ProSense XTP-160-N40140F, XTP-260-N40140F, XTP-360-N40140F, XTP25N-030-N40140F, XTP25N-050-N40140F Installation Instructions

...
XTP product insert Rev. 2
71485817
XTP/XTPS Series Temperature Transmitter Probes and
RTD1/RTD1-S Series Temperature Sensors
Installation Instructions
®
(XTPS/RTD1-S)
XTP-160-N40140F XTP-260-N40140F XTP-360-N40140F XTP25N-030-N40140F XTP25N-050-N40140F XTP25N-100-N40140F XTP25N-150-N40140F XTP50N-030-N40140F XTP50N-050-N40140F XTP50N-100-N40140F XTP50N-150-N40140F XTP-160-0300F XTP-260-0300F XTP-360-0300F XTP25N-030-0300F XTP25N-050-0300F XTP25N-100-0300F XTP25N-150-0300F XTP50N-030-0300F XTP50N-050-0300F XTP50N-100-0300F XTP50N-150-0300F XTP-160-0100C XTP-260-0100C XTP-360-0100C XTP25N-030-0100C XTP25N-050-0100C XTP25N-100-0100C XTP25N-150-0100C XTP50N-030-0100C XTP50N-050-0100C XTP50N-100-0100C XTP50N-150-0100C XTPS15-030-0300F XTPS15-050-0300F XTPS15-100-0300F XTPS15-150-0300F
XTP product insert Rev. 2
-40 to 140°F (-40 to 60°C)
0 to 300°F (-17.8 to 148.9°C)
0 to 100°C (32 to 212°F)
0 to 300°F (-17.8 to 148.9°C) 1.5” Sanitary Tri-Clamp (3-A)
* Transmitter probes are factory configured and ready for use out of the box. If changes are desired,
transmitter probes can be re-configured. See Programming section of these instructions.
None, use compression fitting
1/4” male NPT
1/2” male NPT
None, use compression fitting
1/4” male NPT
1/2” male NPT
None, use compression fitting
1/4” male NPT
1/2” male NPT
160mm 260mm 360mm
30mm
50mm 100mm 150mm
30mm
50mm 100mm 150mm 160mm 260mm 360mm
30mm
50mm 100mm 150mm
30mm
50mm 100mm 150mm 160mm 260mm 360mm
30mm
50mm 100mm 150mm
30mm
50mm 100mm 150mm
30mm
50mm 100mm 150mm
4-20mA
XTP and XTPS Series ProSense Temperature Transmitter Probes
Part Number Measuring Range Process Connection Length Output
A Medium water at T = 50 °C (122 °F)
v (ft/s)
v (m/s)
RTD1-25N-030-H RTD1-25N-050-H RTD1-25N-100-H
1/4” male NPT
RTD1-25N-150-H RTD1-50N-030-H RTD1-50N-050-H RTD1-50N-100-H
-58 to 302 °F (-50 to 150 °C)
1/2” male NPT
RTD1-50N-150-H RTD1-S15-030-H RTD1-S15-050-H RTD1-S15-100-H
1.5” Sanitary Tri-Clamp (3-A)
RTD1-S15-150-H
Temperature limits
Max. Ambient
Temperature
Up to 77°F (25°C) 302°F (150°C) Up to 104°F (40°C) 275°F (135°C) Up to 140°F (60°C) 248°F (120°C) Up to 185°F (85°C) 212°F (100°C)
Max. Process
Temperature
Process pressure limits
With or without NPT process connection
• 1450 psig (100bar) maximum
Note: Working pressure when using
compression fitting should not exceed the fittings rated pressure.
With Sanitary Tri-clamp process connection
• 232 psig (16bar) maximum
XTP product insert Rev. 2
Maximum flow velocity based on insertion length
135
40
120
35
105
30
90
25
75
20
60
15
45
10
30
15
0
L Insertion length, during ow v Flow velocity
A
5
0
0306090120 150 180 210 240 270 300
012345 78 910
L (mm)
L (in)
30mm
50mm
100mm
150mm
30mm
50mm
100mm
150mm
30mm
50mm
100mm
150mm
6
RTD1 and RTD1-S Series ProSense Temperature Sensor Probes
RTD Pt100
Class A
3-wire
11
12
Installation
1 Safety Instructions
1.1 Designated use
• The device is a compact temperature transmitter probe for the acquisition and conversion of temperature input signals for industrial temperature measurement.
1.2 Installation, commissioning, operation
• The device must only be installed, connected and commissioned by qualified and authorized staff (e.g. electrical technicians) strictly adhering to the instructions contained in this manual, the applicable norms, legal regulations and certificates (depending on the application).
• These authorized staff members must have read and understood this manual and follow the instructions it contains.
• Damaged devices must not be put into operation and they must be labeled as defective.
1.3 Operational safety
• The device is safely built and tested according to state-of-the-art technology and has left the factory in perfect condition in regards to technical safety. The applicable regulations and European standards have been taken into account.
• Please observe the technical data on the nameplate!
• The device must only be powered by a power supply unit with a limited energy electric circuit in accordance with IEC 31010-1: “SELV or Class 2 circuit”.
• Due to its design, the device is not repairable. When later disposing of the device, please observe local regulations.
XTP product insert Rev. 2
A B
L
C
Pipe installation
• A: On angle brackets
• B: In smaller pipes, inclined
• C: Perpendicular to the direction of flow (hygienic installation 3° minimum inclination required for inlet to self drain)
• L = Insertion Length
1. For NPT and compression fittings, seal the process
connection with Teflon tape before you screw in the device.
2. Ensure that the hygienic process connection and any
connection adapters can withstand the maximum process pressure.
3. Install the device before the process
application is started.
Minimum insertion length
Lmin = 30mm (1.18 in)
C
L
Dimensions
Ø18.0
Ø50.4
Ø50.4
mm [inches]
[Ø0.71]
[Ø1.98]
[Ø1.98]
XTP
RTD
/
62.5
36.5
[2.46]
[1.44]
XTP25/RTD1-25N Series
NPT Units
Dimensions
A B
30mm [1.18 in] 101mm [3.98 in]
50mm [1.97 in] 121mm [4.76 in]
100mm [3.94 in] 171mm [6.73 in]
150mm [5.91 in] 221mm [8.70 in]
XTP product insert Rev. 2
XTP
RTD
/
60.1
36.5
[2.37]
[1.44]
XTP50/RTD1-50N Series
NPT Units
M12
62.0
[2.44]
B
A
Ø6.0
[Ø0.24]
XTP Series
Compression Units
Dimensions
A B
160mm [6.30 in] 222mm [8.74 in]
260mm [10.24 in] 322mm [12.67 in]
360mm [14.17 in] 422mm [16.61 in]
M12
66.0
[2.60]
B
A
Ø6.0
[Ø0.24]
XTPS Series
3-A Sanitary Units
Dimensions
A B
30mm [1.18 in] 96mm [3.78 in]
50mm [1.97 in] 116mm [4.57 in]
100mm [3.94 in] 166mm [6.54 in]
150mm [5.91 in] 216mm [8.50 in]
M12
44.0
[1.73]
B
A
Ø6.0
[Ø0.24]
RTD1-S15 Series
3-A Sanitary Units
Dimensions
A B
30mm [1.18 in] 74mm [2.91 in]
50mm [1.97 in] 94mm [3.70 in]
100mm [3.94 in] 144mm [5.67 in]
150mm [5.91 in] 194mm [7.64 in]
Wiring
Supply Voltage (VDC)
Hygienic applications: Electrical connection cables must comply with 3-A sanitary standard, must be smooth, corrosion resistant and cleanable.
XTP and XTPS Wiring (4-20 mA)
1 (BN) + 2 (WH) nc 3 (BU) ­4 (BK) nc
M12x1
4
3 0 V (4-20 mA)
Load Impedance
1086
Load ( )
Operating Region
35 V10 V
1
10...35 VDC (4-20 mA)
Note: Wiring colors are based on AutomationDirect
CD12L and CD12M 4-pole cable assemblies.
Sinking Load
3
+
Load
1
1
3
Sourcing Load
-
Load
- -
2
+
POWER SUPPLY
++
POWER
-
SUPPLY
XTP product insert Rev. 2
RLmax = (V
powersupply
-10V) / 0.023 A (current output)
e.g. (24V - 10V) / 0.023A = 608Ω
RTD1 Wiring (3-wire Pt100 RTD)
1 (BN) nc 2 (WH) + 3 (BU) ­4 (BK) -
1
N/C
2
3
4
To prevent damage to the device do not overtighten the M12 plug
XTPS Series
Programming (XTP and XTPS units only)
Transmitter probes are factory configured and ready for use out of the box. If changes are desired,
transmitter probes can be re-configured using the XT-SOFT programming software, available as a free download at www.automationdirect.com, an XT-USB configuration cable and an XT-M12 adapter (purchased separately).
Settable Parameters
Standard Settings
Expanded Settings
Service Functions
Measuring unit °C/°F Part number dependent Measuring range (start and end values) -50 to 150°C (-58 to 302°F) maximum range Part number dependent Fault condition reaction 3.6 mA or 21.0 mA 21mA Output 4-20 mA or 20-4 mA 4-20 mA Filter 0...8s 0s Offset -9.9 to +9.9°C (-17.8 to 17.8°F) 0.0 Measurement point identification/TAG 8 alpha-numeric digits Test Password (Release Code) 4 numeric digits 0000 Output simulation drives output to a
fixed value
on/off off
XT-SOFT PC Configuration Software
XT-USB Conguration Cable
XT-M12 Adapter
Note: XT-SOFT version 1.27.13.0 or later required for use with the XTP or XTPS series transmitters
Factory Settings
XTP product insert Rev. 2
71485817
XTP or
Powered from USB port