Prosensor N480D Operating Manual

Page 1
MICROPROCESSOR BASED TEMPERATURE CONTROLLER
N480D
1. SAFETY SUMMARY
The symbols below are used on the equipment and throughout this document to draw the user’s attention to important operational and safety information.
CAUTION or WARNING:
Read complete instructions prior to installation
and operation of the unit.
CAUTION or WARNING:
Electrical Shock Hazard
All safety related instructions that appear in t he manual must be observed to ensure personal safety and to prevent damage to either the instrument or the syst em. If the instrument is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
2. INSTALLATION
The controller should be installed in a panel cut out as specified in item 2. First remove the mounting cl amp and insert the controller into th e panel cut out. Place the unit into the panel cut-out and slide the mounting clamps from the rear to a firm grip at the panel.
The internal circuitry can be fully removed from the ho using without disconnecting any wiring. Grab firmly the front panel and pull out the circuitry from the housing.
2.1 ELECTRICAL CO NNECTIONS
All electrical connections are made to the screw terminals at the rear of the controller. They accept wire sizes from 0.5 to 1.5 mm2 (16 to 22 AWG). The terminals should be tightened to a torque of 0.4 Nm (3.5 lb in).
The installation must include a power isolatin g switch or circuit breaker that disconnects all c urrent carrying conductors. T he device s hould be m ounted close to the controller, within easy reach of the operator and marked as the disconnecting device for the instrument.
Figure 1 shows the electrical terminals of the controller.
Figure 1 - Back panel terminals
3. SPECIFICATIONS
Dimensions: 48 x 48 x 110 mm (1/16 DIN). Panel cut-out: 45,5 x 45,5 mm. Weight: 160 g (max);
Power: 100 to 240 Vac/dc (±10 %), 50/60 Hz or 24 Vdc/ac (±10 %); Max. Consumption: 9 VA;
Pt100: α= 385. 3-wire connection. Excitation current: 0.170 mA;
Accuracy: 0.2 % of full scale for Pt100 and 0.25 % of full scale ±1 °C for T /C
• Thermocouple input impedance: 10 MΩ
A/D converter resolution: 15000 steps
Sampling rate: 10 measurements per second
Environmental conditions: 5 to 50 °C; Relative humidity (maximum): 80 % up to 30 ºC. For temperatures
above 30 ºC, decrease 3 % per ºC. Installation category II. Pollution degree 2. Altitude < 2000 m.
Front Panel: Polycarbonate UL94 V-2; Back Panel: ABS + PC UL94 V-0
EMC: EN 61326-1:1997 and EN 61326-1/A1:1998
SAFETY: EN61010-1:1993 and EN61010-1/A2:1995
3.1 TEMPERATURE SENSOR INPUT
Thermocouples are connected to terminals 10 and 11 with positive in terminal 11. Pt100 sensors are connected to terminals 10, 11 and 12, as indicated in figure 1. For full compensation of cable resistance only cables with equ al wire electrical resist ance should be used. Table 1 shows the sensor types accepted and their respective codes.
TIPO CÓDIGO FAIXA
J
0000
-50 to 760 °C (-58 to 1400 °F)
K 1111 -90 to 1370 °C (-130 to 2498 °F)
S
2222
0 to 1760 °C (32 to 3200 °F)
Pt100 (Resolution 0,1°C)
3333
-199.9 to 530.0 °C (-199.9 to 986.0 °F)
Pt100 (Resolution 1°C)
4444
-200 to 530 °C (-328 to 986 °F)
T
5555
-100 to 400 °C (-148 to 752 °F)
E 6666 -30 to 720 °C (-22 to 1328 °F)
N
7777
-90 to 1300 °C (-130 to 2372 °F)
R
8888
0 to 1760 °C (32 to 3200 °F)
Table 1 - Sensor types, codes and ranges
3.2 POWER
Mains p ower is connected to terminals 1 and 2. Check the up per side of t he housing for proper power indication.
3.3 CONTROL AND ALARM OUTPUTS
Up to 4 outputs can be co nfigured for control or alarm. The availabl e outputs are identified on the rear panel as OUTA, OUTB, OUTC or OUTD. Electrical characteristics of each output are:
OUTA: SPST Relay, 1,5 A / 250 Vac (3 A / 30 Vdc); Resistive load; 100 k cycles;
OUTB: Voltage Pulse, 5 Vdc / 20 mA;
OUTC: SPST Relay, 1,5 A / 250 Vac (3 A / 30 Vdc); Resistive load; 100 k cycles;
OUTD: SPDT Relay, 3 A / 250 Vac (3 A / 30 Vdc); Resistive load; 6 k cycles;
or 4-20 mA output. With 80 count resolution, precision: 0,25 mA, maximum load: 500 Ohms.
The output function is defined on controller configuration, parameters IO A
IO AIO A
IO A, IO B
IO BIO B
IO B, IO (
IO (IO (
IO ( and IO d.
IO d.IO d.
IO d.
Control Output is used to control the process variable using PID algorithm. More than one output can be selected as control output. When O UTD is configured as Analog Control Output, all other outputs selected as Control Output will not operate.
Control Outputs are turned off when a sensor error is detected (display “ Erro
ErroErro
Erro”).
Alarm Outputs are used to signal abnormal PV values, sensor error or end of program. The alarm function must be selected for each alarm output. (Refer to chapter 9).
4. CONFIGURATION AND OPERATION
Prior t o first operation the controller should be fully configured. The user must set basic parameters as temperature type (“TYPE
TYPETYPE
TYPE”), the desired control set point (“ SP
SPSP
SP “), the alarms set points (“SPA1
SPA1SPA1
SPA1” and
SPA2
SPA2SPA2
SPA2”), etc.
4.1 PARAMET ERS FLOW CHART
The programming parameters are organized in 4 different sets or levels
Operation level / Alarms and tuning level / Configuration level / Cal ibration level
At power up the controller displays a prompt a t the Operation Level and remains in this level while under normal operation.
The other levels are on ly accessed when a change of parameters is necessary (except for Set Point change). To reach these other parameters the user must keep the PROG Key (
P
) pressed for about
three seconds. After this time the controller will show the first parameter of the next level. By keeping the
P
key pressed for another 3 seconds the next level will be accessed.
Release the
P
key when the desired level is reached. Press once the
P
to go to the next prompt in the same level. When a parameter is shown the display will alternate its name and value. The value can t hen be changed by pressing the
or
key.
After the last parameter in one level is reached the controller returns to operation level and the display will indicate the measured temperature.
The display will also go back to the measured temperature w henever the display is inactive for 20 seconds or more. When a parameter value is chan ged via keyboard the controller will only accept the new value af ter the user presses the
P
key to go to next prompt or if the keyboard is left inactive for 20 seconds.
4.2 PROGRAM SE CURITY
To avoid t ampering, parameter “P rot
ProtProt
Prot” and a hardware j umper can be us ed to disable access to
programming parameters. With the jumper in the O FF position, all program levels are unprotected. The “Prot
ProtProt
Prot” parameter can only b e
changed with the jumper in the OFF position. With the jumper in the ON position or removed, the protection level is defined by the current value of t he
Prot
ProtProt
Prot” parameter:
0000 No protection. All parameters can be accessed;
1111 No access to the calibration level;
2222 No access to calibration and configuration levels;
3333 No access to calibration, configuration and tuning and alarms levels;
4444 No access to calibration, configuration, tuning and alarms and operation (except SP) levels;
5555 Fully blocked.
OFF
ON
Figure 2 – Protection Disabled Figure 3 – Protection Enabled
4.3 OPERATIO N LEVEL
TEMPERATURE
INDICATION
END
SP
TEMPERATURE measured by the sensor. At power up, the upper display shows the process temperature value. It also shows the messages described in chapter 5 of this manual. The lower displays shows the set point value which is the temperature value desired for the process.
rAte
TEMPERATURE RATE
OF RISE: The user defines the rate of temperature rise from the
starting temperature to the value set in “ SP
SPSP
SP ”. Rate is defined in °C / minute.
T Sp
TIME FOR SOAK: Time in minutes which the temperature will remain at the selected “
SP
SPSP
SP “. Refer to item 4.
Rvn
run
RUN: At this prompt the user sets the control output and alarms t o active or to inactive.
0000 - inactive outputs; 1111 - active outputs;
4.4 TUNING AND ALARMS LEVEL
Atvn
AUTO-TUNE: Activates the auto-tuning of PID parameters.
0000 - Auto-tune is off; 1111 - Auto-tune is on;
Pb
Proportional band
PROPORTIONAL BAND: percentage of maximum input span.
When set to zero (0), control action is ON/OFF.
Ir
integral rate
INTEGRAL RATE: Integral time constant in repetitions per m inute (Reset). This constant is not used when controller is set to ON/OFF action (Pb=0).
Dt
derivative time
DERIVATIVE TIME: Derivative time constant in seconds. This constant is not used when controller is set to ON/OFF action (Pb=0).
(t
Cycle time
CYCLE TIME: Pulse Width Modulation (PWM) period in seconds. T his term is not used when controller is set to ON/OFF action (Pb=0).
KySt
HYSteresis
CONTROL HYS TERESIS: Is the hysteresis for O N/OFF control (set in temperature units). This parameter is only used when the controller is in ON/OF F mode (Pb=0).
A1SP A2SP
SP Alarm
SETPOINT for Alarm 1/2: Triping point for alarm 1/2.
Page 2
4.5 CO NFIGURATION LEVEL
Type
tYPE
INPUT TYPE: Selects the input sensor type to be connected to the cont roller. This is
the first parameter to be set.
0000 - Thermocouple type J; 5555 - Thermocouple type T; 1111 - Thermocouple type K; 6666 - Thermocouple type E; 2222 – Thermocouple type S; 7777 - Thermocouple type N; 3333 - Pt100 with 0,1° resolution; 8888 - Thermocouple type R; 4444 - Pt100 with resolution;
Vnit
unit
TEMPERATURE UNIT: Selects display indication for degrees Celsius or Fahrenheit.
0000 - degrees Celsius ( °C ); 1111 - degrees Fahrenheit ( °F );
A(t
ACtion
CONTROL ACTION: 0000 - reverse action. Generally used for heating.
1111 - direct action. Generally used for cooling.
Io A
Out A
OUTA FUNCTION: 0000 - OUTA is control output.
1111 - OUTA is Alarm 1 output.
2222 - OUTA is Alarm 2 output.
Io b
Out B
OUTB FUNCTION: 0000 - OUTB is control output.
1111 - OUTB is Alarm 1 output.
2222 - OUTB is Alarm 2 output.
Io (
Out C
OUTC FUNCTION: 0000 - OUTC is control output.
1111 - OUTC is Alarm 1 output.
2222 - OUTC is Alarm 2 output.
Io d
Out D
OUTD FUNCTION: 0000 - OUTD is control output.
1111 - OUTD is Alarm 1 output.
2222 - OUTD is Alarm 2 output.
3333 - OUTD is Analog Control Output (4-20mA).
spll
SP Low Limit
SET POINT LOW LIMIT: sets the lower range for SV.
spKl
SP High Limit
SET POINT HIGH LIMIT: Sets the upper range for SV.
0ffs
OFF Set
SENSOR OFFSET: Offset value to be added to the PV to compensate sensor error.
Default value: zero.
A1fv A2fv
Alarm 1 Function
FUNCTION OF ALARM 1/2
: Refer to table 2 for funct ion description and respective
codes to set at this prompt.
Aiky A2ky
Alarm HYsteresis
ALARM 1 AND ALARM 2 HYSTERESIS: Defines the differential range between the
PV value at which the alarm is turned on and the value at which it is turned off .
Prot
Protection
PROGRAM SECURI TY: Defines the level of parameters protection from tampering.
Refer the chapter 4.2.
4.6 CALIBRATI ON LEVEL
These par ameters are used to calibrate the temperature measurement and should only be dealt with by experienced and well equipped personnel.
Inl(
Input Low Calibration
SENSOR OFFSET CALIBRATION. Set s the temperatur e sensor low calibration
(offset). The display sh ows only the corrected temperature and not the offset added. A s ignal simulator should be used to inject a low value signal to properly adjust the offset.
InK(
Input High Calibration
INPUT HIGH CALIBRATION. Sets the sensor input circuit gain or high
calibration. A signal simulator should be used to inject a high value signal to properly adjust the offset.
(j L
Cold Junction Low
Calibration
COLD JUNCTION OFFSET CALIBRATION: Sets the cold junction of fset
calibration. A good thermometer or a temperature simulator should be used to properly adjust this parameter.
Ovl(
output Low Calibration
OFFSET CALIBRATION OF ANALOG OUTPUT: Offset (zero) calibration of the analog control output (4-20 mA).
OvK(
output High Calibration
GAIN CALIBRATION OF ANALOG OUTPUT: Gain (span) calibration of the
analog control output (4-20 mA).
5. RAMP TO SOAK FUNCTION CHARACTERISTICS
This function makes the process temperature rise gradually from the starting point (present PV) to the temperature value set in “ SP
SPSP
SP “ (Ramp). The user defines the rate of rise in degrees per minute at the “rAtE
rAtErAtE
rAtE
prompt. When SP is reached the temperature is leveled at this point for 1 to 9999 minutes as programmed at the “ t SP
t SPt SP
t SP ” prompt. Setting 0 (zero) at “ t SP
t SPt SP
t SP ” defines an infinite length soak profile.
Soak
Temperature
PV
Ramp
Time
SP
Figure 2 - Ramp to Soak Function
To disable the ramp function Set 0.0 at the “rAtE
rAtErAtE
rAtE” prompt. To disable the s oak function set 1 at the “ t SP
t SPt SP
t SP
” prompt (thus making a 1 m inute soak) and the control output will go off in 1 minute. To restart control s et 1 at the “ rvn
rvnrvn
rvn ” prompt.
After a power failure the controller will resume r amp to soak execution at the equivalent previous ramp point. If the process temperature is th e same as th e SP (no t emperature drop) the controller will repeat the soak segment.
6. PID AUTO TUNE
During auto tune the temperature is controlled in ON/OF F mode at the programmed Set Point (SV). Depending on the process ch aracteristics large oscillations above and below SV may occur and a uto tuning may take several minutes to be concluded.
The recommended procedure is as follows:
Program a new SP close to the desired final temperature other than the present measured temperature.
Enable the auto tune at the “Atvn
AtvnAtvn
Atvn” prompt by selecting 1.
Set 1 at the rvn
rvnrvn
rvn” prompt. The TUNE message will be signaled in the display.
During auto tune large oscillations will be induced around the set point. Make sure the proces s can accept these oscillations. If auto tuning results are not satisfactory refer to t able 3 for manual fine tuning procedure.
PARAMETER RESPONSE SOLUTION
Slow Response Decrease
Proportional
Band
Large Oscillation Increase
Slow Response Increase
Integral
Rate
Large Oscillation Decrease
Slow Response or Instability Decrease
Derivative
Time
Large Oscillation Increase
Table 3 - Suggestions for manual tuning of PID parameters
7. ALARM FUNCTIONS
Low and high alarms are used to signal minimum and maximum temperature values as pro grammed in the “SPA1
SPA1SPA1
SPA1” and “SPA2
SPA2SPA2
SPA2” prompts.
Differential alarms are used t o indicate deviations from the desired set point (SP) temperature. These deviations are programmed at the “SPA1
SPA1SPA1
SPA1” and “SPA2
SPA2SPA2
SPA2” prompts. Error alarm shows sensor defects or not
properly connected. Table 2 shows each alarm function operation wit h their respective code. Alarm 1 is used as an example.
7.1 ALARM INITIA L BLOCKING
The initial blocking option inhibits the alarm from being r ecognized if an alarm condition is present when the controller is first energized. The alarm will actuate only after the occurrence of a non alarm condition followed by a new occurrence for the alarm.
TYPE CODE ACTION
LOW
0000
SPA1
Alarm ON
TEMPERATURE
HIGH
1111
SPA1
Alarm ON
TEMPERATURE
SPA1
SPA1SPA1
SPA1
Negative
SP + SPA1 SP
Alarm
ON
TEMPERATURE
LOW
differential
2222
SPA1
SPA1SPA1
SPA1
Positive
SP + SPA1
SP
Alarm ON
TEMPERATURE
SPA1
SPA1SPA1
SPA1
Negative
SP + SPA1 SP
Alarm ON
TEMPERATURE
HIGH
differential
3333
SPA1
SPA1SPA1
SPA1
Positive
SP + SPA1
SP
Alarm
ON
TEMPERATURE
SPA1
SPA1SPA1
SPA1
Negative
SP - SPA1
SP + SPA1 SP
Alarm ON
TEMPERATURE
differential
or deviation
4444
SPA1
SPA1SPA1
SPA1
Positive
SP + SPA1
SP - SPA1 SP
Alarm
ON
Alarm
ON
TEMPERATURE
Input sensor
error or
heater break
detection
5555
Alarm is ON whenever:
Temperature is below/above sel ected range;
Thermocouple or Pt 100 is broken;
Pt100 is shorted; badly connecte d or wire impedance is too high;
The heater resistance is broken
End of
Program
6666
Activated when the programme d soak time is run out. Refer to item 4 of this manual.
7777
Low limit alarm disabled at power-up
8888
High limit alarm disabled at power-up
9999
Differential low limit alarm disabled at power-up
10
1010
10
Differential high limit alarm disabled at power-up
Alarm
Functions
With alarm
inhibition at
power-up
11
1111
11
Differential alarm disabled at power-up
Table 2 - Alarm functions and their identification codes
8. PROBLEMS WITH THE CONTROLLER
Connection and configuration errors state for most of the problems in using the contr oller. A final revision of parameters will save time and further losses.
Error messages are displayed to help the user to identify possible problems.
: Process temperature is below the selected sensor range.
: Process temperature is above the selected sensor range
: Controller or sensor error. Example: Broken thermocouple or Pt 100, Pt 100 badly
connected, short-circuited or high cable resistance.
5.1 GETTING THE INSTRUMENT SERIAL NUMBER
Upon power-on, the controller displays its firmware version for 3 s econds. The serial number is accessed when the controller is powered while holding the key
pressed.
9. PRODUCT IDENTIFICATION
The label attached to the controller case identifies the model an d the optional present in the product, as described below:
MODEL: N480D – A – B, where:
A: Outputs: RP (OUT A = Relay, OUT B = Pulse)
RPR (OUT A = Relay, OUT B = Pulse, OUT D = Relay) RRR (OUT A = Relay, OUT C = Relay, OUT D = Relay); RAR (OUT A = Relay, OUT C = Relay, OUT D = 4-20 mA )
B. Voltage rating: blank (100-240 Vac/dc) or 24V (24 Vac/dc);
Loading...