Installation, Operating and Service Instructions for
TM
FORCEVFO Residential Water
Models:
• FORCEVFO-3-075E
• FORCEVFO-3-100E
• FORCEVFO-4-120E
• FORCEVFO-4-150E
• FORCEVFO-5-175E
• FORCEVFO-5-190E
Manual Contents Page
1. Dimensional Description, Specification &
Dimensional Data .....................4
2. Pre-installation .......................8
3. Packaged Boiler Assembly ............10
4. Water Boiler Piping & Trim .............11
5. Tankless & Indirect Water Heater Piping ..15
6. Venting ............................17
7. Electrical ...........................20
8. Oil Piping ...........................23
9. System Start-Up .....................25
10. Operating ..........................28
11. Maintenance & Service ...............34
12. Boiler Cleaning .....................36
13. Troubleshooting .....................38
14. Service Parts .......................40
15. Burner Specifications ................46
Appendix ..........................47
• FORCEVFOT-3-075E
• FORCEVFOT-3-100E
• FORCEVFOT-4-120E
• FORCEVFOT-4-150E
• FORCEVFOT-5-175E
• FORCEVFOT-5-190E
• Water Boiler
• Natural Draft
• Oil-Fired
TO THE INSTALLER:
Affix these instructions adjacent to boiler.
9700609
TO THE CONSUMER:
Retain these instructions for future reference.
As an ENERGY STAR Partner, U.S. Boiler Company
has determined that the FORCEVFO-3-075E,
FORCEVFOT-3-075E, FORCEVFO-4-120E, and
FORCEVFOT-4-120E meets the ENERGY STAR®
guidelines for energy efficiency established by the
United States Environmental Protection Agency
(EPA).”
For service or repairs to boiler, call your heating contractor. When seeking information on boiler, provide
Boiler Model Number and Serial Number as shown on Rating Label.
110547-01 - 4/20
Page 2
FORCEVFOInstallation & Service Manual
IMPORTANT INFORMATION - READ CAREFULLY
All boilers must be installed in accordance with National, State and Local Plumbing,
Heating and Electrical Codes and the regulations of the serving utilities. These
Codes and Regulations may differ from this instruction manual. Authorities having
jurisdiction should be consulted before installations are made.
In all cases, reference should be made to the following Standards:
USA BOILERS
A. Current Edition of American National Standard ANSI/NFPA 31, “Installation of Oil
Burning Equipment”, for recommended installation practices.
B. Current Edition of American National Standard ANSI/NFPA 211, “Chimneys, Fire
places, Vents, and Solid Fuel Burning Appliances”, For Venting requirements.
C. Current Edition of American Society of Mechanical Engineers ASME CSD-1, “Controls and Safety Devices for Automatically Fired Boilers”, for assembly and
operations of controls and safety devices.
D. All wiring on boilers installed in the USA shall be made in accordance with the
National Electrical Code and/or Local Regulations.
The following terms are used throughout this manual to bring attention to the presence of hazards of various
risk levels, or to important information concerning product life.
!!
DANGER
Indicates a hazardous situation that, if not
avoided, will result in death or serious injury.
!
WARNING
Indicates a hazardous situation that, if not
avoided, could result in death or serious injury.
NOTICE This boiler has a limited warranty, a copy of which is included with this boiler. The warranty for this boiler
is valid only if the boiler has been installed, maintained and operated in accordance with these instructions.
Surface rust on cast iron sections may be attributed to the manufacturing process as well as condensation
during storage. Surface rust is normal and does not affect the performance or longevity of a boiler.
Indicates a hazardous situation that, if not
avoided, could result in minor or moderate
injury.
NOTICE: Indicates special instructions on
installation, operation, or service which are
important but not related to personal injury
hazards.
CAUTION
2
110547-01 - 4/20
Page 3
FORCEVFOInstallation & Service Manual
DANGER
!
DO NOT store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other
appliance.
WARNING
!
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal
injury or loss of life. Failure to follow all instructions in the proper order can cause personal injury or death.
Read and understand all instructions, including all those contained in component manufacturers manuals
which are provided with the boiler before installing, starting-up, operating, maintaining or servicing this boiler.
Keep this manual and literature in legible condition and posted near boiler for reference by owner and service
technician.
• This boiler requires regular maintenance and service to operate safely. Follow the instructions contained in
this manual.
• Installation, maintenance, and service must be performed only by an experienced, skilled and knowledgeable
installer or service agency.
• All heating systems should be designed by competent contractors and only persons knowledgeable in the
layout and installation of hydronic heating systems should attempt installation of any boiler.
• Installation is not complete unless a pressure relief valve is installed into the tapping located on top left corner
of front section- See Piping and Trim Sections of this manual for details.
• It is the responsibility of the installing contractor to see that all controls are correctly installed and are operating
properly when installation is complete including verifying that the limit sensor is fully installed (seated in bottom
of Well).
• Failure to properly install Limit Sensor may result in property damage, personal injury or loss of life due to
elevated operating temperatures and/or pressures.
• This boiler is suitable for installation on combustible flooring. Do not install boiler on carpeting.
• Do not tamper with or alter the boiler or controls.
• Inspect flueways at least once a year - preferably at the start of the heating season. The inside of
the combustion chamber, the vent system and boiler flueways should be cleaned if soot or scale has
accumulated.
• When cleaning this boiler, DO NOT damage combustion chamber liner and/or rear target wall. If damaged,
combustion chamber insulation must be replaced immediately.
• Oil Burner and Controls must be checked at least once a year or as may be necessitated.
• Do not operate boiler with jumpered or absent controls or safety devices.
• Do not operate boiler if any control, switch, component, or device has been subject to water.
• Boiler materials of construction, products of combustion and the fuel contain alumina, silica, heavy metals,
carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful substances which can cause
death or serious injury and which are known to the state of California to cause cancer, birth defects and other
reproductive harm. Always use proper safety clothing, respirators and equipment when servicing or working
nearby the boiler.
110547-01 - 4/20
3
Page 4
FORCEVFOInstallation & Service Manual
WARNING
!
This boiler contains very hot water under high pressure. Do not unscrew any pipe fittings nor attempt to
disconnect any components of this boiler without positively assuring the water is cool and has no pressure.
Always wear protective clothing and equipment when installing, starting up or servicing this boiler to prevent
scald injuries. Do not rely on the pressure and temperature gauges to determine the temperature and
pressure of the boiler. This boiler contains components which become very hot when the boiler is operating.
Do not touch any components unless they are cool.
• High water temperatures increase the risk of scalding injury. If this boiler is equipped with a tankless heater
for domestic water supply, a flow regulator and automatic mixing valve must be installed properly in tankless
heater piping. See Piping and Trim Sections of this manual for details.
• This boiler must be properly vented and connected to an approved vent system in good condition. DO NOT
operate boiler with the absence of an approved vent system.
• This boiler needs fresh air for safe operation and must be installed so there are provisions for adequate
combustion and ventilation air.
• A clean and unobstructed chimney flue is necessary to allow noxious fumes that could cause injury or loss of
life to vent safely and will contribute toward maintaining the boiler's efficiency.
• This boiler is supplied with controls which may cause the boiler to shut down and not re-start without service.
If damage due to frozen pipes is a possibility, the heating system should not be left unattended in cold
weather; or appropriate safeguards and alarms should be installed on the heating system to prevent damage
if the boiler is inoperative.
• This boiler is designed to burn No. 2 fuel oil only. DO NOT use gasoline, crankcase drainings, or any oil
containing gasoline. Never burn garbage or paper in this boiler. DO NOT convert to any solid fuel (i.e. wood,
coal). DO NOT convert to any gaseous fuel (i.e. natural gas, LP). All flammable debris, rags, paper, wood
scraps, etc., should be kept clear of the boiler at all times. Keep the boiler area clean and free of fire hazards.
• All boilers equipped with burner swing door have a potential hazard which if ignored can cause severe
property damage, personal injury or loss of life. Before opening swing door, turn off service switch to boiler to
prevent accidental firing of burner outside the combustion chamber. Be sure to tighten swing door fastener
completely when service is completed.
1 Product Description, Specification and Dimensional Data
The FORCEVFO Series boiler is a cast iron oil-fired
water boiler designed for closed forced circulation
heating systems. This boiler must be vented by
natural draft into a fireclay tile-lined masonry chimney
or chimney constructed from type L vent or a
factory built chimney that complies with the type HT
requirements of UL103. An adequate supply of air for
combustion, ventilation and dilution of flue gases must
be available in the boiler room.
4
110547-01 - 4/20
Page 5
FORCEVFOInstallation & Service Manual
1 Product Description, Specification and Dimensional Data (continued)
Table 1A: Dimensional Data
Boiler Series
Dimensions
"A""B""C"Round in Dia.
Approx.
Water Content
Gallons
FORCEVFO-317-3/8"8-1/4"5-7/8"166
FORCEVFO-527-3/8"13-3/8"7-7/8"248
Maximum Working Water Pressure: 30 PSI Shipped from Factory, 50 PSI Optional
Based on standard test procedure prescribed by the United States Department of
Energy at combustion conditions of 13.0% CO2.
(3)
Net AHRI Ratings are based on piping and pickup allowance of 1.15 for water.
Recommended Minimum Chimney
Rectangle
in. x in.
Height ft.
8 x 815FORCEVFO-422-3/8"10-7/8"6-7/8"207
AFUE
%
110547-01 - 4/20
5
Page 6
FORCEVFOInstallation & Service Manual
1 Product Description, Specification and Dimensional Data (continued)
'C'
'B'
DIA.
Figure 1-1: Water Boiler without Tankless Heater
6
110547-01 - 4/20
Page 7
FORCEVFOInstallation & Service Manual
1 Product Description, Specification and Dimensional Data (continued)
110547-01 - 4/20
Figure 1-2: Water Boiler with Rear Tankless Heater
7
Page 8
2 Pre-Installation
FORCEVFOInstallation & Service Manual
A. INSPECT SHIPMENT carefully for any signs of
damage.
1. All equipment is carefully manufactured,
inspected and packed. Our responsibility
ceases upon delivery of crated boiler to the
carrier in good condition.
2. Any claims for damage or shortage in shipment
must be filed immediately against the carrier
by the consignee. No claims for variances
from, or shortage in orders, will be allowed by
the manufacturer unless presented within sixty
(60) days after receipt of goods.
B. LOCATE BOILER in front of final position before
removing crate. See Figures 1-1 and 1-2.
1. LOCATE so that vent pipe connection to
chimney will be short and direct.
2. BOILER IS SUITABLE FOR INSTALLATION
ON COMBUSTIBLE FLOOR. Boiler cannot be
installed on carpeting.
3. FOR BASEMENT INSTALLATION, provide a
solid elevated base, such as concrete, if floor
is not level, or if water may be encountered on
floor around boiler.
4. PROVIDE SERVICE CLEARANCE of at least
24” clearance from front jacket panel for
servicing and removal of front tankless heater.
If boiler is equipped with a rear tankless heater,
provide at least 24" service clearance on the
right side of the boiler. Boiler flueways may be
cleaned either from the top. Provide at least
24" clearance from the top of the boiler for
cleaning flueways.
5. For minimum clearances to combustible
materials. See Figure 2-1.
C. PROVIDE COMBUSTION AND VENTILATION
AIR. Local and National Codes may apply and
should be referenced.
Figure 2-1: Minimum Installation Clearances To Combustible Materials (Inches)
NOTES:
1. Listed clearances comply with American
National Standard ANSI/NFPA 31, Installation
of Oil Burning Equipment.
2. FORCEVFO Series boilers can be installed
in rooms with clearances from combustible
material as listed above. Listed clearances
cannot be reduced for alcove or closet
installations.
8
3. For reduced clearances to combustible
material, protection must be provided as
described in the above ANSI/NFPA 31
standard.
110547-01 - 4/20
Page 9
2 Pre-Installation (continued)
FORCEVFOInstallation & Service Manual
NOTICE Clearance to venting is for single wall
vent pipe. If Type L vent is used, clearance may
be reduced to the minimum required by the vent
pipe manufacturer.
!
WARNING
Adequate combustion and ventilation air must
be provided to assure proper combustion and
to maintain safe ambient air temperatures.
DO NOT install boiler where gasoline or other
flammable vapors or liquids, or sources of
hydrocarbons (i.e. bleaches, fabric softeners,
etc.) are used or stored.
1. Determine volume of space (boiler room).
Rooms communicating directly with the
space in which the appliances are installed,
through openings not furnished with doors, are
considered a part of the space.
Volume(ft3) = Length(ft) x Width(ft) x Height(ft)
2. Determine total input of all appliances in the
space.
Add inputs of all appliances in the space and
round the result to the nearest 1000 BTU per
hour.
3. Determine type of space. Divide Volume by
total input of all appliances in space. If the
result is greater than or equal to 50 ft3/1000
BTU per hour, then it is considered an
unconfined space. If the result is less than
50 ft3/1000 BTU per hour then the space is
considered a confined space.
4. For boiler located in an unconfined space of a conventionally constructed building, the fresh
air infiltration through cracks around windows
and doors normally provides adequate air for
combustion and ventilation.
5. For boiler located in a confined space or an
unconfined space in a building of unusually
tight construction, provide outdoor air.
a. Outdoor air may be provided with the
use of two permanent openings which
communicate directly or by duct with the
outdoors or spaces (crawl or attic) freely
communicating with the outdoors. Locate
one opening within 12 inches of top of
space. Locate remaining opening within
12 inches of bottom of space. Minimum
dimension of air opening is 3 inches. Size
each opening per following:
i.Direct communication with outdoors.
Minimum free area of 1 square inch
per 4,000 BTU per hour input of all
equipment in space.
ii. Vertical ducts. Minimum free area of
1 square inch per 4,000 BTU per hour
input of all equipment in space. Duct
cross-sectional area shall be same as
opening free area.
iii. Horizontal ducts. Minimum free area of
1 square inch per 2,000 BTU per hour
input of all equipment in space. Duct
cross-sectional area shall be same as
opening free area.
Alternate method for boiler located
within confined space. Use indoor air if
two permanent openings communicate
directly with additional space(s) of
sufficient volume such that combined
volume of all spaces meet criteria for
unconfined space. Size each opening
for minimum free area of 1 square inch
per 1,000 BTU per hour input of all
equipment in spaces, but not less than
100 square inches.
6. Louvers and Grilles of Ventilation Ducts
a. All outside openings should be screened
and louvered. Screens used should not be
smaller than 1/4 inch mesh. Louvers will
prevent the entrance of rain and snow.
b. Free area requirements need to consider
the blocking effect of louvers, grilles, or
screens protecting the openings. If the free
area of the louver or grille is not known,
assume wood louvers have 20-25 percent
free area and metal louvers and grilles have
60-75 percent free area.
c. Louvers and grilles must be fixed in the
open position, or interlocked with the
equipment to open automatically during
equipment operation.
110547-01 - 4/20
9
Page 10
3 Packaged Boiler Assembly
A. REMOVE CRATE.
1. Remove all fasteners at crate skid.
2. Lift outside container and remove all other
inside protective spacers and bracing.
Remove draft regulator box and miscellaneous
trim bag containing safety or relief valve, and
pipe fittings.
B.REMOVE BOILER FROM SKID.
1. Boiler is secured to base with 4 bolts, 2 in front
and 2 in rear of shipping skid, see Figure 3-1.
Remove all bolts.
2. Tilt boiler to right and to rear. Using right rear
leg as pivot, rotate boiler 90° in a clockwise
direction, and lower left side of boiler to floor.
Tilt boiler and remove crate skid. Care should
be exercised to prevent damage to jacket or
burner.
FORCEVFOInstallation & Service Manual
E. INSTALL OIL BURNER.
1. Open burner carton and remove contents.
Refer to Table 15-1.
2. Place oil burner gasket on burner and align
holes.
CAUTION
!
Do not install burner without Gasket.
3. Remove three (3) 5/16-18 x 3/4” long cap
screws from burner swing door used for
mounting burner.
4. Insert oil burner into opening of burner swing
door. Align the top slotted hole in burner
flange with the top hole on the burner swing
door. Install one (1) cap screw.
5. Align remaining holes and install the two (2)
remaining cap screws.
F. INSTALL SAFETY OR RELIEF VALVE see
Figure 1-1.
1
Use ¾" NPT x 7
Safety or Relief Valve must be installed with
spindle in vertical position. Pipe discharge as
shown in Figures 4-2 and 4-3. Installation of the
safety or relief valve must be consistent with ANSI/
ASME Boiler and Pressure Vessel Code, Section
I V.
/4" nipple included in trim bag.
Figure 3-1 : Packaged Boiler Removal from Skid
CAUTION
!
DO NOT drop boiler. DO NOT bump boiler
jacket against floor.
C.MOVE BOILER TO PERMANENT POSITION
by sliding or walking.
D. INSPECT COMBUSTION CHAMBER TARGET
WALL.
1. Open burner swing door.
2. Using a flashlight, inspect the rear target wall.
The target wall should be rigidly secured to the
rear boiler section.
!
WARNING
Safety valve discharge piping must be piped
near floor to eliminate potential of severe burns.
DO NOT pipe in any area where freezing could
occur. DO NOT install any shut-off valves,
plugs or caps.
G. PACKAGED WATER BOILERS WITH
CIRCULATORS. If your boiler build comes with
factory supplied circulator and circulator is to be
mounted in supply piping connected directly to
1½" boiler supply tapping.
10
110547-01 - 4/20
Page 11
4 Water Boiler Piping and Trim
FORCEVFOInstallation & Service Manual
NOTICE Failure to pipe boiler as specified in this
manual may result in excessive system noise,
water line fluctuations and water carry over.
A. EVALUATE THE EXISTING WATER SYSTEM.
Design a piping system and install boiler which
will prevent oxygen contamination of boiler water
and frequent water additions.
1. There are many possible causes of oxygen
contamination such as:
a. Addition of excessive make-up water as a
result of system leaks.
b. Absorption through open tanks and fittings.
c. Oxygen permeable materials in the
distribution system.
2. In order to insure long product life, oxygen
sources must be eliminated. This can
be accomplished by taking the following
measures:
a. Repairing system leaks to eliminate the
need for addition of make-up water.
b. Eliminating open tanks from the system.
c. Eliminating and/or repairing fittings which
allow oxygen absorption.
d. Use of non-permeable materials in the
distribution system.
e. Isolating the boiler from the system water by
installing a heat exchanger.
WARNING
!
System supply and return piping must be
connected to correct boiler pipe.
U.S. Boiler Company recommends sizing
the system circulator to supply sufficient
flow (GPM) to allow a 20°F temperature
differential in the system. When sizing the
system circulator, the pressure drop of all
radiators, baseboard and radiant tubing and all
connecting piping must be considered.
1. If this boiler is used in connection with
refrigeration systems, the boiler must be
installed so that the chilled medium is piped
in parallel with the heating boiler using
appropriate valves to prevent the chilled
medium from entering the boiler. See Figure
4-1. Also, consult Residential Hydronic
Heating Installation and Design I=B=R Guide.
2. If this boiler is connected to heating coils
located in air handling units where they may
be exposed to refrigerated air, the boiler piping
must be equipped with flow control valves
to prevent gravity circulation of boiler water
during the operation of the cooling system.
3. If boiler is used with an Indirect Domestic
Water Heater, install the Indirect Water Heater
as a separate heating zone. Refer to the
Indirect Water Heater Installation, Operating,
and Service Instructions for additional
information.
4. Use a boiler bypass if the boiler is to be
operated in a system which has a large
volume or excessive radiation where low boiler
water temperatures may be encountered (i.e.
converted gravity circulation system, etc.)
The bypass should be the same size as the
supply and return lines with valves located
in the bypass and return line as illustrated in
Figures 4-2 and 4-3 in order to regulate water
flow for maintenance of higher boiler water
temperature.
WARNING
!
The use of a low water cut-off device, while
not required unless radiation level is below the
boiler, is highly recommended.
5. If a Low Water Cut-Off (LWCO) is required, it
must be mounted in the system piping above
the boiler. The minimum safe water level of a
hot water boiler is just above the highest water
containing cavity of the boiler; that is, a hot
water boiler must be full of water to operate
safely. Refer to Appendix A at the rear of this
manual.
6. If it is required to perform a long term pressure test of the hydronic system,
the boiler should first be isolated to avoid a
pressure loss due to the escape of air trapped
must first be removed from the boiler.
110547-01 - 4/20
11
Page 12
4 Water Boiler Piping and Trim (continued)
To perform a long term pressure test including
the boiler, ALL trapped air must first be
removed from the boiler.
A loss of pressure during such a test, with no
visible water leakage, is an indication that the
boiler contained trapped air.
FORCEVFOInstallation & Service Manual
12
Figure 4-1: Recommended Piping for Combination Heating and Cooling (Refrigeration) System
110547-01 - 4/20
Page 13
4 Water Boiler Piping and Trim (continued)
FORCEVFOInstallation & Service Manual
110547-01 - 4/20
Figure 4-2: Recommended Water Piping for Circulator Zoned Heating System - Supply Side Circulators
13
Page 14
4 Water Boiler Piping and Trim (continued)
FORCEVFOInstallation & Service Manual
14
Figure 4-3: Recommended Water Piping for Zone Valve Zoned Heating System - Supply Side Circulator
110547-01 - 4/20
Page 15
5 Tankless and Indirect Water Heater Piping
FORCEVFOInstallation & Service Manual
A. CONNECT TANKLESS HEATER PIPING as
shown in Figure 5-1. See Table 5-2 for Tankless
Heater Rating.
WARNING
!
Install automatic mixing valve at tankless heater
outlet to avoid risk of burns or scalding due
to excessively hot water at fixtures. Adjust
and maintain the mixing valve in accordance
with the manufacturer's instructions. DO NOT
operate tankless heater without mixing valve.
THE FOLLOWING GUIDELINES SHOULD BE
FOLLOWED WHEN PIPING THE TANKLESS
HEATER:
1. FLOW REGULATION — If flow through the
heater is greater than its rating, the supply of
adequate hot water may not be able to keep
up with the demand. For this reason a flow
regulator matching the heater rating should
be installed in the cold water line to the heater.
The flow regulator should preferably be located
below the inlet to the heater and a minimum of
3’ away from the inlet so that the regulator is
not subjected to excess temperatures that may
occur during “off” periods when it is possible
for heat to be conducted back through the
supply line. The flow regulator also limits
the flow of supply water regardless of inlet
pressure variations in the range of 20 to 125
psi.
2. TEMPERING OF HOT WATER — Installation
of an automatic mixing valve will lengthen the
delivery of the available hot water by mixing
some cold water with the hot. This prevents
the possibility of scalding hot water at the
fixtures. In addition, savings of hot water will be
achieved since the user will not waste as much
hot water while seeking a water temperature.
Higher temperature hot water required by
dishwashers and automatic washers is
possible by piping the hot water from the
heater prior to entering the mixing valve. The
mixing valve should be “trapped” by installing
it below the cold water inlet to heater to prevent
lime formation in the valve. Refer to Figure
16A.
3. FLUSHING OF HEATER — All water
contains some sediment which settles on the
inside of the coil. Consequently, the heater
should be periodically back washed. This
is accomplished by installing hose bibs as
illustrated and allowing water at city pressure
to run into hose bib A, through the heater, and
out hose bib B until the discharge is clear. The
tees in which the hose bibs are located should
be the same size as heater connections to
minimize pressure drop.
4. HARD WATER — A water analysis is
necessary to determine the hardness of your
potable water. This is applicable to some
city water and particularly to well water.
An appropriate water softener should be
installed based on the analysis and dealer’s
recommendation. This is not only beneficial to
the tankless heater but to piping and fixtures
plus the many other benefits derived from soft
water.
Use street elbow fittings in tankless in and out
connections to assure adequate clearance of
piping.
!
CAUTION
Use of hard water with a tankless coil will, over
a short period of time, reduce the output of the
coil, reduce flow due to increased pressure
drop and reduce the useful life of the coil.
110547-01 - 4/20
15
Page 16
FORCEVFOInstallation & Service Manual
5 Tankless and Indirect Water Heater Piping (continued)
Vent this boiler according to these instructions. Failure to do so may cause products of combustion to enter
the home resulting in severe property damage, personal injury or death.
• Insufficient Combustion Air Supply may result in the production and release of deadly carbon monoxide (CO)
into the home which can cause severe personal injury or death.
• Improper venting may result in property damage and the release of flue gases which contain deadly carbon
monoxide (CO) into the home, which can cause severe personal injury, death, or substantial property damage.
• Inspect existing chimney and vent connector for obstructions and deterioration before installing boiler. Failure
to clean or replace perforated pipe or chimney liner will cause severe injury or death.
• Do not de-rate the appliance. Failure to fire the boiler at it's designed input may cause excessive
condensation upon the interior walls of the chimney. In addition, the lower input may not create enough draft
to adequately evacuate the by-products of combustion.
A. GENERAL VENTING GUIDELINES
1. Chimney venting is an important part of a safe
and efficient oil fired appliance system. Contact
your local fire and building officials on specific
requirements for restrictions and the installation
of fuel oil burning equipment. In addition,
consult with a professional knowledgeable on
the requirements of NFPA 31 – Standard for
the Installation of Oil-Burning Equipment and
NFPA 211 - Standard for Chimneys, Fireplaces,
Vents, and Solid Fuel-Burning Appliances for
installations in the United States.
2. The safe venting of oil fired boilers is dependant
on many factors. Some of these factors include:
a. sufficient draft during the entire heating season
to allow for the safe discharge of combustion
by-products and;
b. suitable corrosion protection in the event of
condensing flue gases. Only a trained and
qualified contractor may install this product.
3. The FORCEVFO shall be vented into any of the
following:
a. Masonry or metal chimney. Build and install
in accordance with local buildings codes;
or local authority having jurisdiction; or
“Standards for Chimney, Fireplace, Vents,
and Solid Fuel Burning Appliances”, ANSI/
NFPA 211 and/or National Building Code of
Canada. Masonry chimney must be lined
with listed chimney system. Listed clay
flue lined masonry chimneys meet venting
requirements.
• External chimneys are more susceptible
to flue gas condensation due to colder
outside air temperatures. To prevent
corrosion due to flue gas condensation,
use a listed corrosion-resistant metal
liner in chimney.
• Oversized chimneys are more
susceptible to flue gas condensation.
To reduce the likelihood of flue gas
condensation and ensure proper draft,
use a properly sized listed metal liner in
oversized chimney.
4. Chimney Inspection – Prior to the installation
of any new or replacement fuel burning
equipment the chimney shall be inspected
by a qualified installer. The chimney shall
be inspected for integrity as well as for
proper draft and condensate control. Some
jurisdictions require the use of a liner when
changing fuel types. Some jurisdictions
require the use of a liner even when the same
fuel is used. At a minimum, the chimney
shall be examined by a qualified person in
accordance with the requirements of Chapter
11 of NFPA 211, Standard for Chimneys,
Fireplaces, Vents, and Solid Fuel-Burning
Appliances.
a. Loose Mortar – Loose mortar could be an
indication of a prior history of condensing flue
gases upon the inside walls of the chimney.
Colder climates are more susceptible to this
condition. Under no circumstances shall a
chimney of this condition be used until it meets
the requirements of NFPA 211 or CSA B139.
b. Unlined Chimney – Under no circumstances
shall a chimney constructed of brick only be
used. Only approved clay liners or listed
chimney lining systems shall be used as
specified in NFPA 31.
c. Abandoned Openings – Openings through
the chimney wall that are no longer used
shall be sealed in accordance to NFPA 211.
Often abandoned openings are improperly
sealed and usually covered by a gypsum wall
covering.
110547-01 - 4/20
17
Page 18
6 Venting (continued)
FORCEVFOInstallation & Service Manual
Figure 6-1: Recommended Vent Pipe Arrangement and Chimney Requirements
18
Figure 6-2: Proper and Improper Locations of Draft Regulator
110547-01 - 4/20
Page 19
6 Venting (continued)
d. Clean Chimney – Chimney shall be free of all
loose debris.
5. Draft Regulator – the draft regulator supplied with
the boiler (or equivalent) must be used with this
appliance. Refer to Figures 6-1 and 6-2.
CHIMNEY CONNECTOR
1. A chimney connector (vent pipe) is used to
connect the boiler to the base of the chimney.
The chimney connector should be kept as short
as possible. The horizontal length of the chimney
connector shall not be greater than 10 feet.
DANGER
!
The chimney and connector shall be inspected
annually for signs of debris and corrosion.
Loose mortar at the base of the chimney may be
a sign of condensate damage to the chimney.
A chimney professional shall be contacted
immediately to examine the damage and
recommend a solution. Long term operation
while in this condition may cause a venting
failure and force flue gases into the living
space. If the chimney is to be re-lined use the
recommendations in NFPA 31, Appendix E.
2. Vent Connector shall be any of the following
and of the same size as the outlet of boiler.
a. Type L or a factory built chimney material
that complies with the Type HT requirements
of ANSI/UL 103. Install in accordance with
listing and manufacturer’s instructions.
b. Steel pipe having resistance to corrosion
and heat with a minimum wall thickness of
24 Gauge (0.024”).
DANGER
!
Any sign of condensate seepage at the base
of the chimney shall be inspected immediately.
The discoloration may be a sign of chimney
damage and must be remedied immediately.
FORCEVFOInstallation & Service Manual
2. Minimum Draft Overfire – The draft induced by a
chimney must create at least a pressure of -0.02
inches water column (“ w.c.). The pressure at
the canopy cannot be positive since this could
create a condition that allows flue gas by-products
to escape from the draft regulator. A negative
pressure reading up to -.03 inches water column
is acceptable for proper operation.
STACK TEMPERATURE
1. The temperature of the flue gases has a significant
effect on the amount of draft created in a vertical
chimney as well as the propensity to create
condensate. The higher the stack temperature,
the greater the amount of draft that can be
generated. A lower stack temperature not only
reduces the amount of draft that can be created
but it also increases the possibility that the flue
gases could condense in the chimney connector
or stack.
2. NFPA 31 has information to help the installer make
an appropriate choice of venting materials. In
some cases a chimney may have to be lined to
create sufficient draft. In other cases, the chimney
may have to be lined to prevent the corrosion
of a masonry chimney. Consult with a chimney
specialist knowledgeable on the requirements
for chimney requirements in your area.
CAUTION
!
Any doubt on the condition of a chimney
or it’s ability to prevent the generation and
accumulation of flue gas condensate, must be
relined according to NFPA 31 (United States).
Use the chimney venting tables as a guide. It
is highly recommended that any borderline
application should result in the relining of
the chimney with a suitable liner that creates
sufficient draft and to protect against corrosion
caused by flue gas condensate.
DRAFT
1. The natural draft generated through a chimney is
dependent on several factors including, chimney
height, temperature of flue gases, cross section
area of chimney, chimney wall insulation value,
dilution air and total volume of flue gases, to
name a few. Make sure that the boiler has been
running for at least 5 minutes before measuring
the draft.
110547-01 - 4/20
19
Page 20
7 Electrical
FORCEVFOInstallation & Service Manual
!
DANGER
Positively assure all electrical connections are
unpowered before attempting installation or
service of electrical components or connections
of the boiler or building. Lock out all electrical
boxes with padlock once power is turned off.
WARNING
!
Failure to properly wire electrical connections to
the boiler may result in serious physical harm.
• Electrical power may be from more than one
source. Make sure all power is off before
attempting any electrical work.
• Each boiler must be protected with a properly
sized fused disconnect.
• Never jump out or make inoperative any safety
or operating controls.
• The primary control may be damaged or may
not function properly if 120 volt power supply is
NOT wired into control as follows:
The 120V interrupted hot (black) wire must be
connected to the primary control black wire, the
120V neutral (white) wire must be connected
to the primary control white wire and the 120V
constant hot (red) wire must be connected to
the primary control red wire.
7. Wiring should conform to Figures 7-1 through
7-2.
B. INSTALL A ROOM THERMOSTAT on an inside
wall about four feet above floor. Never install
thermostat on an outside wall or where it will be
influenced by drafts, hot or cold water pipes,
lighting fixtures, television, rays of the sun or
near a fireplace. Keep large furniture away from
thermostat so there will be free movement of room
air around this control.
Heat Anticipator in Thermostat should be set to
match the requirements of the control to which
it is connected. See Figures 7-1 thru 7-2 for
desired system and heat anticipator setting. If
system tends to overheat above the thermostat's
temperature setting, reduce heat anticipator
settings by .1 or .2 amps. If system tends to short
cycle without reaching desired room temperature,
increase heat anticipator setting by .1 or .2
amps.
A. GENERAL
1. Install wiring and electrically ground boiler in
accordance with requirements of the authority
having jurisdiction, or in absence of such
requirements the National Electrical Code, ANSI/
NFPA 70.
2. Refer to National Electric Code or Local Electric
Codes for proper size and type of wire required.
Follow Code.
3. A separate electrical circuit must be run from
the mail electrical service with an over-current
device/disconnect in the circuit. A service
switch is recommended and may be required
by some local jurisdictions.
4. Use anti-short bushings on all wiring passing
through boiler jacket, junction boxes and/or
control boxes.
5. Use armored cable (BX) over all exposed line
voltage wiring.
6. If an indirect domestic water heater is used,
use priority zoning. DO NOT use priority zoning
for Hydro-Air Systems.
Figure 7-2: Schematic Wiring Diagrams For All Burner Options with Various Oil Primary Controls
110547-01 - 4/20
Page 23
8 Oil Piping
A. GENERAL
1. Use flexible oil line(s) so the burner swing door
can be opened without disconnecting the oil
supply piping.
2. A supply line fuel oil filter is recommended as a
minimum for all firing rates but a pleated paper
fuel oil filter is recommended for the firing rates
below 1.0 GPH to prevent nozzle fouling.
3. Use Flared fittings only. Cast iron fittings
cannot be used.
NOTICE DO NOT use compression fittings.
Oil piping must be absolutely airtight or leaks or
loss of prime may result. Bleed line and fuel unit
completely.
Refer to your local jurisdictions regarding
any special considerations for fuel supply
requirements. In addition, refer to NFPA 31,
Standard for the Installation of Oil-Burning
Equipment for Installations in the United States
and CSA B139-04 for Installation in Canada.
4. Use of a high efficiency micron filter (Garber or
equivalent) in addition to a conventional filter is
highly recommended.
5. Piping used to connect the oil burner to the oil
supply tank shall not be smaller than 3/8" iron
pipe or 3/8" OD copper tubing. Copper tubing
shall have a .032" minimum wall thickness.
FORCEVFOInstallation & Service Manual
WARNING
!
Under no circumstances can copper with sweat
style connectors be used.
NOTICE Some jurisdictions require the use of a
fusible shutoff valve at the tank and/or the burner.
In addition, some jurisdictions require the use of a
fusible electrical interlock with the burner circuit.
Check your local Codes for special requirements.
B. SINGLE PIPE OIL LINES
1. Standard burners are provided with singlestage 3450 RPM fuel units with the bypass
plug removed for single-pipe installations.
2. The single-stage fuel unit may be installed
single-pipe with gravity feed or lift. Maximum
allowable lift is 8 feet. See Figure 8-1.
3. Fuel Oil Line Deaerator – On many occasions
a leaky oil delivery line can introduce air
into the fuel oil supply system. This often
creates a rough starting condition and can
create a burner lockout state. In addition to
fixing the leak, a fuel line deaerator can be
installed to eliminate air. The single line from
the fuel tank is connected to the deaerator.
The burner pump must be connected to the
deaerator as a two pipe system. Follow the
oil pump manufacturer’s recommendations for
conversion to a two pipe system.
110547-01 - 4/20
Figure 8-1: Single Pipe Oil Line
23
Page 24
8 Oil Piping (continued)
FORCEVFOInstallation & Service Manual
C. TWO PIPE OIL LINES
1. For two piped systems, where more lift
is required, the two-stage fuel unit is
recommended.
Table 8-2 (two-stage) and Table 8-3 (single-
stage) show allowable lift and lengths of 3/8
inch and 1/2 inch OD tubing for both suction
and return lines. Refer to Figure 8-4.
Table 8-2: Two-Stage Units (3450 RPM) -
Two Pipe Systems
Maximum Length of Tubing
Lift "H"
(See Fig. 25)
0'93'100'
2'85'100'
4'77'100'
6'69'100'
8'60'100'
10'52'100'
12'44'100'
14'36'100'
16'27'100'
18'---76'
"H" + "R" (See Figure 27)
3/8" OD
Tubing (3 GPH)
1/2" OD
Tubing (3 GPH)
Table 8-3: Single-Stage Units (3450 RPM) -
Two Pipe Systems
Maximum Length of Tubing
Lift "H"
(See Fig. 25)
0'84'100'
1'78'100'
2'73'100'
3'68'100'
4'63'100'
5'57'100'
6'52'100'
7'47'100'
8'42'100'
9'36'100'
10'31'100'
11'26'100'
12'21'83'
13'---62'
14'---41'
"H" + "R" (See Figure 27)
3/8" OD
Tubing (3 GPH)
Tubing (3 GPH)
1/2" OD
24
Figure 8-4: Two Pipe Oil Lines
110547-01 - 4/20
Page 25
FORCEVFOInstallation & Service Manual
9 System Start-Up
WARNING
!
All boilers equipped with burner swing door have a potential hazard which can cause severe property
damage, personal injury or loss of life if ignored. Before opening swing door, turn off service switch to boiler
to prevent accidental firing of burner outside the combustion chamber. Be sure to tighten swing door fastener
completely when service is completed.
A. ALWAYS INSPECT INSTALLATION
BEFORE STARTING BURNER.
1. Verify that the venting, water piping, oil piping,
and electrical system are installed properly.
Refer to Installation Instructions contained in
this manual.
2. Confirm all electrical, water and oil supplies
are turned off at the source and that the vent is
clear from obstructions.
WARNING
!
Completely read, understand and follow all
instructions in this manual before attempting
start up.
B
. FILL HEATING SYSTEM WITH WATER.
NOTICE It is important, especially in a steam
system, to properly remove the oil and dirt from
the system. Failure to clean the system can result
in erratic water lines and surging.
CLEAN HEATING SYSTEM if boiler water or
condensate return water is dirty or if erratic water
lines or surging exist after a few days of boiler
operation.
Refer to Maintenance and Service Instructions
Section of this manual for proper cleaning
instructions for water boilers.
1. HOT WATER BOILERS. Fill entire heating
system with water and vent air from system.
Use the following procedure on a series loop or
multi-zoned system installed as per Figures 4-2
and 4-3, to remove air from system when filling:
a. Close full port ball valve in boiler system
piping.
b. Isolate all zones by closing zone valves or
shut-off valves in supply and return of each
zone(s).
c. Attach a hose to vertical purge valve in
boiler system piping.
(Note - Terminate hose in five gallon bucket
at a suitable floor drain or outdoor area).
d. Starting with one zone at a time, open zone
valve or shut-off valve in boiler supply and
return piping.
e. Open purge valve.
f. Open shut-off valve in cold water supply
piping located between the air scoop and
expansion tank.
g. Allow water to overflow from bucket until
discharge from hose is bubble free for 30
seconds.
h. When zone is completely purged of air,
close zone valve or shut-off valve. Open
zone valve to the next zone to be purged.
Repeat this step until all zones have been
purged. At completion, open all zone
valves.
i. Close purge valve, continue filling the
system until the pressure gauge reads
12 psi. Close shut-off valve in cold water
supply piping.
WARNING
!
The maximum operating pressure of this boiler
is posted on the ASME Data Label located
on the top of the boiler. Never exceed this
pressure. DO NOT plug safety or relief valve.
NOTICE If make-up water line is equipped with
pressure reducing valve, system will automatically
fill to 12 psi. Follow fill valve manufacturer's
instructions.
j. Open full port ball valve in boiler system
piping.
k. Remove hose from purge valve.
l. Confirm that the boiler and system have no
water leaks.
C. CHECK CONTROLS, WIRING AND
BURNER to be sure that all connections are tight
and burner is rigid, that all electrical connections
have been completed and fuses installed, and
that oil tank is filled and oil lines have been tested.
D. ADJUST CONTROL SETTINGS with burner
service switch turned “ON”.
1. SET ROOM THERMOSTAT about 10°F below
room temperature.
2. PRESS RED RESET BUTTON on Primary
Control, hold button for one (1) second and
release to reset primary control.
110547-01 - 4/20
25
Page 26
9 System Start-Up (continued)
3. CHECKOUT
Put the system into operation and observe
at least once complete cycle to make sure
that the controller operates properly. See
Troubleshooting Section to use LED to assist in
determining system operation.
E. ADJUST OIL BURNER BEFORE STARTING.
1. CHECK BURNER SETTINGS and readjust if
necessary, see Burner Specifications,Table
15-1 at the rear of this manual.
F.START OIL BURNER.
1. Open vent fitting on fuel pump.
2. TURN ‘ON’ BURNER service switch and
allow burner to run until oil flows from vent
fitting in a SOLID stream without air bubbles
for approximately 10 seconds.
3. Close vent fitting and burner flame should
start immediately after prepurge is completed.
Prepurge prevents burner flame until 10
seconds has elapsed after initial power is
applied to burner. During prepurge the motor
and igniter will operate but the oil valve will
remain closed. Refer to Oil Primary Control
Instructions for more details.
4. Adjust oil pressure.
a. When checking a fuel unit's operating
pressure, a reliable pressure gauge may
be installed in either the bleeder port or the
nozzle port.
b. Locate oil pressure adjusting screw and
turn screw to obtain proper pump pressure,
refer to Table 15-1 at the rear of this manual.
c. To check the cutoff pressure, deadhead a
reliable pressure gauge onto the copper
connector tube attached to the nozzle port.
Run the burner for a short period of time.
Shut the burner off. The pressure should
drop and hold.
d. Remove the gauge and install bleeder port
and/or reconnect the nozzle port line.
G.ADJUST OIL BURNER WHILE OPERATING.
(flame present)
1. SET ROOM THERMOSTAT about 10°F below
room temperature.
2. PRESS RED RESET BUTTON on Oil Primary
Control and release.
3. READJUST THE HEAD SETTING only if
necessary.
FORCEVFOInstallation & Service Manual
4. ADJUST DRAFT REGULATOR for a draft of
-0.02" (water gauge) over the fire after chimney
has reached operating temperature and while
burner is running.
WARNING
!
DO NOT loosen or remove any oil line fittings
while burner is operating.
5. READJUST THE AIR SETTING on the burner
for a light orange colored flame while the draft
over the fire is -0.02". Use a smoke tester and
adjust air for minimum smoke (not to exceed
#1) with a minimum of excess air. Make final
check using suitable instrumentation to obtain a
CO
of 11.5 to 13.0% with draft of -0.02" (water
2
gauge) in fire box. These settings will assure
a safe and efficient operating condition. If the
flame appears stringy instead of a solid fire, try
another nozzle of the same type. Flame should
be solid and compact. After all adjustments are
made, recheck for a draft of -0.02" over the fire.
6. FLAME FAILURE
The FORCEVFO boiler controls operate the
burner automatically. If for unknown reasons
the burner ceases to fire and the reset button
on the primary control has tripped, the burner
has experienced ignition failure. Refer to Oil
Primary Control features, Paragraph I, Step 2 of
this Section and Section XIII, Troubleshooting,
Paragraph B. If the failure re-occurs, call
your heating contractor immediately before
pressing the reset button.
!
WARNING
DO NOT attempt to start the burner when
excess oil has accumulated, when the boiler is
full of vapor, or when the combustion chamber
is very hot.
H. CHECK FOR CLEAN CUT OFF OF
BURNER.
1. AIR IN THE OIL LINE between fuel unit
and nozzle will compress when burner is on
and will expand when burner stops, causing
oil to squirt from nozzle at low pressure as
burner slows down and causing nozzle to drip
after burner stops. Usually cycling the burner
operation about 5 to 10 times will rid oil line of
this air.
26
110547-01 - 4/20
Page 27
9 System Start-Up (continued)
FORCEVFOInstallation & Service Manual
2. IF NOZZLE CONTINUES TO DRIP, repeat
Paragraph H, No. 1 above. If this does not
stop the dripping, remove cut-off valve and
seat, and wipe both with a clean cloth until
clean, then replace and readjust oil pressure.
If dripping or after burn persist replace fuel
pump.
I.TEST CONTROLS.
1. Check thermostat operation. Raise and lower
thermostat setting as required to start and stop
burner.
WARNING
!
Before installation of the boiler is considered
complete, the operation of all boiler controls
must be checked, particularly the primary
control and high limit control.
2. VERIFY OIL PRIMARY CONTROL FEATURES using procedures outlined
in Instructions furnished with control or
instructions provided with burner.
3. CHECK HIGH LIMIT
e. Check operating control on boiler
applications equipped with tankless
heater(s). With burner off, draw hot water
until burner starts, then turn off hot water
and check burner shut-down.
J. IF CONTROLS MEET REQUIREMENT outlined
in Paragraph I.
1. Allow boiler to operate for approximately 30
minute, confirm the boiler and system have no
leaks.
K. IF CONTROLS DO NOT MEET
REQUIREMENTS outlined in Paragraphs I-1
thru I-6, replace control and repeat checkout
procedures.
Figure 9-1: Adjusting Fuel Pump Pressure
a. Adjust system thermostat(s) to highest
setting.
b. Allow burner to run until boiler water
temperature exceeds high limit setting. The
burner should shut down and circulators
continue running.
c. Allow the temperature to drop below control
setting. The burner must restart.
d. Boiler installation is not considered
complete until this check has been made.
110547-01 - 4/20
27
Page 28
10 Operating
FORCEVFOInstallation & Service Manual
A. HydroStat 3250 PLUS SEQUENCE OF
OPERATION
IMPORTANT This boiler is equipped with
a feature that saves energy by reducing the
boiler water temperature as the heating load
decreases.
This feature is equipped with an override which is
provided primarily to prevent the use of an external
energy management system that serves the same
function. THIS OVERRIDE MUST NOT BE USED
UNLESS AT LEAST ONE OF THE FOLLOWING
CONDITIONS IS TRUE:
• An external energy management system is installed
that reduces the boiler water temperature as the
heating load decreases.
• This boiler is not used for any space heating.
• This boiler is part of a modular or multiple boiler
system having a total input of 300.000 BTU.HR or
greater.
• This boiler is equipped with a tankless coil.
1. Setting the Control
a. Setting the High Limit: The high limit is
factory set at 190F. To adjust, turn the
HI TEMP Dial A until the desired setting
is displayed. (Setting range: 100-220F).
b. Setting the Low Limit: The low
limit is designed to maintain temperature
in boilers equipped with tankless coils
used for domestic hot water. The low limit
is factory set to OFF. Prior to adjusting,
remove the jumper (not equipped on all
units) B. Then turn the LP TEMP Dial C
clockwise until the desired
temperature is displayed. For proper
operation, the low temperature limit
setting should be least 10 below the high
limit setting. NOTE: For cold start operation, the low limit must be turned
OFF.
IMPORTANT: If low limit temperature cannot be set
above 140F, remove jumper B. (Setting range: OFF or
110 -200F).
c. Setting the Economy Feature: The
Economy Feature is factory set for a 1
zone heating system. To adjust, turn the
ECONOMY Dial D until the number
displayed equals the number of heating
zones. Do not include indirect water
heaters in the number of heating zones.
The Economy Feature conserves fuel
by reducing boiler temperature (see
“How Thermal Targeting Works”.
If the heating system is unable to
supply needed heat to the house,
the ECONOMY Dial should be turned
lower setting (example: In a three zone
house, turn the dial to 2 or 1.) Conversely,
if the boiler provides adequate heat,
added fuel savings can be achieved
by selecting a higher setting (example:
4 or 5). If the heating and indirect water
heater signals were not separated when
wiring the control, the Economy Feature
should be turned OFF to ensure the boiler
supplies adequate temperature to heat
the indirect tank.
d. Setting the Zone/Indirect Switch: See
WIRING.
Setting
Off
Disables economy function. Will allow boiler to re until hi-limit temp is reached
and re-re with a 10 subtractive dierential
LO
Provides lowest level of fuel savings. Use this setting only if the house does not
stay warm at higher settings.
1
Recommended setting for single zone systems
2
Recommended setting for Two zone systems
3
Recommended setting for Three zone systems
4
Recommended setting for Four zone systems
5
Recommended setting for Five zone systems
HI
Provides highest level of fuel savings
e. Optional Features: NOTE: The program
Mode-Pro - is accessed by turning the LP
TEMP dial to position just above Off.
2. Thermal Pre-Purge: Thermal Pre-Purge
is designed to maximize boiler efficiency.
When activated, the control will supply latent
heat that may remain in the boiler from a
previous run cycle to the heating zone that
is now calling. The control monitors how quickly the boiler temperature is
declining and activates the burner only
when it determines that the latent heat
is insufficient to satisfy the call. During
the purge cycle, the display will indicate Pur.
This feature works with single-zone and multi-zone heating systems utilizing
circulators or zone valves. No change in
wiring is needed.
To activate Thermal Pre-Purge
• Turn the LO TEMP dial to access the
Program Mode - indicated in the display as
Pro.
• Turn the HI TEMP dial to select feature 1.
• Push the Test/Setting Button to turn Thermal
Pre-Purge ON or OFF.
• Reset LO TEMP and HI TEMP settings to
desired temperatures.
28
110547-01 - 4/20
Page 29
10 Operating (continued)
3. Degrees Fahrenheit or Celsius: The control has the ability to operate in degrees Fahrenheit or Celsius. When
operating in Celsius, a c will appear in
the display next to the temperature when
ever the temperature is below 100
degrees.
To change between degrees Fahrenheit and
degrees Celsius
• Turn the LO TEMP dial to access the
Program Mode - indicated in the display as
Pro.
• Turn the HI TEMP dial to select feature 2.
• Push the Test/Setting Button to c for
Celsius or F for Fahrenheit.
• Reset LO TEMP and HI TEMP settings to
desired temperatures.
4. Manual Reset Low Water Cut-Off:
The low water cut-off operation on the
HydroStat can be set to operate in automatic
(default) or manual reset mode. When in
manual reset mode, the control will shut-down
the burner immediately when low water
condition is detected. If the low water
condition is sustained for 30 seconds, the low
water light will blink,indicating that the
control has locked out the burner. The
control can only be reset by pushing the Test
Settings button on the top of the control. The
manual reset feature meets CSD-1 code
requirements.
IMPORTANT: The system must be checked by a
qualified heating professional prior to resuming
operation.
WARNING: DO NOT ADD WATER UNTIL THE
BOILER HAS FULLY COOLED.
To activate Manual Reset LWCO mode
• Turn the LO TEMP dial to access the
Program Mode - indicated in the display as
Pro
• Turn the HI TEMP dial to select feature 3
• Push the Test/Setting Button to A for
Automatic Reset Mode
• Reset LO TEMP and HI TEMP settings to
desired temperatures.
To Test the Manual Reset Feature: Press and hold the Test/Settings button located on the
top of the control for 30 seconds to simulate a low water condition. After 30
seconds, the Low Water light will blink indicating that the control is locked out.
To reset the lock-out condition, press the Test/
Setting button momentarily.
FORCEVFOInstallation & Service Manual
5. Circulator Activation OptionsWhen in the default mode, the HydroStat
activates the circulator (C1/C2 contacts) on
calls to TT. The control can be programmed
to activate the circulator on calls to ZC/ZR in
place of, or in addition to TT.
To change how the Circulator is activated
• Turn the LO TEMP dial to access the
Program Mode - indicated in the display as
Pro.
• Turn the HI TEMP dial to select feature 4.
• Push the Test/Setting Button to select.
between the following options:
A - Circulator on TT call only
b - Circulator on ZC/ZR calls
C - Circulator on both TT & ZC/ZR calls
• Reset LO TEMP and HI TEMP settings to
desired temperatures.
6. Circulator Hold Off (Enhanced Condensing
Protection)
To reduce the potential for condensing, On
a call for heat the control will allow the boiler to heat to 125F prior to energizing
the circulator. Once energized, the circulator
will remain on for the duration of the heating
call unless the boiler temperature drops below
115F. If this occurs, the circulator will
re-energize when the boiler returns to 125F.
Circulator Hold Off will expire after 15
minutes.
To activate Circulator Hold Off
• Turn the LO TEMP dial to access the
Program Mode - indicated in the display as
Pro.
• Turn the HI TEMP dial to select feature 5.
• Push the Test/Setting Button to Circulator
Hold Off ON or OFF.
• Reset LO TEMP and HI TEMP settings to
desired temperatures.
7. Setting the Well Type (Elctro-Well vs. Standard Immersion Well)
When used to replace older temperature only controls, the HyrdroStat can be installed
on the existing well. (The Hydrolevel Elctro Well is required to activate low water cut-off
operation. Older wells may contain hardened
heat transfer grease or other contaminants
that could interfere with metal-to-metal
continually between the sensor head and the
inside of the well. Insufficient contact could
lead to false low water conditions and burner
shut downs. Setting the well type to Standard Well prevents the possibility of
this occurring.
110547-01 - 4/20
29
Page 30
10 Operating (continued)
To change the well type
• Turn the LO TEMP dial to access the
Program Mode - indicated in the display as
Pro.
• Turn the HI TEMP dial to select feature 8.
• Push the Test/Setting Button to select A for
Electro-Well or b for Standard Well.
NOTE: To ensure that the low water cut-off is always
active when the control is installed on an ElectroWell, setting b will ONLY be available when installed
on a standard well. The HydroStat sensor checks to
determine if a standard well is used by looking for low
resistance to ground, a condition that can only exist
with a standard well. If you are installing on a standard
well and either Low Water LED’s are on, setting b
will not be available. Check to see if the inside of
the well tube is badly oxidized or contaminated with
heat transfer grease. It may be necessary to clean
the well to allow for setting b to be selected (See
Troubleshooting Guide for more information).
8. High Limit DifferentialWhen the Economy feature is on, the
control’s Thermal Targeting feature actively sets varying differentials based on
system conditions. This option allows for
selecting a 10, 20 or 30 degree fixed
differential when the Economy feature
is turned OFF. These optional differential
settings are subtractive from the HIGH LIMIT
setting. Note: If the Economy feature in on, this setting will be overridden by the control’s
Thermal Targeting function.
To change the high limit differential
• Turn the LO TEMP dial to access the
Program Mode - indicated in the display as
Pro.
• Turn the HI TEMP dial to select feature 9.
• Push the Test/Setting Button to select a
high limit differential of 10, 20, or 30.
FORCEVFOInstallation & Service Manual
30
110547-01 - 4/20
Page 31
10 Operating (continued)
FORCEVFOInstallation & Service Manual
Dial SettingFeatureOptionsDescription
1Thermal Pre-Pruge
2Fahrenheit or Celsius
3
4Circulator Options
5Circulator Hold Off
6
7
8Well Type
9High Limit Differential
dEF
LWCO Manual or
Automatic Reset
Not available on this
control
Not available on this
control
Restore Factory De-
faults
OFF
OFF
NOTE: If the HydroStat is factory-equipped on a boiler, some options may be set differently from the
default settings. Not all features are available on older HydroStat models.
9. Restore Factory Default Settings
To restore all features to the factory default settings (see following chart for
default settings)
a. Turn the LO TEMP dial to access the Program Mode - indicated in the
display as Pro
b. Turn the HI TEMP dial to select feature
dEF
c. Push the Test/Setting Button to Y
to reset all features to the default settings
d. Reset LO TEMP and HI TEMP settings
to desired temperatures.
10. LED Legend and Test/Settings Buttona. TEMP ACTIVE Indicates that the Fuel Smart HydroStat control is
powered and that the temperature
function is active.
b. TEMP HI TEMP Illuminates when the boiler water temperature reaches
the high limit setting. It will remain
lit until the water temperature falls 10. The Fuel Smart HydroStat prevents burner operation while this
LED is on. See Differential explanation.
ON
F
C
A
b
A
b
c
ON
A
b
10
20
30
Y
N
Default
Setting
Purge Inactive
Purge Active
Degrees Fahrenheit
Degree Celcius
Automatic Reset
Manual Reset
Circulator operation on TT call only
Circulator operation on ZC/ZR call only
Circulator operation on call from either
c. LWCO ACTIVE Indicates that the low
water cut-off (LWCO) function of the
Fuel Smart HydroStat is active. When the
control is installed with a Hydrolevel
Electro-WellTM, this LED will be on at all
times when the control is powered.
IMPORTANT: If the control is installed with
a well other than the Elctro-WellTM, this LED
will no illuminate indicating that the control
is not providing low water cut- off functionality.
d. LWCO LOW WATER Indicates that
the boiler is in a low water condition.
The HydroStat control will prevent burner
operation during this condition. If the
LOW WATER light is blinking, the control has been programmed to provide
lockout protection in the event a low water
condition is detected (see Manual Reset
Low Water Cut-Off). Pressing the TEST/
SETTINGS button will reset the control.
IMPORTANT: The system must be checked by a
qualified heating professional prior to resuming
operation.
110547-01 - 4/20
31
Page 32
10 Operating (continued)
FORCEVFOInstallation & Service Manual
WARNING
!
Allow the boiler to fully cool before adding water.
e. ECONOMY ACTIVE Indicates that
the Thermal Targeting function is active
and the Fuel Smart HydroStat will reduce
boiler temperature to conserve fuel. The
Economy feature is activated using the
ECONOMY dial. (See “How Thermal
Targeting Works” for more information).
f. ECONOMY TARGET When the Economy feature is active, the Fuel
Smart HydroStat continually sets target temperature below the high limit setting to maximize fuel
efficiency. When the boiler water reaches the target temperature, the LED
illuminates and the burner will shut
down. The boiler water will continue
to circulate and heat the house as long as
the thermostat call continues. The LED will
stay lit until the boiler temperature drops below the differential set point
at which point the boiler will be allowed to
fire again. See Differential explanation.
NOTE: This LED illuminates regularly during
normal boiler operation.
g. TEST/TESTING Button
To Test Low Water Cut-Off: Press and hold the Test/Settings button for 5
seconds. The display will read LCO.
LWCO TEST LCO
The red Low Water light should illuminate and the
burner circuit (B1 and B2) should de-energize.
NOTE: The control must be installed with a Hydrolevel
Electro-WellTM for low water cut-off functionality.
To View Current Settings: Press and release the Test/
Settings Button in short intervals to sequentially
display the following settings:
HIGH LIMIT SETTING HL
▼
LOW LIMIT SETTING LL
▼
ECONOMY SETTING ECO
▼
CURRENT TARGET TEMPERATURE 000
The display will return to boiler temperature (default) if
Test/Settings Button is not pressed for 5 seconds.
32
110547-01 - 4/20
Page 33
10 Operating (continued)
Important Product Safety Information:
Refractory Ceramic Fiber Product
Some boiler components contain refractory ceramic fibers (RCF). RCF has
been classified as a possible human carcinogen. When exposed to
temperatures above 1805°F, such as during direct flame contact, RCF
changes into crystalline silica, a known carcinogen. When disturbed as a
result of servicing or repair, these substances become airborne and, if
inhaled, may be hazardous to your health.
AVOID BREATHING FIBER PARTICULATES AND DUST
Precautionary Measures:
FORCEVFOInstallation & Service Manual
WARNING
• Do not remove or replace RCF parts or attempt any service or repair work involving RCF
without wearing the following protective gear:
1. A National Institute for Occupational Safety and Health (NIOSH) approved air-purifying
respirator equipped with 100-series particulate filter, as a minimum
2. Long sleeved, loose fitting clothing
3. Gloves
4. Eye Protection
• Dampen RCF to be removed with light water spray to prevent fibers from becoming
airborne.
• Take steps to assure adequate ventilation.
• Wash all exposed body areas gently with soap and water after contact.
• Wash work clothes separately from other laundry and rinse washing machine after use to
avoid contaminating other clothes.
• Discard used RCF components by sealing in an airtight plastic bag. RCF and crystalline silica
are not classified as hazardous wastes in the United States and Canada.
First Aid Procedures:
• If contact with eyes: Flush with water for at least 15 minutes. Seek immediate medical
attention if irritation persists.
• If contact with skin: Wash affected area gently with soap and water. Seek immediate
medical attention if irritation persists.
• If breathing difficulty develops: Leave the area and move to a location with clean fresh air.
Seek immediate medical attention if breathing difficulties persist.
• Ingestion: Do not induce vomiting. Drink plenty of water. Seek immediate medical
attention.
110547-01 - 4/20
33
Page 34
11 Maintenance and Service Instructions
FORCEVFOInstallation & Service Manual
A. MAINTENANCE OF LOW WATER CUT-OFF
DEVICES
!
WARNING
Probe and float type low water cut-off devices
require annual inspection and maintenance.
1. PROBE TYPE LOW WATER CUT-OFF
Although these devices are solid state in their
operation, the probe is exposed to possible
contamination in the boiler water and subject
to fouling.
It is important to physically remove the probe
from the boiler tapping annually and inspect
that probe for accumulation of scale or
sediment.
Follow these steps to inspect, clean and/or
replace the probe:
a. Turn off electric service to the boiler.
b. Drain boiler water to a level below the
tapping for the probe.
c. Disconnect wiring connections between the
low water cut-off control and the probe.
d. Remove the low water cut-off control from
the probe.
DANGER
!
Assure that the boiler is at zero pressure before
removing the LWCO probe. DO NOT rely on the
pressure gauge to indicate that the boiler is at
zero pressure. Open the safety valve to relieve
all internal pressure prior to proceeding. Safety
valve discharge piping must be piped such that
the potential for burns is eliminated.
e. Unscrew the probe from the boiler tapping.
f. Inspect that portion of the probe that is
exposed to the boiler water for a scale or
sediment buildup.
g. Light deposits may be removed by wiping
the probe with a damp cloth. Wiping the
probe with a cloth soaked in vinegar will
remove more tenacious lime deposits. The
most stubborn deposits may be removed
from the probe by using a diluted amount, 3
parts of water to 1 part of phosphoric acid
(H
Exercise caution when handling phosphoric
acid and follow the instruction label on its
container.
h. Clean the pipe threads of the probe to
remove old, hardened pipe dope and other
foreign matter.
2PO4
).
!
CAUTION
34
i. Apply a moderate amount of good quality
pipe dope to the pipe threads on the probe,
leaving the two end threads bare. DO NOT
use PTFE (Teflon) tape.
j. Screw the probe into the boiler tapping.
k. Mount the low water cut-off control on the
probe.
l. Reconnect the control to probe wiring.
m. Fill the boiler to its normal waterline.
n. Add boiler water treatment compound as
needed (refer to Paragraph B.).
o. Restore electric service to the boiler.
p. Fire burner to bring the water in the boiler to
a boil to drive off free oxygen.
q. WARNING — BEFORE RETURNING
BOILER TO SERVICE: Follow the low water
cut-off check out procedure.
B. BOILER AND SYSTEM CLEANING
INSTRUCTIONS FOR TROUBLE FREE
OPERATION
NOTICE Check with local authorities or consult
local water treatment services for acceptable
chemical cleaning compounds.
1. WATER BOILERS
a. Filling of Boiler and System — General —-In
a hot water heating system, the boiler and
entire system (other than the expansion
tank) must be full of water for satisfactory
operation. Water should be added to the
system until the boiler pressure gauge
registers 12 psi. To insure that the system
is full, water should come out of all air vents
when opened.
b. Boiling Out of Boiler and System. The oil
and grease which accumulate in a new
hot water boiler can be washed out in the
following manner.
i. Remove relief valve using extreme care
to avoid damaging it.
ii. Add an appropriate amount of
recommended boil out compound.
iii. Replace relief valve.iv.Fill the entire system with water.
v. Start firing the boiler.
vi. Circulate the water through the entire
system.
vii. Vent the system, including the radiation.
viii. Allow boiler water to reach operating
temperature, if possible.
110547-01 - 4/20
Page 35
FORCEVFOInstallation & Service Manual
11 Maintenance and Service Instructions (continued)
ix. Continue to circulate the water for a few
hours.
x. Stop firing the boiler.
xi. Drain the system in a manner and
to a location that hot water can be
discharged with safety.
xii. Remove plugs from all available returns
and wash the water side of the boiler as
thoroughly as possible, using a highpressure water stream.
xiii. Refill the system with fresh water.
c. Add appropriate boiler water treatment
compounds as recommended by your
qualified water treatment company.
d. Make pH or Alkalinity Test.After boiler and system have been cleaned
and refilled as previously described, test
the pH of the water in the system. This
can easily be done by drawing a small
sample of boiler water and testing with
hydrion paper which is used in the same
manner as litmus paper, except it gives
specific readings. A color chart on the side
of the small hydrion dispenser gives the
reading pH. Hydrion paper is inexpensive
and obtainable from any chemical supply
house or through your local druggist. The
pH should be higher than 7 but lower
than 11. Add appropriate water treatment
chemicals, if necessary, to bring the pH
within the specified range. With this lower
level of protection, care must be exercised
to eliminate all of the free oxygen in the
system.
e. Boiler is now ready to be put into service.
C. EXCESSIVE MAKE-UP WATER
A leaky system will increase the volume of
make-up water supplied to the boiler which can
significantly shorten the life of the boiler. Entrained
in make-up water are dissolved minerals, salts
and oxygen. When the fresh, cool make-up
water is heated in the boiler the minerals fall
out as sediment, the salts coat the inside of the
boiler, and the oxygen escapes as a gas. The
accumulation of sediment eventually isolates the
water from contacting the cast iron. When this
happens the cast iron in that area gets extremely
hot and eventually cracks. The presence of free
oxygen or chloride salts in the boiler corrodes
the cast iron from the inside. More make-up
water and higher concentrations of contaminants
damage the boiler sooner. Our warranty does
not cover corrosion and sediment-related
damage. Clearly it is in everyone's best interest to
prevent this type of failure. You can do your part
by ensuring that your system is leak-free, keeping
leakage to less than 2 percent of the boiler water
volume each month.
D. ATTENTION TO BOILER WHILE NOT IN
OPERATION
NOTICE If boiler is not used during winter time, it
must be fully drained to prevent freeze damage.
1. Spray inside surfaces with light lubricating or
crankcase oil using gun with extended stem so
as to reach all corners.
2. Always keep the manual fuel supply valve shut
off if the burner is shut down for an extended
period of time.
3. To recondition the heating system in the fall
season after a prolonged shut down, follow the
instructions outlined in Section IX, Paragraphs
A through K.
IMPORTANT
IF, DURING NORMAL OPERATION, IT IS
NECESSARY TO ADD MORE WATER THAT
INDICATION BELOW, CONSULT A QUALIFIED
SERVICE TECHNICIAN TO CHECK YOUR
SYSTEM FOR LEAKS.
Boiler
Series
FORCEVFO-33.004.7
FORCEVFO-43.255.6
FORCEVFO-53.757.2
110547-01 - 4/20
Gallons Per
Month
Gallons Per
Year
WARNING
!
This boiler contains controls which may cause
the boiler to shut down and not restart without
service. If damage due to frozen pipes is a
possibility, the heating system should not be
left unattended in cold weather; or appropriate
safeguards and alarms should be installed on
the heating system to prevent damage if the
boiler is inoperative.
35
Page 36
FORCEVFOInstallation & Service Manual
12 Boiler Cleaning
WARNING
!
All boiler cleaning must be completed with burner service switch turned off. Boilers equipped with burner
swing door have a potential hazard which can cause severe property damage, personal injury or loss of
life if ignored. Before opening swing door, turn off service switch to boiler to prevent accidental firing of
burner outside the combustion chamber. Be sure to tighten swing door fastener completely when service is
completed.
A. CLEAN THE FLUEWAYS (See Figure 12-1).
1. For cleaning from the top:
a. Remove as much vent pipe as necessary
to allow removal of the jacket top panel and
canopy.
b. Remove the jacket top panel.
c. Remove flue baffles.
d. Remove the canopy, being careful not to
damage the gasket.
2. Using a 1¼” diameter wire or fibre bristle brush
(30” handle) clean the flueways. Brush from the
top and/or side using horizontal and diagonal
strokes for best results. DO NOT allow brush to
strike the target wall or liner in the chamber.
B.CLEAN TOP OF BOILER SECTIONS
(if cleaning from the top).
Brush and vacuum the tops of the boiler sections.
C.CLEAN THE COMBUSTION CHAMBERUsing wire or fibre bristle brush, clean crown of
boiler and inside of water legs.
WARNING
!
DO NOT allow brush to strike target wall in the
combustion chamber.
E. REASSEMBLE BOILER
CAUTION
!
DO NOT start the burner unless canopy, vent
pipe, burner swing door and all flue cover
plates are secured in place.
1. Insert the flue baffles.
2. Install the canopy taking care to align the
gasket without blocking the flueways. If gasket
is damaged, replace as needed.
3. Reinstall jacket top panel with #8 x ½" long
sheet metal screws.
4. Reinstall vent pipe on canopy and secure to
collar with sheet metal screws.
5. Close burner swing door. Secure door to front
section with 5/16" lg. bolts.
NOTICE When securing burner swing door make sure
door is drawn-in equally on both sides.
Tighten swing door hardware to provide
adequate seal around perimeter of door.
Use an alternating tightening method from right
to left side cap screw to pull door tight equally.
D.AFTER CLEANING Inspect target wall, burner
swing door insulation for signs of damage. If
damaged, replace as needed.
36
110547-01 - 4/20
Page 37
12 Boiler Cleaning (continued)
FORCEVFOInstallation & Service Manual
Figure 12-1: Cleaning of Boiler Flueways
!
WARNING
The boiler must be connected to an approved chimney in good condition. Serious property damage could
result if the boiler is connected to a dirty or inadequate chimney. The interior of the chimney flue must be
inspected and cleaned before the start of the heating season and should be inspected periodically throughout
the heating season for any obstructions. A clean and unobstructed chimney flue is necessary to allow noxious
fumes that could cause injury or loss of life to vent safely and will contribute toward maintaining the boiler's
efficiency.
110547-01 - 4/20
37
Page 38
13 Troubleshooting
FORCEVFOInstallation & Service Manual
A. COMBUSTION
1. NOZZLES — Although the nozzle is a
relatively inexpensive device, its function is
critical to the successful operation of the oil
burner. The selection of the nozzle supplied
with the FORCEVFO boiler is the result of
extensive testing to obtain the best flame
shape and efficient combustion. Other brands
of the same spray angle and spray pattern
may be used but may not perform at the
expected level of CO2 and smoke. Nozzles are
delicate and should be protected from dirt and
abuse. Nozzles are mass-produced and can
vary from sample to sample. For all of those
reasons a spare nozzle is a desirable item for a
serviceman to have.
2. FUEL LEAKS — Any fuel leak between the
pump and the nozzle will be detrimental to
good combustion results. Look for wet surfaces
in the air tube, under the ignitor, and around
the air inlet. Any such leaks should be repaired
as they may cause erratic burning of the fuel
and in the extreme case may become a fire
hazard.
3. SUCTION LINE LEAKS — Any such leaks
should be repaired, as they may cause erratic
burning of the fuel and in extreme cases may
become a fire hazard. Whatever it takes, The
Oil Must Be Free of Air. This can be a tough
problem, but it must be resolved. Try bleeding
the pump through a clear tube. There must
be no froth visible. There are various test
kits available to enable you to look at the oil
through clear tubing adapted to the supply line
at the pump fitting. Air eliminators are on the
market that have potential. Also, electronic
sight glasses are being used with good
success. At times, new tubing must be run to
the tank or new fittings put on. Just make sure
you get the air out before you leave.
Any air leaks in the fuel line will cause an
unstable flame and may cause delayed ignition
noises. Use only flare fittings in the fuel lines.
4. GASKET LEAKS — If 11.5 to 13.0% CO2
with a #1 smoke cannot be obtained in the
breeching, look for air leaks around the
burner mounting gasket, observation door,
and canopy gasket. Such air leaks will cause
a lower CO2 reading in the breeching. The
smaller the firing rate the greater effect an air
leak can have on CO2 readings.
5. DIRT — A fuel filter is a good investment.
Accidental accumulation of dirt in the fuel
system can clog the nozzle or nozzle strainer
and produce a poor spray pattern from the
nozzle. The smaller the firing rate, the smaller
the slots become in the nozzle and the more
prone to plugging it becomes with the same
amount of dirt.
6. WATER — Water in the fuel in large amounts
will stall the fuel pump. Water in the fuel in
smaller amounts will cause excessive wear on
the pump, but more importantly water doesn’t
burn. It chills the flame and causes smoke and
unburned fuel to pass out of the combustion
chamber and clog the flueways of the boiler.
7. COLD OIL — If the oil temperature
approaching the fuel pump is 40°F or lower,
poor combustion or delayed ignition may
result. Cold oil is harder to atomize at the
nozzle. Thus, the spray droplets get larger and
the flame shape gets longer. An outside fuel
tank that is above grade or has fuel lines in a
shallow bury is a good candidate for cold oil.
The best solution is to locate the tank near the
boiler in the basement utility room or bury the
tank and lines deep enough to keep the oil
above 40°F. Check environmental issues with
local authorities having jurisdiction.
8. FLAME SHAPE — Looking into the
combustion chamber through the observation
port, the flame should appear straight with no
sparklers rolling up toward the crown of the
chamber. If the flame drags to the right or left,
sends sparklers upward or makes wet spots on
the target wall, the nozzle should be replaced.
If the condition persists look for fuel leaks, air
leaks, water or dirt in the fuel as described
above.
9. HIGH ALTITUDE INSTALLATIONS —
Air openings must be increased at higher
altitudes. Use instruments and set for 11.5 to
13.0% CO2.
10. START-UP NOISE — Late ignition is the
cause of start-up noises. If it occurs recheck for
electrode settings, flame shape, air or water in
the fuel lines.
38
110547-01 - 4/20
Page 39
13 Troubleshooting (continued)
FORCEVFOInstallation & Service Manual
11. SHUT DOWN NOISE — If the flame runs out
of air before it runs out of fuel, an after burn
with noise may occur. That may be the result
of a faulty cut-off valve in the fuel pump, or it
may be air trapped in the nozzle line. It may
take several firing cycles for that air to be fully
vented through the nozzle. Water in the fuel or
poor flame shape can also cause shut down
noises.
NOTICE CHECK TEST PROCEDURE. A very good test
for isolating fuel side problems is to disconnect the
fuel system and with a 24" length of tubing, fire out of
an auxiliary five gallon pail of clean, fresh, warm #2 oil
from another source. If the burner runs successfully
when drawing out of the auxiliary pail then the
problem is isolated to the fuel or fuel lines being used
on the jobsite.
B. OIL PRIMARY CONTROL (Oil Primary)
1. Burner (Oil Primary) will not come on.
a. No power to Oil Primary.
b. Oil Primary is in lockout or restricted mode.
Press reset button for one (1) second to exit
lockout. If control has recycled three times
within the same call for heat, it will enter into
restricted mode. To reset from restricted
mode, refer to Section XI, Paragraph I, No.
2 for details.
c. CAD cell seeing light.
d. CAD assembly defective.
e. Control motor relay is stuck closed (see
note below).
2. Burner (control) will light, then shut down after
a short time, then restart after one (1) minute.
a. CAD cell is defective.
b. Air leaking into oil line causing flame out.
c. Defective nozzle causing flame to be
erratic.
d. Excessive airflow or draft causing flame to
leave burner head.
e. Excessive back pressure causing flame to
be erratic.
3. Control locks out after Trial For Ignition (TFI).
a. No oil to burner.
b. Shorted electrodes.
c. Nozzle clogged.
d. Airflow too high.
e. Ignitor module defective.
f. CAD cell defective.
g. Oil valve stuck open or closed.
Note: The Safety Monitoring Circuit (SMC) is
designed to provide lockout in the event
of a stuck or welded motor relay.
NOTICE If flame is not established within 15 seconds
of oil valve actuation (known as Trial For Ignition [TFI])
lockout will occur. Lockout is indicated by a red LED
solid-on located on the oil primary control.
Hard Lockout will occur if the Oil Primary Control
locks-out three (3) times during a call for heat. This is
indicated by red light reset button solid-on.
110547-01 - 4/20
39
Page 40
FORCEVFOInstallation & Service Manual
THIS PAGE IS INTENTIONALLY LEFT BLANK.
40
110547-01 - 4/20
Page 41
FORCEVFOInstallation & Service Manual
14 Service Parts
All FORCEVFO™ Series Boiler Service Parts may be obtained through your local Ferguson branch.
110547-01 - 4/20
41
Page 42
14 Service Parts (continued)
FORCEVFOInstallation & Service Manual
42
Bare Boiler Assembly
110547-01 - 4/20
Page 43
14 Service Parts (continued)
FORCEVFOInstallation & Service Manual
Item
No.
1A
Description
Block Assembly
for Water Includes:
Complete Block
Assembly, Target
Wall Insulation, Coil
Gasket, Coil Cover
Plate/Hardware
Canopy Includes: Canopy, Canopy Gasket
1B
and Hardware
1CCanopy Gasket110272-01111
1GFlue Baffles110276-01234
Combustion Chamber Includes: Target Wall
1H
Insulation, Combustion Chamber Blanket,
Burner Door Insulation
1JBurner Swing Door 104140-01111
Heater Cover Plates &
1K
Gaskets
1LV1-2 Coil6036031111
Rear Heater
Non Heater
Rear Heater-Blank6036032111
Rear Heater-Trapped6036033111
Part
Number
110552-031
110552-041
110552-051
110553-031
110553-041
110553-051
110554-031
110554-041
110554-051
108471-01111
FORCEVFO-3 FORCEVFO-4FORCEVFO-5
110547-01 - 4/20
43
Page 44
14 Service Parts (continued)
FORCEVFOInstallation & Service Manual
44
Water Boilers - Trim and Controls
110547-01 - 4/20
Page 45
14 Service Parts (continued)
FORCEVFOInstallation & Service Manual
Item
No.
2A
2C
2D
2E
Description
Complete Jacket Carton for Water, Rear
Heater
Complete Jacket Carton for Water, NonHeater
Temperature & Pressure Gauge, 1/4" NPT x
2-1/2"
Electro-Well (WN), 1/2" NPT x 1"110555-01111
Electro-Well (WT), 3/4" NPT x 4"110556-01111
HydroStat 3250 Plus (WN) Assembly110557-01111
HydroStat 3250 Plus (WT) Assembly, 3 and
4 Section
FORCEVFO-3-0750.75
FORCEVFO-3-1001.00520.85 x 60B (Hago)Field Provided
FORCEVFO-4-1201.20
FORCEVFO-4-1501.501061.25 x 60B (Hago)Field Provided
FORCEVFO-5-1751.75V1(3)661.50 x 45B (Hago)Installed
FORCEVFO-5-1901.90V1(4)841.35 x 45B (Hago)Field Provided
Rate
GPH
Burner
Model
AFG
Head
(Setting)
V1(0)
Pump
Pressure
140
175
110547-01 - 4/20
47
Page 48
FORCEVFOInstallation & Service Manual
Appendix - Aftermarket Low Water Cut Off (LWCO)
!
WARNING
DO NOT ATTEMPT to cut factory wires to install an aftermarket Low Water Cut Off (LWCO). Only use
connections specifically identified for Low Water Cut Off.
In all cases, follow the Low Water Cut Off (LWCO) manufacturer's instructions.
When
A low water cutoff is required to protect a hot
water boiler when any connected heat distributor
(radiation) is installed below the top of the hot
water boiler (i.e. baseboard on the same floor
level as the boiler). In addition, some jurisdictions
require the use of a LWCO with a hot water boiler.
Where
The universal location for a LWCO on oil hot water
boilers is above the boiler, in either the supply or
return piping. The minimum safe water level of a
water boiler is at the uppermost top of the boiler;
that is, it must be full of water to operate safely.
It is recommended that the LWCO control
is installed above the boiler to provide the
highest level of protection. However, where
the LWCO control is approved by the LWCO
control manufacturer for installation in a high
boiler tapping of a water boiler, the use of the
listed LWCO control is permitted when it is
installed according to the LWCO manufacturer's
instructions.
What Kind
Typically, in residential applications, a probe type
LWCO is used instead of a float type, due to their
relative costs and the simplicity of piping for a
probe LWCO.
Select the appropriate size tee using the LWCO
manufacturer’s instructions. Often, the branch
connection must have a minimum diameter to
prevent bridging between the probe and the tee.
Also, the run of the tee must have a minimum
diameter to prevent the end of the probe from
touching or being located too close to the inside
wall of the run of the tee.
Ideally, manual shutoff valves should be located
above the LWCO and the boiler to allow for
servicing. This will allow probe removal for
inspection without draining the heating system.
Many probe LWCO manufacturers recommend an
annual inspection of the probe.
How to Wire
LWCO’s are available in either 120 VAC or 24
VAC configurations. The 120 VAC configuration
must be applied to oil boilers by wiring it in the
line voltage service to the boiler (after the service
switch, if so equipped).
The presence of water in a properly installed
LWCO will cause the normally open contact of the
LWCO to close, thus providing continuity of the
120 VAC service to the boiler.
It is recommended to supply power to the probe
LWCO with the same line voltage servicing the
boiler as shown below.
How to Pipe
A “tee” is commonly used to connect the probe
LWCO in the supply or return piping, as shown
below.
LWCO Location
48
Wiring of Typical LWCO
110547-01 - 4/20
Page 49
FORCEVFOInstallation & Service Manual
Appendix - Aftermarket Low Water Cut Off (LWCO)
A 24 VAC LWCO is used primarily for gas fired
boilers where a 24 volt control circuit exists within
the boiler. However, a 24 VAC LWCO can only
be used if the boiler manufacturer has provided
piping and wiring connections and instructions to
allow for this application.
Shut off fuel supply. Lower water level until water
level is BELOW the LWCO. Generate a boiler
demand by turning up thermostat. Boiler should
not attempt to operate. Increase the water level
by filling the system. The boiler should attempt to
operate once the water level is above the LWCO.
How to Test
110547-01 - 4/20
49
Page 50
FORCEVFOInstallation & Service Manual
SERVICE RECORD
DATE
SERVICE PERFORMED
50
110547-01 - 4/20
Page 51
FORCEVFOInstallation & Service Manual
SERVICE RECORD
DATE
SERVICE PERFORMED
110547-01 - 4/20
51
Page 52
FORCEVFOInstallation & Service Manual
SERVICE RECORD
DATE
SERVICE PERFORMED
52
110547-01 - 4/20
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.