Proton EX30, EX70, EX50 Operation Manual

Page 1
OPERATIONS MANUAL FOR AIR HEATER PROTON EX
05010416
PROTON EX
Air Heater with the
explosion proof AC-motor
www.protongroup.org
Safety precautions Construction and dimensions
Technical parameters
EN
RU
Page 2
CONTENTS
Operations manual for air heater with the explosion proof motor PROTON EX:
1. Introduction ............................................................................................................................................................
.
2. Safety precautions ..............................................................................................................................................
3. General information ............................................................................................................................................
4. Dimensions .............................................................................................................................................................
5. Construction ..........................................................................................................................................................
6. Technical characteristics ..................................................................................................................................
7. Installation .............................................................................................................................................................
8. Connection of heat medium ...........................................................................................................................
9. Control elements ................................................................................................................................................
10. Wiring control elements ...................................................................................................................................
11. Reference information .....................................................................................................................................
3
4 5 6 7 8
9 11 12 13 14
2
Page 3
1. INTRODUCTION
The company PROTON GROUP LLC thanks you for choosing air heaters PROTON.
This manual is an integral part of the product and must always accompany it, and should be transferred to the user.
To provide proper wiring and application of the unit, please, study this manual thoroughly before installation.
We recommend keeping the manual safe in order to address it during operation.
The user should strictly follow safety instructions while installing, using and servicing the unit.
The access to the unit must be restricted for unauthorized and unqualified personnel. The appropriate training of the maintenance sta should be provided.
The manufacturer disclaims any responsibility for damages caused by wrong installation and misuse of the unit.
The manufacturer disclaims any responsibility for damages done by people who didn’t study the manual.
The manufacturer preserves the right to introduce any amendments to the manual without prior notification.
The manufacturer preserves the right to alter the construction which doesn’t impact its functioning and basic technical parameters.
The air heater is intended only and exclusively to be installed and used for purposes which it has been designed. Any misuse or noncompliance with the manufacturer’s instructions may lead to property damages, personnel injuries or death. The user has to take measures to eliminate possibilities of misuse of the unit.
3
Page 4
2. SAFETY PRECAUTIONS
Before any actions connected with the air heater, please, study this manual to provide safety.
Installation and connection of the equipment to pipelines and networks must be performed by qualified personnel only, having appropriate access.
During installation, start-up, repair and maintenance of the air heater follow the safety rules.
Install the unit on a firm base or surface, which can stand its weight filled with water.
Use screws appropriate for the material which the base is made of.
Check correctness of connections of the system, accordance of the heat medium parameters to the parameters indicated on the rating plate as well as leak proof of joints before filling in the heat medium.
Avoid substances and impurities in the heat medium causing copper corrosion.
Check compliance of parameters of the electrical supply network to the ones indicated on the unit’s rating plate before connecting to the power supply.
Check grounding. Prohibit the use of the unit without grounding as it may cause property damages, personnel injuries and death.
Current network which feeds the unit’s motor and controls must be additionally protected by a fuse to prevent consequences of shunt fault.
Provide protection of a fan against overheat by connecting protection devices to contacts of fan temperature sensor.
While the air heater is operating under low temperatures, the
-t
user must provide protection of the water heat exchanger or use heat medium with special additives preventing copper corrosion.
To prevent defrosting of the air heater’s heat exchanger when circulation of the heat medium is stopped during a heating period under outdoor temperatures lower than 0°C, you need to drain the heat medium from the heat exchanger and blow it o by compressed air.
4
Page 5
3. GENERAL INFORMATION
Explosion proof
design
PROTON EX
It is designed to heat industrial premises and warehouses under conditions of extra explosion safety. This equipment is to be mounted in buildings with increased probability of explosion as a result of interaction with dangerous materials as well as because of some technological processes.
Principle of operation
The air heater PROTON is an element of a heating system. It is designed for heating air and
Outlet pipe
Inlet pipe
its even distribution in buildings. Its work is based on axial fan functioning, which charges the air and pass it through a copper-aluminum heat exchanger in which the heat medium (hot water) flows at certain temperature. Heated air is supplied into a room and is directed to the working area by directing louvers.
Applications
Chemicals production premises Paint and varnish industry Furniture production premises Oil- and gas processing factories Workshops with installed vessels and containers of high pressure Premises of production of highly explosive substances
Model range
PROTON EX 30 heating power 10-30 kW PROTON EX 50 heating power 25-50 kW PROTON EX 70 heating power 40-70 kW
5
Page 6
4. DIMENSIONS
Dimensions of the air heater PROTON EX
380
680
620
Fastening dimensions of the mounting console CM LX
195
195
8,3
200
6,3
147
195
580
680
195
515
6
Page 7
5. CONSTRUCTION
Major components of the air heater PROTON EX
Casing
Metal casing is made of elements dyed by protection cover that provides long-time protection against corrosion and conforms with European quality and design standards.
Fan
Protection-proof axial fan of the air heater PROTON EX provides even air distribution on heat exchanger’s surface. The construction and material of the fan prevents sparks and local temperature increase in motor windings. Overheat protection is provided by a thermistor sensor, not a temperature sensor as for standard motors. The motor meets European requirements on explosion safety. Rated power supply of PROTON EX fans is 3~400 V/50 Hz. Motor protection rating is IP44 (EN60529), isolation class THCL155, protection class II2Gc ExeIIB T3. Operating temperature range is
-20 °C to +40 °C.
Heat exchanger
A heat exchanger consists of copper tubes and aluminum lamellas pressed on them. It is equipped with copper pipes with threading connection (external thread 3/4”). Copper-aluminum heat exchanger is distinguished by high eciency, is not exposed to corrosion if you don’t use substances and impurities in the heat medium causing copper corrosion. Maximal parameters of heat medium supply are 130 °C/1,6 MPa.
Directing louvers
They are made of steel and dyed by special paint, and provide minimal air resistance at the outlet from the air heater. Aesthetic look and high protection from corrosion guarantee durability and safety.
7
Page 8
6. TECHNICAL CHARACTERISTICS
General parameters
Number of heat exchanger rows
Airflow
Heating power
Air temperature increase
Max. temperature of heat medium
Max. working pressure
Max. warm air throw
Volume of water in heat exchanger
Diameter of connection pipes
Weight without heat medium
Supply voltage
Motor power
Rated current of motor
Noise level
Motor protection rating
R
m³/h
kW
°С
°С
MPa
m
dm³
inch
kg
V/Hz
W
А
dB
IP
Parameters according to the heat medium
(°С)
Qp
(m³/h)
T /zT
p
P
p1
(°С)
0 5
10 15
46004 1003700
20 25
P
29.7
27.7
25.7
23.8
21.8
19.8
g
Water 90/70 Water 80/60 Water 70/50 Water 60/40Parameters
Q
P
w
p2 p
(m³/h) (kW) (kPa)
(°С)
19.2
1.3
22.9
1.2
26.6
1.2
30.2
1.1
33.9
1.0
37.6
0.9
8.5
7.5
6.6
5.7
4.8
4.0
Parameters according to the heat medium
(°С)
Qp
(m³/h)
T /zT
p
P
p1
(°С)
0 5
10 15
20 25
P
51.5
48.1
44.7
41.3
37.9
34.5
g
Water 90/70 Water 80/60 Water 70/50 Water 60/40Parameters
Q
P
w
p2 p
(m³/h) (kW) (kPa)
(°С)
37.3
2.3
39.8
2.2
42.3
2.0
44.7
1.9
47.2
1.7
49.6
1.6
15.0
13.2
11.6
10.0
8.5
7.2
Parameters according to the heat medium
(°С)
T /zT
p
Qp
(m³/h)
(°С)
P
p1
0 5
10 15
20 25
– water temperature at the inlet of the unit
P
z
P
– water temperature at the outlet of the unit
p
Q
w
P
66.5
62.2
58.0
53.8
49.5
45.2
g
Water 90/70 Water 80/60 Water 70/50 Water 60/40Parameters
Q
P
w
p2 p
(m³/h) (kW) (kPa)
(°С)
53.3
3.0
54.8
2.8
56.4
2.6
57.8
2.4
59.3
2.2
60.7
2.0
18.5
16.4
14.4
12.5
10.7
9.1
EX 30
1
4600
29.7
19.2
130
1.6
28
1.30
3/4
29.4
400/50
290
0.51
53
44
EX 30
P
25.3
23.3
21.3
19.3
17.2
15.2
g
Q
P
w
p2 p
(m³/h) (kW) (kPa)
(°С)
16.3
1.2
20.0
1.1
23.7
1.0
27.4
0.9
31.0
0.8
34.7
0.7
6.5
5.6
4.7
3.9
3.2
2.6
EX 50
P
44.0
40.6
37.2
33.8
30.4
26.9
g
Q
P
w
p2 p
(m³/h) (kW) (kPa)
(°С)
31.9
2.0
34.4
1.8
36.9
1.7
39.3
1.5
41.8
1.4
44.2
1.2
11.4
9.9
8.4
7.0
5.8
4.6
EX 70
P
57.2
52.9
48.7
44.4
40.1
35.7
g
P P
Q
P
w
p2 p
(m³/h) (kW) (kPa)
(°С)
45.9
47.4
48.9
50.4
51.8
53.2
– air temperature at the inlet of the unit
p1
– air temperature at the outlet of the unit
p2
– water pressure drop in heat exchanger– water consumption
p
14.2
2.6
12.3
2.4
10.6
2.2
8.9
2.0
7.4
1.8
6.0
1.6
8
P
20.8
18.8
16.7
14.7
12.6
10.5
P
36.5
33.1
29.7
26.2
22.7
19.2
P
47.8
43.6
39.2
34.9
30.5
26.0
g
g
g
EX 50
2
4100
51.5
37.3
130
1.6
23
2.25
3/4
31.3
400/50
290
0.51
53
44
Q
P
w
p2 p
(m³/h) (kW) (kPa)
(°С)
13.4
0.9
17.1
0.9
20.8
0.8
24.4
0.7
28.1
0.6
31.7
0.5
Q
P
w
p2 p
(m³/h) (kW) (kPa)
(°С)
26.5
1.6
28.9
1.5
31.4
1.3
33.9
1.2
36.3
1.1
38.7
0.9
Q
P
w
p2 p
(m³/h) (kW) (kPa)
(°С)
38.4
2.1
39.9
1.9
41.4
1.8
42.8
1.6
44.2
1.4
45.6
1.2
4.6
3.9
3.1
2.5
1.9
1.4
8.3
6.9
5.7
4.5
3.5
2.6
10.4
8.8
7.2
5.8
4.6
3.4
EX 70
3
3700
66.5
53.3
130
1.6
20
3.18
3/4
32.9
400/50
290
0.51
53
44
P
P
g
p2 p
(°С)
16.2
10.5
14.2
14.1
12.1
17.8
10.0
21.4
7.8
25.0
5.3
28.4
P
P
g
p2 p
(°С)
28.9
20.9
25.4
23.4
21.9
25.8
18.4
28.2
14.8
30.6
10.9
32.8
P
P
g
p2 p
(°С)
38.3
30.8
34.0
32.2
29.5
33.6
25.0
35.0
20.4
36.2
15.5
37.2
– heat power of the unit
P
g
Q
– air consumption
p
Q
w
(m³/h) (kW) (kPa)
0.8
3.0
0.7
2.4
0.6
1.8
0.5
1.3
0.4
0.8
0.3
0.4
Q
w
(m³/h) (kW) (kPa)
1.3
5.5
1.4
4.4
1.0
3.4
0.8
2.4
0.7
1.6
0.5
1.0
Q
w
(m³/h) (kW) (kPa)
1.7
7.1
1.5
5.7
1.3
4.4
1.1
3.3
0.9
2.2
0.7
1.4
Page 9
7. INSTALLATION
Installation of air heater PROTON EX
Wall mounting Ceiling mounting Distance from a wall, min. Mounting height
Distance of air stream
0,25 m
3-8 m
up to 28 m
Distance from a ceiling, min. Mounting height
* *
0,25 m
4-12 m
3-8 m
28 m
*
directing louvers are installed under angle of 45
*
Ways of installation with mounting console
4-12 m
*
*
*
15 m
directing louvers are installed vertically
**
directing louvers are installed symmetrically under
***
angle of 45
30
45
On a wall vertically or horizontally, and under angle of 30° or 45°.
Under a ceiling horizontally,
30
45
or under angle of 30° or 45°.
9
Page 10
7. INSTALLATION
Монтаж аппарата PROTON E 15
Recommended distances from walls and ceiling Manifold of a heat exchanger
0,25 m
min
min 0,5 m
min
min 0,5 m
0,25 m
min 0,5 m
When connecting the heat medium pay your attention that manifolds of the air heater must be fixed.
For this use two keys: one – for Noncompliance with the minimal distance (0,25 m) from a wall or ceiling will lead to wrong operation of the air heater which, in turn, will influence the useful life of the equipment.
fixing heat exchanger manifolds,
the second – for connecting it to
the system.
Монтаж аппарата PROTON E 15Installation of a few units Recommendations of placing units
12-15 m
5-9 m
27-35 m
When mounting a few air heaters PROTON it is recommended to stick to the following distances between units: installation in one line – 5-9 m, installation opposite to each other – 27-35 m, installation one by one – 12-15 m. These distances are just recommendations. The installer should also take into account dimensions and shape of a building, its encumbering, and recommendations of specialists on a project.
10
Examples of placing the equipment which provide even distribution of heat in a building are presented on the illustrations.
Page 11
8. CONNECTION OF HEAT MEDIUM
Piping unit heaters PROTON ЕX
Air outtake Ball cock
Ball cock
0,003
PROTON EX
Outlet pipeline
Inlet pipeline
Drain
Coarse filter
Air heating units can be installed in closed heating systems with forced circulation with maximal temperature of the heat medium 130 °C and maximal pressure 1,6 MPa.
When connecting to the heating main pipes it is necessary to provide the following conditions:
Installation of the air heater should be carried out referring to the minimal distances from walls,
1. ceiling and floor.
2.
The air heater has to be completed with intercepting cocks on the inlet and outlet pipes.
3.
It is recommended to install a coarse filter on the inlet pipe.
4.
Provide at least one cock for heat medium drainage on the bottom point on the piping scheme of the air heater.
5.
Provide at least one air outtake on the upper point on the piping scheme of the air heater.
6.
The diameter of pipes should be selected in accordance with hydraulic calculations of the heat supply system.
7.
Heating tubes from the heating system pipe to the air heater must be installed with the pitch of 3° to the pipes the heat supply system.
8.
All cable trays for wiring a fan should be installed higher than pipes of the heating system.
9.
Installation must be done by technician/company who has appropriate permissions for performing such a type of work.
11
Page 12
9. CONTROL ELEMENTS
ECOMATIC PRO
ECOMATIC PRO is a control element with help of which advantages of heating and ventilation systems become more noticeable and perceivable as its use provide comfortable inside temperature and significant energy
of climatic conditions in a room. Using PROTON PRO you increase equipment lifetime protecting it from functioning under alarm mode.
STD EX Control board
Control board ECOMATIC STD EX is a board in which automatic switch, a thermistor relay of motor protection, and a “dry contact” of firefighting device are mounted. The board protects a motor from alarms, controls temperature of cable windings. It is a mandatory element for air heaters PROTON EX.
Three-phase construction. Control over motor temperature. Protection device against shunt fault. Connection to «dry contacts» of fireproof main.
DS 2M Сontrol device
The device regulates three-phase motor of a fan by turning on/o from an external thermostat and regulating rotations through recommutation of windings according to the scheme “delta” and “star” with help of a manual switch.
Possibility of smooth star-up (start - basing on “star”, operation - basing on “delta”). Possibility to regulate a group of air heaters. Simple and reliable construction. Dustproof and moisture resistance. Remote control of turn on/o of motor.
savings due to fast response of the system to changes
RD Programmable thermostat
Programmable chrono-thermostat with high accuracy controls set temperature in a room, enables to program operation of air heaters PROTON in the modes “day-night” and “7-day calendar”.
Programmability of working cycles of the air heating system. Available and eective solution. Convenient interface and soft light. Ability to connect external temperature sensor.
NTC 65 External thermal sensor
The sensor is designed to fix temperature in a room and transfer data to a controller. The sensors have IP65 construction, that allows to apply them in industrial buildings (dusty, moist, explosive environments).
High accuracy. Ability to connect a group of large buildings. Ability to use in explosive buildings.
12
Page 13
10. WIRING CONTROL ELEMENTS
DS 2M
Heated building
Three-phase AC-motor
2
W
1
NTC65
PETP TP V2V1U2U1W
2L3
PE PE
L
L
1
STD EX
N PE2 4 6
X1:4 X1:3
«Dry contact» of
fire-proof main
X1:2 X1:1
N PE1 3 5
B4B4B
4
N PE
L
1L2L3
3~400 В/50 Гц
Provide installation of a device protecting the motor from shunt fault (B on the scheme).
4
While wiring, control the direction of fan rotation. It is necessary to swap two supply phases in case of its reverse direction of rotation.
Connect a «dry contact» of fireproof main.
U
V
1
U
V
W
1
1W2
N 2 3 41
2
2
RD
11 10 9 8 7 6 5
It is necessary to remove jumpers between fan terminals while installing control device DS 2M.
It is necessary to provide motor protection against overheat, so wire TP contacts to a device, which controls power.
13
Page 14
11. REFERENCE INFORMATION
11.1 Table of pressure calculation on a wire depending on its section
Material of the conductor – copper:
Material of the conductor – copper
Section of current
conducting core, mm
1.5
2.5
4.0
6.0
10.0
16.0
25.0
35.0
50.0
70.0
95.0
120.0
Material of the conductor – aluminum:
2
Current, A
19.0
27.0
38.0
46.0
70.0
85.0
115.0
135.0
175.0
215.0
260.0
300.0
Voltage, 220 V
Power, kW
4.1
5.9
8.3
10.1
15.4
18.7
25.3
29.7
38.5
47.3
57.2
66.0
Voltage, 380 V
Current, A
16.0
25.0
30.0
40.0
50.0
75.0
90.0
115.0
145.0
180.0
220.0
260.0
Power, kW
10.5
16.5
19.8
26.4
33.0
49.5
59.4
75.9
95.7
118.8
145.2
171.6
Material of the conductor – aluminum
Section of current
conducting core, mm
2.5
4.0
6.0
10.0
16.0
25.0
35.0
50.0
70.0
95.0
120.0
Data is presented as a reference. For calculations for actual projects address to specialists.
2
Voltage, 220 V
Current, A
20.0
28.0
36.0
50.0
60.0
85.0
100.0
135.0
165.0
200.0
230.0
Power, kW
4.4
6.1
7.9
11.0
13.2
18.7
22.0
29.7
36.3
44.0
50.6
Voltage, 380 V
Current, A
19.0
23.0
30.0
39.0
55.0
70.0
85.0
110.0
140.0
170.0
200.0
Power, kW
11.6
15.1
19.8
25.7
36.3
46.2
56.1
72.6
92.4
112.2
132.0
14
Page 15
11. REFERENCE INFORMATION
11.2 Recommended diameters of pipes depending on power of equipment’s
heat output
kW Water consumption Inside diameter Type
15 kW
23 kW
39 kW
61 kW
96 kW
180 kW
0.6 m³/h
1.0 m³/h
1.6 m³/h
2.5 m³/h
4.0 m³/h
8.0 m³/h
20 mm
25 mm
32 mm
40 mm
50 mm
70 mm
3/4
1
1
1
1
1
2
1
2
4
2
2
Data is presented as a reference. For calculations for actual projects address to specialists.
15
Page 16
Service department
In case of any failures in operation of equipment address the authorized support centers of the Manufacturer. For information about support centers and procedure of claim submission contact Manufacturer’s service department:
PROTON GROUP LLC 03680, Ukraine, Kyiv, 3, Nesterova str. Tel.: +380 (44) 537 0930 Fax: +380 (44) 537 0903 E-mail: service@proton.kiev.ua www.protongroup.org
www.protongroup.org
Loading...