ProMinent gamma/l, sigma Installation And Configuration Manual

gamma/ L and Sigma with PROFIBUS
®
Function blocks
Installation and configuration manual
B0288
PROFIBUS
Parts no. 985968 BA G 032 04/11 EN
Please carefully read these operating instructions before use! · Do not discard!
The operator shall be liable for any damage caused by installation or operating errors!
Technical changes reserved.
BA Gala Profi FB, 1, en_GB
© 2011
ProMinent Dosiertechnik GmbH
Im Schuhmachergewann 5-11
69123 Heidelberg
Germany
Telephone: +49 6221 842-0
Fax: +49 6221 842-617
email: info@prominent.com
Internet: www.prominent.com
2
Table of contents
1 Installation of the GSD file in Step 7 Manager................................. 4
1.1 Creating a project.................................................................... 4
1.2
Install GSD file........................................................................ 7
2 Integrating the device and the function block into your own
project............................................................................................ 11
2.1
Add PROFIBUS® Master System.......................................... 11
2.2
Connecting the device to the PROFIBUS® Master System.. 14
2.3 Copying and linking a function block..................................... 17
3 Function blocks for gamma/L and Sigmas.................................... 28
3.1 Introductory information........................................................ 28
3.2 Function block FB110 for basic functionality......................... 30
3.3 Function block FB111 for complete functionality................... 34
3.3.1 Explanations of the operating modes................................. 34
3.3.2 Tables for the addresses.................................................... 38
Table of contents
3
1 Installation of the GSD file in Step 7 Manager
This installation manual is only for persons who are familiar with the Siemens Simatic S7 PLC.
Prerequisites:
The installation package (such as “Delta_S7_function_block” or Gamma‐ Sigma_S7_function_block”), with the GSD file (such as prom0B02.gsd”) must have been downloaded from the
www.prominent.com
website. (The
installation package for the respective product is there.)
The installation package must be open on the PC and the GSD must be copied from the installation package into a folder.
1.1 Creating a project
Installation of the GSD file in Step 7 Manager
4
1.
Follow the path
“File è ‘New Project’ Wizard...”
and click with the
mouse.
ð
The
“Introduction”
window will be displayed:
2. Click the
[Next>]
button.
ð
The window
“Which CPU are you using in your project?”
will be
displayed:
Installation of the GSD file in Step 7 Manager
5
3. Select the correct CPU.
When selecting the correct CPU the software version that is imprinted on the CPU and the order number help.
Click the
[Next>]
button.
ð
The window
“Which blocks do you want to add?”
will be dis‐
played:
4. Always place a check mark for option block OB1.
5. If the function will be called in selectable time intervals, in addition select OB35 with a check mark (the operation blocks can vary depending on CPU).
A more precise description of the performance scope of the CPU is in your operating manual.
Installation of the GSD file in Step 7 Manager
6
6. Click the
[Next>]
button.
ð
The window
“What do you want to call your project?”
will be
displayed:
7. After a project name has been entered (in this case “Pro‐ fibus_Delta”), click the
[Finish]
button.
ð
The Simatic Manager window will open - see the following chapter.
1.2 Install GSD file
Fig. 1: Simatic Manager with main window with navigation bar
Installation of the GSD file in Step 7 Manager
7
1. In Simatic Manager, in the navigation bar (left) select
“Simatic 300
Station”
.
ð
In the main window a symbol
“Hardware”
is displayed.
2. Double click the
“Hardware”
symbol.
ð
The Hardware Configurator will open:
Fig. 2: The Hardware Configurator
3.
Follow the path
“Options è Install GSD File”
and click with the
mouse.
ð
The
“Install GSD File”
window will open:
4. Use the
[Browse]
button to select the folder into which you have copied the GSD file. (In this screenshot the folder "Profibus Delta" is on drive "E:").
Installation of the GSD file in Step 7 Manager
8
5. If the path was correct, the GSD file will be displayed in the window. In this screenshot, this is the file “PROM0B02.gsd” for the delta (for gamma/ L or Sigma it would be the file “PROM0596.gsd”).
6. Select the file and press the
[Install]
button.
ð
A warning will be displayed stating that the action cannot be undone:
7. Click
[Yes]
.
ð
If this GSD file is already present, the following message will be displayed:
Installation of the GSD file in Step 7 Manager
9
8. Click
[Yes]
to install the GSD file.
ð
The following message will be displayed:
9. Click
[OK]
to conclude the installation.
10. Click
[Close]
to close the window.
The next chapter shows how you can integrate the ProMinent device (pump, measuring transducer, etc.) into your own project.
Installation of the GSD file in Step 7 Manager
10
2 Integrating the device and the function block into your own
project
Note: This description cannot go into all the details of PRO‐ FIBUS® communication.
If necessary attend an appropriate training course.
2.1
Add PROFIBUS® Master System
This section describes how to add a PROFIBUS® Master System into your own project and how to generate a PROFIBUS® subnet:
1. Double click to open your own project (shown here with a red border) that you created in chapter 1.1:
Fig. 3
2. Double click the
“Hardware”
symbol to open the Hardware Configu‐
rator:
Fig. 4
Integrating the device and the function block into your own project
11
3. Add a Master System for the CPU: For example, for CPU 314C-2DP, right click slot X2 “DP”.
ð
The context menu will open:
Fig. 5
4. Here select
“Add Master System”
.
ð
The window
“PROFIBUS Interface DP”
will be displayed:
Fig. 6
5.
In the
“Parameters”
tab under
“Address”
enter the PROFIBUS
®
address of the CPU used.
Integrating the device and the function block into your own project
12
6. Click
[New]
.
ð
The
“New Subnet PROFIBUS”
will be displayed:
Fig. 7
7. Under
“Name”
enter a name for the subnet of the PROFIBUS and
click
[OK]
.
ð
The window
“PROFIBUS Interface DP”
will be displayed again:
Fig. 8
8.
(If necessary via
“Properties”
special PROFIBUS® parameters can
be adjusted.)
Integrating the device and the function block into your own project
13
9.
Mark the PROFIBUS® subnet and click
[OK]
.
ð
The Hardware Configurator connects the CPU (the Master System) with the Subnet of the PROFIBUS®, which the Hard‐ ware Configurator now displays in this manner:
Fig. 9: Graphic presentation: Connection CPU (Master System) with the subnet of the PROFIBUS® in the Hardware Con‐ figurator (excerpt)
2.2
Connecting the device to the PROFIBUS® Master System
As soon as the PROFIBUS® master system has been added to the project and the PROFIBUS® subnet is created, the gamma/ L or Sigma metering pump can be connected to the PROFIBUS®:
1.
Call the catalog via
“Options è Display Catalog”
.
ð
To the right in the window you will see:
Fig. 10
Integrating the device and the function block into your own project
14
Loading...