PROSELECT FORCE02, FORCE03, FORCE04, FORCE05, FORCE06 Installation Manual

...
INSTALLATION, OPERATING
AND
SERVICE INSTRUCTIONS
FORCE™ SERIES
CAST IRON GAS-FIRED BOILER
9700609
For service or repairs to boiler, call your heating contractor. When seeking information on boiler, provide Boiler Model Number and Serial Number as shown on Rating Label.
Boiler Model Number
FORCE
Heating Contractor Phone Number
Address
105941-01 - 11/14
Boiler Serial Number Installation Date
The City of New York requires a Licensed Master Plumber supervise the installation of this product.
The Massachusetts Board of Plumbers and Gas Fitters has approved the Force™ Series Boiler. See the Massachusetts Board of Plumbers and Gas Fitters website, http://license.reg.state.ma.us/pubLic/pl_products/pb_pre_form.asp for the latest Approval Code or ask your local Sales Representative.
The Commonwealth of Massachusetts requires this product to be installed by a licensed Plumber or Gas tter.
The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning product life.
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death, serious injury or substantial property damage.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death, serious injury or substantial property damage.
Table of Contents
I. Pre-Installation .................................... 5
II. Unpack Boiler .....................................6
III. Water Piping and Trim ........................7
IV. Gas Piping .........................................10
V. Venting ..............................................11
VI. Electrical ............................................13
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in moderate or minor injury or property damage.
NOTICE
Indicates special instructions on installation, operation, or maintenance which are important but not related to personal injury hazards.
VII. System Start-up and Checkout ..........16
VIII. Operation ..........................................19
IX. Service and Maintenance ...................21
X. Troubleshooting ................................24
XI. Repair Parts .......................................26
Table 1A: Ratings
Force Gas Ratings
Boiler Model Input (MBH) DOE Heating Capacity (MBH) Net AHRI Rating Water (MBH)
FORCE02 37.5 30 26 82
FORCE03 62 50 43 82
FORCE04 96 78 68 82
FORCE05 130 106 92 82
FORCE06 164 134 117 82
FORCE07 198 164 143 82
FORCE08 232 191 166 82
FORCE09 266 218 190 82
FORCE10 299 244 212 82
(1)
Net AHRI Water Ratings shown are based on a piping and pickup allowance of 1.15. Consult manufacturer before selecting boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc.
2
(1)
AFUE (%)
Table 1B: Dimensions and Connections
Boiler Model
FORCE02 4 ½ ¾ ¾ FORCE03 4 ½ ¾ ¾ FORCE04 5 ½ ¾ ¾ FORCE05 6 ½ ¾ ¾ FORCE06 6 ½ ¾ ¾ FORCE07 7 ¾ ¾ ¾ FORCE08 7 ¾ ¾ ¾ FORCE09 8 ¾ ¾ ¾ FORCE10 8 ¾ ¾ ¾
Supply NPT
(inch)
Electrical Requirements: 120VAC, 60 Hz, 1-ph, less than 12A Maximum Allowable Working Pressure - 50 psi. Boiler shipped from factory with a 30 psi relief valve.
Return NPT
(inch)
Vent (inch) Gas NPT (inch)
Relief Valve
NPT (inch)
NPT (inch)
Table 1C: Weights and Volume
Drain
Boiler Model
FORCE02 220 2.4
FORCE03 270 3.2
FORCE04 320 4.0
FORCE05 370 4.7
FORCE06 420 5.5
FORCE07 470 6.3
FORCE08 520 7.0
FORCE09 570 7.8
FORCE10 620 8.6
Shipping Weight
(lbs)
Water Content
(gal)
3
Figure 1: Minimum Clearance to Combustible Materials
4
I. Pre-Installation
WARNING
Carefully read all instructions before installing boiler. Failure to follow all instructions in proper order can cause personal injury or death.
A. Inspect shipment carefully for any signs of damage.
All equipment is carefully manufactured, inspected and packed. Our responsibility ceases upon delivery of boiler to carrier in good condition. Any claim
for damage or shortage in shipment must be led
immediately against carrier by consignee. No claims for variances or shortages will be allowed by Boiler Manufacturer, unless presented within sixty (60) days after receipt of equipment.
B. Installation must conform to the requirements of the
authority having jurisdiction. In the absence of such requirements, installation must conform to National Fuel Gas Code, ANSI Z223.1/NFPA 54. Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1.
C. Appliance is design certied for installation on
combustible ooring. The boiler must not be installed
on carpeting.
D. Provide clearance between boiler jacket and
combustible material in accordance with local re
ordinance. Refer to Figure 1 for minimum clearance from combustible material for alcove installation. Provide 1/2" clearance from water piping to combustible materials.
E. Provide practical service clearances. A minimum
of 24" from the right side and front jacket panels is recommended for servicing but may be reduced to minimums shown in Figure 1.
F. Install on level oor. For basement installation provide
concrete base if oor is not level or if water may be encountered on oor around boiler.
G. Protect gas ignition system components from
water (dripping, spraying, rain, etc.) during boiler operation and service (circulator replacement, control replacement, etc.).
H. Provide combustion and ventilation air in accordance
with the section "Air for Combustion and Ventilation," of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or applicable provisions of local building codes.
WARNING
Adequate combustion and ventilation air must be provided to assure proper combustion.
The following guideline is based on the National Fuel
Gas Code, ANSI Z223.1/NFPA 54.
1. Determine volume of space (boiler room). Rooms communicating directly with space (through openings not furnished with doors) are considered part of space.
Volume [ft³] = Length [ft] x Width [ft] x Height [ft]
2. Determine Total Input of all appliances in space. Round result to nearest 1,000 Btu per hour (Btuh).
3. Determine type of space. Divide Volume by Total Input.
a. If result is greater than or equal to 50 ft³ per
1,000 Btuh, space is considered an unconned space.
b. If result is less than 50 ft³ per 1,000 Btuh, space
is considered a conned space.
4. Determine building type. A building of unusually tight construction has the following characteristics:
a. Walls and ceiling exposed to outside atmosphere
have a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed and sealed, and;
b. Weather-stripping has been added on openable
windows and doors, and;
c. Caulking or sealants applied in joints around
window and door frames, between sole
plates and oors, between wall-ceiling joints,
between wall panels, at plumbing and electrical penetrations, and at other openings.
5. For boiler located in an unconned space in a building of other than unusually tight construction, adequate combustion and ventilation air is normally
provided by fresh air inltration through cracks
around windows and doors.
6. For boiler located within unconned space in building of unusually tight construction or within conned space, provide outdoor air through two permanent openings which communicate directly or by duct with the outdoors or spaces (crawl or attic) freely communicating with the outdoors. Locate one opening within 12 inches of top of space. Locate remaining opening within 12 inches of bottom of space. Minimum dimension of air opening is 3 inches. Size each opening per following:
5
I. Pre-Installation (continued)
a. Direct communication with outdoors. Minimum
free area of 1 square inch per 4,000 Btu per hour input of all equipment in space.
b. Vertical ducts. Minimum free area of 1 square
inch per 4,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
c. Horizontal ducts. Minimum free area of 1
square inch per 2,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
Alternate method for boiler located within conned
space. Use indoor air if two permanent openings communicate directly with additional space(s) of
sufcient volume such that combined volume of all spaces meet criteria for unconned space. Size each
opening for minimum free area of 1 square inch per 1,000 Btu per hour input of all equipment in spaces, but not less than 100 square inches.
7. Ventilation Duct Louvers and Grilles. Equip outside openings with louvers to prevent entrance of rain and snow, and screens to prevent entrance of insects
and rodents. Louvers and grilles must be xed in
open position or interlocked with equipment to open automatically before burner operation. Screens must not be smaller than ¼ inch mesh.
Consider the blocking effect of louvers, grilles and
screens when calculating the opening size to provide the required free area. If free area of louver or grille is not known, assume wood louvers have 20-25 percent free area and metal louvers and grilles have 60-75 percent free area.
I. Do not install boiler where gasoline or other
ammable vapors or liquids, or sources of
hydrocarbons (i.e. bleaches, cleaners, chemicals, sprays, paint removers, fabric softeners, etc.) are used or stored.
II. Unpack Boiler
CAUTION
Do not drop boiler. Do not bump boiler jacket
against oor.
A. Move boiler to approximate installed position.
B. Remove all crate fasteners.
C. Lift outside container and remove with all other
inside protective spacers and bracing. Save two of the wooden slats from the container sleeve for use in Steps E and F.
6
D. Remove all boiler hold-down fasteners.
E. Tilt the boiler to one side and slide a wooden slat under
the two raised feet.
F. Tilt the boiler to the other side and slide another
wooden slat under the two raised feet.
G. Slide the boiler forward or backward off the skid using
the two wooden slats as runners.
H. Move boiler to its permanent location.
III. Water Piping and Trim
WARNING
appropriate valves to prevent chilled medium from entering boiler. See Figure 3.
Failure to properly pipe boiler may result in improper operation and damage to boiler or building.
A. Design and install boiler and system piping to
prevent oxygen contamination of boiler water.
Oxygen contamination sources are system leaks
requiring addition of makeup water, ttings, and
oxygen permeable materials in distribution system. Eliminate oxygen contamination by repairing system
leaks, repairing ttings, and using non-permeable
materials in distribution system.
B. Install circulator with anges, gaskets and bolts
provided.
C. Install Safety Relief Valve. See Figure 2. Safety Relief
Valve must be installed with spindle in vertical position.
WARNING
Safety relief valve discharge piping must be
piped near oor to eliminate potential of severe
burns. Do not pipe in any area where freezing could occur. Do not install any shut-off valves.
D. Connect system supply and return piping to boiler.
Refer to Figures 2, 3, 4, & 5. Maintain minimum ½ inch clearance from hot water piping to combustible materials.
E. If boiler is used in connection with refrigeration
systems, boiler must be installed with chilled medium
piped in parallel with the heating boiler using
F. If boiler is connected to heating coils located in
air handling units where they may be exposed to refrigerated air, boiler piping must be equipped with
ow control valves or other automatic means to prevent
gravity circulation of boiler water during operation of cooling system.
G. Use a boiler bypass if the boiler is to be operated
in a system which has a large volume or excessive radiation where low boiler water temperatures may be encountered (i.e. converted gravity circulation system, etc.).
Remove circulator and install pipe tee between
circulator and boiler return along with second tee in supply piping as shown in Figures 4 and 5. Bypass should be same size as the supply and return lines with valves located in bypass and supply outlet as illustrated
in Figures 4 and 5 in order to regulate water ow to
maintain higher boiler water temperatures.
Set by-pass and boiler supply valves to half throttle
position to start. Operate boiler until system water temperature reaches normal operating range.
Adjust valves to provide 180° to 200°F supply water
temperature. Opening the boiler supply valve will raise system temperature, while opening by-pass valve will lower system supply temperature.
H. If it is required to perform a long term pressure
test of the hydronic system, the boiler should rst be
isolated to avoid a pressure loss due to the escape of air trapped in the boiler.
To perform a long term pressure test including the
boiler, ALL trapped air must rst be removed from the
boiler.
A loss of pressure during such a test, with no visible
water leakage, is an indication that the boiler contained trapped air.
Figure 2: Near Boiler Piping
Figure 3: Recommended Piping for Combination
Heating & Cooling (Refrigeration) Systems
7
III. Water Piping and Trim (continued)
8
Figure 4: Recommended Water Piping for Zone Valve Zoned Heating Systems
III. Water Piping and Trim (continued)
Figure 5: Recommended Water Piping for Circulator Zoned Heating Systems
9
IV. Gas Piping
A. Size gas piping. Design system to provide adequate gas
supply to boiler. Consider these factors:
1. Allowable pressure drop from point of delivery to boiler. Maximum allowable system pressure is ½ psig. Actual point of delivery pressure may be less; contact gas supplier for additional information. Minimum gas valve inlet pressure is listed on rating label.
2. Maximum gas demand. Consider existing and expected future gas utilization equipment (i.e. water heater, cooking equipment).
B. Connect boiler gas valve to gas supply system.
1. Use methods and materials in accordance with local plumbing codes and requirements of gas supplier. In absence of such requirements, follow National Fuel Gas Code, ANSI Z223.1/NFPA 54.
2. Use thread (joint) compounds (pipe dope) resistant
to action of liqueed petroleum gas.
3. Install sediment trap, ground-joint union and manual shut-off valve upstream of boiler gas control valve. See Figure 6.
4. All above ground gas piping upstream from manual shut-off valve must be electrically continuous and bonded to a grounding electrode. Do not use gas piping as grounding electrode. Refer to National Electrical Code, ANSI/NFPA 70.
C. Pressure test. The boiler and its gas connection must
be leak tested before placing boiler in operation.
1. Protect boiler gas control valve. For all testing over ½ psig, boiler and its individual shutoff valve must be disconnected from gas supply piping. For testing at ½ psig or less, isolate boiler from gas supply piping by closing boiler's individual manual shutoff valve.
2. Locate leaks using approved combustible gas
detector, soap and water, or similar nonammable solution. Do not use matches, candles, open ames,
or other ignition source.
10
Figure 6: Pilot and Gas Piping
V. Venting
A. Install vent system in accordance with "Venting of
Equipment" of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or applicable provisions of local building codes. Install any of the following for this Force Series Category I, draft hood equipped appliance:
1. Type B or Type L gas vent. Install in accordance with listing and manufacturer's instructions.
2. Masonry or metal chimney. Build and install in accordance with local building codes; or local authority having jurisdiction; or Standard for
Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances, ANSI/NFPA 211.
Masonry chimney must be lined with approved clay
ue lining or listed chimney lining system.
3. Single wall metal vent. Allowed by ANSI Z223.1/ NFPA 54 under very restrictive conditions.
4. Do not use cellular core PVC (ASTM F891), cellular core CPVC, or Radel® (polyphenolsulfone).
5. Do not cover non-metallic vent pipe and ttings
with thermal insulation. Note: Non-metallic vent cannot be used with this boiler.
B. Inspect chimney and remove any obstructions or
restric tions. Clean chimney if previously used for solid
or liquid fuel-burning appliances or replaces.
DANGER
Inspect existing chimney before installing boiler. Failure to clean or replace perforated pipe or tile lining will cause severe injury or death.
C. Install Vent Damper
OPEN THE VENT DAMPER CARTON and remove the
Installation Instructions. READ THE INSTALLATION INSTRUCTIONS THOROUGHLY before proceeding.
The automatic gas control valve supplied on each
Force Series boiler provides the redundancy referenced in the vent damper Installation Instructions.
CAUTION
Do not use one vent damper to control two heating appliances.
1. The vent damper must be the same size as the outlet of the Draft Hood supplied with the boiler (see Table 1B). Unpack the damper carefully - DO NOT FORCE IT CLOSED! Forcing the damper may damage the gear train and void the warranty.
Figure 7: Vent Damper Installation
2. Mount the vent damper assembly onto the canopy/ diverter. (Refer to Figure 7 and to instructions
packed with the vent damper) for specic
instructions). Do not modify either the draft hood or vent damper.
NOTICE
Provide adequate clearance for servicing.
3. Locate vent damper position indicating means to be visible following installation.
WARNING
Provide 6" minimum clearance between damper and combustible construction.
4. Plug the factory harness vent damper connector into damper motor polarized receptacle.
11
V. Venting (continued)
D. Install Vent Connector
1. Install vent connector from vent damper outlet to chimney.
2. Vent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure.
3. Do not connect into same leg of chimney serving an
open replace.
4. Inspect chimney for obstructions or restrictions and remove. Clean chimney if necessary.
5. Vent pipe to chimney must not be smaller than outlet on draft hood or damper. Type B Vent Connector is recommended. The venting system must be arranged so that only the boiler is served by the damper device. Installation per paragraph (C) complies with this provision.
6. Vent pipe should have the greatest possible initial rise above the draft hood consistent with the head room available and the required clearance from adjacent combustible building structure. Vent Pipe should be installed above the bottom of chimney to prevent blockage.
7. Vent pipe should slope upward from draft hood to vent terminal not less than 1/4" per foot.
8. Support horizontal portions of venting system to prevent sagging. Use pipe straps, brackets or hangers spaced 4 ft. or less.
9. Vent pipe must be inserted into but not beyond inside wall of chimney liner. Seal tight between vent pipe and chimney.
10. Do not install non-listed (AGA, CGA, CSA, ETL or UL) vent damper or other obstruction in vent pipe.
WARNING
E. If an Existing Boiler is Removed:
When an existing boiler is removed from a common
venting system, the common venting system is likely to be too large for proper venting of the appliances remaining connected to it.
At the time of removal of an existing boiler, the
following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation:
a. Seal any unused openings in the common venting
system.
b. Visually inspect the venting system for proper
size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion, and other
deciencies which could cause an unsafe condition.
c. Insofar as is practical, close all building doors and
windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maxi mum speed. Do not operate a summer exhaust fan. Close
replace dampers.
d. Place in operation the appliance being inspected.
Follow the Lighting (or Operating) Instructions. Adjust thermo stat so appliance will operate continuously.
e. Test for spillage at the draft hood relief opening after
5 minutes of main burner operation. Use the ame
of a match or candle, or smoke from a cigarette, cigar or pipe.
f. After it has been determined that each appliance
remain ing connected to the common venting system properly vents when tested as outlined above, return
doors, win dows, exhaust fans, replace dampers and
any other gas-burning appliance to their previous condition of use.
g. Any improper operation of the common venting
system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1/NFPA 54. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Chapter 13 of the National Fuel Gas Code, ANSI Z223.1/NFPA 54.
12
VI. Electrical
A. General. Install wiring and electrically bond boiler to
ground in accordance with requirements of authority having jurisdiction, or in absence of such requirements, with the National Electrical Code, ANSI/NFPA 70.
B. Install thermostat. Locate on inside wall
approximately 4 feet above oor. Do not install on outside wall, near replace, or where inuenced by drafts or restricted air ow, hot or cold water pipes, lighting xtures, television, or sunlight. Allow free air
movement by avoiding placement of furniture near thermostat.
C. Wire boiler. Boiler is rated for 120 VAC, 60 hertz,
less than 12 amperes. A separate electrical circuit must be run from the main electrical service with an over-current device/disconnect in the circuit. A service switch is recommended and may be required by some local jurisdictions. Connect to L1, L2 and green ground screw. See Figures 8 and 9.
D. For installations using zone valves provide separate
transformer for zone valve wiring. Consult zone valve manufacturer for assistance.
CAUTION
This boiler contains controls which may cause the boiler to shut down and not restart without service. If damage due to frozen pipes is a possibility, the heating system should not be left unattended in cold weather; or appropriate safeguards and alarms should be installed on the heating system to prevent damage if the boiler is inoperative.
13
VI. Electrical (continued)
14
Figure 8: Wiring Connection Diagram
VI. Electrical (continued)
Figure 9: Schematic Ladder Diagram
15
VII. System Start-up and Checkout
This boiler is equipped with a feature that saves energy by reducing the boiler water temperature as the heating load decreases. This feature is equipped with an override which is provided primarily to permit the use of an external energy management system that serves the same function. THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE:
An external energy management system is installed that reduces the boiler water
temperature as the heating load decreases.
This boiler is not used for any space heating.
This boiler is part of a modular or multiple boiler system having a total input of
300,000 BTU/hr or greater.
This boiler is equipped with a tankless coil.
IMPORTANT
A. Main Burner Check - Check main burners to see
that they were not dislodged during shipment. Rear of burners should be in the vertical slots in the rear of burner tray and the front of the burners should be seated
completely on the orices.
B. Initial start -
1. Fill entire heating system with water and vent air from system. Use the following procedure on a System equipped with zone valves.
a. Close isolation valve in boiler supply piping.
b. Isolate all circuits by closing zone valves or
balancing valves.
c. Attach a hose to hose bib located just below
isolation valve in boiler supply piping. (Note
- Terminate hose in ve gallon bucket, at a suitable oor drain, or outdoor area).
d. Starting with one circuit, open zone valve.
e. Open hose bib.
f. Open ll valve (Make-up water line should be
located directly above isolation valve in boiler supply piping).
g. Allow water to overow from bucket until
discharge from hose is bubble free for 30 seconds.
h. Open zone valve to the second zone to be
purged, then close the rst. Repeat this step until
all zones have been purged, but always have one zone open. At completion, open all zone valves.
i. Close hose bib, continue lling the system
until the pressure gauge reads 12 psi. Close ll
valve. (Note - If make-up water line is equipped with pressure reducing valve, system will
automatically ll to 12 psi. Leave globe valve
open).
j. Open isolation valve in boiler supply piping.
k. Remove hose from hose bib.
16
2. Turn ROOM THERMOSTAT to lowest setting.
3. Be sure that gas to pilot and main burners has been
off for at least ve minutes and vent damper has
been in the open position.
4. Turn "OFF" the electric switch serving boiler.
5. Open valve on main gas line at meter.
6. PURGE AIR FROM GAS PIPING. Adequate
ventilation must be provided and no smoking or
open ame permitted.
7. Turn "ON" electric switch serving boiler.
8. Open Manual Shut-off Valve upstream of Combination Gas Valve.
9. Loosen or remove Inlet Pressure Tap Plug in Combination Gas Valve and when purging is complete, tighten or replace plug. (See Figure 10).
10. Check pipe and ttings from meter to Combination
Gas Valve using soap solution or other approved methods.
Figure 10: Top View of Honeywell Gas Valves
VII. System Start-up and Checkout (continued)
CAUTION
11. Test gas piping and connections between
Combination Gas Valve and manifold, orices, and
pilot piping for leaks after boiler is operating. Use soap solution or other approved method.
C. Check Gas Input to Boiler
1. Input Rate and Maximum Inlet Pressure shown on Rating Label must not be exceeded. Inlet pressure must not be lower than minimum inlet pressure shown on Rating Label.
2. All Rate checks and all adjustments are to be made
while boiler is ring - all other appliances connected
to the same meter as the boiler must be off.
3. With boiler off, water Manometer or water column gauge should be connected to a shut-off valve installed in the 1/8" outlet pressure tap in the gas valve (See Figure 10). By installing gas valve upstream of manometer, gas pressure can be introduced gradually - without shut-off valve; surge of pressure when boiler is turned on, could blow liquid out of manometer. Replace plug in gas valve
when rate check is nished.
4. LP Gas Input:
Adjust Regulator on Gas Valve so that manifold
pressure is 10 inches water column. Turning Regulator Adjusting Screw Clockwise increases pressure. Counterclockwise rotation decreases pressure.
5. Natural Gas Input
a. Approx. Input - Adjust regulator on Gas Valve
so that manifold pressure is 3½ inches water column. Turning Regulator Adjusting Screw Clockwise increases pressure, Counter-clockwise rotation decreases pressure.
Avoid operating this boiler in an environment
where saw dust, loose insulation bers, dry wall
dust, etc. are present. If boiler is operated under these conditions, the burner interior and ports must be cleaned and inspected daily to insure proper operation.
E. Check Pilot Burner Flame.
1. See Figure 12. The pilot burner should be lit only
Figure 11: 1 Inch Main Burner Flame
CAUTION
if thermostat is calling for heat. The pilot burner
produces three (3) ames. The center ame should
be steady, medium hard blue enveloping 3/8 to 1/2 inch of thermocouple.
D. Check Main Burner Flame. See Figure 11. Flame
should have a clearly dened inner cone with no yellow
tipping. Orange-yellow streaks caused by dust should not be confused with true yellow tipping.
Figure 12: Pilot Burner Flame
17
VII. System Start-up and Checkout (continued)
F. Check Ignition System Safety Shut-off Device.
Remove 3-wire plug from gas valve.
If burners do not shut down determine cause of
malfunction. Replace necessary items and check operation.
G. Check Vent Damper Operation. Vent Damper must
be in open position when main burners are operating.
H. Check High Limit Control.
Jumper Thermostat connections 'TW' and 'TR' in
AquaSmart Control. See Figures 8 and 9. Allow burners to operate until shutdown by limit. REMOVE JUMPER.
I. Check Thermostat Operation. Raise and lower
temperature setting to start and stop boiler operation. Adjust thermostat to normal setting.
J. Combustion Chamber Burn-off
1. The mineral wool combustion chamber panels may contain a cornstarch based binder that must be burned out at installation to prevent odors during subsequent boiler operation.
2. Ventilate the boiler room, set the high limit to its maximum setting, set the thermostat to call for heat.
Allow the boiler to re for at least an hour or until
the odor from the cornstarch has dissipated.
3. Return the high limit and thermostat to their desired settings.
K. Review User's Information Manual and system
operation with owner or operator.
L. Post instructions near boiler for reference by owner
and service personnel.
18
VIII. Operation
A. Temperature Limit/LWCO Control
Refer to the HydroStat 3200 Installation Instructions
and Operating Manual included with these instructions.
B. Electronic Ignition Module
See Figure 13 for electronic ignition (EI). Electronic
Ignition Modules with LED indicators. Table 2 cross­references the ignition module terminal designations to the ignition terminal numbers in the wiring ladder diagrams. Table 3 provides green LED status codes and recommended service action where applicable.. See Figure 13 for Location of LED. See Figure 16 for Troubleshooting Guide.
Figure 13: Location of LED
Table 2: Ignition Module Terminal Cross-
Reference
Ignition Module
Terminal Designation
MV 1
MV/PV 2
PV 3
GND 4
24V (GND) 5
24V 6
SPARK SPARK
1. Flame Current Measurement Procedure. See
Figure 14 “Measuring pilot ame current with
micro-ammeter”
a. Pilot ame current in micro amps can be
measured using any standard micro-ammeter by inserting the meter probes into the module holes labeled FLAME CURRENT as shown in Figure 14.
Wiring Ladder Diagram
Terminal Number
Figure 14: Measuring Pilot Flame Current
with Micro-ammeter
b. Flame current must be measured with pilot
valve open/pilot lit but the main valve closed.
c. Disconnect MV lead wire from the module
before measuring ame current. Trying to measure the pilot ame current in series
with the wiring will not yield the accurate reading.
d. The minimum steady pilot ame signal
must be 1 μAmp (microampere) DC (direct current).
e. For reliable operation the ame current
should be 2 μAmp or greater.
f. To ensure adequate ame current:
i. Turn off boiler power at circuit breaker
or fuse box
ii. Clean the ame rod with emery cloth if
required
iii. Make sure electrical connections are
clean and tight, and wiring not damaged, repair/replace as needed
iv. Check for igniter/sensor cracked ceramic
insulator, replace if needed
19
VIII. Operation (continued)
v. Check the pilot ame. It must be blue,
steady and envelop the ame sensing rod
3/8” to ½”.
vi. If needed, adjust pilot ame by
turning the gas valve pilot adjustment screw clockwise to decrease or counterclockwise to increase pilot
ame. Always reinstall pilot adjustment
screw cover and tighten securely upon completion to assure proper gas valve operation.
g. Reconnect MV lead wire to the module
upon satisfactory completion of pilot ame
current measurement.
h. Check the pilot burner operation/ignition
sequence during ignition cycle:
i. Restore boiler power at circuit breaker or
fuse box.
ii. Set thermostat to call for heat. iii. Watch ignition sequence at burner. iv. If spark does not stop after pilot lights,
replace ignition module.
v. If main burners do not light or if main
burners light but system locks out, check the module ground wire and gas control as described in Figure 16 “ Honeywell Electronic Ignition Troubleshooting Guide”.
Table 3: Green LED Flame Codes
Green LED
Flash
a
Code
OFF No “Call for Heat” N/A None
Flash Fast Power up - internal check N/A None
Heartbeat
4 Seconds ON
then “x” ashes
2
3
4 Flame sensed out of sequence
6 Control Internal Error
7 Flame rod shorted to ground
8
a
Flash Code Descriptions:
- Flash Fast: rapid blinking
- Heartbeat: Constant ½ second bright, ½ second dim cycles.
- 4 second solid on pulse followed by “x” 1 second ashes indicates ame current to the nearest µA. This is only available in run mode.
- A single ash code number signies that the LED ashes X times at 2Hz, remains off for two seconds, and then repeats the sequence.
Normal startup - ignition sequence started (including prepurge)
Device in run mode.
“x” = ame current to the nearest µA.
5 minute Retry Delay
- Pilot ame not detected during trial for
ignition
Recycle
- Flame failed during run
Low secondary voltage supply- (below
15.5 Vac)
Indicates Next System Action Recommended Service Action
N/A None
N/A None
Initiate new trial for ignition after retry delay completed.
Initiate new trial for ignition. Flash code will remain through the ignition trial until
ame is proved.
If situation self corrects within 10 seconds, control returns to normal
sequence. If ame out of sequence
remains longer than 10 seconds, control will resume normal operation 1 hour after error is corrected.
Control remains in wait mode. When the fault corrects, control resumes normal operation.
Control remains in wait mode. When the fault corrects, control resumes normal operation.
Control remains in wait mode. When the fault corrects, control resumes normal operation.
If system fails to light on next trial for ignition check gas supply, pilot burner, spark and
ame sense wiring, ame rod contamination or
out of position, burner ground connection.
If system fails to light on next trial for ignition,
check gas supply, pilot burner, ame sense wiring, contamination of ame rod, burner
ground connection.
Check for pilot ame. Replace gas valve if pi­lot ame present. If no pilot ame, cycle “Call
for Heat.” If error repeats, replace control.
Cycle “Call for Heat”. If error repeats, replace control.
Check ame sense lead wire for damage or shorting. Check that ame rod is in proper position. Check ame rod ceramic for cracks,
damage or tracking.
Check transformer and AC line for proper input voltage to the control. Check with full system load on the transformer.
20
IX. Service and Maintenance
Refractory Ceramic Fiber Product
Important Product Safety Information
Warning:
The Repair Parts list designates parts that contain refractory ceramic fibers (RCF). RCF has been classified as a possible human carcinogen. When exposed to temperatures above 1805°F, such as during direct flame contact, RCF changes into crystalline silica, a known carcinogen. When disturbed as a result of servicing or repair, these substances become airborne and, if inhaled,
may be hazardous to your health.
AVOID Breathing Fiber Particulates and Dust
Precautionary Measures:
Do not remove or replace RCF parts or attempt any service or repair work involving RCF without wearing the following protective gear:
1. A National Institute for Occupational Safety and Health (NIOSH) approved respirator
2. Long sleeved, loose fitting clothing
3. Gloves
4. Eye Protection
Take steps to assure adequate ventilation.
Wash all exposed body areas gently with soap and water after contact.
Wash work clothes separately from other laundry and rinse washing
machine after use to avoid contaminating other clothes.
Discard used RCF components by sealing in an airtight plastic bag. RCF and crystalline silica are not classified as hazardous wastes in the United
States and Canada.
First Aid Procedures:
If contact with eyes: Flush with water for at least 15 minutes. Seek
immediate medical attention if irritation persists.
If contact with skin: Wash affected area gently with soap and water.
Seek immediate medical attention if irritation persists.
If breathing difficulty develops: Leave the area and move to a location
with clean fresh air. Seek immediate medical attention if breathing difficulties persist.
Ingestion: Do not induce vomiting. Drink plenty of water. Seek
immediate medical attention.
21
IX. Service and Maintenance (continued)
22
Figure 15: Operating Instructions
IX. Service and Maintenance (continued)
WARNING
Service on this boiler should be undertaken only by trained and skilled personnel from a qualied service agency. Inspections should be performed at intervals specied in this manual. Maintain
manual in a legible condition.
Keep boiler area clear and free of combustible materials, gasoline and other ammable vapors and
liquids.
Do not place any obstructions in boiler room that will hinder ow of combustion and ventilation air.
A. General. Inspection and service should be conducted
annually. Turn off electrical power and gas supply while conducting service or maintenance. Follow instructions TO TURN OFF GAS TO APPLIANCE. See Figure 15.
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
B. Inspect Vent System.
1. Remove obstructions in vent pipe and chimney.
2. Remove soot accumulations with wire brush and vacuum.
3. Repair or replace deteriorated vent pipe and vent accessories.
4. Provide proper support. Repair sags, particularly in horizontal sections.
5. Repair leaking joints.
C. Inspect Boiler Flue Passages for blockage or soot
accumulation.
1. Remove vent pipe, vent damper, blocked vent switch and draft hood.
2. Remove sheet metal screws securing upper front panel. Remove panel by sliding down.
3. Remove sheet metal screws securing Jacket Top Panel. Lift panel and rotate about supply piping until top of boiler is exposed. If piping or wall prevent full rotation of top panel for access to canopy, cut slot into supply opening and remove top panel.
4. Remove carriage bolts securing Canopy to Section Assembly.
5. Using ashlight, examine all ue passageways.
a. If passageways are free of soot and obstruction,
replace canopy, secure and seal.
b. If passageways need cleaning, remove burners
as described in Paragraph D. Using long handle
wire or bristle ue brush and vacuum, brush ueways thoroughly from top of boiler. Replace
canopy and seal.
6. Install new gasket material (See Section XI: Repair Parts). Install canopy.
7. Install Jacket Top Panel, Blocked Vent Switch, Vent Damper, and vent pipe.
D. Clean Main Burners and Firebox.
1. To remove burners for cleaning, changing orices,
or repairs: a. Remove Jacket Lower Front Panel. b. Disconnect pilot tubing at gas valve. c. Disconnect 3-wire plug at the gas valve.
d. Remove wires to ame rollout switch.
e. Remove the burner access panel. f. Mark the location of the pilot main burner on the
manifold if the marking on manifold is missing or obliterated.
g. Hold burner at throat. Lift front of burner to
clear orice. Burner which holds pilot can only
be removed by lifting the burner adjacent to its
right rst.
2. Brush top of burners with a soft bristle brush. Vacuum burners.
3. Check orices. Drilled passageways must be free of
lint or dirt.
4. Vacuum tip of Pilot Burner.
5. Clean rebox by vacuuming. Exercise care not to
damage base insulation.
6. Install burners by reversing procedure used to remove burners in Step 1. Make sure burner with pilot assembly is in same location as original installation.
Check burners to see that they are located properly
in slot at rear of burner tray.
E. Check Operation. Follow steps C through J from
Section VII: System Start-up and Checkout.
F. Lubrication. There are no parts requiring lubrication
by service technician or owner. Circulator bearings are water lubricated.
23
X. Troubleshooting
A. Temperature Limit/LWCO Control
Refer to the HydroStat 3200 Installation Instructions
and Operating Manual included with these instructions.
B. Electronic Ignition Module (see Figure 16)
24
X. Troubleshooting (continued)
"CALL FOR HEAT."
POWER TO
MODULE? (24 V
NOMINAL)
YES
30 SECOND PREPURGE
DELAY?(S8670
ONLY)
YES
SPARK
ACROSS IGNITOR/
SENSOR
GAP?
YES
TURN GAS SUPPLY ON AND RECYCLE "CALL FOR HEAT."
PILOT BURNER
LIGHTS?
YES
SPARK
STOPS WHEN
PILOT IS
LIT?
YES
CHECK LINE VOLTAGE POWER, LOW VOLTAGE TRANSFORMER, LIMIT CONTROLLER, THERMOSTAT (CONTROLLER), AND WIRING. ALSO,
NO
CHECK AIR PROVING SWITCH ON COMBUSTION AIR BLOWER SYSTEM (IF USED) AND THAT THE VENT DAMPER END SWITCH (IF USED) IS MADE.
REPLACE S8670
NO
PULL IGNITION LEAD AND CHECK SPARK AT MODULE.
NO
CHECK IGNITION CABLE, GROUND WIRING, CERAMIC INSULATOR, AND SPARK GAP AND CORRECT. CHECK BOOT OF THE IGNITION CABLE FOR SIGNS OF MELTING OR BUCKLING. TAKE PROTECTIVE ACTION TO SHIELD CABLE AND BOOT FROM EXCESSIVE TEMPERATURES.
CHECK THAT ALL MANUAL GAS VALVES ARE OPEN, SUPPLY TUBING AND PRESSURES ARE GOOD, AND PILOT BURNER ORIFICE IS NOT BLOCKED (PILOT GAS FLOWING). CHECK ELECTRICAL CONNECTIONS BETWEEN MODULE AND PILOT OPERATOR ON GAS CONTROL.
NO
CHECK FOR 24 VAC ACROSS PV-MV/PV TERMINALS ON MODULE, IF VOLTAGE IS OK, REPLACE GAS CONTROL. IF NOT, REPLACE MODULE. NOTE: IT MAY BE NECESSARY TO RECYCLE THE "CALL FOR HEAT" MORE THAN
NOTE: IF CONTROL GOES INTO LOCKOUT OR RETRY DELAY, RESET THE "CALL FOR HEAT." CHECK CONTINUITY OF IGNITION CABLE AND GROUND WIRE. CLEAN FLAME ROD. CHECK ELECTRICAL CONNECTIONS BETWEEN FLAME ROD AND MODULE.
NO
CHECK FOR CRACKED CERAMIC FLAME ROD INSULATOR. CHECK THAT PILOT FLAME COVERS FLAME ROD AND IS STEADY AND BLUE. ADJUST PILOT FLAME. IF PROBLEM PERSISTS, REPLACE MODULE.
SPARK OK? NO
YES
REPLACE MODULE
ONCE TO CLEAR THE PILOT SUPPLY TUBES OF AIR.
MAIN BURNER
LIGHTS?
YES
SYSTEM
RUNS UNTIL "CALL
FOR HEAT"
ENDS?
YES
"CALL FOR HEAT" ENDS
SYSTEM
SHUTS OFF?
Figure 16: Troubleshooting Guide, Honeywell Electronic Ignition (EI)
CHECK FOR 24 VAC ACROSS PV-MV/PV TERMINALS ON MODULE. IF NO VOLTAGE, REPLACE MODULE. CHECK ELECTRICAL CONNECTIONS BETWEEN MODULE AND GAS CONTROL INCLUDING SAFETY CONTROLS WIRED IN THE CIRCUIT. IF
NO
OKAY, REPLACE GAS CONTROL.
NOTE: IF CONTROL GOES INTO LOCKOUT OR RETRY DELAY, RESET THE "CALL FOR HEAT." CHECK CONTINUITY OF IGNITION CABLE AND GROUND WIRE. NOTE: IF GROUND IS POOR OR ERRATIC, SHUTDOWNS MAY OCCUR OCCASIONALLY EVEN THOUGH OPERATION IS NORMAL AT THE TIME OF CHECKOUT.
NO
CHECK THAT PILOT FLAME COVERS FLAME ROD AND IS STEADY AND BLUE. PILOT FLAME MUST NOT BE MOVING AROUND DUE TO OUTSIDE AIR FLOWS, ETC. ADJUST PILOT FLAM OTHER GAS APPLIANCES ON THE SUPPLY ARE OPERATING AT FULL RATE. IF CHECKS ARE OKAY, REPLACE MODULE.
CHECK FOR PROPER THERMOSTAT (CONTROLLER) OPERATION. REMOVE MV LEAD AT MODULE. IF VALVE CLOSES, RECHECK TEMPERATURE CONTROLLER AND WIRING. IF NOT, REPLACE
NO
GAS CONTROL.
E. CHECK GAS PRESSURE MEETS APPLIANCE SPECIFICATIONS WHILE APPLIANCE MAIN BURNER IS ON AND ALL
25
XI. Repair Parts
All Force™ Repair Parts may be obtained by contacting your local Ferguson branch.
Key No.
1A Block Assembly 617190204 617190304 617190404 617190504 617190604 617190704 617190804 617190904 617191004
1B Canopy Gasket Kit 6206001
1C Canopy Assembly 611191021 611191031 611191041 611191051 611191061 611191071 611191081 611191091 611191101
1D Flue Bafes N/A
Description
FORCE02 FORCE03 FORCE04 FORCE05 FORCE06 FORCE07 FORCE08 FORCE09 FORCE10
Blocked Vent Switch Assembly (not shown)
[Quantity] Part Number
71106001
6016058
(6)
(7)
71106001
(8)
71106001
71106001
26
(9)
XI. Repair Parts (continued)
Key
No.
2A Base Wrapper 718600211 718600311 718600411 718600511 718600611 718600711 718600811 718600911 718601011
2B Base Tray 718600291 718600391 718600491 718600591 718600691 718600791 718600891 718600991 718601091
2C
2D Base Front Panel 618600241 618600341 618600441 618600541 618600641 618600741 618600841 618600941 618601041
2E
2F Base Gasket Kit 6206002
2G
2H
2J
Description
Burner Tray Assembly
Burner Access Panel
Base Side Insulation
Base Rear Insulation
Base Leg Assembly
Flame Rollout Switch Assembly (not shown)
FORCE02 FORCE03 FORCE04 FORCE05 FORCE06 FORCE07 FORCE08 FORCE09 FORCE10
718600205 718600305 718600405 718600505 718600605 718600705 718600805 718600905 718601005
718600261 718600361 718600461 718600561 718600661 718600761 718600861 718600961 718601061
72060025 72060035 72060045 72060055 72060065 72060075 72060085 72060095 72060105
[Quantity] Part Number
(2) 720601
(4) 6186001
6016060
27
XI. Repair Parts (continued)
Key
No.
3A
3B Gas Manifold 104810-02 104810-03 104810-04 104810-05 104810-06 104810-07 104810-08 104810-09 104810-10
3C
3D Pilot Burner 8236118
3E
3F Main Burner
Description
Gas Valve (Natural Gas), Honeywell
Gas Valve (LP Gas), Honeywell
Burner Orices -
Natural Gas #47
Burner Orices -
Natural Gas #45
Burner Orices - LP
Gas 1.25mm
Burner Orices - LP
Gas #55
Burner Orices - LP
Gas 3/64"
Pilot Assembly ­Natural Gas
Pilot Assembly - LP Gas
FORCE02 FORCE03 FORCE04 FORCE05 FORCE06 FORCE07 FORCE08 FORCE09 FORCE10
81660145 81660161
81660146 81660160
(2)
822710
---
(2)
822705
---
(1)
8236119
(3)
822711
---
(3)
822708
(2)
8236119
(5)
822711
(5)
822705
---
(4)
8236119
[Quantity] Part Number
---
(7)
822711
(7)
822705
--- ---
(6)
8236119
(9)
822711
(9)
822705
103704-01
103705-01
(8)
8236119
(12)
822710
(12)
822704
(11)
8236119
(14)
822710
(14)
822704
(13)
8236119
822710
---
---
822704
8236119
(16)
(16)
(15)
(18)
822710
(18)
822704
(17)
8236119
3G Pilot Tubing 8236122 8236123
Ground Wire
3H
Assembly
6136054
28
XI. Repair Parts (continued)
Key
No.
4A HydroStat 3200 105943-01
4B
4C
Description
FORCE02 FORCE03 FORCE04 FORCE05 FORCE06 FORCE07 FORCE08 FORCE09 FORCE10
Honeywell S8610M EI Module
Temp/LWCO Sensor
[Quantity] Part Number
100958-02
105944-03
29
XI. Repair Parts (continued)
Key No.
Complete Jacket
5
Kit
Jacket Horizontal
Clip (not shown)
Jacket Vertical Clip (not shown)
30
Description
[Quantity] Part Number
FORCE02 FORCE03 FORCE04 FORCE05 FORCE06 FORCE07 FORCE08 FORCE09 FORCE10
105519-02 105519-03 105519-04 105519-05 105519-06 105519-07 105519-08 105519-09 105519-10
7041920
7041921
XI. Repair Parts (continued)
Key
No.
6A
6B 30 PSI Relief Valve 81660319
6C Drain Valve 806603061
6D Vent Damper 102284-01 102284-02 102284-03 102284-04 102284-05
Description
Temperature/ Pressure Gauge
Grundfos UPS 15­58 Circulator (not shown)
Circulator Flange Kit 1-1/4" (not shown)
FORCE02 FORCE03 FORCE04 FORCE05 FORCE06 FORCE07 FORCE08 FORCE09 FORCE10
100282-04 100282-01
[Quantity] Part Number
102805-02
105640-01
31
XI. Repair Parts (continued)
Common Replacement Parts ( All Sizes)
HydroStat 3200 105943-01
Temp/LWCO HydroStat Sensor 105944-03
HydroLevel ElectroWell 4" Insulation Length 105310-01
HydroLevel ElectroWell 1" Insulation Length 105203-01
Honeywell S8610M EI Module 100958-01
Flame Rollout Switch 80160044
Blocked Vent Switch 80160157
Natural Gas Pilot Assembly - Honeywell Q3481B1206, 36" Lead 103704-01
Propane Gas Pilot Assembly - Honeywell Q3481B1420, 36" Lead 103705-01
½" Natural Gas Valve - Honeywell VR8204C3007 81660145
¾" Natural Gas Valve - Honeywell VR8304P4306 81660161
½" Propane Gas Valve - Honeywell VR8204C3015 81660146
¾" Propane Gas Valve - Honeywell VR8304P4314 81660160
Ground Wire for Pilot 6136054
Description Part Number
32
Loading...