OPERATING MANUAL
1. SAFETY SUMMARY
The symbols below are used on the equipment and throughout this document to draw the user’s attention to
important operational and safety information.
CAUTION or WARNING:
Read complete instructions prior to installation
and operation of the unit.
CAUTION or WARNING:
Electrical Shock Hazard
All safety related instructions that appear in t he manual must be observed to ensure personal safety and to
prevent damage to either the instrument or the syst em. If the instrument is used in a manner not specified by
the manufacturer, the protection provided by the equipment may be impaired.
2. INSTALLATION
The controller should be installed in a panel cut out as specified in item 2. First remove the mounting cl amp
and insert the controller into th e panel cut out. Place the unit into the panel cut-out and slide the mounting
clamps from the rear to a firm grip at the panel.
The internal circuitry can be fully removed from the ho using without disconnecting any wiring. Grab firmly the
front panel and pull out the circuitry from the housing.
2.1 ELECTRICAL CO NNECTIONS
All electrical connections are made to the screw terminals at the rear of the controller. They accept wire sizes
from 0.5 to 1.5 mm2 (16 to 22 AWG). The terminals should be tightened to a torque of 0.4 Nm (3.5 lb in).
The installation must include a power isolatin g switch or circuit breaker that disconnects all c urrent carrying
conductors. T he device s hould be m ounted close to the controller, within easy reach of the operator and
marked as the disconnecting device for the instrument.
Figure 1 shows the electrical terminals of the controller.
Figure 1 - Back panel terminals
3. SPECIFICATIONS
• Dimensions: 48 x 48 x 110 mm (1/16 DIN). Panel cut-out: 45,5 x 45,5 mm. Weight: 160 g (max);
• Power: 100 to 240 Vac/dc (±10 %), 50/60 Hz or 24 Vdc/ac (±10 %); Max. Consumption: 9 VA;
• Pt100: α= 385. 3-wire connection. Excitation current: 0.170 mA;
• Accuracy: 0.2 % of full scale for Pt100 and 0.25 % of full scale ±1 °C for T /C
• Thermocouple input impedance: 10 MΩ
• A/D converter resolution: 15000 steps
• Sampling rate: 10 measurements per second
• Environmental conditions: 5 to 50 °C; Relative humidity (maximum): 80 % up to 30 ºC. For temperatures
above 30 ºC, decrease 3 % per ºC. Installation category II. Pollution degree 2. Altitude < 2000 m.
• Front Panel: Polycarbonate UL94 V-2; Back Panel: ABS + PC UL94 V-0
• EMC: EN 61326-1:1997 and EN 61326-1/A1:1998
• SAFETY: EN61010-1:1993 and EN61010-1/A2:1995
3.1 TEMPERATURE SENSOR INPUT
Thermocouples are connected to terminals 10 and 11 with positive in terminal 11. Pt100 sensors are
connected to terminals 10, 11 and 12, as indicated in figure 1. For full compensation of cable resistance only
cables with equ al wire electrical resist ance should be used. Table 1 shows the sensor types accepted and
their respective codes.
TIPO CÓDIGO FAIXA
J
0000
-50 to 760 °C (-58 to 1400 °F)
K 1111 -90 to 1370 °C (-130 to 2498 °F)
S
2222
0 to 1760 °C (32 to 3200 °F)
Pt100 (Resolution 0,1°C)
3333
-199.9 to 530.0 °C (-199.9 to 986.0 °F)
Pt100 (Resolution 1°C)
4444
-200 to 530 °C (-328 to 986 °F)
T
5555
-100 to 400 °C (-148 to 752 °F)
E 6666 -30 to 720 °C (-22 to 1328 °F)
N
7777
-90 to 1300 °C (-130 to 2372 °F)
R
8888
0 to 1760 °C (32 to 3200 °F)
Table 1 - Sensor types, codes and ranges
3.2 POWER
Mains p ower is connected to terminals 1 and 2. Check the up per side of t he housing for proper power
indication.
3.3 CONTROL AND ALARM OUTPUTS
Up to 4 outputs can be co nfigured for control or alarm. The availabl e outputs are identified on the rear panel
as OUTA, OUTB, OUTC or OUTD. Electrical characteristics of each output are:
OUTA: SPST Relay, 1,5 A / 250 Vac (3 A / 30 Vdc); Resistive load; 100 k cycles;
OUTB: Voltage Pulse, 5 Vdc / 20 mA;
OUTC: SPST Relay, 1,5 A / 250 Vac (3 A / 30 Vdc); Resistive load; 100 k cycles;
OUTD: SPDT Relay, 3 A / 250 Vac (3 A / 30 Vdc); Resistive load; 6 k cycles;
or 4-20 mA output. With 80 count resolution, precision: 0,25 mA, maximum load: 500 Ohms.
The output function is defined on controller configuration, parameters IO A
IO AIO A
IO A, IO B
IO BIO B
IO B, IO (
IO (IO (
IO ( and IO d.
IO d.IO d.
IO d.
Control Output is used to control the process variable using PID algorithm. More than one output can be
selected as control output. When O UTD is configured as Analog Control Output, all other outputs selected
as Control Output will not operate.
Control Outputs are turned off when a sensor error is detected (display “ Erro
ErroErro
Erro”).
Alarm Outputs are used to signal abnormal PV values, sensor error or end of program. The alarm function
must be selected for each alarm output. (Refer to chapter 9).
4. CONFIGURATION AND OPERATION
Prior t o first operation the controller should be fully configured. The user must set basic parameters as
temperature type (“TYPE
TYPETYPE
TYPE”), the desired control set point (“ SP
SPSP
SP “), the alarms set points (“SPA1
SPA1SPA1
SPA1” and
“SPA2
SPA2SPA2
SPA2”), etc.
4.1 PARAMET ERS FLOW CHART
The programming parameters are organized in 4 different sets or levels
Operation level / Alarms and tuning level / Configuration level / Cal ibration level
At power up the controller displays a prompt a t the Operation Level and remains in this level while under
normal operation.
The other levels are on ly accessed when a change of parameters is necessary (except for Set Point
change). To reach these other parameters the user must keep the PROG Key (
key to go to next prompt or if the keyboard is left inactive for 20 seconds.
4.2 PROGRAM SE CURITY
To avoid t ampering, parameter “P rot
ProtProt
Prot” and a hardware j umper can be us ed to disable access to
programming parameters.
With the jumper in the O FF position, all program levels are unprotected. The “Prot
ProtProt
Prot” parameter can only b e
changed with the jumper in the OFF position.
With the jumper in the ON position or removed, the protection level is defined by the current value of t he
“Prot
ProtProt
Prot” parameter:
0000 No protection. All parameters can be accessed;
1111 No access to the calibration level;
2222 No access to calibration and configuration levels;
3333 No access to calibration, configuration and tuning and alarms levels;
4444 No access to calibration, configuration, tuning and alarms and operation (except SP) levels;
5555 Fully blocked.
Figure 2 – Protection Disabled Figure 3 – Protection Enabled
4.3 OPERATIO N LEVEL
TEMPERATURE
INDICATION
END
SP
TEMPERATURE measured by the sensor. At power up, the upper display shows the
process temperature value. It also shows the messages described in chapter 5 of this
manual. The lower displays shows the set point value which is the temperature value
desired for the process.
rAte
TEMPERATURE RATE
OF RISE: The user defines the rate of temperature rise from the
starting temperature to the value set in “ SP
SPSP
SP ”. Rate is defined in °C / minute.
T Sp
TIME FOR SOAK: Time in minutes which the temperature will remain at the selected “
SP
SPSP
SP “. Refer to item 4.
Rvn
run
RUN: At this prompt the user sets the control output and alarms t o active or to inactive.
0000 - inactive outputs; 1111 - active outputs;
4.4 TUNING AND ALARMS LEVEL
Atvn
AUTO-TUNE: Activates the auto-tuning of PID parameters.
0000 - Auto-tune is off; 1111 - Auto-tune is on;
Pb
Proportional band
PROPORTIONAL BAND: percentage of maximum input span.
When set to zero (0), control action is ON/OFF.
Ir
integral rate
INTEGRAL RATE: Integral time constant in repetitions per m inute (Reset). This
constant is not used when controller is set to ON/OFF action (Pb=0).
Dt
derivative time
DERIVATIVE TIME: Derivative time constant in seconds. This constant is not used
when controller is set to ON/OFF action (Pb=0).
(t
Cycle time
CYCLE TIME: Pulse Width Modulation (PWM) period in seconds. T his term is not
used when controller is set to ON/OFF action (Pb=0).
KySt
HYSteresis
CONTROL HYS TERESIS: Is the hysteresis for O N/OFF control (set in temperature
units). This parameter is only used when the controller is in ON/OF F mode (Pb=0).
A1SP
A2SP
SP Alarm
SETPOINT for Alarm 1/2: Triping point for alarm 1/2.