ProMinent DULCOMARIN II DXM Series, DXMaAW200001, DXMaAH200001, DXMaAH300001, DXMaAE200001 Supplementary Instructions Manual

...
Page 1
Supplementary Instructions
®
DULCOMARIN® II, A Module (Actuator Module, Pumps and Standard Signal Outputs mA) DXMaA
ProMinent
DXMa
Please carefully read these operating instructions before use! · Do not discard!
The operator shall be liable for any damage caused by installation or operating errors!
Part No. 986906 ProMinent Dosiertechnik GmbH · 69123 Heidelberg · Germany BA DC 048 12/08 GB
___ ___ ___ ___ ___ ___
Please enter the identcode of your module!
Page 2
Imprint
These operating resp. supplementary instructions apply only in conjunction with the following ticked operating resp. supplementary instructions:
Operating Instructions Multi-Channel Measuring and Control System DULCOMARIN® II Swimming Pool Controller and Disinfection Controller DXCa Part 1: Mounting and Installation
Operating Instructions Multi-Channel Measuring and Control System DULCOMARIN® II Swimming Pool Controller DXCa Part 2: Operation
Operating Instructions Multi-Channel Measuring and Control System DULCOMARIN
®
II Disinfection Controller DXCa
Part 2: Operation
Supplementary Instructions DULCOMARIN® II Videographic Recorder Operation
Supplementary Instructions DULCOMARIN® II, M Module (Measurement Module for pH, Redox/ORP, Temperature) DXMaM Operation
Supplementary Instructions DULCOMARIN® II, M Module (Measurement Module for pH, Redox/ORP, Temperature) DXMaM Connection
Supplementary Instructions DULCOMARIN® II, A Module (Actuator Module, Pumps and Standard Signal Outputs mA) DXMaA
Supplementary Instructions DULCOMARIN® II, N Module (Power Supply Module without Relays) DXMaN
Supplementary Instructions DULCOMARIN® II, P Module (Power Supply Module with Relays) DXMaP
Supplementary Instructions DULCOMARIN® II, I Module (Current Input Module, Standard Signal Inputs mA) DXMaI
Imprint:
Supplementary Instructions DULCOMARIN® II, A Module (Actuator Module, Pumps and Standard Signal Outputs mA) DXMaA © ProMinent Dosiertechnik GmbH, 2004
ProMinent Dosiertechnik GmbH Im Schuhmachergewann 5-11 69123 Heidelberg Germany
Phone: +49 6221 842-0 Fax: +49 6221 842-419
info@prominent.com www.prominent.com
Technical changes reserved. Printed in Germany
Page 2
ProMinent
®
Page 3
Page
Identcode ......................................................................................... 4
1 About this Module ................................................................. 5
2 Safety Chapter ....................................................................... 5
3 Storage and Transport .......................................................... 5
4 Mounting and Installation ..................................................... 5
5Technical Data ....................................................................... 6
6Terminal Assignment ............................................................ 6
7Terminal Connection Diagram ............................................. 7
Contents
ProMinent
®
Page 3
Page 4
Identcode
Identcode
The identcode describes the external modules for the DULCOMARIN® II, series DXM
DXMa Measurement module for DULCOMARIN® II, series DXM
Module:
A A-module, actuator module: 3 pump and 4 standard signal outputs mA
Type of mounting:
WWall mounting (IP 65)
H Mounting rail (IP 20) E Retrofit module (installation module for DXCa, IP 20)
Version:
2 Without controls 3 Without controls (only mounting type E and H)
Application:
0 Standard
Language:
00 No controls
01 CE mark
2)
Approval:
2)
only with Version: 2, no operator control
DXMa A W 2 0 00 01
Only the measurement module in the mounting type W wall-mounted is available with controls and different languages.
DXMa Internal modules for DULCOMARIN® II, series DXC
These modules can be ordered via the identcode of the DXC (see Operating Instructions Multi-Channel Measuring and Control System DULCOMARIN
Page 4
®
II Swimming Pool Controller and Disinfection Controller DXCa, Part 1: Mounting and Installation”).
ProMinent
®
Page 5
About this Module / Safety Chapter / Storage and Transport / Mounting and Installation
1 About this Module
The actuator module DXMaA provides to the DULCOMARIN® II with the control options for 3 dosing pumps via pulse frequency, e.g. to raise and lower the pH value or to dose disinfectants.
The actuator module DXMaA is equipped with the following outputs:
4 standard signal outputs 0/420 mA, user-programmable and scalable for the measuring values of e.g. pH value, redox/ORP, concentration of free chlorine or total chlorine or combined chlorine or temperature.
3 frequency outputs for controlling dosing pumps, e.g. to raise and lower the pH value or to dose disinfectants.
and the following inputs:
3 digital inputs for evaluating the alarm relay of the dosing pumps and for monitoring of the tank level.
2 Safety Chapter
The actuator module DXMaA may only be used as component part of the DULCOMARIN® II.
The installation may only be performed by specially trained personnel!
3 Storage and Transport
Only store and transport the module in its original packaging.
CAUTION
Also protect the packaged module against humidity and exposure to chemicals.
Environmental conditions for storage and transport:
Temperature: - 10 °C to 70 °C
Climate: Permissible relative humidity: 95%, non-condensing (DIN IEC 60068-2-30)
4 Mounting and Installation
WARNING
• The installation may only be performed by specially trained personnel!
• Please carefully read the instructions in the “Operating Instructions Multi-Channel Measuring and Control System DULCOMARIN Disinfection Controller DXCa, Part 1: Mounting and Installation” before carrying out any mounting and installation work!
CAUTION
The standard signals can be distorted, which might have consequences for the process!
Only devices with own electrical isolation of the individual standard signal inputs (e.g. standard signal inputs of a recorder, …) may be directly connected to the standard signal outputs!
If a multi-channel standard signal input module of a PLC is to be connected to several standard signal outputs of the DXMaA module, each standard signal line is to be routed via a 3-way standard signal separator (a 3-way standard signal separator electrically isolates the input, the output and the supply voltage).
In case of several standard signal lines, a multi-channel isolating amplifier can be used. ProMinent recommends 4-channel isolating amplifiers of the type LC-TV-4I.4I of the company of Rinck (www.rinck-electronic.de) or of the type 6185D of the company of PR Electronics (www.prelectronics.de) to connect up to 4 standard signal lines.
®
II Swimming Pool Controller and
ProMinent
NOTE
The terminal connection diagram is enclosed at the end of these supplementary instructions.
Carry out the CAN connection as described in the Operating Instructions Multi-Channel Measuring and Control System DULCOMARIN Controller DXCa, Part 1: Mounting and Installation”.
®
®
II Swimming Pool Controller and Disinfection
Page 5
Page 6
Technical Data / Terminal Assignment
5Technical Data
Electrical data
Frequency outputs
(Opto-MOS relay)
for pump control
(R1, R2, R3): Contact type: make contact with series inductance, interference-suppressed
Load rating: 400 V peak, 250 mA switching current, max. 0.8 W maximum frequency: 8.33 Hz (500 strokes/min.) Close/open time: 5 ms
Digital inputs
(K1, K2, K3) (Kl. 9 – 14): galvanically isolated among each other
Insulation voltage: 500 V max. switch frequency: 2 kHz
Connectable contacts: mechanical relays max. connectable cable length: 20 m
Standard signal outputs mA
(I out 1 - I out 4): Insulation voltage: 500 V
Output range: 0/4-20 mA (programmable) 23 mA for error message maximum load: 400 Accuracy: 0.5% of the output range For the installation, Chap. 4 Mounting and installation must be observed!
Environmental conditions
Storage temperature: -10...70 °C
Type of protection IP 20 (within the housing DXM: IP 65)
Humidity: Permissible relative humidity: 95 %, non-condensing (DIN IEC 60068-2-30)
Materials
Housing: PPE-GF 10
6Terminal Assignment
Description Terminal Terminal no. Pole Function
Frequency output 1 R 1
Frequency output 2 R 2 redox pump
Frequency output 3
Digital input 1 K 1
Digital input 2 K 2
Digital input 3 K 3
Power output 0/4-20 mA 1 I out 1
description
1+pH lowering pump (control)
2- pH raising pump
3+chlorine pump (control)
4- acid pump
5+ flocculant pump
R 3 redox pump
6- chlorine pump
7+ error pump
8-
9+ error pump
10 -
11 + error pump
12 -
13 + pH value
14 - control variable pH lowering
control variable pH raising
control variable chlorination
control variable flocculation
control variable redox/ORP
(recorder connection)
Page 6
ProMinent
®
Page 7
Terminal Assignment / Terminal Connection Diagram
Description Terminal Terminal no. Pole Function
Power output 0/4-20 mA 2 I out 2 15 + redox/ORP value
Power output 0/4-20 mA 3 I out 3 17 + chlorine value
Power output 0/4-20 mA 4 I out 4 19 + combined chlorine
description
16 - control variable pH lowering
control variable pH raising
control variable chlorination
control variable flocculation
control variable redox/ORP
(recorder connection)
18 - control variable pH lowering
control variable pH raising
control variable chlorination
control variable flocculation
control variable redox/ORP
(recorder connection)
20 - control variable pH lowering
control variable pH raising
control variable chlorination
control variable flocculation
control variable redox/ORP
(recorder connection)
Internal
External
7Terminal Connection Diagram
Extra-low voltage Relay outputs
R1 R2 R3 K1 K2 K3
Digital inputs DXMaA
Standard signal outputs
0/4 - 20 mA
I out 1 I out 2 I out 4I out 3
ProMinent
®
Page 7
Page 8
Technical changes reserved.
ProMinent Dosiertechnik GmbH Im Schuhmachergewann 5-11 69123 Heidelberg Germany
Phone: +49 6221 842-0 Fax: +49 6221 842-419
info@prominent.com www.prominent.com