Proton Guard G710, Guard G750 Operation Manual

OPERATIONS MANUAL FOR AIR HEATER PROTON GUARD
ErP
05021616
PROTON GUARD
Air heater with
corrosion-resistant
heat exchanger
www.protongroup.org
Safety precautions Construction and dimensions
Technical parameters
Installation
EN
RU
CONTENTS
Maintenance guide for air heating unit PROTON GUARD with corrosion-resistant heat exchanger:
1. Introduction .............................................................................................................................................................
2. Safety precautions ...............................................................................................................................................
3. General information ............................................................................................................................................
4. Dimensions ..............................................................................................................................................................
5. Construction ...........................................................................................................................................................
6. Technical characteristics ....................................................................................................................................
7. Mounting consoles ................................................................................................................................................
8. Installation .............................................................................................................................................................
9. Connection of heat medium ...........................................................................................................................
10. Maintenance .........................................................................................................................................................
11. Operational conditions ......................................................................................................................................
12. Control elements ................................................................................................................................................
12.1. Control elements for air heater PROTON G 710 .........................................................................
12.2. Control elements for air heater PROTON G 750 .........................................................................
13. Wiring PROTON G 710 ......................................................................................................................................
14. Wiring PROTON G 750 ......................................................................................................................................
15. Reference information .....................................................................................................................................
3 4 5 6 7 8
9 13 14 15 16
17 17 20 22 31 34
2
1. INTRODUCTION
The company PROTON GROUP LLC thanks you for choosing air heaters PROTON.
This manual is an integral part of the product and must always accompany it, and should be transferred to the user.
To provide proper wiring and application of the unit, please, study this manual thoroughly before installation.
We recommend keeping the manual safe in order to address it during operation.
The user should strictly follow safety instructions while installing, using and servicing the unit.
The access to the unit must be restricted for unauthorized and unqualified personnel. The appropriate training of the maintenance sta should be provided.
The manufacturer disclaims any responsibility for damages caused by wrong installation and misuse of the unit.
The manufacturer disclaims any responsibility for damages done by people who didn’t study the manual.
The manufacturer preserves the right to introduce any amendments to the manual without prior notification.
The manufacturer preserves the right to alter the construction which doesn’t impact its functioning and basic technical parameters.
The air heater is intended only and exclusively to be installed and used for purposes which it has been designed. Any misuse or noncompliance with the manufacturer’s instructions may lead to property damages, personnel injuries or death. The user has to take measures to eliminate possibilities of misuse of the unit.
3
2. SAFETY PRECAUTIONS
Before any actions connected with the air heater, please, study this manual to provide safety.
Installation and connection of the equipment to pipelines and networks must be performed by qualified personnel only, having appropriate access.
During installation, start-up, repair and maintenance of the air heater follow the safety rules.
Install the unit on a firm base or surface, which can stand its weight filled with water.
Use screws appropriate for the material which the base is made of.
Check correctness of connections of the system, accordance of the heat medium parameters to the parameters indicated on the rating plate as well as leak proof of joints before filling in the heat medium.
Avoid substances and impurities in the heat medium causing copper corrosion.
Check compliance of parameters of the electrical supply network to the ones indicated on the unit’s rating plate before connecting to the power supply.
Check grounding. Prohibit the use of the unit without grounding as it may cause property damages, personnel injuries and death.
Current network which feeds the unit’s motor and controls must be additionally protected by a fuse to prevent consequences of shunt fault.
Thermal protection of fan’s motor is built-in and works in a standalone mode.
While the air heater is operating under low temperatures, the
-t
user must provide protection of the water heat exchanger or use heat medium with special additives preventing copper corrosion.
To prevent defrosting of the air heater’s heat exchanger when circulation of the heat medium is stopped during a heating period under outdoor temperatures lower than 0°C, you need to drain the heat medium from the heat exchanger and blow it o by compressed air.
4
3. GENERAL INFORMATION
*
ErP
2015
PROTON GUARD
This equipment is designed for using in buildings with extremely heavy conditions: increased dustiness, aggressive particles in the air, corrosiveness. Design solutions applied in this series significantly increase operational safety and life time. Due to using: casings of special construction, heat exchanger with polymeric protection cover, enlarged thickness of lamellas and interlamellar distance – PROTON GUARD sets a new standard of industrial air heaters.
Air heaters PROTON G 710 are equipped with three-speed AC-motors. Air heaters PROTON G 750 are equipped with electronically commutated EC-motors.
Principle of operation
Outlet pipe
Inlet pipe
*
It can be optionally equipped with a front panel and louvers.
The air heater PROTON is an element of a heating system. It is designed for heating air and its even distribution in buildings. Its work is based on axial fan functioning, which charges the air and pass it through a copper-aluminum heat exchanger in which the heat medium (hot water) flows at certain temperature. Heated air is supplied into a room and is directed to the working area.
5
4. DIMENSIONS
Dimensions of the air heater PROTON GUARD
675
580675
Dimensions of the air heater PROTON GUARD with the front panel and louvers
350
*
*
Depends on a motor type.
680
680
*
390
590
6
5. CONSTRUCTION
Major components of the air heater PROTON GUARD
Diuser
Only plastic diusers are used for this series produced by the method of vacuum molding. In addition to creating a form around an impeller, the diuser performs a role of a body to fix a fan and additional stiening ribs are provided ad hoc. The diuser is fixed to a heat exchanger by a flat side, that enables to fully use air charged by a fan to move through lamellas of the heat exchanger.
Fan
The fan is fixed in a plastic diuser on the back of the unit, thanks to which air can be eectively charged in a heat exchanger. The diuser is made in the shape of a ring around fan blades as well as creates a body of the air heater. Fans applied are axial and can have either single-phase electronically commutated or single-phase asynchronous motors. These fans are manufactured in a single production process, tested and balanced by the manufacturer, installed on a protection grill which protects the heater from falling in of debris, leaves etc. as well as prevents possible personnel injures or death caused by rotating fan blades.
PROTON G 710 with single-phase asynchronous motor
This type of motors can work only with nominal voltage of 230 V. To start the motor a capacitor is needed, so the latter is installed into the motor, and this eliminates the necessity of using external elements to be connected to the power network. The use of the single-phase motor enables regulation of rotation speed by additional step-down transformers or to use of additional contacts from motor windings with dierent powers.
PROTON G 750 with electronically commutated motor
The motor contains a built-in electronic controller which enables to set rotation speed. This technology makes possible remote smooth regulation of the motor and increases its eciency. Using appropriate control elements in an automatic mode you can maintain necessary speed for as comfortable as possible relation between noise of blades and heating power of the unit. Construction of these motors doesn’t dier from asynchronous ones.
Heat exchanger
The heat exchanger consists of copper tubes and aluminum lamellas pressed on them. It is equipped with copper pipes with threading connection (external thread 3/4”). The copper-aluminum heat exchanger is distinguished by high eciency, is not exposed to corrosion if you don’t use substances and impurities in a heat medium causing copper corrosion. Maximal parameters of heat medium supply are 105 °C/1,6 MPa. The air heaters PROTON GUARD are equipped with the heat exchanger with polymeric protection cover with enlarged thickness and interlamellar distance, that allows to use them eectively in the agriculture sector.
7
6. TECHNICAL CHARACTERISTICS
General parameters
Number of heat exchanger rows
Airflow
Heating power
Air temperature increase
Max. temperature of heat medium
Max. working pressure
Max. warm air throw
Volume of water in heat exchanger
Diameter of connection pipes
Weight without heat medium
Supply voltage
Motor power
Rated current of motor
Noise level
Motor protection rating
R
m³/h
kW
°С
°С
MPa
m
dm³
inch
kg
V/Hz
W
А
dB
IP
Parameters according to the heat medium
(°С)
Qp
(m³/h)
T /zT
p
P
p1
(°С)
0 5
10 15
20
5500
25
30
35
52.0
48.8
45.5
42.2
38.9
35.6
32.2
32.2
P
g
Water 90/70 Water 80/60 Water 70/50 Water 60/40Parameters
Q
P
w
p2 p
(m³/h) (kW) (kPa)
(°С)
24.8
2.3
28.8
2.2
31.6
2.0
35.0
1.9
38.3
1.7
41.7
1.6
45.0
1.4
48.3
1.3 8.8
25.8
22.9
20.2
17.6
15.1
12.9
10.7
P
44.9
41.6
38.3
35.0
31.7
28.3
24.9
21.4
g
G 710
3
5500
52.0
24.8
105
1.6
26
3.50
3/4
24.4
230/50
420
2.00
57
54
Q
P
w
p2 p
(m³/h) (kW) (kPa)
(°С)
21.4
2.0
24.8
1.8
28.2
1.7
31.6
1.5
34.9
1.4
38.3
1.3
41.6
1.1
44.9
0.9
G 710
20.1
17.5
15.0
12.7
10.6
8.6
6.9
5.2
37.7
34.4
31.1
27.7
24.3
20.9
17.4
13.8
P
g
Q
P
w
p2 p
(m³/h) (kW) (kPa)
(°С)
18.0
1.7
21.4
1.5
24.8
1.4
28.1
1.2
31.5
1.1
34.8
0.9
38.1
0.8
41.5
0.6
14.9
12.6
10.5
8.5
6.8
5.1
3.7
2.5
G 750
3
5600
53.1
24.3
105
1.6
27
3.50
3/4
20.1
230/50
300
2.05
54
54
P
g
14.5 10.4
30.5
17.9
27.1
21.3
23.8
24.6
20.6
28.0
16.9
31.2
13.3
34.4
9.5
37.3
5.1
Q
P
w
p2 p
(m³/h) (kW) (kPa)
(°С)
1.3
1.2
1.0
0.9
0.7
0.6
0.4
0.2
8.5
6.7
5.0
3.6
2.4
1.3
0.4
Parameters according to the heat medium
(°С)
T /zT
p
Qp
(m³/h)
(°С)
P
p1
0 5
10 15
20
5600
25
30
35
– water temperature at the inlet of the unit
P
z
P
– water temperature at the outlet of the unit
p
Q
w
Data on operating characteristics of air heater PROTON, when using heat medium with diering temperatures, is to be provided on demand. There is danger of heat exchanger defrosting (breakage) if room temperature falls lower than 0 °C. As maximal pressure of the heat medium is 1,6 MPa, the water cir cuit system must have protection from pres sure rise higher than accepted value.
53.1
49.8
46.4
43.1
39.7
36.3
32.9
29.5
P
g
Water 90/70 Water 80/60 Water 70/50 Water 60/40Parameters
Q
P
w
p2 p
(m³/h) (kW) (kPa)
(°С)
2.3
24.3
2.2
27.8
2.1
31.2
1.9
34.6
1.8
38.0
1.6
41.4
1.4
44.7
1.3 9.1
48.1
26.8
23.8
20.9
18.2
15.7
13.3
11.1
P
P
g
p2 p
(°С)
45.8
21.0
42.5
24.4
39.1
27.8
35.7
31.2
32.3
34.6
28.9
38.0
25.4
41.4
21.9
44.7
– air temperature at the inlet of the unit
P
p1
P
– air temperature at the outlet of the unit
p2
– water pressure drop in heat exchanger– water consumption
p
Q
w
(m³/h) (kW) (kPa)
20.8
2.0
18.1
1.9
15.6
1.7
13.2
1.6
11.0
1.4
1.3
9.0
1.1
7.1
1.0
5.4
G 750
38.5
35.1
31.7
28.3
24.8
21.3
17.8
14.1
P
g
Q
P
w
p2 p
(m³/h) (kW) (kPa)
(°С)
17.6
1.7
21.1
1.5
24.5
1.4
27.9
1.2
31.3
1.1
34.7
1.0
38.0
0.8
41.3
0.6
P
g
14.3
31.1 10.8
15.5
13.1
10.9
8.9
7.0
5.4
3.8
2.5
17.7
27.7
21.1
24.3
24.4
20.8
27.8
17.2
31.1
13.6
34.4
9.7
37.3
5.2
– heat power of the unit
P
g
Q
– air consumption
p
Q
P
p2 p
(m³/h) (kW) (kPa)
(°С)
1.4
1.2
1.0
0.9
0.8
0.6
0.4
0.2
8
w
8.8
6.9
5.2
3.7
2.4
1.4
0.5
7. MOUNTING CONSOLES
7.1 Installation on a mounting console CM 2D
Order of installation
3
1
3
2
М8
М8
2
3
2
М8
3
2
Fasten the mounting console on the air heater’s body using fixing screws and rings .
Use fasteners designed for the material which the base is made of.
.
1
М8
2 3
9
7. MOUNTING CONSOLES
Fastening dimensions of the mounting console
9
620
120 510
12
Ways of installation with mounting consoles
30
30
45
45
On a wall vertically or horizontally, and under angle of 30° or 45°.
30
Under a ceiling horizontally,
45
or under angle of 30° or 45°.
Noncompliance with the minimal distance (0,25 m) from a wall or ceiling will lead to wrong operation of the air heater which, in turn, will influence the useful life of the equipment.
10
7. MOUNTING CONSOLES
7.2 Installation on a mounting console CM 3D
Order of installation
6
М8
2
4
3
B
4
3
М8
М8
М8
1
М8
М8
А
4
3
5
4
3
6
1. Fasten brackets and on the air heater’s body using screws and rings . Follow the brackets position – , .
2. Fasten the console under necessary angle (position ) using anchoring screws (are to be bought separately).
3. Install the air heater on the console in the position into the hole on the console (position ). Then putting together holes on the bracket and upper hole on the console , fix everything by screws .
4. Mount the air heater under necessary angle and fix by screws .
1 2
6
Use fasteners designed for the material which the base is made of.
.
A
B
5
1
2
3 4
4
5
6
11
Loading...
+ 25 hidden pages