ProMinent multiFLEX M10, multiFLEX M5 User Manual

Page 1
11
multiFLEX
M10 and M5
User Manual
Page 2
Page 3
CONTENTS
Safety
1. STANDARD OPERATIONS 4
1.1 What’s Happening Now
1.2 Checking & Clearing Alarms
1.3 Checking & Changing Setpoints
1.4 Calibrating Sensors
1.5 Changing Biocide Timing
1.6 Adjusting % Feeds
1.7 Userid - Passwords
2. ADDITIONAL OPERATIONS 16
2.1 Setting Biocide Prebleed-Lockout
2.2 Adjusting Boiler Blowdown Timing
2.3 Sensor Diagnostics
2.4 Control Diagnostics
2.5 System Diagnostics
3. START UP PROCEDURE 28
3.1 Read this first!
3.2 Connect Sensors
3.3 Connect Pumps, Valves, Solenoids
3.4 Verify controls
3.5 Setting Sensor Alarms
3.6 Setting Output Alarms
3.7 Verify Interlocks
3.8 Verify Blocking Relays
3.9 Selecting Special Controls
3.10 Modifying Variable Cycles
3.11 Modifying Feed Verification
3.12 Modifying Time & Date
4. ADDITIONAL INFORMATION 46
4.1 Spare Parts
4.2 Technical Support
4.3 Specifications
4.4 Keypad Navigator
4.5 Revision Log
Page 4
Saftey
Electrical Shock Hazard
CAUTION: The operator of this instrument is advised that if the equipment is used in a
manner not specified in this manual, the protection provided by the equipment may be impaired.
Opening the controller enclosure with the controller plugged in, exposes the user to AC line voltages on the lower of the two controller circuit boards.
Ground the controller AC power to the ground screw labeled and located on the bottom, right of the aluminum backplate.
External, 120VAC plug boxes are provided with controllers installed in North
America External plug boxes are grounded to the ground screw labeled located on the bottom, center of the aluminum backplate.
USER WARNING : CAUTION
Water Treatment Controllers operate steam and water valves and may pump hazardous, corrosive and toxic chemicals. Opening the controller enclosure exposes user to the risk of electrical shock at power line voltages.
Understand fully the implications of the control setpoints, interlocks and alarms that you select. Harm to personnel and damage to equipment may result from mis-application.
Unplug or turn OFF the AC power to the controller if you have any concerns regarding safety or incorrect controller operation and notify supervisory staff.
YOUR CONTROLLER
Controllers are supplied in many different configurations.
The HELP section in the back of this manual contains the information for terminating the sensors supplied with your specific controller.
The HELP section in the back of this manual depicts the installation plumbing header showing the sensor set supplied with your specific controller.
Page 5
1.1 What’s Happening Now
.
Power UP, first display, current date
Key ENTER for System menu
.
Key DOWN & enter to clear all alarms
And to view detail on Sensor ‘D’, Relay ‘2’ and
‘Sys’tem Alarms
. .
Sensors and the relays they control are grouped
.
Key ENTER on sensor for sensor ‘O’ menu
& ENTER on the relay ‘1’ relay menu
. . .
Sensor ‘E’ menu: Diagnostics | Alarms | Calibrate |
Configure
.
Relay ‘2’ menu: Diagnostics | Configure |
Alarms | Timed Events | Setup
. .
The display line with the ENTER arrow
Displays Relay ‘9’ menu on ENTER
.
Sampling timing is adjusted by keying ENTER, DOWN
to Configure & ENTER
. . .
Sensor display current value
Relays sown ON/OFF state and run time if ON
.
Water meters show volume from midnight
. . .
Flowswitch ‘T’ is ON and has been on for 560.2
minutes from midnight
.
Biocide B pump is controlled by Relay #8
and is now OFF:
System:2003-10-03 S/N: M0389001 Alarms: 16:38:11 D G 2 Sys
Tower Make-up O 12800 Gal Inhibitor Feed 1 OFF:
Tower Conduct'y E 1246 uS Tower 1 Bleed 2 ON: 18.6min
Blr 2 Conduct'y F 5240 uS B2 B'down Valve 9 ON: 0.4min
Corrosion Rate D
1.45 mpy Tower Bleed meter Q 34000 Gal
Flowswitch 1 T ON: 560.2min Biocide B 8 OFF:
Page 6
1.2 Checking & Clearing Alarms 1 of 3
CHECK ALARMS
Power UP, first display
. .
Key DOWN to Alarms & ENTER
to view detail on Sensors ‘C’ ,‘K’ & Relay ‘3’
& to clear alarms
. .
Key DOWN to view active alarms
& ENTER
. . . . . .
Display on no active alarms
. .
OR
Scroll down to view all active alarms
. .
Name of alarming Sensor
Alarm type: pH Sensor value above High alarm for a
user set time.
. . . . .
Name of alarming Water Meter
Alarm type: Low alarm checked at midnight
High meter alarm trip immediately
. . . .
Name of Output control alarming
Alarm type: Feed limit timer turns OFF Pump
Day Timer may be set to limit on time/day
.
System:2003-10-03 S/N: M0389001 Alarms: 16:38:11 C K 3
Alarms: Clear Alarms Alarms
Alarms:
Alarms..............
No Active Alarms
Alarms:
Alarms..............
pH Sensor Alarmed High
Alarms:
Alarms..............
Water Meter O Alarmed Low
Alarms:
Alarms..............
Acid Pump Limited, ON timer
or to exit
Page 7
1.2 Checking & Clearing Alarms 2 of 3
.
CLEAR ALARMS
Power UP, first display
. .
Key ENTER
to view detail on Sensors ‘C’ ,‘K’ & Relay ‘3’
& to clear alarms
. .
Key ENTER to Clear Alarms
. . . .
Clear Alarms:
Resets only all active alarms
.
If you wish to end biocide events.
Prebleeds or lockouts.
OR restart special controls:
Clear the target relay alarm.
See page 3 of 3.
.
Information only display
EXIT key escapes
.
Internet HELP reference for more detail
Refer to Technical Support.
.
System:2003-10-03 S/N: M0389001 Alarms: 16:38:11 C K 3
Alarms: Clear Alarms Alarms
Alarms:
Clear Alarms.........
Clear All Alarms YES
Alarms Alarms Cleared Key to Exit iNet HELP# 0700
Page 8
1.2 Checking & Clearing Alarms 3 of 3
RESET RELAY USING CLEAR ALARMS
.
Key UP or DOWN to the output relay
& key ENTER
.
Any relay can be reset
.
This example is a Biocide pump with 16.6 minutes
of ON time remaining
.
Key DOWN to Alarms & ENTER
. .
Key DOWN to ‘Reset Alarm & Time & ENTER
Relay 4 will turn OFF
.
Biocide feeds and prebleeds will end
If this relay is timing a biocide lockout, it will end
.
Special controls like Bleed & Feed, % Time
or Boiler Captured Sample controls will restart.
.
. .
After you key ENTER you see the value of the relay
feed limit timer.
. .
Key EXIT twice
& you’ll see that Relay 4 is now OFF
. .
Relays don’t need to be ON to be reset
You may wish to restart special control
Or end the lockout of a bleed relay
Biocide A 4 ON:owes 16.6 Biocide B 5 OFF: No Control
Biocide A 4 Diagnostics Configure Alarms
Biocide A 4
Alarms..............
Reset Alarm & Time YES
Biocide A 4
Alarms ............
Minutes/Actuation
120.0 minutes
Biocide A 4 OFF: No Control Biocide B 5 OFF: No Control
then
then
to exitand
Page 9
1.3 Checking & Changing Setpoints
. .
Key UP or DOWN to the output relay
& key ENTER
.
Relays follow the controlling sensor
. . .
Key DOWN to Configure & ENTER
. . . . . .
Key DOWN to ‘Turn ON’ & ENTER
Select ‘Measure Volume’ for water meter controls.
Current setpoint is 1000uS
. . .
Use the UP & DOWN keys to adjust the setpoint
RIGHT moves the cursor across the screen
.
EXIT abandons adjusting the setpoint
. . . .
You can adjust ON or OFF setpoints or both
. .
Key ENTER to adjust or UP – DOWN to view current
settings
. . . . .
Turn OFF > Turn ON not allowed with a Rising
Setpoint control
. . .
Tower Conduct'vty E 986 uS Bleed Valve 2 OFF: Setpoints
Bleed Valve 2 Diagnostics Configure Alarms
Bleed Valve 2
Configure...........
Turn ON 1000 uS
Editing Value
Turn ON ............
1150 uS Executes, Exits
--
Bleed Valve 2
Configure...........
Turn OFF 980 uS
Editing Value
Turn OFF............
1130 uS Executes, Exits
--
then
then
then
then
then
Page 10
1.4 Calibrating Sensors 1 of 2
SENSORS
.
Key ENTER at selected sensor
. . . . . . .
Key DOWN to Calibrate & ENTER
. . . . . .
Key ENTER to change sensor value
OR
DOWN & ENTER to Reset to Factory option
. . .
Use the UP & DOWN keys to adjust the value
RIGHT moves the cursor across the screen
.
EXIT abandons calibrating
. .
If the calibration succeeds,
you’ll return to the sensor value display
.
If the sensor is outside of calibration limits
You’ll view the override option
. .
Key ENTER then UP or DOWN to override
. .
If you key DOWN, you’ll have the
Reset to Factory option
.
Key ENTER then UP or DOWN to Reset
.
Tower Conduct'vty E 986 uS Bleed Valve 2 OFF: Setpoints
Tower Conduct'vty E Diagnostics Alarms Calibrate
Tower Conduct'vty E
Calibrate...........
Enter Current Value 986 uS
Editing Value: Enter Current Valu.. 996 uS Executes, Exits
--
Tower Conduct'vty E
Calibrate...........
Sensor fault Override warning
Tower Conduct'vty E
Calibrate...........
Reset to Factory NO
then
then
then
then
then
Page 11
1.4 Calibrating Sensors 2 of 2
CONTACT HEAD & TURBINE METERS
.
Key ENTER at selected water meter
. . . . . . .
Key DOWN to Calibrate & ENTER
. . . . . .
Key ENTER to change value
OR
DOWN & ENTER to Reset to Factory option
. . .
Use the UP & DOWN keys to adjust the value
RIGHT moves the cursor across the screen
.
EXIT abandons calibrating
. .
If the calibration succeeds,
you’ll return to the sensor value display
.
Turbine and Paddlewheel meters
use pulses/unit volume as calibration value
. . . .
If you key DOWN, you’ll have the
Reset to Factory option
.
Key ENTER then UP or DOWN to Reset
Setting Volume per Contact OR ‘K’ Factor to 100
Make-up meter O 23400 gal Inhibitor Pump 1 OFF: Setpoints
Make-up meter O Diagnostics Alarms Calibrate
Make-up meter O
Calibrate...........
Volume per Contact 100 gal
Editing Value: Volume per Contact.. 200 gal Executes, Exits
--
Editing Value:
'K' Factor..........
321.5 gal Executes, Exits
Make-up meter O
Calibrate...........
Reset to Factory NO
then
then
then
then
or
or
Page 12
1.5 Changing Biocide Timing 1 of 2
.
MODIFY EXISTING EVENT, REVIEW EVENTS
.
Key ENTER at selected chemical pump
This one’s powered by Relay No.5
. . . . . .
Key DOWN to Timed Events & ENTER
. . . . . .
This Biodispersant has 8 existing events
See Page 2 for Add an Event
. . . .
If there are ‘0’ events then the Edit an Event
option does not exist
. .
ENTER to select the Event you wish to edit
. .
Key UP DOWN to Select one of 28 events
OR
Review existing timed events
.
Day = 1 to 28 for 4 week feed cycles
Day = 1 to 7 on weekly feed cycles
. . .
Key RIGHT to select the field you wish to modify
.
Key UP DOWN to modify the field
ENTER to update.
.
Biocide A 4 ON: 36.5 min Biodispersant 5 OFF: Setpoints
Biodispersant 5 Configure Alarms Timed Events
Biodispersant 5
Timed Events........
Add an Event YES Events,8
Select one: Day Start ON min... 12 04:30 45 Executes, Exits
then
then
Biodispersant 5
Timed Events........
Edit an Event YES
then
Edit an Event: Day Start ON min... 12 06:15 119 Executes, Exits
--
Page 13
1.5 Changing Biocide Timing 2 of 2
.
ADD AN EVENT OR EVENTS
.
Key ENTER at selected chemical pump
.
Key DOWN to Timed Events & ENTER
. . .
Key RIGHT to select the field you wish to modify
.
Key UP DOWN to modify the field
ENTER to update.
. .
Key UP DOWN to select ONCE | WEEKLY
| ALTERNATE WEEKS
.
7 Day Cycles select one of ONCE | DAILY
| ALTERNATE DAYS
1 Day Cycles select one of ONCE | HOURLY
| ALTERNATE HOURS
. .
In this example, we added weekly events
Increasing the total events from 8 to 12.
. . .
Keying UP DOWN @ Add an Event
Displays the Delete all Events option
. .
Key ENTER to remove all events
Biodispersant 5
Timed Events........
Add an Event YES Events,8
Add an Event: Day Start ON min... 6 14:30 15 Executes, Exits
Select one:
Event frequency.....
Once Executes, Exits
Biodispersant 5
Timed Events........
Add an Event YES Events,12
--
Biodispersant 5
Timed Events........
Delete all Events YES
then
then
Page 14
1.6 Adjusting % Feeds 1 of 2
.
ADJUST BASE FEED
Key UP or DOWN to the pump control
& key ENTER
. . . . .
Key DOWN to Configure & ENTER
. . . . . .
Key DOWN to Special Control & ENTER
.
Key enter to View or change existing control
.
Percentage Time turns ON for user set %
every 5 minutes
. . .
Key ENTER to view adjust current %
. . . . .
Percentage Time is set to 28%
Pump runs for 84 seconds every 5 minutes
.
Key ENTER to modify
. . . .
Key UP DOWN & RIGHT to modify
then key ENTER
.
31% is 93 sec. every 5 minutes
.
Tower 1 Inhibitor 6 ON: 6.2 min Tower 2 Inhibitor 8 OFF: No Control
Tower 1 Inhibitor 6 Diagnostics Configure Alarms
Tower 1 Inhibitor 6
Configure ..........
Special Control Percentage Time
then
then
Tower 1 Inhibitor 6
Special Control.....
Percentage Time Executes, Exits
Editing Value:
% ON Time...........
31% Executes, Exits
--
Tower 1 Inhibitor 6
Percentage Time.....
% ON Time 28%
then
Page 15
1.6 Adjusting % Feeds 2 of 2
.
ADJUST % BLEED FEEDS
. .
Key UP or DOWN to the pump control
& key ENTER
. . . .
Key DOWN to Configure & ENTER
. . . . . .
Key DOWN to Special Control & ENTER
.
Key enter to View or change existing control
. .
Key DOWN if you wish to switch from
BLEED & FEED
to
BLEED THEN FEED
. . .
Key DOWN to % of Time & ENTER
. . .
Percentage Time is set to 54%
Pump runs for 162 seconds every 5 minutes
.
Key ENTER to modify
. . .
Key UP DOWN & RIGHT to modify
then key ENTER
.
49% is 147 sec. every 5 minutes
.
Tower 1 Inhibitor 6 ON: 6.2 min Tower 2 Inhibitor 8 OFF: No Control
Tower 2 Inhibitor 8 Diagnostics Configure Alarms
Tower 1 Inhibitor 6
Configure ..........
Special Control Bleed & Feed
then
then
Tower 1 Inhibitor 6
Special Control.....
Bleed & Feed Executes, Exits
Editing Value:
% of Time...........
49% Executes, Exits
--
Tower 1 Inhibitor 6
Bleed & Feed........
% of Time 54 %
then
then
then
Page 16
1.7 Userid – Passwords
.
IGNORE IF PASSWORDS NOT ‘ON’
IN YOUR CONTROLLER
.
‘YES’ appears if passwords are ON’
Your present USERID also displays.
. . .
If ‘YES’ Key ENTER
& key in your password.
. .
Key an incorrect password to log off.
Auto-logoff occurs 30 minutes after the last keystroke.
. .
If you keyed a correct password,
you’ll see this display
. . .
If your password is incorrect,
you’ll still be the ‘public’ user
. .
If you require the ADMIN password,
you’ll see this display when you are already
logged in under another userid
. .
If you are any user but ‘public’
& you key DOWN @ ‘Login Required’
you can adjust your password
. . . .
Keep your password simple
If you are using the keypad
. .
System:
Passwords...........
Login Required YES,public
Editing Value:
Key Password......
G Executes, Exits
System: Time & Date LAN Setup Passwords
System:
Passwords...........
Login Required YES, public
System: New Password XK Executes, Exits
--
System:
Passwords........
New Password YES
--
then
then
Page 17
2.1 Setting Biocide Prebleed- Lockout 1 of 2
.
.
Key UP or DOWN to the biocide pump control
& key ENTER
. . . . . .
Key DOWN to Configure & ENTER
. . . .
Key DOWN to Special Control & ENTER
.
If not set to Prebleed-Lockout, key UP DOWN
. .
Key ENTER to adjust Prebleed-Lockout parameters
. .
‘Bleed Relay’ prebleeds before each biocide feed
and is locked-out after each feed event
.
Key ENTER to modify
. . . .
‘Lockout Time’ turns OFF the bleed relay
during biocide kill time
.
Key ENTER to modify
. . .
‘Prebleed Time’ turns ON the bleed relay
reducing the tower conductivity before
a biocide feed event
.
Key ENTER to modify
.
Biocide A 3 OFF: No Control Biocide B 4 OFF: No Control
Biocide A 3 Diagnostics Configure Alarms
Biocide A 3
Configure ..........
Special Control Prebleed-Lockout
then
Biocide A 3 Prebleed-Lockout---­Bleed Relay Tower 1 Bleed
Biocide A 3 Prebleed-Lockout---­Prebleed time
30.0 minutes
Biocide A 3 Prebleed-Lockout---­Lockout Time
120.0 Minutes
then
then
Continued on Page 2
Page 18
2.1 Setting Biocide Prebleed- Lockout 2 of 2
.
You can ‘Prebleed’ until this sensor measures
the conductivity that you set
.
Key ENTER to modify
. .
This is the ‘Prebleed’ conductivity target
.
‘Prebleed’ ends at this conductivity
OR at the end of ‘Prebleed Time’
.
Key ENTER to modify
Set high to control on ‘Prebleed Time’ only
. . .
All Prebleed-Lockout parameters are modified
by ENTER when the parameter is displayed
.
. . . . .
Key UP DOWN & RIGHT to modify
then key ENTER
. . . . . .
Bleed solenoid or valve now turns ON
For 45 minutes before each feed event
on Biocide A, powered by Relay No.3
. .
Biocide A 3 Prebleed-Lockout---­Prebleed Sensor Tower Conduct'ty
Biocide A 3 Prebleed-Lockout---­Prebleed Value
750.0 uS
Biocide A 3 Prebleed-Lockout---­Prebleed time
30.0 minutes
then
Editing Value:
Prebleed Time.......
45.0 minutes Executes, Exits
--
Biocide A 3 Prebleed-Lockout---­Prebleed time
45.0 minutes
Typical: Modify Bleed time
Page 19
2.2 Adjusting Boiler Blowdown Timing 1 of 2
.
Key UP or DOWN to the boiler blowdown control
& key ENTER
.
This example is using Relay No.2
.
It’s been ON for 1.2 minutes
either Blowing down OR Sampling
. . .
Key DOWN to Configure & ENTER
. . . . .
Key DOWN to Special Control & ENTER
. .
Key ENTER twice to view or adjust timing
. .
‘Sampling’ opens the blowdown valve so the
conductivity sensor gets a new sample.
.
Key ENTER to modify
. . . .
‘Measure’ cools the sample at the conductivity sensor.
At the end of ‘Measure’ conductivity is compared
to the ON – OFF setpoints.
.
Key ENTER to modify
. . .
If the conductivity is above the TURN ON setpoint,
the valve opens for the Blowdown Time
.
Key ENTER to modify
.
Boiler 1 Cond. E 2546 uS B1 Blowdown 2 ON: 1.2 minutes
B1 Blowdown 2 Diagnostics Configure Alarms
B1 Blowdown 2
Configure ..........
Special Control Captured Sample
then
B1 Blowdown 2 Captured Sample----­Sampling Time 30 seconds
B1 Blowdown 2 Captured Sample----­Blowdown Time 60 seconds
B1 Blowdown 2 Captured Sample----­Measure Time 60 seconds
then
then
Continued on Page 2
Page 20
2.2 Adjusting Boiler Blowdown Timing 2 of 2
If the measured conductivity is below
the TURN OFF setpoint,
the next Sample occurs after the ‘Re-Sample delay’
.
If the measured conductivity is above
the TURN OFF setpoint,
Blowdown Time’s are followed by Measure Times
as the boiler conductivity falls.
.
Key ENTER to modify
.
If your installation does not include
a Fail-to-Sample sensor
‘none’ will be displayed
. . .
Key UP DOWN to Blowdown Time & ENTER
.
Key ENTER to adjust timing
. . . . .
Key UP DOWN & RIGHT to modify
then key ENTER
. . .
We’ve increased the Blowdown Time
from 60 to 90 seconds
.
Sampling Time, Measure Time and
Re-sample delay are adjusted
using the same key sequence
B1 Blowdown 2 Captured Sample----­Re-sample delay 45 minutes
B1 Blowdown 2 Captured Sample----­Fail-to-Sample B1 Fail-to-Sample
B1 Blowdown 2 Captured Sample----­Blowdown Time 60 seconds
then
Editing Value:
Blowdown Time.......
90.0 seconds Executes, Exits
--
B1 Blowdown 2 Captured Sample----­Blowdown Time 90 seconds
Typical: Modify Blowdown time
Page 21
2.3 Sensor Diagnostics 1 of 2
.
Key UP or DOWN to the desired sensor
& key ENTER
. .
This example is a cooling tower conductivity sensor
Connected to input ‘E’
. . .
Key ENTER at Diagnostics
. .
Each I/O type has it’s own set of Diagnostics
. .
Sensors have driver cards
Water Meters and contact sets connect directly to
top-center terminal blocks
. . . .
‘Operational’ sensors are not Alarmed
This example is a sensor operating outside
of the HIGH or LOW alarms
. . . . . .
Current displayed value of the sensor
and sensor units
. . . .
An increasing Gain indicates a fouled sensor
Gain Multiplier changes with sensor calibration
. . . .
Tower Conduct'vty E 986 uS Bleed Valve 2 OFF: Setpoints
Tower Conduct'vty E Diagnostics Alarms Calibrate
Tower Conduct'vty E
Diagnostics.........
Input Card Type Conductivity
Tower Conduct'vty E
Diagnostics.........
Current State Alarmed
Tower Conduct'vty E
Diagnostics.........
Displayed Value
968.4 uS
Tower Conduct'vty E
Diagnostics.........
Gain Multiplier
5.7160
Continued on Page 2
Page 22
2.3 Sensor Diagnostics 2 of 2
. .
Selecting ‘Reset to Factory’ during sensor calibration
sets the Gain Multiplier to the Default Gain
. . . .
Conductivity adjusts Gain Multiplier to calibrate
. .
pH, ORP and temperature
modifies Offset Adjust to calibrate
. . . .
Selecting ‘Reset to Factory’ during sensor calibration
sets the Offset Adjust to the Default Offset
. . . . .
Measured Level is the raw sensor level
Before Gain Multiplier and Offset Adjust are applied
. . . .
Each driver card range and configuration jumper
setting has a unique ID used by the
controller to auto-configure
Watermeters and contact sets do not require IDs
. . .
Some driver cards have internal drive levels
Corrosion Rate cards use Drive Level
to correct for DC isolation offsets
.
Key EXIT to return to sensor menu
Tower Conduct'vty E
Diagnostics.........
Default Gain
5.6000
Tower Conduct'vty E
Diagnostics.........
Offset Adjust
-35.0000
Tower Conduct'vty E
Diagnostics.........
Default Offset
-35.0000
Tower Conduct'vty E
Diagnostics.........
Measured Level
184.5 mV
Tower Conduct'vty E
Diagnostics.........
Input card ID
76.7 mV
Tower Conduct'vty E
Diagnostics.........
Drive level
0.0 mV
Page 23
2.4 Control Diagnostics 1 of 4
.
INHIBITOR FEED EXAMPLE page 1
.
Key UP DOWN to Inhibitor Pump & ENTER.
.
The pump is ON and owes 6.1 minutes of ON time
. . .
Key ENTER at Diagnostics
. .
Each control type has it’s own set of Diagnostics
. .
Key ENTER to turn ON the Pump
for 5 minutes
.
WARNING: Immediately turns ON pump
Unless blocked, interlocked or on biocide lockout
Select Alarms then
Reset Alarm & Time to end Prime Output
. .
Current State displays Interlocked, Blocked,
Timed Out, status messages
. . . .
Controlling sensor in this example is water meter ‘O’
.
Current value of control displayed
. . . . .
Volume controls measure a user set volume
before turning ON the pump
In this example 100 gallons
.
Make-up Meter O 38400 gal Inhibitor Pump 1 ON: owes 6.1
Inhibitor Pump 1 Diagnostics Configure Alarms
Inhibitor Pump 1
Diagnostics.........
Prime Output YES
Inhibitor Pump 1
Diagnostics.........
Current State ON: owes 5.6
Inhibitor Pump 1
Diagnostics.........
Control by: O 38400 gal
Inhibitor Pump 1
Diagnostics.........
Measure volume
100.00 gal
Continued on Page 2
Page 24
2.4 Control Diagnostics 2 of 4
.
INHIBITOR FEED EXAMPLE page 2
.
In this example, after each 100 gallons,
the Inhibitor pump turns ON for 20 seconds.
. . . . . .
Water meter volume when last feed occurred
. . .
Event Cycles may repeat every 1,7 or 28 days
.
This example has 8 events which repeat
every 4 weeks, 28 days
.
Today is Day 9, Monday of week No.2
. . . . .
Today’s Inhibitor pump ON time from midnight
. . . . .
Inhibitor pump ON Time Owed
Increases while the cooling tower is making up
and decreases to zero when the make-up float closes.
. . .
Varying Cycles and Feed Verification status
Displays follow the Special Control display
.
Inhibitor Pump 1
Diagnostics.........
Then turn ON for 20 sec
Inhibitor Pump 1
Diagnostics.........
Last fed at 38300 gal
Inhibitor Pump 1
Diagnostics.........
28 Day Event Cycle 8 events, Day 9
Inhibitor Pump 1
Diagnostics.........
minutes ON today
110.6 minutes
Inhibitor Pump 1
Diagnostics.........
Time Owed
0.3 minutes
Inhibitor Pump 1
Diagnostics.........
Special Control none
Page 25
2.4 Control Diagnostics 3 of 4
.
CAPTURED SAMPLE EXAMPLE page 1
.
Key UP DOWN to the blowdown control & ENTER.
.
Blowdown valve is ON and has been
ON for 1.2 minutes
. . .
Key ENTER at Diagnostics
. .
Each control type has it’s own set of Diagnostics
. . .
Priming overrides boiler timing, turning ON the
blowdown valve for 5 minutes
.
Select Alarms then
Reset Alarm & Time to end Prime Output.
. . .
Current State displays that the Captured Sample
Special Control has turned ON the Blowdown
. . . . .
Controlling sensor in this example is sensor ‘F’
.
Current value of controlling sensor displayed
. . . . . .
Controller checks Turn ON Setpoint
at the end of every Measure period
.
Boiler 3 Cond. F 3628 uS B3 Blowdown 4 ON: 1.2 min
B3 Blowdown 4 Diagnostics Configure Alarms
B3 Blowdown 4
Diagnostics.........
Prime Output YES
B3 Blowdown 4
Diagnostics.........
Current State Special Control,ON
B3 Blowdown 4
Diagnostics.........
Control by: F
3420.23 uS
B3 Blowdown 4
Diagnostics.........
Turn ON setpoint 3300 uS
Continued on Page 2
Page 26
2.4 Control Diagnostics 4 of 4
.
CAPTURED SAMPLE EXAMPLE page 2
.
Controller checks Turn OFF Setpoint
at the end of every Measure period.
. . . .
Rising Setpoint blows down above Turn ON and
samples only below Turn OFF.
. . . . .
It would be unusual to have timed feed events
on a boiler blowdown valve.
.
In this example there are 0 events set
and its day 4, Wednesday today
. . . .
Today’s ON time for the blowdown valve
from midnight
. . . .
Captured Sample, Time Owed would usually be zero
If Prime Output is active, Time Owed
will count down from 5 minutes.
. .
Displays the Captured Sample ON/OFF state
and which timer is counting down
SAMPLE | MEASURE | BLOWDOWN | RESAMPLE
are the four captured sample states
.
Varying Cycles and Fail-to-Sample status
Displays follow the state display
B3 Blowdown 4
Diagnostics.........
Turn OFF setpoint
3275.00 uS
B3 Blowdown 4
Diagnostics.........
Control Type Rising Setpoint
B3 Blowdown 4
Diagnostics.........
7 Day Event Cycle 0 events, Day 4
B3 Blowdown 4
Diagnostics.........
minutes ON today
234.6 minutes
B3 Blowdown 4
Diagnostics.........
Time Owed
0.0 minutes
Inhibitor Pump 1
Diagnostics.........
Captured Sample:OFF Resample: 26.4 m
Page 27
2.5 System Diagnostics 1 of 2
.
Power ON display
OR key UP DOWN to System: & ENTER.
. . . . . .
Key ENTER at Diagnostics
. . . .
Firmware version is followed by the two modules that
form the base controller
.
M7 is a 7 analog, 7 digital input module
M14 is a 14 analog, 12 digital input module
.
PR10 is a 10 relay output; PR5 a 5 relay output
. . .
PR10 controllers include an AC Current Transformer
AC Current is the total controller current including
All pumps, valve & solenoid current
. . .
OK is an intact, Relay 1 to 5 load fuse
.
OPEN is a failed fuse.
Pumps & Solenoids controlled by relays 1-5 are OFF.
. . . .
OK is an intact, Relay 6 to 10 load fuse
.
OPEN is a failed fuse.
Pumps & Solenoids controlled by
relays 6-10 are OFF.
.
System:2003-10-03 S/N: M0389001 Alarms: 16:38:11 D G 2 Sys
System: Diagnostics Enable I/O Configure
System:
Diagnostics.........
Firmware Version A814-M7-PR10
System:
Diagnostics.........
AC Current
4.26
System:
Diagnostics.........
Relay 1-5 Fuse OK
System:
Diagnostics.........
Relay 6-10 Fuse OPEN
Continued on Page 2
Page 28
2.5 System Diagnostics 2 of 2
Current state of alarm contacts
.
The controller may be configured to
OPEN or CLOSE alarm contacts on alarm.
.
Displays the current state of the dry contacts at the
AL1 & AL2 terminal block on the PR5 or PR10 module
. . .
Increasing watchdog resets indicate external
electrical spikes or internal controller faults
. . . . . .
Date and time of most recent full control reset
. . . . . .
A Default Admin Password has not
been changed from the factory default
. . . . .
Internal calibration check
Factor required to correct internal 2.5V reference
1 +/- 0.05
. .
Current loop and turbine water meter power supply
Thermally fused. Will read <10V if there is wiring a
loop or meter fault
.
Internal 12V Relay Supply, Ethernet Option
& Feed Verify Option
displays follow the 15V display.
System:
Diagnostics.........
Alarms CLOSED
System:
Diagnostics.........
Watchdog Resets 0
System:
Diagnostics.........
Reset to Factory 2003-11-08 10:30:00
System:
Diagnostics.........
Admin Password Default
System:
Diagnostics.........
Internal 2.5V
0.9996
System:
Diagnostics.........
15V External Supply
20.276
Page 29
3.1 Read this first!
ONE CONTROLLER – MANY APPLICATIONS
Controllers are shipped configured with a wide range of sensors
for one or more cooling towers, multiple boilers, hot & chilled closed loops,
condensate monitoring, waste water control and monitoring
YOUR CONTROLLER – SENSOR SET
The installation instructions for your specific controller are
in the HELP section YELLOW pages.
HELP is the last tab in the manual binder.
YOUR APPLICATION CHANGES
The controller can be completely reconfigured using the keypad or optional browser
Feed methods and interlocking can be changed.
pH control can be switched to ORP
A tower controller can be switched to waste water or boiler-condensate controls
You need to automate sensor cleaning, measure more water meters,
Feed based on steam production, Bleed on the ratio of make-up & bleed volume
YOU NEED TO ADD ANOTHER PH, ORP, BOILER CONDUCTIVITY
Upgrade kits can expand the controller to 14 analog sensors,
10 watermeter-digital inputs and 10 Relay controls
The controller recognizes new sensor drivers and auto-configures.
The digital inputs can be switched between water meter inputs to contact closure inputs.
THE REST OF SECTION 3.
Not all of the following sections apply to your controller or application.
You may need some of these functions as your application evolves.
Page 30
3.2 Connect Sensors 1 of 4
M7 Type Controllers
Water meters are typically connected to inputs O,P & Q.
Flowswitches, fail-to-sample sensors and contact sets connected to R, S & T.
M14 Type Controllers
Water meters are typically connected to inputs O,P & Q and U,V & W.
Flowswitches, fail-to-sample sensors and contact sets connected to R, S & T and X,Y & Z.
Digital Inputs
Inputs ‘O’ to ‘Z’ may be user configured for water meters and volume measurements
OR contact closure and state, interlocking functions
Typical Water Meter & Flowswitch Connections
Flowswitches
& Interlocks
15 VDC
O P
Sensor Module
C & D
Sensor Module
A & B
Q R S T
LNK ACT
M7 Module
CR2032
LAN
Contact Head Water Meters
Red
Black Red
Red
Water Meters, Turbine Meters, Flowswitches
and Contact Sets may be connected any
digital input 'O' to 'T'
Page 31
3.2 Connect Sensors 2 of 4
Typical Sensor Driver Connections
Sensor, Entry &
Solution Ground
S+ S- T+ T-
Part: CT
Conductivity
&
Temperature
>100uS
Conductivity Temperature
Sensor
Rd Bk Wh Gn
<100uS
Red to S+ Black to S­White to T+ Green to T-
Part: OP
pH or ORP
S1 S1 S2 S2
Part: B
CND
BLR
Sensor 2
CND
BLR
Sensor 1
Sensor 1
Boiler
or
Condensate
Sensor 1
Part: OP
pH or ORP
S1 S1 S2 S2
Part: CR
Single
Corrosion
Rate
Sensor 1
1+ 1- 2+ 2-
2O PO
Part: OP
pH or ORP
ID S2 S1
Sensor cabling is
not polarized
Sensor cabling is
not polarized
Bare Shield to '-'
Clear, center wire to '+'
2nd sensor
connects to
S2 Terminals
2nd sensor
connects to
S2 Terminals
2nd sensor
connects to
2+ 2- Terminals
Conductivity
Temperature
ORP & pH
Boiler
Condensate
Corrosion
Rate
Page 32
3.2 Connect Sensors 3 of 4
Page 33
1+ 2+
Part: CI
Loop 2
>3.5 mA
Loop 1
>3.5 mA
4-20mA
Current Loop
Dual Input
- +
Powered Loop
4-20mA Output
15 VDC
Controller DC Supply
- +
Loop Powered
Sensor
Current Loop Inputs
may be any
combination
or powered and
loop powered
15 to 22 VDC Supply
15 VDC
Controller DC Supply
- +
Loop Powered Pump or Valve
15 to 22 VDC Supply
+24V IN
Remote Monitor
4-20mA Input
Proportional
Control
1+ 1- 2+ 2-
Part: IO
Dual 4-20mA
Output
Dual output driver
shown. Sinlge Driver has 1+ & 1- Terminals
Typical 4-20mA Output &
Input Connections
Page 34
3.2 Connect Sensors 4 of 4
Sensor GSensor B
Sensor A
Sensor E
Sensor F
Sensor D
Sensor C
M7 Module
Sensor E
Sensor F
Sensor G
Sensor H
Sensor M
Sensor N
Sensor K
Sensor L
Sensor J
Sensor I
Sensor D
Sensor C
Sensor B
Sensor A
M7 Module
Sensor Locations
M14 Module
Sensor Locations
Page 35
3.3 Connect Pumps,Valves,Solenoids
Page 36
Page 37
3.4 Verify Controls 1 of 2
VERIFY SENSORS MATCH CONTROLS
.
Controlling sensors are followed by the
controlled pumps, valve & solenoids.
.
Make-meter connected to input ‘O’.
Controls the inhibitor pump powered by Relay 1.
.
Key ENTER to verify, modify pump setpoints
. .
Conductivity Sensor connected to ‘B’
Controls the bleed solenoid powered by Relay 2
.
Key ENTER to verify, modify bleed setpoints
. . .
pH Sensor connected to ‘C’
Controls the acid pump powered by Relay 3
.
Key ENTER to verify, modify acid feed setpoints
Page 2 shows key sequence
. . .
Boiler Conductivity Sensor connected to ‘E’
Controls the blowdown valve powered by Relay 4
.
Key ENTER to verify, modify blowdown setpoints
. . .
Biocides follow sensor no used for control
As you key UP DOWN
. . .
Sensors may be used to control 4-20mA outputs
In controllers with IO Driver cards
.
Condensate Monitoring Sensor connected to ‘F’
Controls the C1 4-20mA control
.
Key ENTER to verify, modify 4-20mA span
Tower Make-up O 12650 gal Inhibitor Pump 1 OFF: Setpoints
Tower conduct'ty B 1862 uS Bleed Solenoid 2 ON: 113.2 min
Tower pH C
7.62 pH Acid Pump 3 ON: 8.6 min
Boiler 1 cond. E 3521 uS Bl B'down Valve 4 OFF: Setpoints
Biocide 1 7 ON: owes 13.4 Biocide 2 8 OFF:No Control
Condensate Cond. F
20.3 uS 4-20mA Output C1 C1
8.46 mA 20.3 uS
Page 38
3.4 Verify Controls 2 o f 2
VERIFY – MODIFY SETPOINTS
The Tower pH sensor at input ‘C’
Controls the acid pump powered by relay 3
.
Key ENTER at Acid Pump to verify-modify setpoints
. . . . .
Key DOWN to Configure and key ENTER
. . . .
Key DOWN to Turn ON Setpoint
Its’ currently 8.25pH, Key ENTER to Modify.
.
Key DOWN to verify-modify Turn OFF Setpoint.
. . .
Key ENTER at 4-20mA display
.
Key DOWN to Configure & key ENTER
. . . . . .
4mA level = 0uS
.
Key ENTER to modify or DOWN
to verify-modify 20mA Level
. .
20mA level = 100uS
.
Key ENTER to modify
.
Tower pH C
7.62 pH Acid Pump 3 ON: 8.6 min
Acid Pump 3 Diagnostics Configure Alarms
Acid Pump 3
Configure...........
Turn ON setpoint
8.25 pH
4-20mA Output C1 C1 Diagnostics Configure
4-20mA Output C1 C1
Configure...........
4mA Level
0.00 uS
4-20mA Output C1 C1
Configure...........
20mA Level
100.00 uS
then
then
or
Page 39
3.5 Setting Sensor Alarms
VERIFY – MODIFY ALARMS
Key UP DOWN to the target sensor
and key ENTER
. . . . . .
Key DOWN to Alarms and key ENTER
. . . . . .
Key ENTER to modify High Alarm
or DOWN for Low Alarm
. . . . .
Key ENTER to modify Low Alarm
or DOWN for Alarm Relay
. . . .
A Tower pH alarm will trip the controller alarm relay
Key ENTER & UP DOWN to select NO
to not set the alarm relay on a pH alarm
. . .
A high or low alarm will register 5 minutes
after it occurs, to block alarms on transients
.
Key ENTER to modify
A delay of 0.0 minutes will alarm immediately.
Tower pH C
7.62 pH Acid Pump 3 ON: 8.6 min
Tower pH C Diagnostics Alarms Calibrate
Tower pH C
Alarms..............
High Alarm
10.00 pH
Tower pH C
Alarms..............
Low Alarm
5.50 pH
Tower pH C
Alarms..............
Set Alarm Relay YES
Tower pH C
Alarms..............
Delay on Alarm
5.0 minutes
then
or
or
or
Page 40
3.6 Setting Output Alarms
VERIFY – MODIFY
FEED LIMIT ALARMS
Key UP DOWN to the target control
and key ENTER
. . . . . .
Key DOWN to Alarms and key ENTER
. . .
An acid pump limit timer prevents overfeed
on pH sensor fault.
. .
Key ENTER to modify Minutes/Actuation
or DOWN for Minutes/Day
. . . . .
Key ENTER to modify Minutes/Day
or DOWN for action on alarm
. .
Acid pumps are usually set to Turn OFF on Alarm
Bleed controls are usually set to
NOT Turn OFF on alarm.
. . .
A feed limit alarm will trip the controller alarm relay
Key ENTER & UP DOWN to select NO
to not set the alarm relay on feed limiting.
.
Key down to view Reset & Most Recent Alarm.
Tower pH C
7.62 pH Acid Pump 3 ON: 8.6 min
Acid Pump 3 Diagnostics Configure Alarms
Acid Pump 3
Alarms..............
Minutes/Actuation
45.0 minutes
Acid Pump 3
Alarms..............
Minutes/Day
600.0 minutes
Acid Pump 3
Alarms..............
Turn OFF on Alarm YES
Acid Pump 3
Alarms..............
Set Alarm Relay YES
then
or
or
or
Page 41
3.7 Verify Interlocks
INTERLOCKS PREVENT CONTROLS
FROM TURNING ON
Key UP DOWN to the target control
and key ENTER
. . . . .
Key DOWN to Configure and key ENTER
then key DOWN to Interlocked by
. . . .
In this example, when the Flowswitch connected to
input ‘T’ closes, the Tower Bleed can operate
.
Key ENTER to modify the interlock
. . .
In the 2nd example, Steam Treatment is being fed
based on Steam demand
. .
Key ENTER , then key DOWN
to Configure and key ENTER
. . . .
Key DOWN to Interlocked by
An R | S, ‘ORS’ requiring either R or S contact
sets closed to operate the pump
.
R+S ‘ANDS’, requiring both R & S contact set to be
closed to operate the pump
.
In this example, R & S may close when
Boiler s1 & 2 are ON-line
Conductivity E 1245 uS Tower Bleed 2 ON: 8.6 min
Tower Bleed 2 Diagnostics Configure Alarms
Tower Bleed 2
Configure...........
Interlocked by T
Steam Demand P 32500 lb Steam Treatment 5 ON: 10.4 min
Steam Treatment 5 Diagnostics Configure Alarms
Steam Treatment 5
Configure...........
Interlocked by R|S
then
then
Page 42
3.8 Verify Blocking Relays
BLOCKING PREVENTS TWO
CONTROLS FROM TURNING ON
AT THE SAME TIME
This example shows an Inhibitor Pump,1 blocked
when the Oxidant Pump,3 is ON
to prevent Inhibitor – Oxidant reaction
. .
Key ENTER
Key DOWN to Configure and key ENTER
then key DOWN to Blocking Relays
. . .
This example shows that Relay 1 is OFF
whenever relay 3 is ON
.
Key ENTER to modify the blocking relay
Selecting ‘none’ removes the block
. . .
This example shows an Inhibitor Pump
turned OFF when Relay 2 is ON.
.
Relay 2 is a tower bleed solenoid.
This block stops Inhibitor from being
pumped down the tower drain
. .
Key ENTER , then key DOWN
to Configure and key ENTER
. .
Key DOWN to Blocking Relays
A ‘2+3’ block would prevent the Inhibitor
from feeding during bleed AND Oxidant feed.
.
Key ENTER to modify the blocking relays
Inhibitor Pump 1 OFF:Blocked 3 Oxidizing Biocide 3 ON: 14.2 min
Inihibitor Pump 1 Diagnostics Configure Alarms
Inhibitor Pump 1
Configure...........
Blocking Relays 3
Inhibitor Pump 1 OFF:Blocked 2 Oxidizing Biocide 3 ON: 14.2 min
Inihibitor Pump 1 Diagnostics Configure Alarms
Inhibitor Pump 1
Configure...........
Blocking Relays 2+3
then
then
Page 43
3.9 Selecting Special Controls
This example shows an Inhibitor Pump
with ‘Bleed then Feed’ Special Control
. .
Key ENTER
Key DOWN to Configure and key ENTER
then key DOWN to Special Control
.
Displays current special control
.
Key UP DOWN to view available Special Controls
Meter controlled relays do not have Special Controls
No Control & sensor controlled relays can select from:
Bleed & Feed, Bleed then Feed, Captured Sample,
% Time, Prebleed-Lockout, Time Modulation,
Holding Time and Time Modulation
.
Key ENTER to view, modify current Special Control
. . . .
Key ENTER to modify the Bleed Relay
Or DOWN to view the % of Time
. . .
In this Bleed Then Feed example: For every 5 minutes of Tower Bleed time, the Inhibitor runs for 46% or 136 seconds
AFTER the bleed turns OFF
. . .
Key ENTER to modify the % of Time
This example increase the % of time from 46% to 52%
. .
Special Controls are detailed in the on-line
M714_Tech, technical service manual
Inhibitor Pump 1 OFF: No Control Biocide A 3 ON: 8.6 min
Inhibitor Pump 1 Diagnostics Configure Alarms
Inhibitor Pump 1
Configure...........
Special Control Bleed then Feed
Inhibitor Pump 1 Bleed then Feed----­Bleed Relay Tower Bleed
Inhibitor Pump 1 Bleed then Feed----­% of Time 46%
Editing Value:
% of Time...........
52% Executes Exits
then
then
and
then
--
Page 44
3.10 Modifying Variable Cycles 1 of 2
Variable Cycles may be used where varying
make-up conductivity cause water treatment fault.
Requires a make-up conductivity sensor
.
Key ENTER
. . . .
Key DOWN to Variable Cycles and key ENTER
. . . . . .
Key ENTER to modify Low Range
. .
When the Make-up Conductivity is
less than Low Range
Bleed is controlled at Low Cycles
.
Key ENTER to modify the Low Cycles
. . . . . .
Key ENTER to modify Medium Range
. .
When the Make-up Conductivity is
less than Medium Range & greater than Low Range
Bleed is controlled at Medium Cycles
. .
Key ENTER to modify the Medium Cycles
. .
Conductivity E 1384 uS Tower Bleed 2 ON: 8.6 min
Tower Bleed 2 Timed Events Setup Variable Cycles
Tower Bleed 2
Variable Cycles.....
Low Range 350 uS
Tower Bleed 2
Variable Cycles.....
Low Cycles
6.100 cycles
Tower Bleed 2
Variable Cycles.....
Med. Range 650 uS
Tower Bleed 2
Variable Cycles.....
Med. Cycles
4.250 cycles
then
or
or
or
or
Continued on Page 2
Page 45
3.10 Modifying Variable Cycles 2 of 2
. . .
Key ENTER to modify High Range
. .
When the Make-up Conductivity is
less than High Range & greater than Med. Range
Bleed is controlled at High Cycles
. .
Key ENTER to modify the High Cycles
. . .
When the Tower Conductivity exceeds
Maximum Conductivity the
Bleed is controlled at Max Conductivity
. .
Key ENTER to modify the Maximum Conductivity
. .
Variable Cycles Primer
.
Variable Cycles must be set to YES in the Bleed control Configure menu option
The bleed relay must be controlled by a conductivity ratio.
Example: Control Equation is E/F where E = Tower Conductivity & F = Makeup Conductivity.
The Control Equation may be modified in the Bleed control Configure menu option
.
Variable Cycles modifies bleed setpoints as make-up conductivity changes
Setpoint adjustment is blocked when Variable Cycles is controlling.
Bleed Setpoint units are set to ‘cycles’ when Variable Cycles are selected.
.
You will need to modify the Range and Cycle Setpoints for your site
makeup water chemistry and water treatment program
Tower Bleed 2
Variable Cycles.....
High Range 1000 uS
Tower Bleed 2
Variable Cycles.....
High Cycles
2.500 cycles
Tower Bleed 2
Variable Cycles.....
Max Conduct. 3000 uS
or
or
or
or
Page 46
3.11 Modifying Feed Verification 1 of 2
Controller Option: Feed Verification calculates
Inhibitor ppm and Inhibitor tank level
with fail-to-feed alarms.
Requires a feed verification meter on the
inhibitor chemical pump feed.
.
Key ENTER
. . .
Key DOWN to Feed Verify and key ENTER
. . .
The Verify Meter measures the volume
pumped by the inhibitor pump
.
Key ENTER to modify Verify Meter sensor location
. . .
Inventory Location logs tank level,
lowering level as inhibitor is pumped
.
Key ENTER to modify Inventory location
. . .
ppm location logs the calculated ppm
based on volume pumped and the method used to
calculate cycles
.
Key ENTER to modify ppm location
. .
One of three methods is used to calculate cycles
Fixed Cycles | Bleed Cycles | Meter Cycles
.
Key ENTER to modify the cycles method
.
Tower Make-up O 18425 gal Inhibitor Pump 1 ON: 10.6 min
Inhibitor Pump 1 Setup Variable Cycles Feed Verify
Inhibitor Pump 1
Feed Verify.........
Verify Meter Meter Input Q
Inhibitor Pump 1
Feed Verify.........
Inventory location Sensor Input G
Inhibitor Pump 1
Feed Verify.........
ppm location Sensor Input H
Inhibitor Pump 1
Feed Verify.........
ppm method select Fixed Cycles
then
or
or
or
Continued on Page 2
Page 47
3.11 Modifying Feed Verification 2 of 2
.
Fixed Cycles applies a user set cycles
to calculate ppm
. .
Key ENTER to view-modify cycles
. . . . .
ppm is calculated using 3.5 cycles of concentration
Key ENTER to modify
. . . .
Key UP DOWN and RIGHT to modify
then ENTER
.
Increasing the concentration from 3.5 to 4.23
increases the calculated ppm.
.
.
Feed Verification Primer
.
Feed Verification must be set to YES in the Inhibitor pump control Configure menu option
The Inhibitor pump relay must be controlled by the make-up water meter.
.
A fail-to-feed alarm is set on the feed verification meter input if the meter
does not measure volume after the pump has been ON for 30 seconds
. .
Meter Cycles ppm calculation requires a water meter on the tower bleed.
Cycles of concentration is calculated using ratio of the Make-up to Bleed meter volumes
.
Bleed Cycles ppm calculation requires the conductivity of the tower make-up.
Cycles of concentration is calculated using ratio of the Tower to Make-up conductivities
Select one: ppm method select... Fixed Cycles Executes Exits
Inhibitor Pump 1 ppm method select--­Fixed Cycles
3.500 cycles
Inhibitor Pump 1
Fixed Cycles........
4.230 cycles Executes Exits
then
--
Page 48
3.12 Time & Date
Time & Date are battery backed
Adjusting Timer & Date may not be
required on start-up
. .
Key ENTER at System:
. . . .
Key DOWN to Time & Date and key ENTER
. . . . .
Displays current Date and Time
. .
Key ENTER to modify
. . . .
Key UP DOWN and RIGHT to modify
the Date and Time
. .
Key ENTER
. .
Displays modified Date & Time
.
EXIT returns to System:
.
System:2003-10-27 S/N: M0389001 Alarms: 16:38:11 none
System: Enable I/O Configure Time & Date
System:
Time & Date.........
Adjusts Date-Time 2003-10-27 16:38
System: Adjusts Date-Time... 03-11-27 17:38 Wed Executes Exits
System:
Time & Date.........
Adjusts Date-Time 2003-11-27 17:38
then
then
--
Page 49
4.1 Spare Parts
Fusing
Protects
Rating / Type
Manufacturer - Vendor
Power Relays
Fuse 1-5
&
Fuse 6-10
6.3 Amps @ 120VAC
3 Amps @ 250VAC
5mm x 20mm,
Fast Acting
Littlelfuse, Type 217, 250VAC
Digikey Part# F953-ND
Digikey Part# F950-ND
www.digikey.com 1-800-344-4539
Controller – Modem
Control Fuse
1.5 Amp @ 120VAC
½ Amp @ 250VAC
Cooper Bussmann, PC-TRON, PCC Series, 250VAC
Digikey Part# 283-2758-ND
Digikey Part# 283-2120-ND
www.digikey.com 1-800-344-4539
Controller Parts
Part#
Description
M-FUSES
120VAC Fuse Kit, 20 x 6.3A Relay Fuses,
4 x 1 Amp control fuses
Cable-Xover
Crossover cable, Controller RJ45 to Notebook NIC
Mod-LCD4
Replacement 4x20 LCD Display
Mod-M3000
Micro controller module
Mod-M7
Seven analog, Six digital input module
Mod-M14
Fourteen analog, Twelve digital input module
Mod-PR5
Five power relay, power module
Mod-PR10
Ten power relay, power module
Modem
Modem, serial cable & power cube
SFCBL4
120VAC Four Plug box, flex conduit & fittings, pre-wired
SFCBL2
120VAC Two Plug box, flex conduit & fittings, pre-wired
H-SEN6
Sensor entry gland, six cable seal
Replacement Sensors and Upgrade Kits
Refer to 4.2 Technical Support
Page 50
4.2 Technical Support
ProMinent Fluid Controls, Inc.
(formerly Aquatrac, Inc.)
.
136 Industry Drive
Pittsburgh, PA
15275
412-787-2484
8:00AM - 5:00PM EST
Other Keypad Functions
Navigation to keypad functions is detailed in Section 4.4, Keypad Navigator
Upgrade Kits
Controls can be added to installed controllers.
Upgrade kits include sensor, entry fitting, driver card and installation instructions
On-Line Help
Internet HELP is linked in real time by browser users
with internet accessible controllers
Keypad connect to www.aquatrac.com/help with ‘iNet HELP#’ from LCD display
Browser Users Manual
Download M714_browse from www.aquatrac.com
Controller Technical Manual
Download M714_tech from www.aquatrac.com
Page 51
4.3 Specifications 1 of 4
Controllers configured M7-PR5, M7-PR10, M14-PR5 & M14-PR10
Analog – Digital I/O
Rating - Detail
Notes
Analog Inputs
M7: 7 Analog Sensors
M14: 14 Analog Sensors
3 Dual & 1 Single Driver
7 Dual Drivers Auto-configure on
Driver installation and removal
4-20 ma Outputs
0 to 8, DC isolated,
loop powered.
Nominal 0.1% resolution.
Auto polarity correction field wiring.
Single & Dual Drivers
Each 4-20mA output uses an Analog Input.
Auto-configure on Driver installation and removal
Digital Inputs
M7: 6
M14: 12
Dry Contacts, 250mS response
Water Meters, 400 Hz max
0.5mA @ 5VDC
measurement current
User configurable as water meters or contact sets.
Contact head meters software debounced. Turbine-Paddle wheel rating = Seametrics max pulse rate.
Relay Outputs
M7: 5 1 SPST, 4 SPDT
M14: 10 2 SPST, 8 SPDT
Relays rated 10A, 120VAC Fused in sets of 5 relays
Detection and Alarm on fusing
Alarm Relay
Dry contact set, Unfused
User selected NO or NC
Load Current
PR10 Only
Measures total AC load current
Communications
User Interface
Rating – Detail
Notes
Keypad - LCD
5 Key Tactile feedback: UP / DOWN / ENTER / EXIT / RIGHT
4 Line x 20 Character, Backlit
Scan rate 100mS nominal
User adjustable contrast
10 BaseT, TCP-IP
Ethernet LAN
(Optional)
HTML, Telnet micro Web Server
Full command, control, reconfigure
via browser.
Network parameters and ports
User set.
Password, UserID protected.
Browser can show LCD is real time.
Auto-configures views linking sensors and controls.
HELP links for on-line users.
Modem
(Optional)
56K, V.90 Remote Telnet access.
Dedicated controller serial port.
Dial-out on alarm to pager or PC
Forced dial-out diagnostics
Page 52
4.3 Specifications 2 of 4
Controls
Rating - Detail
Notes
ON/OFF
User set deadband and controlling sensor(s) or contact set.
User defined rising, falling or between Setpoints or active only during timed events
Any relay can be user configured for any Control.
Control by up to 4 analog sensors using +,-,x & / math
Biocide Feed
(Timed Events)
28 Events per relay
1 minute resolution
Lockout, Prebleed on both time and conductivity.
Each relay can be set to 1,7 or 28 day cycle.
Timed events may exist concurrently with other controls
Proportional 4-20mA
User defined control by sensor or relay control equation.
Auto-Manual switching.
Software ZERO & SPAN adjust.
Interlocked current loops go to 4mA
Proportional ON/OFF
Timed Modulation and Timed Cycling Special Controls
ON time modified by Setpoint to actual delta.
Volumetric
User set, measure volume
& pump ON time.
Sequential control, measures Makeup volume, then bleeds for user set volume.
Rate-to-Volume conversion routes analog input to Water Meter(s).
Timed
Bleed & Feed and Bleed then Feed
Includes % of Bleed Time.
User set % Time
Prime
Holding Time
% Bleed & Feed based on 5 minute period.
% Time & Prime on 5 minute period.
Holding time averages sensor values for control.
Captured Sample – Boilers
Sample / Measure / Blowdown / Resample user set timing.
Fail-to-Sample sensor support included.
Any sensor may be used.
Support for high pressure sites
Interlocking
1 to 4 contact set inputs,
AND & OR support
Relay OFF when contact set opens.
Blocking
1 to 4 relays may block any other relay
Support for common
Oxidant –Inhibitor feed.
If Blocking relay ON, this relay OFF
Page 53
4.3 Specifications 3 of 4
Controls
Rating - Detail
Notes
Alarms – Feed Limit Timers
Minutes / Actuation
Minutes / Day
User defined trip alarm relay,
and/or dial-out
User defined OFF on Feed Limit
Auto reset on Bleed & Feed and
Bleed then Feed
Variable Cycles
Three user defined ranges of make-up conductivity and target cycles.
User defined maximum tower conductivity.
Requires control by the ratio of analog sensors.
1% deadband on cycles and maximum conductivity
Feed Verification
(Option)
ppm calculation based on volume fed and cycles of concentration.
Alarm on fail to feed.
User selected cycles method: Fixed, Ratio of Tower/Makeup conductivity, Ratio of Makeup/Bleed Volume.
Requires feed volume meter or 4-20mA input on feed rate.
Fail-to-to feed is no volume fed after 30 seconds
Data Logging
Rating - Detail
Notes
Log Content
Analog Inputs: Min, Max & Average
Digital -Water Meters: Volume
Digital-Contact Set: ON Time
Year to date included for Meters
Log Size
600 entries for each of 26 analog and digital inputs and each of 10 relay outputs
21,600 Entries Total
600 entries = 25 Days
at 60 minutes Logging Rate
Logging Rate
User set independently for each I/O from 5 to 1440 minutes / entry
Default 60 minutes
Log File Format
XML
User defined start & end date for XML download
.dtd defines date stamping for each of 21,600 log entries
System
Rating - Detail
Notes
Controller Configuration
User selected Save and Restore to FLASH memory
Makes current configuration factory default.
Watchdog
1 sec. Hardware relay lockout
Active on power up and firmware blocked
Field Upgrades
Enable ETHERNET, Feed Verification.
Add Sensors and Drivers
Upgrades locked to Serial# and date limited.
Page 54
4.3 Specifications 4 of 4
Electrical
Rating - Detail
Notes
AC Input
120 or 240 VAC, 50/60Hz,
Switch selectable
Fusing
M10 Version
12.6 Amps @ 120VAC
6 Amps @ 240VAC
M5 Version
6.3 Amps @ 120VAC
3 Amps @ 240VAC
5x20mm, 120VAC fusing:
Relays 1-5 & 6-10: 6.3A ea.
Control: 1.5A
Surge-Spike Suppression
Relays 2-5 and 7-10, NO contacts snubbed 0.1uF, 150R
Varistor on control AC input
Controller, transformer isolated from AC line
AC Terminals
AC Input: AWG 12, 240mm2
AC Outputs: AWG 14, 150mm2
Electrical grounds at bottom of aluminum backplate
Conductor insulation rated 600VAC minimum.
Sensor, Digital Input
Terminals
AWG 22, 0.25 – 0.50mm2
MAX AWG14, 150 150mm
2
Conductor insulation rated 600VAC minimum.
DC Loop – Turbine Meter
Power
15 – 22 VDC, unregulated
Thermally fused @ 200mA
Field wiring terminals
on M7 & M14
Mechanical
Rating
Notes
Enclosure
Rating, Dimensions,
Weight
Non-metallic, NEMA4X, IP65
M10 Version
14”W x 17”H x 6.75”D
355mm W x 430mm H x 170mm D
17lb. 7.7kg nominal
M5 Version
12.5”W x 15”H x 6.5”D
320mm W x 380mm H x 165mm D
11.8lb. 5.4kg nominal
Nominal dimensions, excluding entry fittings and flexible conduit. Including mounting.
Enclosure door hinged left.
Allow 18”, left for door opening.
Allow 24”, below for cable­conduit access.
120VAC Plug Boxes
Rated for outdoor use.
Limited to 5 Amps / plugbox
2 & 4 plug boxes provided with 36” of flexible non-metallic conduit
Plug boxes not included:
1. At hardwired and 240VAC sites.
2. With controllers shipped outside of North America
Environmental
Pollution Degree 2, Altitude 2000m, Installation Category II, Humidity 5% to 95%,
Page 55
Temperature 0C to 40C
Page 56
4.4 Keypad Navigator 1 of 2
Activity
Top Level
UP DOWN
to:
then
DOWN
& ENTER
then
& Notes
4-20mA Output
MANUAL-AUTO
Output
C1..C8
Configure
ENTER & ENTER to toggle MANUAL-AUTO
4-20mA Output
Control Modify
Output
C1..C8
Configure
DOWN to Control by:
4-20mA Output
C1..C8 Location
Output
C1..C8
Diagnostic
DOWN to Output Card @:
See Section 3.2, 4 of 4
Alarm Relay OPEN-CLOSE
System:
Configure
DOWN to
Alarm opens contacts
Biocide Cycle:
Set 1, 7,28 days
Output 1..10
Setup
DOWN to Event Cycle
Contact Set to Meter: Modify
Input O..Z
Configure
DOWN to Digital Input Type
ENTER, DOWN to Contact Head OR Turbine Meter
Control Type
(Action on Setpoints)
Output 1..10
Configure
DOWN to Control Type
Rising/Falling & Between Setpoints OR Active only during Timed Events
Default Configuration LOAD
System:
Configure
DOWN to Load Configuration
Restores Default Controller
Default Configuration SAVE
System:
Configure
DOWN to Save Configuration
Makes current configuration the default
Disable Input
Input A..Z
Configure
DOWN to Disable Input
Disable Output
Output 1..10
C1..C8
Setup
DOWN to Disable Output
Page 57
4.4 Keypad Navigator 2 of 2
Activity
Top Level
UP DOWN
to:
then
DOWN
& ENTER
then
& Notes
Enable I/O
System:
Enable I/O
DOWN to inputs or outputs
Key ENTER & DOWN to select
Input Name: Modify
Input A..Z
Configure
DOWN to Description
Input Resolution: Modify
Input A..Z
Configure
DOWN to Digits after decimal
LCD & Browser display
Input Units: Modify
Input A..Z
Configure
DOWN to Displayed Units
LAN:
IP, Netmask, Gateway,
MAC, Ports
System:
LAN Setup
WARNING !
Do not modify network parameters without site IT permission.
Metric: ON-OFF
System:
Configure
DOWN to Metric Units
Meter to Contact Set: Modify
Input O..Z
Configure
DOWN to Digital Input Type
ENTER,
DOWN to Contact Set
Output Name: Modify
Output 1..10
Setup
DOWN to Description
Password: Modify
System:
Passwords
DOWN to New Password
for current userid
Passwords: ON-OFF
System:
Configure
DOWN to Keypad Password
Upgrade: Reset Passwords
System:
Upgrade
Requires upgrade code
Linked to controller serial#
Page 58
4.5 Revision Log 1 of 1
Issued
Contents
2004-01-01
Original issued
2004-03-16
Section 1.7.
Removes ‘userid’ selection for keypad log-in. Applies only to controllers with Keypad Passwords ON
2004-04-05
Cover page revised, Repagination, Safety grounding information added to page 3.
2004-04-21
Section 4.3 - Specification
1. Specification revised to match controller nameplate
2. M5 & M10 enclosure sizing and weights added
3. Installation cabling insulation rating specified.
Section 3.1 – Read This First!
1. Emphasis added for controller specific HELP section
2007-10-02
Section 4.3 – Specification / Environmental
Added CSA statements. Page 51
2015-8-24
Safety
Added caution statement on pg. 4
Loading...