5
6. Slide the Microwave Electronic Assembly back into
the housing, pulling the excess wire out of the rear
of the housing. Tighten the four-faceplate screws
uniformly to obtain a weather seal between the front
bezel and the housing gasket.
7. Make sure the
tamper switch actuator arm is fully
depressed when it contacts the rear of the housing
for a NORMALLY CLOSED contact on terminals
8 and 9.
8.
In most installations, it is best to aim the sensor at
a slightly downward angle as this minimizes the
small “dead zone” directly beneath the sensor. is
also helps to terminate the sensor’s protection
pattern within the protected area.
9. Apply power (8.5 to 20 VDC) to terminals 2(-)
and 3 (+) and allow at least 1 minute of
stabilization time before walk testing.
10. Check the LED On/Off Switch to verify that it is
in the “ON” position. e LED On/Off Switch
controls the “Walk Test” LED’s and the Voltage
OK LED.
11. Observe the Green Voltage OK LED on the
printed circuit board to verify that it is “ON”. e
Voltage OK LED will TURN ON continuously
when the input voltage reaches 10.5 VDC and will
TURN OFF when the input voltage drops below
9.5 VDC.
6
SENSOR ADJUSTMENTS
e key to success in many applications is the
proper adjustment of the sensor’s Range Control
Switch, Sensitivity Control Switch and Bird/Animal
Control Switch. Note: Refer to diagram on Pages
13 and 14 for detail.
RANGE CONTROL SWITCH
e Range Control Switch adjusts the overall
size of the sensor’s detection area. It may be necessary
to set the sensor at the higher settings (70, 80, 90
and 100 percent of maximum) to attain the desired
protection pattern coverage.
Note: Although the sensor can be set at
maximum range and operate properly, the “rule of
thumb” is to set at the lowest setting to attain the
desired range.
SENSITIVITY CONTROL SWITCH
The Sensitivity Control Switch adjusts the
amount of movement required for an alarm condition.
e Sensitivity Control Switch is very precise as the
PIRAMID XL2 can determine the exact “distance
in inches (cm.)” that an object must move to initiate
an alarm. e following table shows the amount of
movement required based on the switch setting.
WALK-TESTING
1. e Analytic Walk Test LED’s are very difficult
to see in bright sunlight. erefore, PROTECH
highly recommends that the XL-SOUNDER
Audible Tester be utilized for sensor walk-test.
e XL-SOUNDER will enable a single installer
to walk-test the sensor and will greatly reduce
installation time!
HELPFUL HINTS FOR WALK TESTING
2. It is best to start with range and sensitivity settings
at maximum. Loosen swivel locking screw just
enough so that the sensor will be held in place but
can be aimed slightly upward and downward in
approximately 1 degree increments. It is best to locate
the IR protection pattern first. e IR sensor portion
is most sensitive to movement across the pattern and
therefore walk testing should entail taking a few
steps across (transverse) the area at the maximum
desired range. Once the desired IR protection
pattern is located, tighten the swivel-locking
screw to lock the sensor in place. e microwave
protection pattern overlaps the passive infrared
pattern and should be present.
Now that the proper sensor alignment is locked
in place, try to reduce the sensitivity first. e lower
the setting, the better the false alarm rejection.
Next, try to reduce range. e “Rule of thumb” is to
adjust the sensor’s range and sensitivity to the lowest
possible settings to attain the desired coverage.
IMPORTANT: e most critical adjustment
for false alarm rejection is the SENSITIVITY
CONTROL. Settings of 1, 2, 3, and 4 are best
for false-alarm-free performance.