PROTEK PAC-130, PAC-240, PAC-95 Datasheet

PAC-95
05186
. . . engineered solutions for the transient environment™
AC POWER LINE TVS COMPONENT
APPLICATIONS
AC Power MainsModule Lightning Protection
IEC COMPATIBILITY (EN61000-4)
61000-4-5 (Power): 8/20µs - 1kA, L4 (Line-Line), 333A, L4 (Line-Ground)
FEATURES
4784 to 6920 Kilowatts Peak Pulse Power per Line (8/20µs)Glass Passivated ChipBidirectional ConfigurationEasy Mounting to Printed Circuit BoardsAvailable in Voltage Types Ranging From: 90V to 240VAC
MECHANICAL CHARACTERISTICS
thru
PAC-240
RADIAL LEADS
Epoxy CaseWeight 7.2 - 11.3 grams (Approximate)Flammability Rating UL 94V-0Marking: Logo & Device Marking Code
90V 120V 240V
APPLICATION
AC POWER LINE PROTECTION
AC
AC
AC
05186.R0 1/03
1
www.protekdevices.com
DEVICE CHARACTERISTICS
MAXIMUM RATINGS @ 25°C Unless Otherwise Specified
PAC-95
thru
PAC-240
PARAMETER Peak Pulse Power Dissipation (tp =8/20µs) - See Fig. 1 Storage Temperature Operating Temperature
ELECTRICAL CHARACTERISTICS
PA RT
NUMBER
VOLTS AC
PAC-95 PAC-130 PAC-240
RATED
STAND-OFF
VOLTAGE
V
WM
95 130 240
V
WM
VOLTS DC
135 202 380
BREAKDOWN
VOLTAGE
MIN V
(BR)
VOLTS DC
157 214 400
SYMBOL VALUE
PP
T
STG
J
MAXIMUM
LEAKAGE
CURRENT
@V @I mA
1 1 1
T
I
µA
20 20 20
WM
D
4784 & 6920P
-40 to +125
-40 to +125
MAXIMUM
CLAMPING
VOLTAGE
@ 8/20µs
VC @ I
299V @ 16kA 378V @ 16kA 692V @ 10kA
UNITS
kilowatts
0
C
0
CT
TEMPERATURE
COEFFICIENT
OF V
(BR)
θV
(BR)
PP
%/°C
0.1
0.1
0.1
2 www.protekdevices.com05186.R0 1/03