the
temperature and humidity at two locations simultaneously. Just plug
them into your PQube and it will start recording data immediately.
DC Monitoring
ATT1
Interested in High Voltage DC Monitoring? Use an ATT1 module. It is
available with a full scale of 600VDC and 1200VDC, and can measure up to
1000VDC and 2000VDC, respectively. Measure 1 differential voltage, or 2
voltages relative to earth.
ATT2
Do you want to monitor both DC voltage and DC current? Use an ATT2
module, it is available with a full scale of 600VDC and can measure up to
1000VDC. The ATT2 module accepts a DC current sensor that is powered by
±15VDC, and has a ±5V nominal output.
Page 10 of 113
PQube User Manual 2.1
Snap your PQube (and any plug-in modules) on to your DIN rail.
Don’t have an ETH1, XCT4 or CT4 plug-in module? Go to step 3.
a) ETH1 module? Connect your Ethernet cable.
b) XCT current interface module? Connect your current transformer to the screw terminals of your
XCT module.
c) CT4 current sense module? Pass your current carrying conductors through the CT openings.
(a) (b) (c)
Connect Earth and Mains wires to your PQube.
Quickstart
Installation
Page 11 of 113
PQube User Manual 2.1
Connect 24VAC or 24-48VDC POWER to your PQube,
or plug in a PS1 or PS2 Power Supply module and connect 100~240VAC to it.
or
Use the joystick and pushbutton to change settings ….
… and check that your PQube has correctly determined your mains voltage
Page 12 of 113
PQube User Manual 2.1
Your PQube is recording power quality events on its SD card. If you have an XCT or a CT4, your PQube
is also measuring energy.
Edit your Setup.ini file on your SD card to set location, thresholds, transformer ratios, email access,
and other settings. See Appendix 2.
General Installation
Mount your PQube securely
Your PQube, and its optional modules, are designed to be mounted on an industry-standard 35mm
DIN rail as rack- or panel-mounted equipment.
The optional PS1 Power Supply module connects to the right side of your PQube. The optional
ETH1 Ethernet module and current sensing modules connect to the left side of your PQube.
Connect them to your PQube in any order that is convenient. Do not connect multiple current
sensing modules. Only connect one current sensing module, either a CT4 or XCT4.
In the United States and Canada, the equipment installation shall meet ANSI/NFPA 70, NEC, with
CSA C22.1, CEC, Part I or with both as appropriate. In other countries, follow all local installation
requirements and regulations.
Your PQube’s “enclosure”, as defined in UL/IEC 61010-1, is provided by the installation, and must
be evaluated in the end product.
Page 13 of 113
PQube User Manual 2.1
2
IMPORTANT: Your PQube must be installed only by an expert for electrical installations2. The
instrument power screw terminals must be connected to no more than 24Vac +/- 20%, or
24Vdc~48Vdc +/- 20%, supplied by a certified isolating power supply.
PQube instrument power
Your PQube can take its operating power from three different sources: its Power screw terminals
[23][31], its internal Lithium Polymer rechargeable battery, or an optional PS1 Power Supply
module.
Power screw terminals
Your PQube’s Power screw terminals [23][31] accept 24VAC nominal, or 24Vdc~48Vdc nominal.
They are most commonly connected to 24Vdc, 24VAC, or -48Vdc.
Polarity does not matter. Also, your PQube provides a minimum of 150V of transformer-based
isolation between these terminals and all other terminals, eliminating any problems with ground
loops.
Internal Li-Polymer battery
Your PQube’s internal Li-Polymer battery is automatically charged from all the other power
sources. An application-specific chip manages the charging process, paying attention to voltage,
current, and temperature. The battery itself is equipped with an internal high-temperature shutdown circuit.
The battery operating capability depends on the options installed in your PQube, and on the
ambient temperature. In typical tests, the battery can operate your PQube for about one hour.
However, you can choose the operating duration by writing a value in your Setup.ini file. The value
can be set from 1 to 9 minutes (the default is 3 minutes). This guarantees that there will be enough
charge in the battery to record several successive power interruptions.
As the battery ages, its capacity will decline. For maximum performance, it may be necessary to
replace the battery in 5 years. Some normal swelling of the battery may result from high
temperature operation, but this does not interfere with battery performance.
Connecting the wires
Observe the wire size specifications and limitations. All conductors must be stranded copper. All
conductors and insulation systems and crimped devices must be appropriate for the application.
PSL recommends crimped ferrules on stranded wire, or crimped snap-on forked lugs. Tighten the
screw terminals to 0,8 newton-meters (7 inch-pounds) of torque. Observe all voltage ratings and
limits.
Page 14 of 113
PQube User Manual 2.1
For mains connections and current connections, PSL recommends snap-on forked terminals, such as 3M Scotchlok® P/N MU186FL or MU14-6FL, or Panduit P10-6lF. For other connections, PSL recommends wire ferrules for stranded wire, such as Panduit
F77 series, for example Panduit F77-6-M.
Figure 1: Your PQube meets all IEC requirements for highfrequency emissions and susceptibility, both conducted and
radiated. For further protection, you can use clamp-on
ferrites on signal cables to minimize radio-frequency
emissions. For example, these are Panasonic
KRCBC160928B and KRCBC130714B.
Figure 2: To minimize emissions with the optional PS1
Power Supply module, optionally use a shielded power
conductor.
Connection
Minimum wire size
Maximum wire size
Limitations and remarks
Comply with all local safety and installation
requirements and regulations.
PQube terminals
L1, L2, L3, N
[9] [11] [13] [15]
20AWG (0,52 mm2)
14 AWG (2.1mm2)
Min 600V UL-recognized insulation system required.
These terminals require less than 0,01 amps.
Connection to N (15) is optional. For single phase
monitoring, connect either L1-N or L1-L2 as
appropriate for the mains configuration.
PQube Earth terminal
[32]
Wire size used for
L1,L2,L3,N terminals
14 AWG (2.1mm2)
Connect this terminal to a suitable earth connection.
For proper PQube operation, you must connect this
terminal to earth. It is used as a measurement
reference, and as a reference for your PQube’s low
voltage circuits.
Optional
PQube RLY4 terminals
[25] [26]
20AWG (0,52 mm2)
14 AWG (2.1mm2)
Min 600V UL-recognized insulation system required.
Wire size must be adequate for relay contact load.
These terminals are rated at 30 VAC max, 60 Vdc
max, 2 amps max.
All other PQube
terminals
20AWG (0,52 mm2)
14 AWG (2.1mm2)
Min 600V UL-recognized insulation system required.
Optional PS1
terminals
20AWG (0,52 mm2)
14 AWG (2.1mm2)
Min 600V UL-recognized insulation system required.
Shielded cable recommended for minimizing
emissions.
Optional XCT4
terminals
20AWG (0,52 mm2)
14 AWG (2.1mm2)
Ring lugs or snap-on forked terminals are
recommended for CT connections. Self-retaining
screws in terminals may make ring lugs challenging to
install. Wire size must be adequate for 1-amp or 5amp currents. Min 600V UL-recognized insulation
system required
Optional CT4 passthrough inputs
20AWG (0,52 mm2)
Limited by physical
dimension of passthrough locations:
8.5 mm (0.34”) dia.
Min 600V UL-recognized insulation system required.
Insulated wire is required!
Conductor characteristics
Page 15 of 113
PQube User Manual 2.1
Connection
Maximum voltage
with respect to Earth
Maximum current
Limitations and remarks
PQube terminals
L1, L2, L3, N
[9] [11] [13] [15]
400 Vrms, CAT III
up to 300Vrms, CAT
IV
Corresponds to 690 Vrms phase-to-phase on centeredneutral mains systems.
Corresponds to 480Vrms phase-to-phase on centeredneutral mains systems.
All voltage channels must be covered after installation.
PQube Earth terminal
[32]
N/A
Optional PQube RLY4
terminals [25] [26]
30 Vrms or 60 Vdc
All other PQube
terminals
30 Vrms or 60 Vdc
Optional PS1 terminals
240 Vrms, CAT III
AC voltage input terminal must be covered after
installation.
Optional XCT4 terminals
400 Vrms, CAT III
1 amp for XCT4-1A
5 amps for XCT4-5A
Usually connected to external current transformer
secondaries, which provide insulation from mains.
Corresponds to 690 Vrms phase-to-phase on centered
neutral mains systems.
up to 300Vrms, CAT
IV
Usually connected to external current transformer
secondaries, which provide insulation from mains.
Corresponds to 480Vrms phase-to-phase on centered
neutral mains systems.
Optional CT4 passthrough inputs
Insulated wire is
required!
400 Vrms, CAT III
20 amps for CT4-20
50 amps for CT4-50
Corresponds to 480Vrms phase-to-phase on centered
neutral mains systems.
up to 300Vrms, CAT
IV
Corresponds to 690 Vrms phase-to-phase on centered
neutral mains systems.
Maximum voltages
Using your PQube with external Potential Transformers
Note: “CAT III” means Measurement Category III as defined in UL / IEC 61010-1: “Measurement category III is for
measurements performed in the building installation…. Examples are measurements on distribution boards, circuit-breakers,
wiring, including cables, bus-bars, junction boxes, switches, socket-outlets in the fixed installation, and equipment for industrial
use…”
“CAT IV” means Measurement Category IV as defined in UL / IEC 61010-1: “measurements performed at the source of the lowvoltage installation…. Examples are electricity meters and measurements on primary overcurrent protection devices and ripple
control units.”
If you want to measure nominal voltages higher than 690 volts, you can connect your PQube
voltage inputs to the secondary windings (low voltage windings) of any standard Potential
Transformer.
In general, the accuracy of your PQube’s voltage measurements are so precise (roughly ±0.1%) that
any accuracy specification will be determined almost entirely by the potential transformer that you
select. If using calibrated potential transformers, you can enter the calibration constants into your
PQube to further improve your accuracy.
For information on configuring your PQube to read correct voltages when using a potential
transformer, see Setting Your Potential Transformer Ratio (page 28).
Page 16 of 113
PQube User Manual 2.1
The operator must be protected from the hazardous screw terminals by a barrier. The screw terminals must be made “not
ACCESSIBLE”, as defined in UL /IEC 61010-1 6.2, using an enclosure or barrier that meets the rigidity requirements of UL /IEC 61010-
1 8.1 and that requires a tool to remove.
3
Include overcurrent protection and a disconnecting device
An external overcurrent protection device, such as a fuse or a circuit breaker, must be installed on
each mains connection. The device shall meet the relevant requirements of IEC 60947-1 and IEC
60947-3, and be suitable for the application.
The overcurrent protection device must be rated between 1 amp (minimum) and 20 amps
(maximum).
Your PQube can share the overcurrent protection device with other loads.
An operator-activated disconnecting device, such as a switch or a circuit breaker, must be installed
on the mains connections. This device must be clearly marked as the disconnecting device for your
PQube, and must be marked to indicate the disconnection function. Do not install your PQube in
such a way that it becomes difficult to operate this disconnecting device. The disconnecting device
must not disconnect the earth connection. The disconnecting device should be installed near your
PQube, within easy reach of the operator.
Protect the operator from the hazardous terminals
IMPORTANT: All high voltage parts must be covered, including the AC power to your PQube.
Install your PQube so that all of the screw terminals are not ACCESSIBLE3 to the operator. Your PQube
can also be installed without a cover if installed in a lockable IUL 508 control panel.
Page 17 of 113
PQube User Manual 2.1
If you choose to install your PQube in an enclosure, select a UL-listed enclosure that is appropriate for the purpose, such as the
Altech EK series (www.AltechCorp.com). If you plan to use an enclosure of this type, you should review its mechanical
compatibility with any optional features of your PQube that you plan to use: optional USB connections, optional temperaturehumidity probes, etc.
A different example of how to correctly protect your PQube operator from the screw terminals. A 6,35mm (0.25 in) clear
Plexiglass® sheet, which requires a tool to remove, protects the operator. A rectangular cutout in the Plexiglass gives the operator
access to your PQube controls, the Ethernet connection, etc. Note the 1-amp, 3-phase circuit breaker, at far right, used both as
external overcurrent protection and disconnecting device, near your PQube. The rectangular opening in the Plexiglass should be
74mm x 47mm (for your PQube alone), or 110mm x 47mm (for your PQube and the ETH1 module, or your PQube and the PS1
module), or 146mm x 47mm (for your PQube and both the ETH1 and PS1 modules).
Protect antenna terminals from lightning
If you install a PQube antenna (GPS, Zigbee, etc.) in an outdoor location where it may be exposed
to lightning, you must include a properly installed UL-497C-listed lightning protection device on the
antenna cable. Follow all local installation safety requirements and
regulations.
Installing Your ETH1 Ethernet Module
The optional ETH1 Ethernet module connects to the left side of your
PQube; just snap it in. Connect the module before supplying power to
your PQube. The ETH1 Ethernet module contains a standard RJ-45
Ethernet port. The module uses 10BaseT Ethernet with built-in crossover
detection. You can connect your ETH1 Ethernet module to any standard
Page 18 of 113
PQube User Manual 2.1
Ethernet network using a standard Ethernet cable. For information on configuring your ETH1
module see Setting up Your Optional ETH1 Ethernet Module (page 32).
Installing Your PS1 or PS2 Power Supply Module
The optional PS1 or PS2 Power Supply Module connects to the right side of
your PQube; just snap it in. It accepts any 50/60 Hz single-phase input
between 100Vac and 240Vac nominal. Verify that you are connecting the
line and neutral wires to the correct terminals on the module. The PS1 and
PS2 Power Supply modules contain an internal fuse.
Installing Current Modules
If you want to measure current with your PQube you can install an optional module. Simply plug
the module into the side of your PQube.
PQube current modules provide transformer-based electrical isolation, except for the XCT5-0.333V,
XCT5-01V, XCT5-05V, and XCT5-10V, which take low-voltage inputs.
Note that your PQube makes current measurements with a Crest Factor of 3.5. This means that
your PQube can measure instantaneous currents up to 350% of the nominal rated current (for
example, if you have selected a 300-amp current transformer with a 5-amp secondary, your PQube
will accurately measure up to ±1050 amps instantaneous). This is a very useful feature when
dealing with inrush currents, and currents with high harmonic contents.
When connecting a Current Module, it is important to match the phases to the voltage inputs and
current input (connect the L1 voltage input and the L1 current sensor to the same conductor). This
is important for correct power and energy calculations.
There are three main types of current module, the XCT4 with current inputs, the XCT5 with voltage
inputs, and the CT4. You only need one current module to measure current, power, and energy.
Pick the version that works best for you.
XCT4 Current Module – Current inputs
You can connect external current transformers to your PQube. There
are two versions of the XCT4 module: each will work with a different
type of CT. Make sure you carefully read all safety information
provided by the manufacturer before installing CTs.
If you are using a CT with a current secondary, you can use the XCT41A-00 or the XCT4-5A-00 which have 1 and 5 Amp inputs, respectively.
Your PQube places almost zero burden on the current transformer
(less than 0.1 VA), so you can select almost any current transformer.
XCT5 Current Module – Voltage inputs
If you are using a current sensor that has a voltage output, you can choose between the XCT5-
0.333V-00, XCT5-01V-00, XCT5-05V-00, and XCT5-10V-00 which have 0.333, 1, 5, and 10 Volt
inputs, respectively.
You can use either standard current transformers, or split-core current transformers. Standard
current transformers are generally less expensive, and are often more accurate. Split-core
transformers are much easier to install.
Page 19 of 113
PQube User Manual 2.1
In general, the accuracy of your PQube’s current measurements are so precise (roughly ±0.1%) that
the accuracy of your current measurements will be determined almost entirely by the current
transformer that you select.
CT4 Current Module
If you don’t already have CTs, but you want to measure current, you
can use the optional CT4 module. It has the CTs already built in and
ready to use.
The CT4 comes in two models: the CT4-20A (for nominal currents up to
20 amps) and the CT4-50A (for nominal currents up to 50A). Both
versions can accept conductors up to 0.34 inches (8,6mm) in diameter.
600V, UL-recognized insulation is required.
Page 20 of 113
PQube User Manual 2.1
(a) PQube monitors complete Voltage Quality
(b) With CT4 Current Module
(c) With XCT4 Current Module, 1 current transformer
(d) With XCT5/CTE1 Current Module, 1 current
transformer
Wiring Diagrams
Single-Phase L-N
Page 21 of 113
PQube User Manual 2.1
(a) PQube monitors complete Voltage Quality
(b) With CT4 Current Module
(c) With XCT4 Current Module, 2 current
transformers
(d) With XCT5/CTE1 Current Module, 2 current
transformers
(e) With XCT4 Current Module, 3 current
transformers
(f) With XCT5/CTE1 Current Module, 4 current
transformers
Split-Single-Phase L-N-L
Page 22 of 113
PQube User Manual 2.1
(a) PQube monitors complete Voltage Quality
(b) With CT4 Current Module
(c) With XCT4 Current Module, 1 current transformer –
PQube calculates current on other phase
(d) With XCT4 Current Module, 2 current transformers
– PQube measures current on both phases
(e) With XCT5/CTE1 Current Module, 1 current
transformer – PQube calculates current on other phase
(f) With XCT5/CTE1 Current Module, 2 current
transformers – PQube measures current on both
phases
Single-Phase L-L
Page 23 of 113
PQube User Manual 2.1
(a) PQube monitors complete Voltage Quality
(b) With CT4 Current Module
(c) With XCT4 Current Module, 2 current transformers
– PQube calculates current on third phase
(d) With XCT4 Current Module, 3 current transformers
– PQube measures current on all phases
(e) With XCT5/CTE1 Current Module, 2 current
transformers – PQube calculates current on third phase
(f) With XCT5/CTE1 Current Module, 3 current
transformers – PQube measures current on all phases
Delta
Page 24 of 113
PQube User Manual 2.1
(a) PQube monitors complete Voltage Quality
(b) With CT4 Current Module
(c) With XCT4 Current Module, 3 current transformers
– PQube calculates current on neutral conductor
(d) With XCT4 Current Module, 4 current transformers
– PQube measures current on phase and neutral
conductors
Wye/Star
Page 25 of 113
PQube User Manual 2.1
(e) With XCT5/CTE1 Current Module, 3 current
transformers – PQube calculates current on neutral
conductor
(f) With XCT5/CTE1 Current Module, 4 current
transformers – PQube measures current on phase and
neutral conductors
(g) With XCT5/CTE1 Current Module, 5 current
transformers – PQube measures Earth conductor
current
(h) With XCT5/CTE1 Current Module, 5 current
transformers – Net Earth Current measurement
Wye/Star (continued)
Page 26 of 113
PQube User Manual 2.1
A
Battery compartment latch
I USB port. Optically isolated from local earth.
Factory use for Rev 1.2 firmware; user access in free
future firmware upgrades.
B
SD memory card and adjacent LED
J Digital input. 60-volt tolerant. 1.5-volt threshold.
Wetted with 5.4V at 3 microamps.
C
Select button
K Power inputs. 24VAC, or 24VDC to 48VDC (either
polarity) nominal. 15VA max.
D
Joystick. Click like a button to return to
main menu.
L
Earth – functional. Used as the reference voltage.
E
Heartbeat LED
M Analog inputs. Maximum ±60V to earth. Can be used
as differential inputs.
F
Temperature/humidity probe inputs.
Optically isolated from local earth.
N Signal relay outputs. One is standard on all PQubes.
Two more signal relay outputs are available as a
factory-installed RLY option.
G
L1, L2, L3 voltage inputs. 690Vrms max
phase-to-phase (equivalent to 400Vrms
phase-to-earth)
P
Relay contact output rated at 30VAC, 60VDC, 2 amps,
- included in factory-installed RLY option.
H
Neutral terminal – optional connection
Overview of connections and controls
Disconnect mains prior to servicing
Always disconnect all mains connections, and verify disconnections, prior to servicing.
Calibration Information for Your PQube
Every PQube is calibrated and traced to NIST at the factory. You can download a free NIST trace
certificate that contains the specific calibration information for your PQube by entering your
PQube’s serial number at www.powerstandards.com/CalibCerts.htm.
Page 27 of 113
PQube User Manual 2.1
Setting up your PQube
Your PQube will work right out of the box. Simply follow the Quickstart Guide (page 11) and your
PQube will begin recording data immediately. The default settings will work for most applications,
but if you have special requirements you may need to change a few settings. Don’t worry, it’s an
easy process.
Setting the Date and Time
You can set the time and date via your PQube’s display. For information on how
to use your PQube’s display, see Your PQube’s Display and User Interface (page
39). Go to the configuration menu and scroll to the Date/Time screen. Press the
select button and then use the joystick to set the date and time.
Setting the date and time is important because all of the output files your PQube produces include
a time stamp.
Note that if you have an ETH1 Ethernet module and you are using the SNTP feature (off by default),
your PQube will override any changes you make to the date and time.
Setting Your Languages
In previous firmware versions, you set the language at the Languages screen on
the PQube display.
In Firmware 1.4 and newer, you can specify up to two languages to be used in
the PQube at any time in your setup file. Setting languages remotely is now
possible, and the selected language(s) remain even after a firmware update.
Everytime your PQube resets or starts up, make sure your PQube “locks” onto
the appropriate power configuration, nominal voltage, and nominal frequency.
This is important for proper event detection and data recording. Your PQube
will not begin recording until it has locked onto the power configuration.
If you are using your PQube for DC monitoring only, and do not wish to record AC voltage, you can
set your Power Configuration to “NONE” in your setup file.
Setting Your Potential Transformer Ratio
If you are using Potential Transformers (PT) to monitor voltages above 690Vac Phase-to-Phase
(400Vac Phase-to-Earth) you can tell your PQube about the ratio to use to calculate the measured
voltage. For example, to use your PQube on a 24 kilovolt distribution system, you might use a
100:1 potential transformer to reduce the 24 kilovolts to 240 volts. In your PQube’s Setup.ini file,
you would set
Potential_Transformer_Ratio=24000:240
Or, if you prefer, you could set
Page 28 of 113
PQube User Manual 2.1
Potential_Transformer_Ratio=100:1
Note that, if you choose to set the nominal voltage in your PQube’s Setup.ini file, you would set
Nominal_Phase_To_Neutral_Voltage=24000
even though the voltage at your PQube’s terminals is 240 volts nominal.
Potential Transformers with Calibrated Ratios
In Firmware 2.1, you can now apply a gain correction factor for the mains voltage terminals, with a
range of 0.95 to 1.05. Use with calibrated potential transformers to improve the accuracy of your
measurements!
Example: Assuming a 10000:100 PT ratio, use the settings below:
PQube Configurator Settings:
Setup.ini tags
; ------ Valid values: from 1:1 up to 500000:1
; You can use fractional values such as 1250.5:120
; If your application requires a ratio higher than 10000:1
; please contact factory for additional information
If you are using a CT4 current sensing module, you don’t need to set a CT ratio – your PQube will
set it automatically.
If you are using an XCT4 current sensing module, you will need to set the CT ratio so that your
PQube can correctly display the amount of current, as well as correctly calculate power and energy
usage.
For example, to use your PQube on a system with 200 amps flowing in the power conductors, you
might choose current transformers rated at 300 amps, with a 5-amp secondary. In your PQube’s Setup.ini file, you would set
Current_Transformer_Ratio=300:5
If you have a current transformer with voltage output, simply enter the primary current and
secondary voltage into your CT ratio. For example, if you have a current transformer rated at 300
amps, with 0.333V secondary, then you would set
Current_Transformer_Ratio=300:0.333
Inverting Current Channels
During installation, it is easy to make a mistake in your current transformer connections, either by
reversing the secondary connections (when using an XCT4) or by feeding the main power
conductor through your current transformer backwards (when using a CT4 or XCT4).
You will know when the current transformers are installed backwards by looking at your power
(watts) readings. If you are expecting positive watts values and you are getting negative watts (or
vice versa), then you know your current transformers need to be inverted.
Of course, you can always correct your wiring; but an easier alternative is to use your PQube’s
Setup.ini file to invert one or more of your current channels. If you realize that you have installed
your L2 current transformer backwards, you can fix this easily:
It is important to correctly connect your CTs (or use the method above to correct a wiring
error). Power (watt) calculations are made by multiplying the instantaneous current by the
instantaneous voltage. If one or more of your current transformers is incorrectly set up,
your PQube will calculate negative power for that phase.
Calculating Current With a Missing CT
You do not need to connect CTs to all of the conductors that you want to monitor. When current
flows through a system, the net current is always zero. Because of this, you can connect one fewer
CT than you have conductors (for a delta system, you only need two CTs, for a wye/star system you
only need 3 CTs, and you must calculate the Neutral current). Your PQube can calculate the
Page 30 of 113
Loading...
+ 83 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.