Pro Sense DPM3- E User Manual

TRMS
uSer Manual
TRMS
ProSenSe DPM3-e SerieS
Digital Panel Meter for
true rMS ac or Dc voltage
anD aMPerage electrical
inPut SignalS
Models:
User Manual - DPM3-E Series Electrical Panel Meters
C
US
In this Chapter...
General Information ......................................................................................................4
Package Contents .........................................................................................................4
Recycling Instructions ...................................................................................................4
General Safety Considerations ......................................................................................4
Symbols Identification ..................................................................................................4
Maintenance ................................................................................................................5
Technical Support ........................................................................................................5
Agency Approvals .........................................................................................................5
Device Description .........................................................................................................6
Dimensions and Mounting ............................................................................................7
Installation....................................................................................................................7
Wiring Terminals ............................................................................................................8
Wiring Examples ..........................................................................................................10
DC/AC Voltage Input Wiring (Ranges: 2, 20, 200, 600 V) ..........................................10
DC/AC Current Input Wiring (Ranges: 1A, 5A) ...........................................................10
DC/AC Current Input Wiring (Range: 200mA)............................................................10
DC/AC Current Input Wiring (Ranges: 50/60/100mV shunt) ......................................11
Display and Key Pad ....................................................................................................11
Configuration: ..............................................................................................................12
Programming numerical values ..................................................................................12
Input Configuration .....................................................................................................13
Display Configuration ..................................................................................................14
Scaling .......................................................................................................................14
Programming of the scale ..........................................................................................15
SCAL method .............................................................................................................15
tEACH method ...........................................................................................................15
Weighted Average Filter P ..........................................................................................15
Round ........................................................................................................................16
Brightness ..................................................................................................................16
Eco .............................................................................................................................16
Additional Functions ....................................................................................................16
MAX/MIN function.....................................................................................................16
2
U
R
L
DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
Configuration Lockout ................................................................................................17
Programming Mode ...................................................................................................17
Return to Factory Configuration .................................................................................17
Direct Access to Relay Setpoints .................................................................................17
Logic functions ...........................................................................................................17
Logic functions menu .................................................................................................18
Table of programmable functions ............................................................................... 19
Configuration Lock Out ...............................................................................................20
Lock-out menu diagram .............................................................................................21
Lock-out menu diagram continued ............................................................................22
Output Options ............................................................................................................23
Relay Configuration ....................................................................................................23
Description of Operation ............................................................................................23
Relay Configuration menu diagram ............................................................................24
Direct access to the relay setpoints value programming .............................................24
Analog output ............................................................................................................25
Analog output menu diagram ....................................................................................25
Technical Specifications ............................................................................................... 26
DPM3-E Electrical User Manual, 1st Edition
3
User Manual - DPM3-E Series Electrical Panel Meters

General Information

Package Contents

• DPM3-E Series True RMS Electrical Parameter digital panel meter
• Quick start guide
• Mounting panel accessories (a sealing gasket and 2 fixing clips)
• Wiring accessories (plug-in terminal block connectors and 2 key tools for wire insertion)
• 4 adhesive engineering unit label sheets

Recycling Instructions

This electronic instrument is covered by the 2002/96/CE European Directive so, it is properly marked with the cros]sed-out wheeled bin symbol that makes reference to the selective collection for electrical and electronic equipment which indicates that at the end of its lifetime, the final user cannot dispose of it as unsorted municipal waste.
In order to protect the environment and in agreement with the European legislation regarding waste of electrical and electronic equipment from products put on the market after August 13, 2005, the user can give it back, without any cost, to the place where it was acquired to proceed to its controlled treatment and recycling.

General Safety Considerations

All instructions and guidelines for the installation and manipulation that are present in this manual must be considered to ensure personal safety and to prevent damage to either the instrument or any equipment connected to it.
Safety of any equipment incorporated to this instrument is the responsibility of the system installer.
If this electronic indicator is used in a manner not specified by the manufacturer in this manual, the protection provided by the instrument may be impaired.

Symbols Identification

Warning: Potential risk of danger.
Read complete instructions when this symbol appears in order to know the potential risk and know how to avoid it.
Warning: Risk of electric shock.
Instrument protected by double isolation or reinforced isolation.
4
DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters

Maintenance

To ensure instrument accuracy, it is recommended to check its performance according to the technical specifications listed in this manual.
For front cover cleaning, just wipe with a damp cloth and neutral soap product. DO NOT USE
SOLVENTS!

Technical Support

We strive to make our manuals the best in the industry. We rely on your feedback to let us know if we are reaching our goal. If you cannot find the solution to your particular application, or, if for any reason you need technical assistance, please call us at:
1-800-633-0405
Our technical support group will work with you to answer your questions. They are available Monday through Friday from 9:00 A.M. to 6:00 P.M. Eastern Time. We also encourage you to visit our web site where you can find technical and non-technical information about our products and our company.
www.AutomationDirect.com

Agency Approvals

DPM3-E Electrical User Manual, 1st Edition
5
User Manual - DPM3-E Series Electrical Panel Meters

Device Description

The ProSense DPM3-E series offers a simple, feature packed digital display of True RMS AC or DC voltage or amperage electrical parameters. The 5-digit tri-color red, green or amber LED display is easily scaled into any engineering units from -19999 to 19999 with a selectable decimal point location. Two point direct or reverse acting linear scaling values can be entered manually or by introducing actual sensed values in Teach mode. Models are available with two SPDT relay outputs that can be set to activate on an increasing or decreasing input signal with hysteresis or time delay operation. Additionally the display color can be set to change on relay operation. Models are also available with a 4-20mA analog output. The meter is powered from an external AC or DC power supply. The 1/8 DIN housing is easy to install in a panel and the meter face has an IP65 rating. Configuration parameters can be totally or selectively locked out to prevent unauthorized or accidental changes to the meter’s operation. Other features include memory and reset of minimum (valley) and maximum (peak) display values, display hold function, filtering to minimize display bounce, and display brightness adjustment. ProSense digital panel meters are backed by a 3 year warranty.
• 96 x 48mm 1/8 DIN
• Simple menu driven pushbutton configuration
• 5 digit (-19999 to 19999) tri-color (red, green, amber) LED display
• Selectable decimal point
• True RMS for AC voltage and current inputs
• AC/DC voltage input 600V, 200V, 20V, 2V
• AC/DC current input 200mA, 1A, 5A, shunt 50mV, shunt 60mV, shunt 100 mV
• AC or DC powered
• Display scaling or teaching modes
• Optional 4-20mA analog output
• Optional (2) Form C SPDT
Activation on increasing or decreasing input signal
Hysteresis or time delay operation
Display color change on relay operation
• Configuration for direct or reverse acting
• Total or selective configuration lock out
• Programmable functions include:
Minimum (valley) and maximum (peak) value memory
Minimum (valley) and maximum (peak) value reset
Hold
• Filtering to minimize display bounce
• Display brightness adjustment
• 3 year warranty
6
DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters

Dimensions and Mounting

Sealing gasket
DPM3 Meter
TRMS
(2) Fixing clips
Panel mounting surface

Installation

To install the instrument, prepare a 92mm x 45mm panel cut-out and slide the unit inwards making sure to place the sealing gasket between the front side panel and the front bezel.
While holding the unit in place, put the fixing clips on both sides of the case and slide them through the guide tracks until they reach the panel at the rear side.
Press slightly to fasten the clips to the latching slots on the case and get the unit fully assembled and close fitted to achieve a good seal.
To remove the instrument from the panel, pull the rear fixing clips latching tabs outwards until they are disengaged, then slide the fixing clips back over the case.
DPM3-E Electrical User Manual, 1st Edition
Dimensions Panel Cutout Case Material
Installation
96 x 48 x 83.1mm (1/8 DIN)
92 x 45mm (Max. panel thickness 10mm)
Polycarbonate UL 94 V-0
7
User Manual - DPM3-E Series Electrical Panel Meters

Wiring Terminals

CN5
CN4
1 2
1
4
2
5
6
3
CN1 CN2 CN3
1 2 3 4 5
CN6
1
2
1 2 3 4
CN1
AC Supply
1 Line 1 VDC 2 Neutral 2 VDC
Polarity insensitive for DC power
DC
Supply
CN3
1 Common 2 Peak 3 Valley 4 Hold
CN2
Electrical Inputs
1 Common 2 Shunt / 2V 3 200mA 4 1A / 5A 5 20 / 200 / 600V
DPM3-E-A2R-H & DPM3-E-A2R-L 2 SPDT Relays
CN4 (Relay 2)
4 NO2 5 CM2 6 NC2
Terminals
Connector CN1 CN2 CN3
Wire cross section
Strip length 8 to 9mm 5 to 6mm 5 to 6mm 8 to 9mm 8 to 9mm
Manufacturer
Cage clamp connection
0.08 to 2.5mm² (28 to 12 AWG)
Wago 231­202/026-000 Insertion tool or screwdriver with 0.5 mm x
3.0 mm blade
0.08 to 1.5mm² (28 to 14 AWG)
Wago 734-105 Wago 733-104
Insertion tool or screwdriver with 0.3 mm x
1.8 mm blade
0.08 to 0.5mm² (28 to 20 AWG)
Insertion tool or screwdriver with 0.3 mm x
1.8 mm blade
CN4 &
CN5
0.08 to 2.5mm² (28 to 12 AWG)
Wago 231­303/026-000 Insertion tool or screwdriver with 0.5 mm x
3.0 mm blade
CN6
0.08 to 2.5mm² (28 to 12 AWG)
Wago 231­302/026-000 Insertion tool or screwdriver with 0.5 mm x
3.0 mm blade
CN5 (Relay 1)
1 NO1 2 CM1 3 NC1
NO: Normally open, CM: Common, NC: Normally closed
CN6
Analog Output 1 (-) 4-20mA 2 (+) 4-20mA
CN2 and CN3 Terminals
Refer to the instructions in this manual to preserve safety protections.
8
CN1, CN4, CN5
Insertion Tool (included with meter)
Insert wires into the proper terminal while using the insertion tool to open the clip inside the connector. Release the insertion tool to fix wire to the terminal.
DPM3-E Electrical User Manual, 1st Edition
and CN6 Terminals
Insertion Tool (included with meter)
Insert wires into the proper terminal while using the insertion tool to open the clip inside the connector. Release the insertion tool to fix wire to the terminal.
User Manual - DPM3-E Series Electrical Panel Meters
WARNING: If this instrument is not installed and used in accordance with these instructions, the protection provided against hazards may be impaired.
To meet the requirements of EN 61010-1 standard, where the unit is permanently connected to main supply, it is obligatory to install a circuit breaking device easily reach by the operator and clearly marked as the disconnecting device.
To guarantee electromagnetic compatibility, the following guidelines should be kept in mind:
• Power supply wires should be separately routed from signal wires and never run in the same conduit.
• Use shielded cable for signal wiring.
• Cables section should be 0.25 mm².
Before connecting signal wires, signal type and input range should be verified to be within the right limits. Do not connect simultaneously more than one input signal to the meter.
CAUTION: Connect only one input signal range to the meter. Hazardous signal levels may be present on unused inputs.
CAUTION: The isolation rating of the input common of the meter with respect to the option card common and to the Logical Functions common (if used) is 250 Vrms and 500 Vrms with respect to AC Power (terminals 1 and 2 of connector CN1). To be certain that the ratings are not exceded, these voltages should be verified by a high-voltage meter before wiring the meter.
CAUTION:
1. Where possible, connect the neutral side of the signal (including current shunts) to the input common of the meter. If the input signal is sourced from an active circuit, connect the lower impedance (usually circuit common) to the imput signal common of the meter. (pin 1 CN2)
2. For phase to phase line monitoring where a neutral does not exist, or for any other signal input in which the isolation voltage rating is exceeded, an isolating potential transformer must be used to isolate the input voltage from earth. With the transformer, the input common of the meter can then be earth referenced for safety.
3. When measuring line currents, the use of a current transformer is recommended. If using external current shunts, insert the shunt in the neutral return line. If the isolation voltage rating is exceeded, the use of an isolating current transformer is necessary.
DPM3-E Electrical User Manual, 1st Edition
9
User Manual - DPM3-E Series Electrical Panel Meters

Wiring Examples

DC/AC Voltage Input Wiring (Ranges: 2, 20, 200, 600 V)

Note: MAXIMUM VOLTAGE APPLICABLE IS: 600V DC/ AC
Terminals CN2
1 2 3 4 5
Terminals CN2
1 2 3 4 5
N
V
L
Voltmeter 20/ 200/ 600 V
DC/ AC
N
V
L
Voltmeter 2 V
DC/ AC

DC/AC Current Input Wiring (Ranges: 1A, 5A)

DC/AC Direct Connection
Terminals CN2
1 2 3 4 5
N
I
L
1/5 A DC/ AC
Important:
When using a current transformer, the input impedance (Ri) of the DPM3 is 14 mOhms. To maintain measurement accuracy, use connecting wires of appropriate gauge and length to prevent the total resistance of the measuring circuit (R1+R2+Ri) from exceeding the Burden rating of current transformer .
Connection using and AC Current Transformer
Terminals CN2
1 2 3 4 5
R
R2
1
N
L
1A / 5A AC MAX.
I

DC/AC Current Input Wiring (Range: 200mA)

Terminals CN2
1 2 3 4 5
10
N
I
L
200mA DC/AC
DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
2
3
6

DC/AC Current Input Wiring (Ranges: 50/60/100mV shunt)

Terminals CN2
1 2 3 4 5
N
SHUNT
I
L
Shunt
50/ 60/ 100 mV

Display and Key Pad

1
4
MICRA
# Description Run Mode Programming Mode
1 True RMS
2 MAX Indicates peak displayed ---
3 MIN Indicates valley displayed ---
4 PROG --- Indicates programming mode
5 DISPLAY Displays the input variable Displays programming parameters
6 UP Direct access to setpoints
SHIFT/MAX/MIN
7
KEY
8 ENTER KEY
Free space for
9
units label
10 LED Output 4 --- ---
11 LED Output 3 --- ---
12 LED Output 2 Activaton Output 2 Programming output 2
13 LED Output 1 Activation Output 1 Programming output 1
TRMS
MAX
MIN
PROG
5
MAX/MIN
DATA
ENTER
8
7
13
1
12
2
11
3
4
10
9
Programming Panel
Indicates reading AC using true RMS
Increments the value of the flashing digit
Recalls Max/Min values Moves to the right
Enters in PROG mode. Displays data
Accepts data. Advances program
---
---
DPM3-E Electrical User Manual, 1st Edition
11
User Manual - DPM3-E Series Electrical Panel Meters

1


2
345

Configuration:

When the power is applied to the meter, a display test begins automatically to check the function of the LED’s and digits. Once this test is finished the display shows the internal software version and then the unit goes to RUN mode.
Configuration follows a structure composed of a number of menus and submenus. By pressing the ENTER key, the display show “Pro”. Pressing the SHIFT key repeatedly provides access to the main menu level which includes menus for input configuration (CnInP), display configuration (CndSP), relay configuration if present (SEtP), analog output configuration if present (Anout), logic functions configuration (LoGIn). Press ENTER to access the submenus under each main menu.
If configuration has been totally locked-out, when pressing ENTER to access the main menu level, the display shows dAtA instead of Pro. This indicates that it is only possible to see programmed information and that it is not allowed to modify any parameter from the entire configuration. In this visualization mode, the meter automatically switches back to RUN mode after 15 seconds sine the last key press.
-
12
Input
Menu
Programming Key Pad
ENTER: Vertical displacement.
UP: Changes active digit.
SHIFT: Horizontal displacement.
Display
Menu
Relay
Configuration
Menu
Analog
Output
Menu
Logic
Functions
Menu
The progress through the programming routines is done by pressing ENTER key. In general, push SHIFT key a certain number of times to select an option and push ENTER key to validate the change and move forward to the next step of the program.

Programming numerical values

When the parameter is a numerical value, the display will show the first of the digit to be programmed blinking.
Digit selecting: Press repeatedly the SHIFT key to shift from left to right over all the display digits.
Changing the digit value: Press repeatedly the UP key to increase the value of blinking digit until it has the desired value.
The minus sign is programmed depending on the variable type. A variable that represents the value of an input will be able to take a value in the range -19999 to 19999, without taking into account the decimal point. When a digit is selected it shows values from (0) to (9), and then (-1), (-), and comes back to show values from 0 to 9. A variable that represents a display value
DPM3-E Electrical User Manual, 1st Edition
will be able to take a value in the range -19999 to 19999, without taking into account the decimal point. In these case the first digit shows 0, 1, -1, 2, 3 or -.
Completion of each submenu routine returns the meter to Pro mode. To save data entered or changed during configuration press the ENTER key while in Pro mode. StorE will be displayed for a few seconds while all of the configuration data is stored in memory. The meter will then return to RUN mode.

Input Configuration

The figure below shows the input configuration menu. Divided into four submenus, each one of them separated by the dotted line in the manual, each menu corresponds to the programming of the different types of input: Volt dc, Volt ac, Amp dc, Amp ac. Once the type of signal has been selected you have then to select the range. Usually the 100, 60, 50mV (nU) ranges are shunts signals. .
Programming Keys (Bottom view)
ENTER: Vertical displacement.
UP: Changes active digit.
SHIFT: Horizontal displacement.
CnInP
User Manual - DPM3-E Series Electrical Panel Meters
U-dC U-AC A-dC A-AC
600 U
PRO
200 U 20 U 2 U 5 A 1 A 0.2 A 100nU 60nU 50nU
DPM3-E Electrical User Manual, 1st Edition
13
User Manual - DPM3-E Series Electrical Panel Meters
NOTE: In the programming of the 600 V DC

Display Configuration

Programming Key Pad
ENTER: Vertical displacement.
CndSP
InP 1
±18.888
dSP 1
±18888
±188.88
InP 2
±18.888
dSP 2
±188.88
UP: Changes active digit.
SHIFT: Horizontal displacement.
tEAcHScAL FILtP round briGH Eco
InP 1
±18.888
dSP 1
±18888
±188.88
InP 2
±18.888
dSP 2
±188.88
8
-Pro-
or V AC range, 600.0 is accepted as a maximum in both ScAL and tEAcH methods .
88
-Pro-
-HI-
-Pro-
-Lo-
-oFF-
-Pro-
-on-
88
-Pro-

Scaling

For linear signals, scaling is achieved by programming two coordinates (InP1, DSP1) and
(InP2, dSP2), between which is established a linear relation where each input signal value corresponds to a display value. The relationship can be direct or reversed. In order to obtain more accuracy, points 1 and 2 should be located approximately at both extremes of the process.
display2
display1
14
-Pro-
display1
display2
Input2
input
1
input
1
input
2
DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
2
±1
8888
±8
±1
88.88
Dec. point

Programming of the scale

There are two methods for programming the scale, the SCAL method and the tEACH method.
Programming Key Pad
ENTER: Vertical displacement.
CndSP
UP: Changes active digit.
SHIFT: Horizontal displacement.
±8
±1
SCAL
InP 1
8.888
dSP 1
88.
tEACH
InP 2
88

SCAL method

The input and display values are programmed manually. This method can be used when the value of the signal at each points of the process is known.

tEACH method

The input values are introduced directly from actual electrical values. The input signal device must be connected to the meter and operational when each point is programmed. The display values are programmed manually. This method can be used when it is possible to bring the process to the conditions of each one of the points to be programmed.

Weighted Average Filter P

0 to 9 (4Hz to 0.05 Hz)
Sets low-pass filter cutoff frequency (Fc) which allows the meter to smooth out undesirable display reading fluctuations. The value can be modified through the SHIFT key. This parameter will set in reverse order the cut-off frequency of the low pass filter, getting the filter deactivated for 0 value.
DPM3-E Electrical User Manual, 1st Edition
15
User Manual - DPM3-E Series Electrical Panel Meters

Round

01 05 10
Will take each one of the values by pressing successively on the SHIFT key. with 01 there will be no round, 05 will round the display value at 0 to 5, and with 10 will round at 0 to 10.

Brightness

HI Lo
Display brightness level selection.
Hi: high brightness
Lo: low brightness
Display color selection between green, red or amber is possible for both RUN and Pro modes.
Eco
on off
Allows choosing an operative mode with an up to 45% of ENERGY SAVING*
on: After a programmable time without pressing any key, display will turn off leaving only the
right decimal point flashing; all functions remain active. Display will be again active after pressing any key.
oFF: Deactivates the function.
* Measured at 230V AC power supply, display 100.00, amber colour and with no options.

Additional Functions

Several functions can be controlled via Key Pad that will produce different actions depending on the instrument operating mode:

MAX/MIN function

With the meter in RUN mode: Activated after pressing the SHIFT key. From RUN mode, a press shows the maximum value (peak) read by the instrument since the last time it has been switched on, unless a RESET MAX/MIN is done, the MAX led will light up. A second press shows the minimum value in the same conditions as before, with the consequent minimum (valley) indication through the MIN led. A third press brings the instrument back to RUN mode.
Reset MAX/MIN
With the meter in RUN mode: Pressing the SHIFT key for 3 seconds, while the meter shows the peak value (MAX), will produce a reset of the value. Pressing SHIFT key for 3 seconds while the meter shows the valley value (MIN) will produce a reset of the value.
16
DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
PIN 4=function
6
-

-

3s?
=74?

Configuration Lockout

In mode RUN if the ENTER key is pressed for 3 seconds, the meter will show the indication CodE, and following 0000, allowing the user to introduce the security code. If the code that
has been introduced is wrong, the meter will go back to RUN mode, if it is correct, it will allow the access to the security menu. See section detailing Configuration Lockout.

Programming Mode

One press on the ENTER key will bring the instrument to the Programming Mode -Pro- mode.

Return to Factory Configuration

After accessing programming mode, Pro press and hold the up key for 3 seconds. Allows entering a code of access to the reset of the configuration parameters, this code is 74. When entering this code the instrument shows the LoAdIng dEFAuLt ConFIGurAtIon legend, and then StorE, which means that they have been stored in the non volatile memory of the meter.
Factory c
onfigura
tion
.000, Setpoint 2: +02.000
Color:No C
hange
CONFIGURA
Green
TION
, Prog
Mode.:Amber
3=function 4
  

INPUT
: 600V DC
DISPLAY
Input 1: 0000.0 Display 1: 0000.0 Input 2: 600.0 Display 2: 600.0 Filter P: 0 Round: 01 Brightness: High Eco: off
DISPLAY COLORS Run Mode:
SETPOINTS
Setpoint 1: +01 Mode: HI Dly: 00.0
Alarm
ANALOG OUTPUT
Display HI: 1000.0 Display LO: 0000.0
LOGIC FUNCTIONS PIN 2=function 3, PIN
and

Direct Access to Relay Setpoints

If the DPM3 has relay outputs present the meter allows direct access to the programming of the setpoint values. After accessing programming mode, Pro, pressing the UP key provides access to each relay setpoint value.

Logic functions

The connector CN3 provides 3 optocoupled inputs that can be operated from external switches. Three different functions may be assigned to the inputs using the front panel keys. Each function is associated to a pin (PIN 2, PIN 3 or PIN 4) that is activated by applying an external switch closure with respect to PIN 1 or COMMON. Function assignments to the inputs are achieved
DPM3-E Electrical User Manual, 1st Edition
17
User Manual - DPM3-E Series Electrical Panel Meters
1 2 3 4
1 2 3 4
CN3

-
through the programming of a number between 0 and 15 corresponding to one of the functions listed in the following table.
Factory configuration
As shipped from the factory, the CN3 connector allows remote control of the PEAK, VALLEY functions as well as the HOLD function.When a HOLD is made, the display value remains frozen while the corresponding pin is activated. The HOLD state affects neither the meter
internal operation nor the analog and relay outputs if present.
PIN (INPUT)
PIN 1 PIN 2 (INP-1) PIN 3 (INP-2) PIN 4 (INP-3)
The external electronics applied to the CN3 connector inputs must be capable of withstanding a potential of 40V / 20 mA present at all terminals with respect to COMMON. In order to guarantee the electromagnetic compatibility please refer to the connection instructions in the Wiring Terminal section.

Logic functions menu



Factor Default Functions
COMMON
PEAK Function No. 3
VALLEY Function No. 4
HOLD Function No. 6
-
Function
-
Logic functions diagram
1 2 3 4
Programming Key Pad
ENTER: Vertical displacement.
UP: Changes active digit.
SHIFT: Horizontal displacement.
18
-



-

-
-
-


-
DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters

Table of programmable functions

Nº: Number to select the function.
Function: Function name.
Description: Description and characteristics of the function.
Activation by:
Falling edge: the function is activated applying a falling edge to the corresponding pin with respect to common. Low level: the function will remain activated as long as the corresponding pin is held at a low level.
No. Function Description Activation By
0 1 2 3 4
5
6 7 8 9 10 11 12 13 14 15 16
* It’s mandatory programming the 3 logical inputs with function 16
Deactivated None None
Deactivated None None
Deactivated None None
PEAK Displays the peak value. (MAX.) Low level
VALLEY Displays the valley value. (MIN) Low level
RESET PEAK/VALLEY
HOLD Freeze the display while all the outputs remain active Low level
Deactivated None None
Deactivated None None
Deactivated None None
Deactivated None None
BRIGHTNESS Change the display brightness from Hi to Low Low level
SETPOINT VALUE Displays the selected setpoint value (see diagram next page) Low level
False Setpoints Simulates that the instrument has a four setpoints option installed Low level
Deactivated None None
Deactivated None None
Remote keypad The three logic inputs act as a remote keypad* Edge
Perform a reset of the peak or the valley, depending on which is being displayed.
Falling edge
DPM3-E Electrical User Manual, 1st Edition
19
User Manual - DPM3-E Series Electrical Panel Meters

Configuration Lock Out

The meter is delivered with the programming not locked out, giving access to all the programming levels. Once completed the meter programming the following security measures are recommended:
1. Lock out the programming access to prevent from programmed parameters modifications.
2. Lock out Key Pad functions to prevent from accidental modifications.
3. There are two lockout modes: selective and total. If the parameters are going to be readjusted frequently, make a selective lockout. If no adjustment is going to be made, make a total lockout. Key Pad functions lockout is always possible.
4. The access to the lockout routine is allowed by entering a personalised code. We recommend changing the code set at factory and to write down your personalised code and keep it in a safe place.
TOTAL LOCKOUT
The access to the programming routines to read data is allowed even if all parameters are locked out totLC=1, but it won t be possible to enter or modify data. In this case, when entering in the programming mode, the display shows the indication “-dAtA-”.
PARTIAL LOCKOUT
When only some parameters are locked out, all configuration data can be read but only non protected parameters can be modified. In such case, when entering in the programming mode, the display shows the indication -Pro- “.
Menus or submenus that can be locked out are:
• Relay 1 configuration (SEt 1). If present in meter.
• Relay 2 configuration (SEt 2). If present in meter.
• Input configuration (InPut).
• Display (diSP).
• Display color (CoLor).
• Relay setpoints value (SPVAL). If present in meter.
• Analog output configuration (Anout). If present in meter.
• Logic inputs configuration (LoGIn).
• Direct access to MAX. and MIN values (MAHMn).
20
DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
StorE
StorE
Si
≠----?
Pro
(Green)
Pro
(Yellow)
Pro
(Red)
totLC
(Total lock.)
- - - -
Run
(Red)
Run
(Green)
Run
(Yellow)
CHANG
CoLor
LISt
(param. list)
=Code?
8888
3s?
ENTER
CodE
Page 31
RUN
RUN

Lock-out menu diagram

The following figure shows the lock-out menu. The access to this menu is accomplished from the run mode by pressing the ENTER key for 3 seconds, until the “CodE” indication appears. The instrument is shipped from factory with the following default code: “0000”. Once this code is entered, the LISt indication will appear, from which lockout parameters will be entered. Accessing the “CHAnG” menu a new personal code is entered. Write down and keep this code in a safe place (Do not count on your memory).
If an incorrect code is entered, the meter will return automatically to the run mode. Total lockout programming is achieved by changing the “totLC” variable to 1, changing it to 0, will lead to the selective lockout of the programming variables. Programming each one of the parameters to 1 will active the lockout, if they are set to 0 programming will be accessible. Though the programming is locked out, it remains possible to visualise the current programming.
The “StorE” indication informs that the modifications effectuated have been stored correctly.
Programming Keys (Bottom view)
ENTER: Vertical displacement.
UP: Changes active digit.
SHIFT: Horizontal displacement.
Note: the color selection of the alarms is made in the setpoints menu
DPM3-E Electrical User Manual, 1st Edition
21
User Manual - DPM3-E Series Electrical Panel Meters
*
*

Lock-out menu diagram continued

Previous
Page
SEt 1
SEt 2
InPut
diSP
SPVAL
LoGIn
Anout
StorE
0 allows its programming
1 locks the access to programming
* Only appear if the corresponding
options are present in the meter
*
*
22
DPM3-E Electrical User Manual, 1st Edition

Output Options

Delay action
Asymmetrical hysteresis
All options are optoisolated with respect to input signal and power supply.
2500Vrms for 1 minute to signal terminals (CN2) and relays terminals (CN3 or CN4).
2500Vrms for 1 minute to power terminals (CN1) and relays terminals (CN3 or CN4).

Relay Configuration

Introduction
Some DPM3 models are equipped with either 2 relays that can provide individual alarm and control capabilities. All relays can be configured to function based on independent setpoint values within the full configured display range, time delay (in seconds), hysteresis (in counts of display) and selectable HI/LO acting.

Description of Operation

The relay outputs activate when the display value reaches the corresponding programmed relay setpoint value. The following relay operational parameters must also be set:
a. HI/ LO ACTING MODE.
In HI mode, the output activates when the display value exceeds the setpoint level and in LO mode, the output activates when the display value falls below the setpoint
b. PROGRAMMABLE TIME DELAY or HYSTERESIS.
Each output action can be deferred by a programmable time delay or hysteresis level.
The time delay is the time that takes the output to activate after passing through the setpoint in the up or down direction, while the hysteresis band will be selected asymmetrical i.e. only acts on the output deactivation edge. The delay is programmable in seconds, from 0 to 99.
The hysteresis can be programmed, in counts, within the full display range. The decimal point appears in the same position as programmed in the display configuration module.
The figures 1 and 2 show the time delay action (dly) and the hysteresis action (hys) of two alarms (SET1 and SET2) programmed to activate in HI mode (OUT1) and LO mode (OUT2)
User Manual - DPM3-E Series Electrical Panel Meters
dly
dly
dly
dly
DPM3-E Electrical User Manual, 1st Edition
23
User Manual - DPM3-E Series Electrical Panel Meters
3
-
-
-
SEt 2
R
ed
Green
Am
ber

Relay Configuration menu diagram

T
SEt
SEt 1
P
he complete programming of one of the setpoints
the setpoints
is showed here, it is valid for the rest of
on
-
±1
88.88
-Hi- -Lo-
-
Hys
- -
1
88.88
dLy
88
-
o
Programming Key Pad
ENTER: Vertical displacement.
-
Pro
-
no CH
-
Pro
-
UP: Changes active digit.
SHIFT: Horizontal displacement.
ALArM

Direct access to the relay setpoints value programming

It is possible to directly access the relay setpoint values without the need to go through the programming menu just by pressing the UP key in Pro mode, as shown in diagram below.
Setpoints configured at “off ” do not appear on the list”.
Remember that the decimal point
-
Pro
±1
SEt 1
88.88
-
StorE
position is determined by
what has been programmed in the SCAL menu.
Programming Keys (Bottom view)
ENTER: Vertical displacement.
ALArM
ALArM
24
±1
SEt 2
88.88
DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters

Analog output

Introduction
Some DPM3 models include an analog output (4-20 mA).
The output is optoisolated with respect to the signal input and the power supply.
The meter provides a two terminal connector [(+ ) and (-)] that drives out a signal variation from 4mA to 20mA proportional to a user-defined display range.
The signal can be used to transmit display information to a variety of terminal equipment such as graphic recorders, controllers, remote displays or other devices that accept input data in analog form.
The display values producing the full scale output (OUT-HI and OUT-LO) are introduced via front-panel buttons in the same programming module.
The output signal can be set up for reverse action by programming the low display for the high output (OUT-HI) and the high display for the low output (OUT-LO).

Analog output menu diagram

Programming Key Pad
ENTER: Vertical displacement.
Anout
outHI
-
Pro
-
UP: Changes active digit.
SHIFT: Horizontal displacement.
±1
outLo
±1
88.88
88.88
Display value for output: 20 mA
Display value for output: 4 mA
DPM3-E Electrical User Manual, 1st Edition
25
User Manual - DPM3-E Series Electrical Panel Meters

Technical Specifications

Technical Specifications
Input DC Voltage AC Voltage DC Current AC Current
Range....Input
Impedance
Input Frequency Range
Resolution
Accuracy
Accuracy Conditions
Conversion
Display
Relays
-A2R Only
Analog Output
-A2R Only
2V....100kΩ
20V....1MΩ
200V....1MΩ
600V....1MΩ
2V....0.1 mV
±20V....1mV
±200V....10mV
±600V....0.1 V
2V.... 0.05% rdg
± 0.3 mV
±20V....0.05% rdg
± 3mV
±200V....0.05% rdg
± 30mV
±600V....0.05% rdg
± 0.3 V
AC or DC Input:
15 minutes warmup
25°C ± 5°C ambient temperature
100 ppm/°C temperature coefficient
10-75% RH non-condensing
Technique Sigma-Delta Resolution ±15 bits Conversion rate 20 times per second Range -19999 / +19999, 5 LED digits 14mm (Programmable color Red, Green, Amber) LEDs 8, functions and outputs status Display refresh rate 20 times per second
Display / Input overrange indication
(2) Relays, Form C SPDT
Type 4-20 mA Sourcing Maximum load ≤500Ω Resolution 13 bits Accuracy 0.1%FS ±1 bit Response time 10ms Thermal drift 0.5µA / ºC
2V....75kΩ
20V....850kΩ
200V....850kΩ
600V....850kΩ
40Hz to 10kHz True RMS
Measurement
2V....0.1 mV
20V....1mV
200V....10mV
600V....0.1 mV
2V.... 0.3% rdg ± 0.3 mV
20V....0.3% rdg ± 3mV
200V....0.3% rdg ± 30mV
600V....0.3% rdg ± 0.3 V
Nominal contact rating....................8A at 250VAC / 24VDC
Maximum switching current (resistive load)....................8A
Maximum switching power.........................2000VA / 192W
Maximum switching voltage...................400VAC / 125VDC
Contact resistance...........................≤100mΩ at 6VDC at 1A
Operate time.................................................................≤10ms
200mA....0.75 Ω
1A....0.014 Ω
5A....0.014 Ω
50mV.... 1.8 MΩ
60mV....1.8 MΩ
100mV....1.8 MΩ
200mA....0.01 mA
1A....1mA
5A....1mA
50mV....0.01 mV
60mV....0.01 mV
100mV....0.01 mV
200mA.... 0.1 % rdg ± 0.05 mA
1A....0.1 % rdg ± 5mA
5A....0.1 % rdg ± 5mA
50mV.... 0.1 % rdg ± 0.1 mV
60mV....0.1 % rdg ± 0.1 mV
100mV....0.1 % rdg ± 0.1 mV
AC Input:
3% to 100% of input range
45 Hz to 400 Hz sine wave
40 Hz to 10 kHz Accuracy +/-(1% + 20 digits)
Crest Factor: 3, Accuracy +/-(0.2% + 10 digits); 5, Accuracy +/-(1%
"-oUEr” , “oUEr
+ 20 digits)
200mA.... 0.75 Ω
1A....0.014 Ω
5A....0.014 Ω
50mV.... 1.5 MΩ
60mV....1.5 MΩ
100mV....1.5 MΩ
40Hz to 10kHz True RMS
Measurement
200mA....0.01 mA
1A....1mA
5A....1mA
50mV....0.01 mV
60mV....0.01 mV
100mV....0.01 mV
200mA.... 0.3 % rdg ± 0.05 mA
1A....0.3 % rdg ± 5mA
5A....0.3 % rdg ± 5mA
50mV.... 0.3 % rdg ± 0.1 mV
60mV....0.3 % rdg ± 0.1 mV
100mV....0.3 % rdg ± 0.1 mV
26
DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
Technical Specifications Continued
Input DC Voltage AC Voltage DC Current AC Current
Power Supply and Fuses
Power Consumption
Filter
Environmental Conditions
Environmental Air
-H High Voltage:
-L Low Voltage:
Cutoff frequency 4Hz to 0.05Hz
Slope 20dB/Dec.
Operating temperature -10ºC to +60ºC (14ºF to 140ºF)
Storage temperature -25ºC to +85ºC (-13ºF to 185ºF)
Relative humidity (non-condensing)
Maximum altitude 2000m Frontal protection
degree
85-265 VAC 50/60 Hz (100-300 VDC), (recommended fusing 0.5A/250V, DIN 41661)
22-53 VAC 50/60 Hz (10.5 - 70 VDC), (recommended fusing 2A/250V, DIN 41661)
5W without options, 8W max.
<95% @ 40ºC (104ºF)
IP65
No corrosive gases permitted
Agency Approvals
CE
DPM3-E Electrical User Manual, 1st Edition
27
Loading...