ProMinent Sigma / 2 Basic S2Ba Operating Instructions Manual

Page 1
Operating instructions
P_SI_0074_SW
Diaphragm Motor-Driven Metering Pump Sigma / 2 Basic Type S2Ba
Please carefully read these operating instructions before use! · Do not discard!
The operator shall be liable for any damage caused by installation or operating errors!
Original operating instructions (2006/42/EC)Part no. 985908 BA SI 063 01/14 EN
Page 2
Supplemental instructions
Supplementary information
Fig. 1: Please read!
Read the following supplementary information in its entirety! Should you already know this information, you will benefit more from referring to the operating instructions.
The following are highlighted separately in the document:
n Enumerated lists
Operating guidelines
Outcome of the operating guidelines
ð
- see (reference)
Information
This provides important information relating to the correct operation of the unit or is intended to make your work easier.
Validity
State the identity code and serial number
Safety notes
Safety notes are identified by pictograms - see Safety Chapter.
These operating instructions conform to current EU regulations applicable at the time of publication.
Please state identity code and serial number, which you can find on the nameplate when you contact us or order spare parts. This enables the device type and material versions to be clearly identified.
2
Page 3

Table of contents

Table of contents
Identity code.................................................................................... 4
1
2 Safety chapter................................................................................. 6
3 Storage, transport and unpacking................................................. 11
4 Overview of equipment and control elements............................... 12
5 Functional description.................................................................... 14
5.1 Pump..................................................................................... 14
5.2 Liquid end.............................................................................. 14
5.3 Integral relief valve................................................................ 14
5.4 Multi-layer safety diaphragm................................................. 15
6 Assembly....................................................................................... 16
Installation, hydraulic..................................................................... 18
7
7.1 Basic installation notes.......................................................... 22
8 Installation, electrical..................................................................... 23
9 Start up.......................................................................................... 28
10 Maintenance.................................................................................. 31
11 Repairs.......................................................................................... 34
11.1 Cleaning valves................................................................... 35
11.2 Replacing the diaphragm.................................................... 36
12 Troubleshooting............................................................................. 40
13 Decommissioning.......................................................................... 43
14 Technical data............................................................................... 45
14.1 Performance data................................................................ 45
14.2 Shipping weight................................................................... 46
14.3 Wetted materials................................................................. 47
14.4 Ambient conditions.............................................................. 47
14.4.1 Ambient temperatures...................................................... 47
14.4.2 Media temperatures......................................................... 47
14.4.3 Air humidity...................................................................... 48
14.5 Motor data........................................................................... 48
14.6 Stroke actuator.................................................................... 48
14.7 Stroke control drive............................................................. 48
14.8 Diaphragm rupture sensor.................................................. 48
14.9 Stroke sensor "Sigma"........................................................ 49
14.10 Relay................................................................................. 50
14.11 Gear oil.............................................................................. 50
14.12 Sound pressure level........................................................ 50
14.13 Supplementary information for modified versions............. 50
15 Diagrams for setting the metering capacity................................... 52
16
Dimensional drawings................................................................... 53
17 Motor data sheet standard motor.................................................. 56
18 Liquid ends Sigma/ 2..................................................................... 57
19 Wear parts for Sigma/ 2................................................................. 61
19.1 Standard.............................................................................. 61
19.2 Physiological safety............................................................. 61
20 EC Declaration of Conformity for Machinery................................. 63
21
EC Declaration of Conformity for Machinery Used in Areas at
Risk of Explosion........................................................................... 64
3
Page 4
Identity code
1 Identity code
S2Ba Sigma 2 Basic Type
H Main power end, diaphragm
Type: Capacity
_ _ _ _ _ _
Dosing head material
Performance data at maximum back pressure and type: see nameplate on pump housing
PV PVDF
SS Stainless steel
Seal material
T PTFE seal
Displacement body
S Multi-layer safety diaphragm with optical rupture indicator
A Multi-layer safety diaphragm with diaphragm rupture signalling (contact)
H Diaphragm for hygienic pump head
Dosing head design
0 no valve springs
1 with 2 valve springs, Hastelloy C; 0.1 bar
4 ** with relief valve, FPM seal, no valve spring
5 ** with relief valve, FPM seal, with valve springs
6 ** with relief valve, EPDM seal, no valve spring
7 ** with relief valve, EPDM seal, with valve springs
H Hygienic pump head with tri-clamp connectors (max. 10 bar)
Hydraulic connector
0 Standard threaded connector (in line with technical data)
1 Union nut and PVC insert
2 Union nut and PP insert
3 Union nut and PVDF insert
4 Union nut and SS insert
7 Union nut and PVDF tube nozzle
8 Union nut and SS tube nozzle
9 Union nut and SS welding sleeve
Design
0
With ProMinent®
1
Without ProMinent® logo
F Physiological safety with
regard to wetted mate‐ rials
logo (standard)
FDA No. 21 CFR §177.1550 (PTFE)
FDA No. 21 CFR §177.2510 (PVDF)
M Modified* * order-related design, refer to
order paperwork for pump features
Electric power supply
4
Page 5
S2Ba Sigma 2 Basic Type
Identity code
_ Connection data - refer to nameplate on motor
1 No motor, with B14 flange, size 71 (DIN)
2 No motor, with C 42 flange (NEMA)
3 No motor, with B 5, size 56 (DIN)
Degree of protection
0 IP 55 (standard)
1 Exe design ATEX-T3
2 Exd version ATEX-T4
Stroke sensor
0 No stroke sensor (standard)
2 Pacing relay (reed relay)
3 Stroke sensor (Namur) for haz‐
ardous locations
Stroke length adjustment
0 Manual (standard)
1 With servomotor, 230 V,
50/60 Hz
2 With servomotor, 115 V,
50/60 Hz
3 With control motor 0...20 mA
230 V, 50/60 Hz
4 With control motor 4...20 mA
230 V, 50/60 Hz
5 With control motor 0...20 mA
115 V, 50/60 Hz
6 With control motor 4...20 mA
115 V, 50/60 Hz
FPM = fluorine rubber
** Standard with hose nozzle in the bypass Threaded connection on request.
5
Page 6
Safety chapter
2 Safety chapter
CAUTION! These operating instructions include notes and quotes from
German guidelines relating to the system operator's scope of responsibility. This information does not discharge the oper‐ ator from his responsibility as an operator and is intended only to remind him or make him aware of specific problem areas. This information does not lay claim to being complete, nor applicable to every country and every type of application, nor to being unconditionally up-to-date.
Identification of safety notes
Warning signs denoting different types of danger
The following signal words are used in these operating instructions to denote different severities of danger:
Signal word Meaning
WARNING Denotes a possibly dangerous sit‐
uation. If this is disregarded, you are in a life-threatening situation and this can result in serious inju‐ ries.
CAUTION Denotes a possibly dangerous sit‐
uation. If this is disregarded, it could result in slight or minor inju‐ ries or material damage.
The following warning signs are used in these operating instructions to denote different types of danger:
Warning signs Type of danger
Warning – high-voltage.
Warning – danger zone.
Intended use
n Only use the pump to meter liquid metering chemicals. n In potentially explosive atmospheres in zone 1, device category II 2G,
explosion group II C, only operate the pump with the appropriate nameplate (and the respective EC Declaration of Conformity) for pumps for use in areas at risk of explosion in compliance with Direc‐ tive 94/9/EC in accordance with the European guidelines. The explo‐ sion group, category and degree of protection specified on the label should correspond to or be better than the conditions given in the intended field of application.
n Only pumps with the identity code option "Multi-layer safety diaphragm
with visual rupture display" and "Multi-layer safety diaphragm with rup‐ ture signalling (contact)" are approved for use with flammable feed chemicals, at back pressures of over 2 bar and if the operator takes appropriate safety measures.
n Only pumps with the design "F - Physiological safety with regard to
wetted materials" are approved for use with physiologically harmless applications.
n Only start up the pump after it has been correctly installed and com‐
missioned in accordance with the technical data and specifications contained in the operating instructions.
6
Page 7
Safety chapter
n Observe the general limitations with regard to viscosity limits, chem‐
ical resistance and density - see also ProMinent Resistance List (in the Product Catalogue or at www.prominent.com/en/downloads)!
n All other uses or modifications are prohibited. n Never operate pumps without the relevant nameplate (and the respec‐
tive EC Declaration of Conformity) for pumps for use in atmospheres at risk from explosion in atmospheres potentially at risk from explo‐ sion.
n The pump is not intended for the metering of gaseous media or solids. n The pump is not intended to meter explosive substances and mix‐
tures.
n The pump is not intended for unprotected outside use. n The pump is only intended for industrial use. n The pump should only be operated by trained and authorised per‐
sonnel.
n Observe the information contained in the operating instructions at the
different phases of the device's service life.
Qualification of personnel
Action Qualification
Storage, transport, unpacking Instructed person
Assembly Technical personnel, service
Planning hydraulic installation Qualified personnel who have a
thorough knowledge of oscillating diaphragm pumps.
Hydraulic installation Technical personnel, service
Installation, electrical Electrical technician
Operation Instructed person
Maintenance, repair Technical personnel, service
Decommissioning, disposal Technical personnel, service
Troubleshooting Technical personnel, electrical
technician, instructed person, service
Explanation of the terms:
Technical personnel
A qualified employee is deemed to be a person who is able to assess the tasks assigned to him and recognise possible dangers based on his/her technical training, knowledge and experience, as well as knowledge of pertinent regulations.
Note:
A qualification of equal validity to a technical qualification can also be gained by several years employment in the relevant work area.
Electrical technician
Electrical technicians are deemed to be people, who are able to complete work on electrical systems and recognise and avoid possible dangers independently based on their technical training and experience, as well as knowledge of pertinent standards and regulations.
Electrical technicians should be specifically trained for the working envi‐ ronment in which they are employed and know the relevant standards and regulations.
Electrical technicians must comply with the provisions of the applicable statutory directives on accident prevention.
Instructed person
7
Page 8
Safety chapter
Safety notes
An instructed person is deemed to be a person who has been instructed and, if required, trained in the tasks assigned to him/her and possible dan‐ gers that could result from improper behaviour, as well as having been instructed in the required protective equipment and protective measures.
Service
Customer Service department refers to service technicians, who have received proven training and have been authorised by ProMinent or Pro‐ Maqua to work on the system.
WARNING!
Observe the European Operator Directive 99/92/EC
(ATEX 137), implemented in Germany by the Industrial Health and Safety Regulation and the German Ordi‐ nance on Hazardous Substances, for the installation and operation of equipment in areas at risk from explosion.
Observe the European standards EN 1127-1, EN
60079-10, EN 60079-14, EN 60079-17 and EN 60079-25 and EN 50039 for inherently safe electrical cir‐ cuits. (In Germany these standards are partly imple‐ mented by VDE 0165 and VDE 0118).
Adhere to the respective national regulations outside of
the EU.
Ensure that installations in areas at risk from explosion
are checked by a "recognisably trained" skilled opera‐ tive. This applies specifically to intrinsically safe elec‐ trical circuits.
The following information relates essentially to the
unique characteristics in areas at risk from explosion but does not replace the standard operating instructions.
Only clean plastic parts carefully with a damp cloth to
avoid electrostatic charges and sparks.
WARNING! Warning of dangerous or unknown feed chemical Should a dangerous or unknown feed chemical be used: It
may escape from the hydraulic components when working on the pump.
Take appropriate protective measures before working on
the pump (e.g. safety glasses, safety gloves, ...). Observe the safety data sheet for the feed chemical.
Drain and flush the liquid end before working on the
pump.
WARNING! Danger from hazardous substances! Possible consequence: Fatal or very serious injuries.
Please ensure when handling hazardous substances that you have read the latest safety data sheets provided by the manufacture of the hazardous substance. The actions required are described in the safety data sheet. Check the safety data sheet regularly and replace, if necessary, as the hazard potential of a substance can be re-evaluated at any time based on new findings.
The system operator is responsible for ensuring that these safety data sheets are available and that they are kept up to date, as well as for producing an associated hazard assess‐ ment for the workstations affected.
8
Page 9
WARNING
Electrostatic charge may cause an explosion! Clean plastic parts very carefully using a damp cloth!
Safety chapter
CAUTION! Warning of feed chemical spraying around Feed chemical can spray out of the hydraulic components if
they are manipulated or opened due to pressure in the liquid end and adjacent parts of the system.
Disconnect the pump from the mains power supply and
ensure that it cannot be switched on again by unauthor‐ ised persons.
Depressurise the system before commencing any work
on hydraulic parts.
CAUTION! Warning of feed chemical spraying around An unsuitable feed chemical can damage the parts of the
pump that come into contact with the chemical.
Take into account the resistance of the wetted materials
when selecting the feed chemical - see the ProMinent product catalogue or visit www.prominent.com/en/down‐ loads.
Safety equipment
CAUTION! Danger of personnel injury and material damage The use of untested third party parts can result in personnel
injuries and material damage.
Only fit parts to metering pumps, which have been
tested and recommended by ProMinent.
CAUTION! Danger from incorrectly operated or inadequately maintained
pumps Danger can arise from a poorly accessible pump due to
incorrect operation and poor maintenance.
Ensure that the pump is accessible at all times.
Adhere to the maintenance intervals.
WARNING! – Attach the following safety note to pumps that contain
parts made of electrically non-conductive plastic.
Ensure that the label is always fitted and legible.
Isolating protective equipment
Fig. 2
All isolating protective equipment must be installed for operation:
9
Page 10
Safety chapter
n Drive front cover n Motor fan cowling n Terminal box cover, motor
Only remove them when the operating instructions request you to do so.
Information in the event of an emergency
Safety information relating to the operating instructions
Sound pressure level
In the event of an electrical accident, disconnect the mains cable from the mains or press the emergency cut-off switch fitted on the side of the system!
If feed chemical escapes, also depressurise the hydraulic system around the pump as necessary. Adhere to the safety data sheet for the feed chemical.
Prior to commissioning the system or system component, the system oper‐ ator is obliged to obtain the latest safety data sheet from the supplier for the chemicals / resources to be used with the system. The operator should create the legal framework for safe operation of the system or system component, such as for example the preparation of operating instructions (operator duties), based on the information provided in the data sheets concerning health and safety, water and environmental protection and taking into consideration the actual operating environment on site.
Sound pressure level LpA < 70 dB according to EN ISO 20361
at maximum stroke length, maximum stroke rate, maximum back pressure (water)
10
Page 11
3 Storage, transport and unpacking
Safety notes
WARNING! Only return the metering pump for repair in a cleaned state
and with a flushed liquid end - refer to the chapter "Decom‐ missioning"!
Only return metering pumps with a completed Decontamina‐ tion Declaration form. The Decontamination Declaration con‐ stitutes an integral part of an inspection / repair order. A unit can only be inspected or repaired when a Declaration of Decontamination Form is submitted that has been completed correctly and in full by an authorised and qualified person on behalf of the pump operator.
The "Decontamination Declaration Form" can be found at www.prominent.com/en/downloads.
WARNING! Slings can tear ProMinent only supplies non-reusable slings. These can tear
with repeated use.
Only use the slings once.
Storage, transport and unpacking
Scope of supply
Storage
CAUTION! Danger of material damage The device can be damaged by incorrect or improper storage
or transportation!
The unit should only be stored or transported in a well
packaged state - preferably in its original packaging. Only transport the unit when the red gear bleeding plug
is pushed in.
The packaged unit should also only be stored or trans‐
ported in accordance with the stipulated storage condi‐ tions.
The packaged unit should be protected from moisture
and the ingress of chemicals.
Compare the delivery note with the scope of supply:
Personnel:
1. Plug the caps on the valves.
2. Check if the red gear bleeding plug is pushed in.
3. Preferably place the pump standing vertically on a pallet and secure against falling over.
4. Cover the pump with a tarpaulin cover - allowing rear ventilation.
Technical personnel
n
Store the pump in a dry, sealed place under the ambient conditions according to chapter "Technical Data".
11
Page 12
1
2
3
4
5
P_SI_0068_SW
1
2
P_SI_0088_SW
Overview of equipment and control elements
4 Overview of equipment and control elements
Fig. 3: Overview of equipment and control elements S2Ba
1 Drive motor 2 Drive unit 3 Stroke length adjustment knob 4 Liquid end with relief valve 5 Diaphragm rupture sensor
Fig. 4: Sigma control elements
1 Relief valve 2 Diaphragm rupture sensor (visual)
12
Page 13
20 0
0 50
25 75
5
75%
0
5
0
25
10
30%
P_SI_0095_SW
PG11
PG9
1
2
3
A B
P_SI_0036
Overview of equipment and control elements
Fig. 5: Adjusting the stroke length
n 100 % = 4 rotations n 25 % = 1 rotation n 0.5 % = 1 scale mark on stroke adjustment dial
Fig. 6: Front cover for version with pacing relay
A Pacing relay cable B Supply voltage cable for pacing relay PCB
13
Page 14
4
2
1
5
3
13
Functional description
5 Functional description
5.1
Pump
The metering pump is an oscillating diaphragm pump, the stroke length of which is adjustable. An electric motor drives the pump.
5.2 Liquid end
The diaphragm (2) hermetically shuts off the pump volume of the dosing head (4) towards the outside. The suction valve (1) closes as soon as the diaphragm (2) is moved in to the dosing head (4) and the feed chemical flows through the discharge valve (3) out of the dosing head. The dis‐ charge valve (3) closes as soon as the diaphragm (2) is moved in the opposite direction due to the vacuum pressure in the dosing head and fresh feed chemical flows through the suction valve (1) into the dosing head. One cycle is thus completed.
Fig. 7: Cross-section through the liquid end
1 Suction valve 2 Diaphragm 3 Discharge valve 4 Dosing head 5 Backplate 13 Safety diaphragm
5.3 Integral relief valve
The integral relief valve normally operates as a simple, directly controlled bleeder valve. The feed chemical then flows out through the hose connec‐ tion, e.g. into a storage tank, as soon as the pressure exceeds the pre-set pressure value.
The integral relief valve can only protect the motor and the gear, and then only against impermissible positive pressure that is caused by the metering pump itself. It cannot protect the system against positive pres‐ sure.
The integral relief valve works as a bleed valve if the rotary dial is turned clockwise up to the "open" stop, acting as a priming aid when starting up the pump against pressure.
14
Page 15
1 2
5
4
3
P_SI_0019
Fig. 8: Integral relief valve
1 Spring, large 2 Ball 3 Rotary dial 4 Spring, small 5 Hose connection
Functional description
5.4 Multi-layer safety diaphragm
With visual diaphragm rupture sensors, in the event of a diaphragm rup‐ ture, the lowered red cylinder (6) springs forward beneath the transparent cover (7) so that it then becomes clearly visible - see
Fig. 9.
With the electrical diaphragm rupture sensor, a switch is switched. A sig‐ nalling device must be connected to signal the diaphragm rupture.
Fig. 9: Visual diaphragm rupture sensor, triggered and untriggered
15
Page 16
h
P_MOZ_0016_SW
A
A
P_MOZ_0018_SW
1
3
2
f
f
f
P_MOZ_0017_SW
Assembly
6 Assembly
Base
Compare the dimensions on the dimension sheet and pump.
WARNING! Danger of electric shock If water or other electrically conducting liquids penetrate into
the drive housing, in any other manner than via the pump's suction connection, an electric shock may occur.
Position the pump so that it cannot be flooded.
Fig. 10
Space requirement
WARNING! The pump can break through the base or slide off it – Ensure that the base is horizontal, smooth and perma‐
nently load-bearing.
Capacity too low Vibrations can disrupt the liquid end valves.
The supporting floor must not vibrate.
CAUTION! Danger from incorrectly operated or inadequately maintained
pumps Danger can arise from a poorly accessible pump due to
incorrect operation and poor maintenance.
Ensure that the pump is accessible at all times.
Adhere to the maintenance intervals.
Position the pump so that control elements such as the stroke length adjustment knob or the indicating dial A are easily accessible.
Fig. 11
Fig. 12
1 Discharge valve 2 Dosing head 3 Suction valve
Ensure that there is sufficient free space (f) around the dosing head, as well as the suction and discharge valve, so that maintenance and repair work can easily be carried out on these components.
16
Page 17
Liquid end alignment
DNm
m
P_MOZ_0015_SW
Fastening
Fig. 13
Assembly
Capacity too low The liquid end valves cannot close correctly if they are not
upright.
Ensure that the discharge valve is upright.
Capacity too low Vibrations can disrupt the liquid end valves.
Secure the metering pump so that no vibrations can occur.
Take the dimensions (m) for the fastening holes from the appropriate dimensional drawings or data sheets.
Fix the pump base to the base with suitable screws.
17
Page 18
Installation, hydraulic
7 Installation, hydraulic
WARNING! EX pumps in areas at risk from explosion – It is essential that metering pumps to be used in areas at
risk from explosion are fitted with an appropriate safety relief valve on the outlet side of the metering pump (to protect it from excessive heating up from overloading and from impact sparks resulting from overloading trig‐ gered by the breakage of drive parts).
In the event of different temperature classes with the various components, the possible uses of the complete pump are based on the component with the lowest tem‐ perature class.
Diaphragm pump with mechanically actuated diaphragm,
e.g. MTMa.., TZMa.., Sigmas S1Ba...., S2BaHM...,
S3Ba: no additional action is required, but in principle use the design with Ex"i" diaphragm rupture indicator.
Ensure that installations in areas at risk from explosion
are checked by a "recognisably qualified and skilled" operative.
Please observe the relevant national regulations and
guidelines during installation!
WARNING! Danger of fire with flammable feed chemicals – Combustible media may only be transported using stain‐
less steel dosing heads. In exceptional cases where this is not possible, PTFE with carbon can be used, whereby our TT_ versions are manufactured from this conducting plastic. Here, the operator is urged to take special care due to the low mechanical strength.
Only designs of metering pump with Ex"i" diaphragm rupture indicators are permitted in principle to meter flammable media.
The following applies to all metering pumps for the
metering of combustible media: During filling and draining of the liquid end, an expert
must ensure that feed chemical does not come into con‐ tact with oxygen.
WARNING! Warning of feed chemical reactions to water Feed chemicals that should not come into contact with water
may react to residual water in the liquid end that may origi‐ nate from works testing.
Blow the liquid end dry with compressed air through the
suction connector. Then flush the liquid end with a suitable medium through
the suction connector.
WARNING! The following measures are an advantage when working with
highly aggressive or hazardous feed chemicals:
Install a bleed valve with recirculation in the storage
tank. Install an additional shut-off valve on the discharge or
suction ends.
18
Page 19
P_SI_0021
Installation, hydraulic
CAUTION! Warning of feed chemical spraying around PTFE seals, which have already been used / compressed,
can no longer reliably seal a hydraulic connection.
New, unused PTFE seals must always be used.
CAUTION! Suction problems possible The valves may no longer close properly with feed chemicals
with a particle size of greater than 0.3 mm.
Install a suitable filter in the suction line.
CAUTION! Warning against the discharge line bursting With a closed discharge line (e.g. due to a clogged discharge
line or by closing a valve), the pressure that the metering pump generates can reach several times the permissible pressure of the system or the metering pump. This could lead to lines bursting, resulting in dangerous consequences with aggressive or toxic feed chemicals.
Install a relief valve that limits the pressure of the pump
to the maximum permissible operating pressure of the system.
Fig. 14: Moulded composite seals with corrugated insert
CAUTION! Uncontrolled flow of feed chemical Feed chemicals can leak through a stopped metering pump if
there is back pressure.
Use an injection valve or a vacuum breaker.
CAUTION! Uncontrolled flow of feed chemical Feed chemical can leak through the metering pump in an
uncontrolled manner in the event of excessive priming pres‐ sure on the suction side of the metering pump.
Do not exceed the maximum permissible priming pres‐
sure for the metering pump.
Arrange the installation properly.
CAUTION! Warning against leaks Leaks can occur on the pump connection depending on the
insert used.
The pump is supplied with PTFE moulded composite
seals with a flare, which are used for the pump connec‐ tions. They seal the connections between grooved pump valves and the grooved inserts from ProMinent - see Fig. 14.
In the event that an unflared insert is used (e.g. third party part), an elastomer flat seal must be used - see Fig. 15.
19
Page 20
P_SI_0022
Installation, hydraulic
Fig. 15: Elastomer flat seal for a smooth insert
Integral relief valve
CAUTION! Warning of backflow Liquid ends, foot valves, back pressure valves, relief valves
or spring-loaded injection valves do not constitute absolutely leak-tight sealing elements.
Use a shut-off valve, a solenoid valve or a vacuum
breaker for this purpose.
WARNING! Product can be dangerously contaminated Only with the design "Physiologically safety with regard to
wetted materials".
If the integral bleed valve or the integral relief valve opens, the feed chemical comes into contact with physiologically harmful seals.
Do not route feed chemical that escapes from the inte‐
gral bleed valve or the integral relief valve back into the process.
CAUTION! Danger due to incorrect use of the integral relief valve The integral relief valve can only protect the motor and the
gear, and then only against impermissible positive pressure that is caused by the metering pump itself. It cannot protect the system against positive pressure.
Protect the motor and gear of the system against posi‐
tive pressure using other mechanisms.
Protect the system against illegal positive pressure using other mechanisms.
CAUTION! Warning of feed chemical spraying around If no relief valve was connected to the overflow line, the feed
chemical sprays out of the hose connection as soon as the relief valve opens.
An overflow line must always be connected to the inte‐
gral relief valve and be fed back to the storage tank or ­if required by the regulations - into a special storage tank.
CAUTION! Danger of cracking Cracking of the PVT liquid end can occur if a metal overflow
line is connected to the relief valve.
Never connect a metal overflow line to the relief valve.
20
Page 21
P_SI_0023
Installation, hydraulic
CAUTION! Danger of the integral relief valve failing The integral relief valve no longer operates reliably with feed
chemicals having a viscosity of greater than 200 mPa s.
Only use the integral relief valve with feed chemicals
having a viscosity up to 200 mPa s.
CAUTION! Warning against leaks Feed chemical which remains in the overflow line at the relief
valve, can attack the valve or cause it to leak
Route the overflow line with a continuous slope and
moreover with the tube nozzle pointed downwards - see Fig. 16.
If the overflow line is fed into the suction line, the bleed func‐ tion is blocked.
Therefore lead the overflow line back into the storage tank.
Fig. 16: Permissible alignment of the relief valve
Diaphragm rupture sensor
When operating the integral relief valve close to the opening pressure, a minimal overflow into the overflow line can occur.
CAUTION! Danger resulting from unnoticed diaphragm rupture If the pump has been ordered with an electric diaphragm rup‐
ture sensor, it still has to be installed.
Screw the enclosed diaphragm rupture sensor into the
liquid end.
CAUTION! Warning of unnoticed diaphragm rupture Only above approximately 2 bar system back pressure is a
signal generated upon a diaphragm rupture.
Only rely on the diaphragm rupture sensor at back pres‐
sures greater than 2 bar.
21
Page 22
P_MOZ_0043_SW
2
1
A)
B)
*
PD
1
2
Installation, hydraulic
7.1 Basic installation notes
Safety notes
CAUTION! Danger resulting from rupturing hydraulic components Hydraulic components can rupture if the maximum permis‐
sible operating pressure is exceeded.
Never allow the metering pump to run against a closed
shut-off device.
With metering pumps without integral relief valve: Install a relief valve in the discharge line.
CAUTION! Hazardous feed chemicals can escape With hazardous feed chemicals: Hazardous feed chemical
can leak out when using conventional bleeding procedures with metering pumps.
Install a bleed line with a return into the storage tank.
Shorten the return line so that it does not dip into the feed chemical in the storage tank.
Fig. 17: (A) standard installation, (B) with pulsation damper
1 Main line 2 Storage tank
Legend for hydraulic diagram
Symbol Explanation Symbol Explanation
Metering pump Foot valve with filter meshes
Injection valve Level switch
Multifunctional valve Manometer
22
Page 23
8 Installation, electrical
Installation, electrical
WARNING! EX pumps in areas at risk from explosion – Potential-free switches can be evaluated as simple elec‐
trical devices (EN 60079-14 or EN 50020).
Only connect potential-free as well as non-isolating low voltage switch accessories, such as diaphragm rupture indicators, stroke frequency instruments etc., to an intrinsically safe power circuit in areas at risk from explo‐ sion.
If several electrical components are connected together,
test and confirm the technical safety of the entire con‐ nected system. This can either be in the form of a decla‐ ration of conformity from the supplier (ProMinent) for the entire unit or, with the supply of individual components, with the operator's explosion protection document.
Only motor protection switches, mains switches and
fuses permitted for use in areas at risk from explosion in line with the manufacturer's information may be used as electrical components in areas at risk from explosion.
Note the enclosed documentation for the individual elec‐
trical components.
WARNING! Danger of electric shock Unprofessional installation may lead to electric shocks.
Provide all shortened cable cores with cable end
sleeves.
Only technically trained personnel are authorised to undertake the electrical installation of the device.
WARNING! Danger of electric shock In the event of an electrical accident, it must be possible to
quickly disconnect the pump, and any electrical ancillaries which may possibly be present, from the mains.
Install an emergency cut-off switch in the mains supply
line to the pump and any electrical ancillaries which may be present or
Integrate the pump and electrical ancillaries which may
be present in the emergency cut-off management of the system and inform personnel of the isolating option.
WARNING! Danger of electric shock This pump is equipped with a protective earth conductor, to
reduce the risk arising from an electric shock.
Connect the PE conductor to "earth" with a clean and
permanent electrical connection.
23
Page 24
P_SI_0012_SW
Installation, electrical
WARNING! Danger of electric shock A mains voltage may exist inside the motor or electrical ancil‐
laries.
If the housing of the motor or electrical ancillaries has
been damaged, you must disconnect it from the mains immediately. The pump must only be returned to service after an authorised repair.
What requires electrical installation?
n Motor n External fan (optional) n Stroke control drive (optional) n Stroke adjusting drive (optional) n Diaphragm rupture sensor (Option) n Stroke sensor (optional) n Pacing relay (option) n Frequency converter (optional)
Motor
Fig. 18: Direction of rotation of motor
WARNING! EX pumps in areas at risk from explosion – Protect drive motors with appropriate motor protection
switches. Only use motor protection permitted for this kind of application with Ex"e" motors. (Protection against heating from overloading)
Ensure that motors are only installed and inspected by a "recognisably trained" skilled operative in areas at risk from explosion.
Observe the enclosed operating instructions for the Ex
motor.
CAUTION! The motor can be damaged Provide appropriate motor protection devices (e.g. motor pro‐
tection switch with thermal overcurrent trip) to protect the motor against overloading.
Fuses do not provide motor protection.
CAUTION! The pump can be damaged The pump can be damaged if the motor drives the pump in
the wrong direction.
When connecting the motor, pay attention to the correct
direction of rotation indicated by the arrow on the fan cover, as shown in Fig. 18.
Install an electrical isolating device in the mains supply cable, e.g. a mains switch, to be able to switch off the pump independently of the entire installation (e.g. for repair).
24
Page 25
Installation, electrical
1. Install a motor protection switch, as the motors have no fuse.
2. Install an emergency cut-off switch or include the motor in the emer‐ gency cut-off management plan for the system.
3. Only connect the motor to the voltage supply using a suitable cable.
Key motor data can be found on the nameplate.
– –
The terminal wiring diagram is located in the terminal box.
Motor data sheets, special motors, special motor flanges, external fan, temperature monitoring
For further information for the motor with identity code specification "S", refer to the motor data sheet in the Appendix. Motor data sheets can be requested for all other motors.
For motors other than those with identity code specifica‐ tions "S", "M" or "N": Pay special attention to the oper‐ ating instructions for the motors.
Special motors or special motor flanges are possible on request.
External fans
Variable speed motors with frequency converter
Stroke length actuators / control drives
Diaphragm rupture sensor (Option)
CAUTION! Provide a separate power supply for the external fan with
motors with external fans (identity code specification "R" or "Z").
Connect up the motor as per the wiring diagram for the controller, if it is controlled by an electronic control unit (such as direct current motors by a frequency converter).
Connect the motors as per the enclosed wiring diagram or the wiring dia‐ gram on the inside of the housing.
CAUTION! Only operate stroke length actuators / control drives when
the pump is running!
Otherwise they will be damaged.
WARNING! Risk of electric shock In event of a defect, there is a risk of electric shock when
conductive feed chemical are used.
For safety reasons we recommend connecting to a pro‐
tective low voltage, e.g. in accordance with EN 60335-1 (SELV ).
25
Page 26
Installation, electrical
Stroke sensor (identity code specification "Stroke sensor": 3)
CAUTION! Danger resulting from unnoticed diaphragm rupture If the pump has been ordered with an electric diaphragm rup‐
ture sensor, it must also be electrically installed.
Install the enclosed diaphragm rupture sensor electri‐
cally to a suitable monitoring device.
a) Diaphragm rupture sensor with switch contact
The cable can be poled as required.
b) Namur sensor, inherently safe
The monitor / power supply installed by the customer must be able to eval‐ uate the current variations of the Namur sensor for indicating a diaphragm rupture!
Connect the stroke sensor to a suitable monitoring device according to the technical data provided with the monitoring device and that of the stroke sensor - see chapter "Technical data".
Pacing relay (identity code specification "Stroke sensor": 2)
1. Install the cable which originates from the pacing relay - see the figure in the chapter entitled "Overview of equipment and control elements": Cable A, left.
The cable polarity is unimportant.
2. Install the power supply cable to the pacing relay PCB - see the figure in the chapter entitled "Overview of equipment and control elements": Cable B, right.
CAUTION! Warning of overload If the current through the relay becomes too high, it
can be destroyed by heating.
Fit a circuit breaker.
Pacing relay terminal output data
Data Value Unit
Maximum voltage 24 VDC
Maximum current 100 mA
Closing duration, approx. 100 ms
Service life *
50 x 106 (10 V,
Play
10 mA)
26
Page 27
* at rated load
The contacts are potential-free.
The pacing relay is a N/O as standard.
Supply voltage for pacing relay PCB
Installation, electrical
Heating cartridge
Other units
Available supply vol‐ tages
Mains supply fre‐ quency
Power consumption
230 V AC (180-254 V) 50 / 60 Hz 10 mA (at 230 V, 50 Hz)
115 V AC (90-134 V) 50 / 60 Hz 15 mA (at 115 V, 60 Hz)
24 V DC (20-28 V) - 10 mA (at 24 V DC)
Install the heating cartridge according to its documentation. It must only be connected to the supplied power supply!
Install the other units in line with their documentation.
27
Page 28
Start up
9 Start up
Safety notes
WARNING! EX pumps in areas at risk from explosion – An appropriately skilled operative should check whether
the appropriate installation information from the "Installa‐ tion " chapter has been implemented correctly.
WARNING! Fire hazard with flammable media Only with combustible media: These may start to burn when
combined with oxygen.
During filling and draining of the liquid end, an expert
must ensure that feed chemical does not come into con‐ tact with oxygen.
CAUTION! Feed chemical could escape – Check suction and discharge lines and liquid end with
valves for leak-tightness and tighten if necessary. Check whether the necessary flushing pipes or bleed
lines have been connected.
Diaphragm rupture sensor
CAUTION! Prior to commissioning, check that the power end motor and
corresponding ancillary equipment is connected in compli‐ ance with the regulations.
CAUTION! When using pumps with speed control, observe the instruc‐
tions in the frequency converter operating instructions.
CAUTION! Danger resulting from unnoticed diaphragm rupture If the pump has been ordered with an electric diaphragm rup‐
ture sensor, it still has to be installed.
Screw the enclosed diaphragm rupture sensor into the
liquid end.
CAUTION! Warning of unnoticed diaphragm rupture Only above approximately 2 bar system back pressure is a
signal generated upon a diaphragm rupture.
Only rely on the diaphragm rupture sensor at back pres‐
sures greater than 2 bar.
28
Page 29
Start up
CAUTION! Possible environmental and material damage In event the red gear bleeding plug is sealed, during opera‐
tion it prevents any pressure compensation between the drive housing and the surroundings. This ensure that oil can be pushed from the drive housing.
Remove the gear bleeding plug before commissioning.
Remove the gearbox vent stopper
Checking the oil level
Checking the direction of rotation
Using the integral relief valve
Before start up pull the red gearbox vent stopper off, see chapter "Over‐ view of equipment and control elements".
When the pump is idle, check whether the oil level in the pump is in the middle of the oil level indicator.
This will rule out the pump losing oil and suffering damage.
When commissioning the unit, check whether the drive motor is rotating correctly - check this against the arrow on the motor housing or the dia‐ gram in the chapter entitled "Electrical Installation."
CAUTION! Danger due to incorrect use of the integral relief valve The integral relief valve can only protect the motor and the
gear, and then only against impermissible positive pressure that is caused by the metering pump itself. It cannot protect the system against positive pressure.
Protect the motor and gear of the system against posi‐
tive pressure using other mechanisms.
Protect the system against illegal positive pressure using
other mechanisms.
Priming against pressure
CAUTION! Danger of the integral relief valve failing The integral relief valve no longer operates reliably with feed
chemicals having a viscosity of greater than 200 mPa s.
Only use the integral relief valve with feed chemicals
having a viscosity up to 200 mPa s.
1. Hydraulically isolate the discharge line from the pump using an iso‐ lation device.
2. Turn the rotary dial on the integral relief valve in a counter-clockwise direction as far as the "open" stop.
The excess pressure escapes through the hose connector.
ð
3. Run the pump until the feed chemical coming out of the hose con‐ nector is free from bubbles.
4. Turn the rotary dial on the integral relief valve in a clockwise direc‐ tion up to the "close" stop.
The pump can be started.
ð
29
Page 30
20 0
0 50
25 75
5
75%
0
5
0
25
10
30%
P_SI_0095_SW
Start up
Adjusting the stroke length
When operating the integral relief valve close to the opening pressure, a minimal overflow into the overflow line can occur.
Only adjust the stroke length when the pump is running. This is easier and also better for the pump.
Fig. 19: Adjusting the stroke length
n 100 % = 4 rotations n 25 % = 1 rotation n 0.5 % = 1 scale mark on stroke adjustment dial
30
Page 31
10 Maintenance
Safety notes
Maintenance
WARNING! EX pumps in areas at risk from explosion – Ensure correct operation in general, particularly of the
power end and bearing, by regular monitoring (for leaks, noises, temperatures, smell ...).
Do not allow the pump to become hot due to a lack of oil. Regularly check lubricated metering pumps for the exis‐
tence of lubricant, for example by checking the liquid level, visual leak control etc. If oil is leaking, examine the leakage point immediately and eliminate the cause.
Check the correct operation of the relief valve down‐
stream of the pump. In premises at risk from explosion, the relief valve should prevent the gear from becoming overloaded and becoming hot.
When cleaning plastic components, ensure that no elec‐
trostatic charges are generated by excessive friction. ­see warning label.
Replace wear parts, such as bearings, as soon as unac‐
ceptable wear is detected. (The nominal service life
cannot be calculated with lubricated bearings). – Use genuine spare parts for replacement. – Only perform tests and repairs in compliance with DIN
EN IEC 60079-17 and only permit "experienced per‐
sonnel who have the requisite knowledge" to perform the
work. – These measures constitute the minimum protective
measurements stipulated by ProMinent. It is the duty of
the operator to eliminate any other dangers identified by
appropriate measures.
WARNING! Fire hazard with flammable media Only with combustible media: These may start to burn when
combined with oxygen.
During filling and draining of the liquid end, an expert
must ensure that feed chemical does not come into con‐
tact with oxygen.
WARNING! It is mandatory that you read the safety information and
specifications in the "Storage, Transport and Unpacking" chapter prior to shipping the pump.
CAUTION! Warning of feed chemical spraying around Feed chemical can spray out of the hydraulic components if
they are manipulated or opened due to pressure in the liquid end and adjacent parts of the system.
Disconnect the pump from the mains power supply and
ensure that it cannot be switched on again by unauthor‐
ised persons.
Depressurise the system before commencing any work
on hydraulic parts.
31
Page 32
Maintenance
WARNING! Warning of dangerous or unknown feed chemical Should a dangerous or unknown feed chemical be used: It
may escape from the hydraulic components when working on the pump.
Take appropriate protective measures before working on
the pump (e.g. safety glasses, safety gloves, ...). Observe the safety data sheet for the feed chemical.
Drain and flush the liquid end before working on the
pump.
WARNING! Danger of an electric shock When working on the motor or electrical auxiliary equipment,
there is a danger of an electric shock.
Before working on the motor, take note of the safety
instructions in its operating instructions!
Should external fans, servomotors or other auxiliary equipment be installed, these should also be discon‐ nected and checked that they are voltage free.
Third party spare parts for the pumps may lead to problems when pumping.
Use only original spare parts.
Use the correct spare parts kits. In case of doubt, refer to the exploded views and ordering information in the appendix.
Standard liquid ends:
Interval Maintenance work Personnel
After approx. 5,000 oper‐ ating hours
Quarterly Check the oil level.
Quarterly*
Change gear oil - refer to "Changing gear oil" in this chapter. Instructed personnel
n Check that the metering lines are fixed firmly to the liquid end. n Check that the suction valve and discharge valve are correctly
seated.
n Check that the dosing head screws are tight. n Check the condition of the metering diaphragm - see
the condition of the metering diaphragm’ on page 32
n Check that the flow is correct: Allow the pump to prime briefly. n Check that the electrical connections are intact.
Ä ‘Check
.
Technical personnel
Check the condition of the metering dia‐ phragm
* Under normal loading (approx. 30 % of continuous operation).
Under heavy loading (e.g. continuous operation): shorter intervals.
The diaphragm is a wearing part, the service life of which is dependent upon the following parameters:
n System back pressure n Operating temperature n Feed chemical properties
32
Page 33
1
3
2
P_SI_0143_SW
Maintenance
When using abrasive feed chemicals, the diaphragm service life is reduced. In such cases, more frequent checking of the diaphragm is rec‐ ommended.
Tightening torques
Liquid ends with integral relief valve
Changing gear oil
Data Value Unit
Tightening torques for dosing head
4.5 ... 5.0 Nm
screws:
WARNING! Warning of eye injuries When opening the relief valve, a spring under high tension
can jump out.
Wear protective glasses.
Draining gear oil
Fig. 20
1. Remove the vent screw (1).
2. Place an oil trough under the oil drain plug (2).
3. Unscrew the oil drain plug (2) from the power end housing.
4. Allow the gear oil to run out of the power end.
5. Screw in the oil drain plug (2) with a new seal.
Filling with gear oil
Prerequisites: Gear oil according to the "Ordering information" chapter is available.
1. Slowly pour gear oil through the vent screw (1) opening until the oil inspection window (3) is half covered.
2. Allow the pump to run for 1... 2 minutes
3. Replace the vent screw (1).
33
Page 34
Repairs
11 Repairs
Safety notes
WARNING! EX pumps in areas at risk from explosion – Generally check the proper operation of the system, par‐
ticularly of the power end and bearings, by regular moni‐
toring (for leaks, noises, temperatures, smell .... ).
WARNING! Fire hazard with flammable media Only with combustible media: These may start to burn when
combined with oxygen.
During filling and draining of the liquid end, an expert
must ensure that feed chemical does not come into con‐ tact with oxygen.
WARNING! It is mandatory that you read the safety information and
specifications in the "Storage, Transport and Unpacking" chapter prior to shipping the pump.
CAUTION! Warning of feed chemical spraying around Feed chemical can spray out of the hydraulic components if
they are manipulated or opened due to pressure in the liquid end and adjacent parts of the system.
Disconnect the pump from the mains power supply and
ensure that it cannot be switched on again by unauthor‐ ised persons.
Depressurise the system before commencing any work
on hydraulic parts.
WARNING! Warning of dangerous or unknown feed chemical Should a dangerous or unknown feed chemical be used: It
may escape from the hydraulic components when working on the pump.
Take appropriate protective measures before working on
the pump (e.g. safety glasses, safety gloves, ...). Observe the safety data sheet for the feed chemical.
Drain and flush the liquid end before working on the pump.
34
Page 35
11.1 Cleaning valves
1
2
3
4
5
P_SI_0013_SW
Unsuitable spare parts for the valves may lead to problems for the pumps.
Only use new components that are especially adapted to fit your valve (both in terms of shape and chemical resistance).
Use the correct spare parts kits. In case of doubt, refer to the exploded views and ordering information in the appendix.
Only with the "Physiologically safe" design:
WARNING! Product can be dangerously contaminated Only use the spare parts from the "Physiologically safe"
spare parts kits.
Repairs
Repairing ball valves
Personnel:
Technical personnel
n
CAUTION! Warning of personal injury and material damage Feed chemical may escape from the liquid end, for example,
if ball valves not repaired correctly.
Only use new components which fit your valve - both in
terms of shape and chemical resistance! Note the flow direction of the discharge and suction con‐
nectors when fitting the valve.
CAUTION! Warning of feed chemical spraying around PTFE seals, which have already been used / compressed,
can no longer reliably seal a hydraulic connection.
New, unused PTFE seals must always be used.
Fig. 21: Simple cross-section through ball valve
1 Flat seal 2 Valve body 3 Valve ball 4 Valve seat 5 Valve cap
35
Page 36
Repairs
11.2 Replacing the diaphragm
Third party spare parts for the pumps may lead to problems when pumping.
Use only original spare parts.
Use the correct spare parts kits. In case of doubt, refer to the exploded views and ordering information in the appendix.
Personnel:
Requirements:
n If necessary take protective measures. n Adhere to the safety data sheet for the feed chemical. n Ensure that the system is at atmospheric pressure.
1. Drain the liquid end: Place the liquid end on its head and allow the feed chemical to run out; flush out with a suitable medium; flush the liquid end thoroughly when using hazardous feed chemicals!
2. With the pump running, move the stroke adjustment dial to the stop at 0 % stroke length.
The drive axle is now difficult to turn.
ð
3. Switch off the pump.
4. Unscrew the hydraulic connectors on the discharge and suction side.
5. Unscrew the diaphragm rupture sensor from the dosing head.
6. Remove the 6 screws on the dosing head.
7. Remove the dosing head.
8.
Check the condition of the diaphragm rupture sensor - see
Technical personnel
n
Ä
Checking the condition of the diaphragm rupture sensor’ on page 38
9. Loosen the diaphragm from the drive axle with a gentle backwards turn in the anti-clockwise direction.
10. Completely unscrew the diaphragm from the drive axle.
11. Tentatively screw the new diaphragm anticlockwise up to the stop on the drive axle.
ð
.
The diaphragm now is now seated against the stop of the thread while the diaphragm flap is within the tolerance range.
36
Page 37
P_SI_0029
2
3
A
1
Repairs
Fig. 22: Tolerance range of the flap on the backplate
1 Diaphragm 2 Backplate 3 Flap A Tolerance range
12. Should this not work, remove dirt or swarf out of the thread and screw the diaphragm correctly onto the drive axle this time.
If this is still unsuccessful, contact ProMinent-ProMaqua cus‐
ð
tomer service.
13. Place the dosing head with the screws onto the diaphragm - the suction connector must be pointing downwards in the pump's fitting position.
14. Tighten the screws gently to start with.
15. Screw the diaphragm rupture sensor into the dosing head.
16. Start up the pump and adjust the stroke length to 100 %.
17. Stop the pump and tighten the screws crosswise. Tightening torque
Ä ‘Tightening torques’ on page 33
- see
18. Start the pump and at maximum pressure, check for leaks.
.
CAUTION! Warning of escaping feed chemical The liquid end may leak should it not be possible to check
the tightening torque of the screws.
Check the tightening torque of the screws after 24 hours
of operation!
With PP, PC and TT dosing heads also re-check the tightening torques quarterly!
37
Page 38
7 6 5 4 3
21
P_SI_0020_SW
Repairs
Checking the condition of the diaphragm rupture sensor
1. If the inside of the diaphragm rupture sensor has become damp or dirt has penetrated it: replace.
Fig. 23: Section through the Sigma diaphragm rupture warning system ("Visual break indicator" version)
1 Working layer (≙ operating diaphragm) 2 Safety layer (≙ safety diaphragm) 3 Flap 4 Piston 5 Diaphragm rupture sensor 6 Cylinder, red 7 Cover, transparent
2. If the piston of the diaphragm rupture sensor - see
Fig. 23, item 4 ­should have become dirty or damp, clean both it and the hole in which it runs.
3. Check whether it can move freely in the hole.
4. Refit the clean diaphragm rupture sensor with the clean piston.
5. Test the diaphragm rupture sensor.
Optical diaphragm rupture sensor
1. Unscrew the transparent cover from the diaphragm rupture sensor.
2. Press the red cylinder into the diaphragm rupture sensor until it engages.
3. Press the piston on the other side of the diaphragm rupture sensor with a blunt, smooth object into the dosing head (approximately 4 mm) until it triggers.
CAUTION! Feed chemical may escape If the expandable flap of the diaphragm is damaged,
then feed chemical can escape when there is a dia‐ phragm rupture.
The piston must not be scratched, it must remain com‐ pletely smooth so that during operation it does not damage the expandable flap of the diaphragm.
4. Press the red cylinder into the diaphragm rupture sensor again and repeat the test.
5. If it does not trigger both times, replace the membrane rupture sensor.
38
Page 39
4
2
1
5
3
13
P_SI_0038
Repairs
6. After a successful test, screw the transparent cover onto the dia‐ phragm rupture sensor and then continue at the top by fitting the diaphragm.
Electrical diaphragm rupture sensor
1. Press the piston of the diaphragm rupture sensor with a blunt, smooth object into the dosing head (approximately 4 mm) until the monitor triggers alarm.
CAUTION! Feed chemical may escape If the expandable flap of the diaphragm is damaged,
then feed chemical can escape when there is a dia‐ phragm rupture.
The piston must not be scratched, it must remain com‐ pletely smooth so that during operation it does not damage the expandable flap of the diaphragm.
2. Repeat the test.
3. If the monitor does not trigger an alarm both times, replace the membrane rupture sensor.
4. After a successful test, continue at the top by fitting the diaphragm.
Fig. 24: Cross-section through the liquid end
1 Suction valve 2 Diaphragm 3 Discharge valve 4 Dosing head 5 Backplate 13 Safety diaphragm
39
Page 40
Troubleshooting
12 Troubleshooting
Safety notes
WARNING! EX pumps in areas at risk from explosion – Ensure correct operation in general (no leaks, unusual
noises, high temperatures, unusual smells etc.), particu‐ larly of the power end and bearings.
Do not allow the pump to become hot due to a lack of oil! If oil is escaping, investigate the leak immediately and
eliminate the cause.
When cleaning plastic parts, ensure that excessive fric‐
tion does not cause electrical charges - see warning label.
Replace wear parts, such as bearings, as soon as unac‐
ceptable wear is detected. (The nominal service life
cannot be calculated with lubricated bearings). – Use genuine spare parts for replacement. – Only perform tests and repairs in compliance with DIN
EN IEC 60079-17 and only permit "experienced per‐
sonnel who have the requisite knowledge" to perform the
work.
WARNING! Fire hazard with flammable media Only with combustible media: These may start to burn when
combined with oxygen.
During filling and draining of the liquid end, an expert
must ensure that feed chemical does not come into con‐
tact with oxygen.
WARNING! Danger of an electric shock Personnel working on electrical parts can be electrocuted if
all electrical lines carrying current have not been discon‐ nected.
Disconnect the supply cable before working on the motor
and prevent it from being reconnected accidentally.
Any separately driven fans, servo motors, speed control‐
lers or diaphragm rupture sensors fitted should also be
disconnected. – Check that the supply cables are de-energised.
WARNING! Warning of dangerous or unknown feed chemical Should a dangerous or unknown feed chemical be used: It
may escape from the hydraulic components when working on the pump.
Take appropriate protective measures before working on
the pump (e.g. safety glasses, safety gloves, ...).
Observe the safety data sheet for the feed chemical. – Drain and flush the liquid end before working on the
pump.
40
Page 41
Troubleshooting
CAUTION! Warning of feed chemical spraying around Feed chemical can spray out of the hydraulic components if
they are manipulated or opened due to pressure in the liquid end and adjacent parts of the system.
Disconnect the pump from the mains power supply and
ensure that it cannot be switched on again by unauthor‐ ised persons.
Depressurise the system before commencing any work
on hydraulic parts.
Tasks
Fault description Cause Remedy Personnel
Pump does not prime in spite of full stroke motion and bleeding.
The valves are dirty or worn.
The feed chemical has par‐ ticles larger than 0.3 mm.
Pump does not reach high pres‐ sure rates.
The valves are dirty or worn.
The motor is wired incor‐ rectly.
The mains voltage has failed.
Fluid is escaping from the back‐ plate.
The dosing head screws are no longer tight enough.
The diaphragm leaks.** Replace the diaphragm - refer to the
Large leaks occur at the relief valve.
The diaphragm rupture sensor has triggered.
The ball or ball seat are dirty or worn.
The operating diaphragm has ruptured.**
The drive motor is very hot. The discharge line is seri‐
ously constricted.
Repair the valves - see chapter enti‐ tled "Repair".
Install a suitable filter in the suction line.
Repair the valves - see chapter enti‐ tled "Repair".
1. Check the mains voltage and
Technical per‐ sonnel
Technical per‐ sonnel
Technical per‐ sonnel
Electrician
mains frequency.
2. Wire the motor correctly.
Eliminate the cause. Electrician
Tighten the screws crosswise to the specified tightening torque.
Technical per‐ sonnel
Technical per‐
"Repair" chapter.
Clean or replace the ball and ball seat.
Replace the diaphragm - refer to the "Repair" chapter.
Rectify any constriction of the dis‐ charge line.
sonnel
Technical per‐ sonnel
Technical per‐ sonnel
Technical per‐ sonnel
All other faults. Other causes. Call the ProMinent customer serv‐
ices.
* If necessary use the cross-section drawing of the integral relief valve in the "Functional Description" chapter.
WARNING! Warning of eye injuries When opening the relief valve, a spring under high tension
can jump out.
Wear protective glasses.
41
Page 42
Troubleshooting
**
WARNING! Warning of escaping feed chemical When dosing combustible feed chemicals or in hazardous
locations, under no circumstances must the second dia‐ phragm also rupture.
If the pump diaphragm rupture sensor triggers, stop the
pump immediately and only operate once a new multi-
layer safety diaphragm has been fitted.
CAUTION! Warning of inaccurate dosing Once the operating membrane has ruptured, precise dosing
of the pump can no longer be guaranteed.
Do not continue to use the pump for critical process
dosing. – For uncritical processes, the pump can continue to be
operated for some time after the break in emergency
service mode at full operating pressure and free from
leaks up until replacement of the diaphragm.
Only with the "Physiologically safe" design:
WARNING! Following a rupture of the diaphragm, the pump loses its
FDA approval until the diaphragm has been replaced.
42
Page 43
13 Decommissioning
Decommissioning
Decommissioning
WARNING! Fire hazard with flammable media Only with combustible media: These may start to burn when
combined with oxygen.
During filling and draining of the liquid end, an expert
must ensure that feed chemical does not come into con‐ tact with oxygen.
WARNING! Danger of an electric shock When working on the motor or electrical auxiliary equipment,
there is a danger of an electric shock.
Before working on the motor, take note of the safety
instructions in its operating instructions!
Should external fans, servomotors or other auxiliary equipment be installed, these should also be discon‐ nected and checked that they are voltage free.
WARNING! Danger from chemical residue There is normally chemical residue in the liquid end and on
the housing after operation. This chemical residue could be hazardous to people.
It is mandatory that the safety notes relating to the
"Storage, Transport and Unpacking" chapter are read before shipping or transporting the unit.
Thoroughly clean the liquid end and the housing of
chemicals and dirt. Adhere to the safety data sheet for the feed chemical.
WARNING! Warning of dangerous or unknown feed chemical Should a dangerous or unknown feed chemical be used: It
may escape from the hydraulic components when working on the pump.
Take appropriate protective measures before working on
the pump (e.g. safety glasses, safety gloves, ...). Observe the safety data sheet for the feed chemical.
Drain and flush the liquid end before working on the
pump.
CAUTION! Warning of feed chemical spraying around Feed chemical can spray out of the hydraulic components if
they are manipulated or opened due to pressure in the liquid end and adjacent parts of the system.
Disconnect the pump from the mains power supply and
ensure that it cannot be switched on again by unauthor‐ ised persons.
Depressurise the system before commencing any work on hydraulic parts.
43
Page 44
Decommissioning
WARNING! Warning of eye injuries When opening the relief valve, a spring under high tension
can jump out.
Wear protective glasses.
CAUTION! Danger of damage to the device The device can be damaged by incorrect and improper
storage or transportation.
Take into account the information in the "Storage, Trans‐
port and Unpacking" chapter if the system is decommis‐
sioned for a temporary period.
(Temporary) decommissioning
Final decommissioning
Disposal
1. Disconnect the pump from the mains power supply.
2. Depressurise and bleed the hydraulic system around the pump.
3. Drain the liquid end by turning the pump upside down and allowing the feed chemical to run out.
4. Flush the liquid end with a suitable medium - Observe the safety data sheet! Flush the dosing head thoroughly when using haz‐ ardous feed chemicals!
5. Possible additional work - see chapter "Storage, Transport and Unpacking".
Also drain the gear oil - refer to the chapter entitled "Maintenance".
CAUTION! Environmental hazard due to incorrect disposal – Note the local guidelines currently applicable in your
country, particularly in regard to electronic waste!
CAUTION! Environmental hazard due to gear oil The pump contains gear oil, which can cause damage to the
environment.
Drain the gear oil from the pump.
Note the local guidelines currently applicable in your
country!
44
Page 45
14 Technical data
Only for "M - modified" design:
14.1 Performance data
S2Ba under 50 Hz operation
Technical data
WARNING! Risk of personal injuries Please observe the ”Supplement for modified version“ at the
end of the chapter!
It replaces and supplements the technical data!
Type Minimum pump capacity at maximum
back pressure
bar l/h ml/stroke Strokes/min m WS bar R"-DN
16050 PVT 10 50 11.4 73 7 3 1" - 15
16050 SST 16 47 11.4 73 7 3 1" - 15
16090 PVT 10 88 11.4 132 7 3 1" - 15
16090 SST 16 82 11.4 132 7 3 1" - 15
16130 PVT 10 135 10.9 198 7 3 1" - 15
16130 SST 16 124 10.9 198 7 3 1" - 15
07120 PVT 7 126 27.4 73 5 1 20*
07120 SST 7 126 27.4 73 5 1 20*
07220 PVT 7 220 27.7 132 5 1 20*
07220 SST 7 220 27.7 132 5 1 20*
04350 PVT 4 350 29.4 198 5 1 20*
04350 SST 4 350 29.4 198 5 1 20*
All figures refer to water at 20 °C.
The suction lift applies to filled suction line and filled liquid end - when installed correctly.
Maximum stroke rate
Suction lift Permissible
priming pres‐ sure, suction side
Connector size
* For Sigma types 07120, 07220 and 04350 the valves in the dosing head are of type DN 25 (G1 1/2). As for these types of pipes, DN 20 is generally sufficient (see technical data, suction/discharge side connector), the connector parts that can be ordered under the identity code (e.g. inserts) are already reduced to DN 20, i.e. piping and accessories can be installed in DN 20.
45
Page 46
Technical data
S2Ba under 60 Hz operation
Type Minimum pump capacity at maximum back pres‐
sure
bar psi l/h gph Strokes/
16050 PVT 10 145 60 15.9 87 7 3 1" - 15
16050 SST 16 232 56 14.8 87 7 3 1" - 15
16090 PVT 10 145 106 27.8 158 7 3 1" - 15
16090 SST 16 232 98 26.0 158 7 3 1" - 15
16130 PVT 10 145 156 41.0 238 7 3 1" - 15
16130 SST 16 232 148 39.2 238 7 3 1" - 15
07120 PVT 7 102 150 39.7 87 5 1 1 1/2" -
07120 SST 7 102 150 39.7 87 5 1 1 1/2" -
07220 PVT 7 102 264 69.7 158 5 1 1 1/2" -
07220 SST 7 102 264 69.7 158 5 1 1 1/2" -
Maximum stroke rate
min
Suction lift Permissible
priming pressure, suction side
m WS bar R"-DN
Connector size
25*
25*
25*
25*
04350 PVT 4 58 420 108.0 238 5 1 1 1/2" -
04350 SST 4 58 420 108.0 238 5 1 1 1/2" -
All figures refer to water at 20 °C.
The suction lift applies to filled suction line and filled liquid end - when installed correctly.
25*
25*
* For Sigma types 07120, 07220 and 04350 the valves in the dosing head are of type DN 25 (G1 1/2). As for these types of pipes, DN 20 is generally sufficient (see technical data, suction/discharge side connector), the connector parts that can be ordered under the identity code (e.g. inserts) are already reduced to DN 20, i.e. piping and accessories can be installed in DN 20.
Precision
Data Value Unit
Reproducibility ±2 % *
* - when installed correctly, under constant conditions, at least 30 %
stroke length and water at 20 °C
14.2 Shipping weight
Types
kg
16050 ... 16130 PVT 15
SST 20
46
Material version Shipping weight
Page 47
14.3 Wetted materials
Technical data
Types Material version Shipping weight
kg
07120 ... 04350 PVT 16
SST 24
Material ver‐ sion
PVT PVDF PVDF PTFE/PTFE Ceramic /
SST Stainless steel
14.4
Liquid end Suction/pres‐
1.4404
sure connector
Stainless steel
1.4581
Ambient conditions
Seals* / ball seat
PTFE/PTFE Stainless steel
* Metering diaphragm is PTFE coated
** Types 07120, 07220, 04350
Balls Springs Integral relief
glass **
1.4404
14.4.1 Ambient temperatures
Pump, compl.
Data Value Unit
Storage and transport temperature -10 ... +50 °C
Ambient temperature in operation (drive + motor):
valve
Hastelloy C PVDF/FPM or
EPDM
Hastelloy C Stainless
steel/FPM or EPDM
-10 ... +45 °C
14.4.2 Media temperatures
PVT liquid end
SST liquid end
Data Value Unit
Max. temperature long-term at max. oper‐ ating pressure
Max. temperature for 15 min at max. 2 bar 100 °C
Minimum temperature -10 °C
Data Value Unit
Max. temperature long-term at max. oper‐ ating pressure
Max. temperature for 15 min at max. 2 bar 120 °C
Minimum temperature -10 °C
65 °C
90 °C
47
Page 48
Technical data
14.4.3 Air humidity
Air humidity
14.5 Motor data
Electrical data
Data Value Unit
Maximum air humidity *: 92 % rel.
* non-condensing
For motor data - refer to the nameplate.
Motor data sheets, special motors, special motor flanges, external fan, temperature monitoring
For further information for the motor with identity code specification "S", refer to the motor data sheet in the Appendix. Motor data sheets can be requested for all other motors.
For motors other than those with identity code specifica‐ tions "S", "M" or "N": Pay special attention to the oper‐ ating instructions for the motors.
Special motors or special motor flanges are possible on request.
humidity
14.6 Stroke actuator
14.7 Stroke control drive
14.8 Diaphragm rupture sensor
Voltage Mains supply fre‐
quency
230 V ±10 % 50/60 Hz 11.7 W.
115 V ±10 % 60 Hz. 11.7 W.
Voltage Mains supply fre‐
quency
230 V ±10 % 50/60 Hz 6.5 W
115 V ±10 % 60 Hz 6.5 W
Install the sensor according to the chapter "Installation, elec‐ trical".
Capacity
Capacity
48
Page 49
a) Contact (Standard for identity code specification "Displacement body“: A)
Contact loading, max.
at voltage Maximum current
30 V DC 1 A.
The diaphragm rupture sensor is an NC.
For safety reasons we recommend connecting to a pro‐ tective low voltage, e.g. in accordance with EN 60335-1 (SELV ).
The cable can be connected as required.
Technical data
a) Namur sensor (for identity code specifi‐ cation "Displacement body“: A)
14.9 Stroke sensor "Sigma"
5–25 V DC, in accordance with Namur or DIN 60947-5-6, potential-free design.
Data Value Unit
Nominal voltage * 8 VDC
Power consumption - active surface uncovered
Power consumption - active surface cov‐ ered
Rated switching distance 1.5 mm
* Ri ~ 1 kΩ
Cable colour Polarity
blue -
brown +
> 3 mA
< 1 mA
a) Pacing relay (stroke sensor with ...) (Identity code specification "Stroke sensor": 2)
Install the sensor according to the chapter "Installation, elec‐ trical".
For more information, see "Pacing relay" in the "Relay" chapter.
49
Page 50
Technical data
b) Namur sensor (identity code specifica‐ tion "Stroke sensor": 3)
5–25 V DC, in accordance with Namur or DIN 60947-5-6, potential-free design.
Data Value Unit
Nominal voltage * 8 VDC
14.10 Relay
Power consumption - active surface uncovered
Power consumption - active surface cov‐ ered
Rated switching distance 1.5 mm
* Ri ~ 1 kΩ
Cable colour Polarity
blue -
brown +
> 3 mA
< 1 mA
The electrical data for the relay are contained in the chapter "Installation, electrical".
14.11 Gear oil
14.12
Sound pressure level
14.13
Sound pressure level
Supplementary information for modified versions
Manufac‐ turer
Mobil Mobil
* or comparative gear oil
Sound pressure level LpA < 70 dB according to EN ISO 20361
at maximum stroke length, maximum stroke rate, maximum back pressure (water)
(With identity code specification "Version": "M" - "modified")
Name Viscosity
class (ISO
3442)
VG 460 1004542 1.0 l 0.5 l Gear 634 *
Part no. Oil volume,
supplied
Oil volume, needed
Technical data
Technical data of pumps in the modified version can deviate from those of the standard pumps. They can be queried by stating the details of the serial number.
50
Page 51
Technical data
During operation with an automatic stroke length adjustment control together with a variable speed motor, the stroke rate must not fall below 30 strokes / min. Otherwise technical problems occur, because the mechanical resistance of the stroke adjustment spindle becomes too high.
motor
Spare parts
The motor data sheets for the modified version are valid. They may deviate from the standard motor data sheets.
With a modified version, it is absolutely necessary to specify the details of the serial number requesting and ordering the spare and replacement parts.
51
Page 52
0
50
100
150
200
250
300
350
400
450
806040200 100 120
04350 07220 07120 16130 16090 16050
p [bar]
S [%]
C [l/h]
C [l/h]
A
B
p [bar]
S [%]
C [l/h]
C [l/h]
S2Ba (50 Hz) S2Ba (60 Hz)
A
B
2 4 6 8
16141210
0
50
100
150
200
250
300
350
400
450
0
04350 07220 07120 16130 16090 16050
0
50
100
150
200
250
300
350
400
450
500
04350 07220 07120 16130 16090 16050
0
20 40 60 80 100 120
1614121086420
0
50
100
150
200
250
300
350
400
450
500
04350 07220 07120 16130 16090 16050
Diagrams for setting the metering capacity
15 Diagrams for setting the metering capacity
Fig. 25: A) Capacity C at minimum back pressure dependent on the stroke length s. B) Capacity C dependent on the back pressure p.
52
Page 53
16 Dimensional drawings
Dimensional drawings
Compare the dimensions on the dimension sheet and pump.
All dimensions are in mm.
53
Page 54
Dimensional drawings
54
Page 55
Dimensional drawings
55
Page 56
tension nominale
380 480/220 280V
courant de démarrage
fois
Motor Datenblatt / Motor data sheet / Fiche technique pour moteur
Bestell Nr. 1011036 Hersteller ATB order no. / no. de commade producer / producteur Mat.Nr.. 376108
Motor- Typ AF63/4C-7 Leistungsfaktor 0,64
motor type power factor 0,66 type du moteur facteur de puissance
Maschinenart 3 Ph. Motor Wirkungsgrad 66% type of machine efficiency 69% désignation rendement
Schutzart IP55 Bemessungsfrequenz 50 / 60 Hz degree of protection rated frequency degré de protection fréquence nominale
Bauform IMB5 Bemessungsdrehzahl 1380 U/min mounting rated speed 1680 rpm construction vitesse nominale t/mn
Bemessungsleistung 0,250kW Wärmeklasse F rated output temperature class puissance nominale class d'isolement
Bemessungsspannung
/ Δ
Anzugsstrom 3,5/4,0 fach
rated voltage 380-420/220-240V starting current fold
- -
Bemessungsstrom 0,89/1,54A Anzugsmoment 2,3/2,4 fach rated current 0,80/1,47A starting torque fold courant nominale couple de démarrage fois
Geprüft nach
EN60034
Kippmoment 2,4/2,7 fach tested in acc. with pull-out torque fold contrôlé selon couple de décrochage fois
ATEX Nr. Umgebungstemperatur 40°C
ambient temperature
température ambiante
Ex-Schutzklasse Schaltung / Δ
ex-protective system connection
branchement
Drehzahlregelbereich
speed ajustment range
Anmerkung * auf Anfrage beim Hersteller comments * upon request at manufacturer observation * sur demande auprès du producteur
ProMinent
Pumpentyp S2BaHM _ _ _ _ _ _ _ _ _ _ _ _ S _ _ _
S2CaHM _ _ _ _ _ _ _ _ _ _ _ _ U _ _ _ _ _ _ SiBa _ _ _ _ _ _ _ _ _ _ _ _ S _ _
Die Daten entsprechen den Angaben der Motorenhersteller. Kenndaten funktionsgleicher Motoren anderer Hersteller ändern sich nur unwesentlich. Angaben ohne Gewähr. The data correspond to the details given by the motor manufacturers. Ratings of motors with the same functions made by other producers show insignificant changes only. This information is supplied without liability. Les données techniques correspondent au descriptif d
u
fabricant des moteurs. Les données techniques des moteurs similaires chez d’ autres fabricants varient très peu. Données sont d’ ordre général.
Motor data sheet standard motor
17 Motor data sheet standard motor
56
Page 57
18 Liquid ends Sigma/ 2
P_SI_0024
1
5
4
5
6
2 3
Liquid end Sigma/ 2 130-DN 15 and 350­DN 25 PVT
Liquid ends Sigma/ 2
Fig. 26: Liquid end Sigma/ 2 130-DN 15 and 350-DN 25 PVT
Item. Description Type 16050,
1 Spring ** **
2 Ball * *
3 Ball seat * *
4 Diaphragm rupture sensor,
5 Valve 792517* 740615*
6 Multi-layer diaphragm 1029771* 1033422*
* The items listed are included in the spare parts kit. ** Special accesso‐ ries (not included in the spare parts kit). Technical changes reserved.
visual
16090, 16130
1033323 1033323
Type 04350, 07120, 07220
57
Page 58
P_SI_0086_SW
*
*
*
*
*
*
10
Liquid ends Sigma/ 2
Sigma/ 2 PVA relief valve-A
Fig. 27: Sigma/ 2 PVA relief valve-A
Item. Description Type 16050,
16090, 16130
10 Relief valve, compl. 10 bar PVA 1018947
10 Relief valve, compl. 7 bar PVA 740811
10 Relief valve, compl. 4 bar PVA 740812
* The items listed are included in the spare parts kit. Springs made from Hastelloy C, O-rings from FPM-A and EPDM. Technical changes reserved.
Type 07120, 07220
Type 04350,
58
Page 59
P_SI_0025_SW
1
5
4
5
6
2 3
Liquid end Sigma/ 2 130 and 350 SST
Liquid ends Sigma/ 2
Fig. 28: Liquid end Sigma/ 2 130 and 350 SST
Item. Description Type 16050,
1 Spring * *
2 Ball * *
3 Ball seat * *
4 Diaphragm rupture sensor,
visual
5 Valve 809404 803708
6 Multi-layer diaphragm 1029771* 1033422*
* The items listed are included in the spare parts kit. Technical changes reserved.
16090, 16130
1033323 1033323
Type 04350, 07120, 07220
59
Page 60
*
*
*
P_SI_0087
10
Liquid ends Sigma/ 2
Sigma/ 2 SSA relief valve-A
Fig. 29: Sigma/ 2 SSA relief valve-A
Item. Description Type 16050,
16090, 16130
Type 07120, 07220
Type 04350,
10 Relief valve, compl. 16 bar SSA 1019246
10 Relief valve, compl. 7 bar SSA 740815
10 Relief valve, compl. 4 bar SSA 740814
* The items listed are included in the spare parts kit. Springs made from Hastelloy C, O-rings from FPM-A and EPDM. Technical changes reserved.
60
Page 61
19 Wear parts for Sigma/ 2
Wear parts for Sigma/ 2
19.1
Spare parts kits PVT (liquid ends)
Spare parts kit Types 16050, 16090, 16130 Types 04350, 07120, 07220
FM 130 - DN15 1035951
FM 350 - DN25 1035953
Spare parts kits SST (liquid ends)
Spare parts kit Types 16050, 16090, 16130 Types 04350, 07120, 07220
FM 130 - DN15 1035957
FM 130 - DN15 with 2 complete valves 1035954
FM 350 - DN25 1035960
FM 350 - DN25 with 2 complete valves 1035959
Spare parts kits for integrated relief valve
Spare parts kit for material version Seals Part no.
Standard
Scope of supply: see exploded view drawings.
Scope of supply: see exploded view drawings.
SPK PRV 4 bar PVT/SST FPM-A / EPDM 1031199
SPK PRV 7 bar PVT/SST FPM-A / EPDM 1031200
SPK PRV 10 bar PVT FPM-A / EPDM 1031201
SPK PRV 16 bar SST FPM-A / EPDM 1031203
Scope of supply: see exploded view drawings.
19.2
Spare parts kits
Scope of supply with PVT material version
1 x Diaphragm, 2 x Suction valve complete, 1 x Discharge valve complete, 1 x Valve balls
1 x Elastomer sealing set (EPDM)
2 x Ball seat housings, 2 x Ball seat discs, 4 x Composite seals
1x Seal washer (for bleed valve or relief valve)
Scope of supply with SST material version
1 x Diaphragm, 2 x Valve balls
Physiological safety
2 x Cover rings
4 x Composite seals
1x Seal washer (for bleed valve or relief valve)
61
Page 62
Wear parts for Sigma/ 2
Ordering Information
Spare parts kits PVT (liquid ends)
Liquid end Types 16050, 16090, 16130 Types 07120, 07220, 04350
FM 130 - DN 15 1046472 -
FM 350 - DN 25 - 1046475
Spare parts kits SST (liquid ends)
Liquid end Types 16050, 16090, 16130 Types 07120, 07220, 04350
FM 130 - DN 15 1046473 -
FM 130 - DN 15 with 2 valves com‐
1046474 -
plete
FM 65 - DN 10 - 1046476
FM 65 - DN 10 with 2 valves complete - 1046477
Wetted materials – "Physiologically safety with regard to wetted materials" design
Material version Liquid end Suction / pressure
connector
Seals* / ball seat Balls Integrated bleed
valve or relief valve
PVT PVDF PVDF PTFE / PVDF Ceramic / glass ** PVDF / EPDM
SST Stainless steel
1.4404
Stainless steel
1.4581
PTFE / PVDF Stainless steel
1.4404
Stainless steel / EPDM
* Metering diaphragm is PTFE-coated; seals are PTFE composite seals
PTFE: FDA No. 21 CFR §177.1550
PVDF: FDA No. 21 CFR §177.2510
** with 07120, 07220, 04350
62
Page 63
EC Declaration of Conformity for Machinery
20 EC Declaration of Conformity for Machinery
For pumps without explosion protection:
Designation of the product: Metering pump, Sigma product range
Product type: S2Ba...
Serial number: refer to nameplate on the device
Relevant EC directives: EC Machinery Directive (2006/42/EC)
EC EMC Directive (2004/108/EC)
Compliance with the protection targets of the Low Voltage Directive (2006/95/EC) according to Appendix I, No. 1.5.1 of the Machinery Directive 2006/42/EC
In accordance with DIRECTIVE 2006/42/EC OF THE EUROPEAN PAR‐ LIAMENT AND OF THE COUNCIL, Appendix I, BASIC HEALTH AND SAFETY REQUIREMENTS, section 1.7.4.2. C.
We,
n ProMinent Dosiertechnik GmbH n Im Schuhmachergewann 5 - 11 n D - 69123 Heidelberg,
hereby declares that the product specified in the following, complies with the relevant basic health and safety requirements of the EC Directive, on the basis of its functional concept and design and in the version distributed by us.
This declaration loses its validity in the event of a modification to the product not agreed with us.
Harmonised standards applied, in particular:
EN ISO 12100
EN 809
EN 61010-1
EN 61000-6-2/3
Date: 20/09/2013
63
Page 64
EC Declaration of Conformity for Machinery Used in Areas at Risk of Explosion
21
EC Declaration of Conformity for Machinery Used in Areas at Risk of Explosion
For pumps with explosion protection:
Designation of the product: Metering pump, Sigma 2 product range.
Version "Explosion protection" in accordance with "ATEX 95"
Product type: S2Ba_ _ _ _ _ _ _ _ _ _ _ _ _ _XY_ _
Characteristic value "X" = "P" or "L",
and characteristic value Y = "1" or "2"
or "X" = "1, 2, 3, 4 or 5" and "Y" = "A"
We,
n ProMinent Dosiertechnik GmbH n Im Schuhmachergewann 5 - 11 n DE - 69123 Heidelberg,
hereby declares that the product specified in the following, complies with the relevant basic health and safety requirements of the EC Directive, on the basis of its functional concept and design and in the version distributed by us.
This declaration loses its validity in the event of a modification to the product not agreed with us.
Serial number: refer to nameplate on the device
Relevant EC directives: EC Machinery Directive (2006/42/EC)
EC EMC Directive (2004/108/EC)
EC Explosion Prevention Directive (94/9/EC)
Harmonised standards applied, in particular:
The combination of the components does not give rise to any new Ex-related dangers
Ex-designations: Pump without motor: II 2G c IIC T4 X
Overall system: II 2G c IIC T3 X (for "Y"="1") or II 2G c IIC T4 X (for "Y"="2" or
Pump without motor: EN ISO 12100-1/2, EN 809, EN 13463-1/5
Motor Ex "e": EN 50014, EN 50019
Motor Ex "d": EN 60079-0, EN 60079-1, EN 60079-7, EN 61241-0, EN 61241-1
Stroke sensor: EN 60079-0, EN 60079-11, EN 60079-26
Motor (characteristic value "Y"="1") : II 2G EEx e IIC T3
Motor (characteristic value "Y"="2") : II 2G EEx de IIC T4
Diaphragm rupture sensor: II 1G Ex ia IIC T6
"A")
Date: 26/05/2010
64
Page 65
65
Page 66
66
Page 67
67
Page 68
ProMinent Dosiertechnik GmbH
Im Schuhmachergewann 5-11
69123 Heidelberg
Germany
Telephone: +49 6221 842-0
Fax: +49 6221 842-612
email: info@prominent.com
Internet: www.prominent.com
986271, 2, en_GB
© 2011
Loading...