These operating instructions describe the technical data and function of the series DULCOMETER® D1C
controller, provide detailed safety information and are divided into clear steps.
IMPORTANT
• Please observe the parts of these operating instructions applicable to your particular
version! This is indicated in the Section “Device Identification / Identity Code”.
• Correct measuring and dosing is only possible in the case of impeccable operation of the
probe. The probe has to be calibrated / checked regularly!
NOTE
A form “Documentation of controller settings type D1C” is available under
www.prominent.com/documentation_D1C for the purpose of documenting the controller
settings.
3
Page 4
3Device Overview / Controls
"Change"
Button
"Branch back"
Button
"Down"
Button
Redox/ORP
STOP
START
Display field
Measured variable
Redox/ORP
Graphic
display
®
"Start/stop"
Button
"Enter"
Button
"Up"
Button
STOP
START
CHANGE button
To change over within a menu level
and to change from one variable to
another within a menu point.
START/STOP button
Start/stop of control and metering
function.
ENTER button
To accept, confirm or save a displayed
value or status. For alarm acknowledgement.
D1C2-002-GB
UP button
To increase a displayed numerical value
and to change variables (flashing
display)
BRANCH BACK button
Back to permanent display or to start
of relevant setting menu.
DOWN button
To decrease a displayed numerical
value and to change variables (flashing
display).
4
Page 5
4Functional Description
NOTE
Please refer to the description of the complete operating menu in Section 8 for a detailed
description of the individual characteristics of the DULCOMETER® D1C controller!
4.1Operating Menu
The D1C controller permits settings to be made in two different menus. All values are preset and can be
changed in the complete operating menu.
The controller is delivered with a restricted operating menu so that the D1C controller can be used
effectively in many applications from the very onset. If adaptations prove to be necessary, all relevant
parameters can then be accessed by switching over to the complete operating menu (see “General
Settings”).
4.2Access Code
Access to the setting menu can be prevented by setting up an access code. The D1C controller is supplied
with the access code 5000 which permits free access to the setting menu. The calibration menu remains
freely accessible even if access to the setting menu is blocked by the code.
4.3Control
The D1C can operate as a proportional controller or as a PID controller - depending on the device version
(see identity code) and the setting.
The controlled variable is recalculated once a second. Control procedures which require rapid correction of
setpoint deviations (less than approx. 30 seconds) cannot be processed with this controller. The cycle
times must be taken into consideration when activating solenoid valves (pulse length) in the same way as
their running times when activating servomotors (3-point).
Via the control input pause, the control function (selection of controlled variable) can be switched off. The
calculation of the controlled variable starts again after cessation of "pause".
4.4Feed Forward Control
The D1C controller can process a signal of a feed forward control. Depending on the device version (see
identity code) and the setting, this signal can be obtained in any form of a 0–20 mA or 4–20 mA signal or as
a digital contact signal with the maximum frequencies 10 Hz or 500 Hz.
This signal can be used, for example, for flow-proportional metering (multiplicative effect) or feed forwarddependent basic load metering (additive effect). The result of control variable calculation from the
proportional or PID control is multiplied by or added to the feed forward signal. A multiplicative feed forward
variable at the level of the set rated value carries over the calculated controlled variable unchanged into the
control variable:
Control variable = Feed forward variable/rated value x calculated controlled variable
During start-up, the zero point has to be checked. The feed forward control is not designed for switching off
permanently the actuating variable (signal ≈ 0).
An additive feed forward variable at the level of the rated value results in maximum control variable:
Control variable (max. 100 %) = (Feed forward variable/rated value x
max. control variable) + calculated controlled variable
4.5Error Messages
Error messages and information are indicated on the bottom line in the permanent display 1. Errors to be
acknowledged (acknowledgement switches off the alarm relay) are indicated by the "
which still apply after acknowledgement are indicated alternately. During correction variable processing
(temperature for correction of pH-value), the value is indicated in the same line as the error/note. Faults
which are rectified of their own accord due to changed operating situations are removed from the
permanent display without the need for acknowledgement.
". Errors/notes
5
Page 6
5Display Symbols
The display of the DULCOMETER® D1C controller uses the following symbols:
DescriptionCommentSymbol
Limit value transgressionSymbol
Relay 1, upperleft
Symbol
Relay 1, lowerleft
Symbol
Relay 2, upperright
Symbol
Relay 2, lowerright
Metering pump 1 (oxidant)Symbol
Control offleft
Symbol
Control onleft
Metering pump 2 (reducing agent)Symbol
Control offright
Symbol
Control onright
Solenoid valve 1 (oxidant)Symbol
Control offleft
Symbol
Control onleft
Solenoid valve 2 (reducing agent)Symbol
Control offright
Symbol
Control onright
Servomotor
Control, open relay
Control, close relay
Without control
Thickness of bar
Position feedbackincreases from left to right
during opening
Stop button pressed
Manual metering
Fault
6
Page 7
6Operation
Permanent
display 1
Permanent
display 2
Calibration
menu
Various
Setting menus
Access code
The various menus are selected with
the CHANGE button
The menu is started with
the ENTER button
BRANCH BACK to permanent display
or to relevant setting menu
Calibration notes
Access code, correct
Parameter
setting
D1C2-007-GB
NOTE
Access to the setting menus can be barred with the access code!
The number and scope of setting menus is dependent on the device version!
If the access code is selected correctly in a setting menu, then the following setting menus are
also accessible!
If within a period of 10 minutes no button is pushed, the unit automatically branches back from the
calibrating menu or a setting menu to the permanent display 1.
BRANCH BACK without
saving setting
BRANCH BACK to
start of setting
Variables flash
Text 1
Selection 1
Text 2
Selection 2
Text 1
Selection 1
Text 2
Selection 2
CHANGE from selection to selection
Change numbers or
settings of selection
ENTER and save setting,
continue to next menu
D1C2-008-GB
7
Page 8
7Restricted Operating Menu / Layout
The restricted operating menu permits simple operation of the most important parameters. The following
overview shows the settings which can be selected.
mV
750
mea. val.
fd. fwd.:
reg. val.:
w:750 mV
check probe
ORP
limits
setting ?
750 mV
70 %
59 %
Permanent display 1
Permanent display 2
only with control
(w = setpoint)
check probe
ORP
probe in buffer
460 mV
limit 2
900 mV
limit 1
100 mV
upper
lower
Positive values of setting variable:
Negative values of setting variable:
check probe
measurement act.
please wait !
460 mV
check probe
ORP
value:
buffer:
Number and scope of setting menus
is dependent on the device.
Access to setting menus can
be blocked with access code.
Oxidant agent
Reducing agent
460 mV
465 mV
control
settings ?
Setting in
complete
operating
menu
general setting
information
Only with control
control
regulated value:
positive oxide
negative reduc
control
normal
current regulat.
value:30 %
or
control
with dead zone
current regulat.
value:30 %
or
control
manual
current regulat.
value:30 %
ident-code: D1CA
DxRxxxxxxxxxx
Software version
D1C-A1 FW-5.00
For normal control
setpoint
750 mV
Control with dead zone
setpoint 2 upper
750 mV
setpoint 1 lower
650 mV
Proportional control
ctrl. parameter
xp =
PID control
ctrl. parameter
xp =
Ti =
Td =
For manual control
manual dosing
15 %
regulated range
alarm relayaccess c.:
active
operating menu:
english
=
=
restricted
10 %
10 %
0 s
0 s
5000
D1C2-010-Redox-GB
8
Page 9
Restricted Operating Menu / Description
mV
Permanent display 1
750
mea. val.
fd. fwd.:
reg. val.:
w:750 mV
750 mV
70 %
59 %
Permanent display 2
only with control
(w = setpoint)
Checking the Redox Probe
During calibration, the D1C sets the command outputs to “0”. Exception: if a basic load or a manual control
variable was set, these are maintained during calibration. The standard signal outputs mA (measuring value
or correction value) are frozen. The measured value or the standard buffer value 220 mV or 465 mV is
proposed as the buffer value; this value is adjustable (arrow keys). After everything has been checked, all
error tests which refer to the measured value are restarted.
check probe
ORP
check probe
ORP
probe in buffer
460 mV
Positive values of setting variable:
Negative values of setting variable:
ident-code: D1CA
DxRxxxxxxxxxx
software version
D1C-A1 FW-5.00
Possible values
not active
codecode
complete
alarm relayaccess c.:
active
operating menu:
english
=
=
restricted
5000
D1C2-016-GB
Access Code
Access to the setting menu can be prevented by setting up an access code. The DULCOMETER
controller is supplied with the access code 5000 which permits free access to the setting menu. The
calibration menu remains freely accessible even if access to the setting menu is blocked by the code.
®
D1C
11
Page 12
8Complete Operating Menu / Overview
All parameters of the controller can be set in the complete operating menu (access see previous page). The
following overview shows the settings which can be selected:
mV
750
mea val.
fd. fwd.:
reg. val.:
w:750 mV
check probe
ORP
meas. value
setting ?
pumps
setting ?
750 mV
70 %
59 %
Permanent display 1
Permanent display 2
only with control
(w = setpoint)
Number and scope of setting menus
is dependent on the device.
Access to setting menus can
be blocked with access code.
Only with pumps
relays
setting ?
limits
setting ?
servomotor
setting ?
control
setting ?
feed forward ctrl.
setting ?
Only with limit relay,
solenoid valve relay
or servomotor
Only with
servomotor
Only with control
Only with feed
forward control
signal output 1
mA setting ?
signal output 2
mA setting ?
general setting
information
Only with standard
signal output
Only with 2 standard
signal outputs
12
D1C2-017-Redox-GB
Page 13
Complete Operating Menu / Description
mV
Permanent display 1
750
mea. val.
fd. fwd.:
reg. val.:
w:750 mV
750 mV
70 %
59 %
Permanent display 2
only with control
(w = setpoint)
Checking the Redox Probe
During calibration, the D1C sets the command outputs to “0”. Exception: if a basic load or a manual control
variable was set, these are maintained during calibration. The standard signal outputs mA (measuring value
or correction value) are frozen. The measured value or the standard buffer value 220 mV or 465 mV is
proposed as the buffer value; this value is adjustable (arrow keys). After everything has been checked, all
error tests which refer to the measured value are restarted.
check probe
ORP
check probe
ORP
probe in buffer
460 mV
Positive values of setting variable:
Negative values of setting variable:
Standard signal input4 mA0 mA
lower signal limit4 mA
Allocated0–1 V1 mV-2000 mV+2000 mV
probe voltage
Checkout timeoff1 s1 s9999 sConstant measurement
signal results in message
and alarm.
Function off = 0 s
Control Time Measuring Value
IMPORTANT
This function may not be activated for applications where it can be assumed that the
measuring value does not change.
This function checks whether the measuring value from the sensor (measuring value input) changes within
the “control time measuring value”. It is assumed that the value does not change for an intact sensor.
If the measuring value does not change during this control time, the DULCOMETER
®
D1C sets the control
output to “0” and the alarm relay drops out. The LCD display shows e.g. the message “check mV-probe”.
14
Page 15
Complete Operating Menu / Description
Correction Value*
Access to all setting menus can be blocked with an access code !
correction value
setting ?
correction value
temperature
automatic
*In the setting menu “correction value” for this equipment enables you to display the temperature or to
maintain an mA signal proprotional to the temperature. No temperature adjustment is made to the
measured variable!
Pumps
Access to all setting menus can be blocked with an access code !
Period (Cycle)off1 h1 h / off240 hfor timer
t on1 min1 min1 min60 minfor timer
NOTE
The limit value relay can be defined in such a way as to respond as an actuator, i.e. if a limit
value relay closes a circuit, it opens when a pause contact is activated and/or for a
subsequent delay period td (if td is set to > 0 min in “General settings”).
Cycle
t
Timer relay
on
off
on
IMPORTANT
The timer will be reset if there is a drop in the power supply.
16
t
Page 17
Complete Operating Menu / Description
At the end of the (timer) cycle time, the DULCOMETER® D1C closes the assigned relay for the duration of
“t on” (timer). “Pause” interrupts the timer.
When the clock is shown in the LC display, the timer can be reset to the start of the cycle at precisely this
point using the Enter button.
The % figure in the LC display indicates the progress of the current cycle.
Timer relays may be used, e.g. for shock metering or sensor cleaning.
Cycle
Solenoid
valve
on
off
on
off
The switching time of the DULCOMETER® D1C (solenoid valve) depends on the actuating variable and the
“min. time” (smallest permitted operating factor of the connected device).
The actuating variable determines the ratio ton/cycle and thus the switching times (see fig. above).
The “min. time” influences the switching times in two situations:
a) theoretical switching time < min. time:
Cycle
min. time
on
off
Cycle
on
off
t
on
t
on
Cycle
Cycle
Cycle
Cycle
Cycle
min. time
min. time
Control
variable: 80 %
t
on
Cycle
t
Control
variable: 50 %
t
on
Cycle
t
theoretical
t
actual
t
= 0.80
= 0.50
The DULCOMETER® D1C does not switch for a certain number of cycles until the sum of the theoretical
switching times exceeds the “min. time”. Then the
total time
.
b) theoretical switching time > (cycle - min. time) and calculated switching time < cycle
Cycle
min. time
on
off
Cycle
on
off
The DULCOMETER® D1C does not deactivate for a certain number of cycles until the differences between
cycle and theoretical switching time exceed the “min. time”.
Cycle
Cycle
DULCOMETER® D1C
Cycle
Cycle
min. time
t
t
switches for the duration of this
theoretical
actual
17
Page 18
Complete Operating Menu / Description
Limits
Access to all setting menus can be blocked with an access code !
Type of limit transgressionupperLimit transgression when
Limit 1:lowerlowerexceeding or dropping below value
Limit 2:upperoff**only with limit relay
Limit valueLimit 1:500 mV1 mV-2000 mV2000 mV
Limit 2:1000 mV1 mV-2000 mV2000 mV
Hysteresis limits10 mV1 mV10 mV2000 mVEffective in direction of cancelling
limit transgression
Checkout time limitsoff1 s1 s9999 sResults in message and alarm.
off = 0 s:
Function switched off,
no message, no alarm
Controlonon
off
Actuating directionactive closedactive closedReacts as make contact
limit value 1;active openReacts as break contact
limit value 2
Switch-on delay ∆t on0 s1 s0 s9999 s
Switch-off delay ∆t off0 s1 s0 s9999 s
If the limit is exceeded for longer than the “Delay time - limit values”, an error message is given which
must be acknowledged, and the alarm relay circuit is broken. If “Control” is also set to “off” the control
process stops.
18
Page 19
Complete Operating Menu / Description
Servomotor
The operating range is defined by the total resistance range of the feedback potentiometer. The maximum
limit of the range actually used is set by defining the control range.
IMPORTANT
• To ensure correct operation, the activation time of the actuator used should not be less
than 25 seconds for the control range from 0…100 %!
• Activation of the servomotor must be carried out with the same meticulous care as taken
when calibrating a measuring probe.
Access to all setting menus can be blocked with an access code !
Range measured
value0–1 V1 mV-2000 mV2000 mVMinimum range 10 mV
Range controlled
variable0 %…+100 %1 %-100 %+100 %Minimum range 1 % of
signal output 2
regulated value
0 mA =
20 mA =
0%
100%
D1C2-030-Redox-GB
when alarm relay switches
(not limit value violation)
measured value
General Setting
Access to all setting menus can be blocked with an access code !
general setting
information
22
ident-code: D1CA
DxRxxxxxxxxxx
software version
D1C-A1 FW-5.00
alarm relay
active
pause normal
- active... closed
- alarm off
- td: 0 min
access c.:
operating menu:
english
=
=
complete
5000
D1C2-028-GB
Page 23
Complete Operating Menu / Description
Possible values
Initial valueIncrementLower value Upper valueRemarks
Alarm relayactiveactive
not active
Pausenormalnormal
Hold
Control input pauseactive closedactive closedReacts as make contact
active openReacts as break contact
Pause with alarmoffoffAlarm relay can be
ontriggered by pause contact
td0 min1 min0 min60 min
Access code5000119999
Languageas per identityas per identity
codecode
Operating menucompleterestricted
complete
Standard Pause
If the pause switch is off, the DULCOMETER® D1C sets the operating outputs to “0” for as long as the
pause switch is off or for a set time-delay td (if td is set to > 0 min). Whilst the pause switch is off, the D1C
establishes the P-proportion in the background.
With PID control (Identity code characteristics “control characteristic” = 2): the I-proportion is stored when
the pause is switched off (I-proportion then usually only present if Ti > 0 has been selected in the “Control
setting?” setting menu).
Exception: the standard signal outputs mA for the measured value or correction value are not affected by
the pause.
After pause is activated, the operating outputs remain at “0” for the length of the time delay td. The time
delay td must be set up in such a way that in this time e.g. sample water (process-specific current
concentration) flows to the sensor.
With PID control (Identity code characteristics “control characteristic” = 2): The control variable output
resulting from the pause and the expiry of the time-delay td is reconciled jointly with the current
P-component and (if Ti is set > 0) with the stored I-component.
Pause Hold
If the pause switch is off, the DULCOMETER® D1C freezes the operating output at the most recent value for
as long as the pause switch is off or for a set time-delay td (if td is set to > 0 min). Whilst the pause switch is
off, the D1C establishes the P-proportion in the background.
With PID control (Identity code characteristics “control characteristic” = 2):
Even the mA standard signal outputs for measured value or correction value are frozen.
After pause is activated, the operating outputs remain frozen for the length of the time delay td. The time
delay td must be set up in such a way that in this time e.g. sample water (process-specific current
concentration) flows to the sensor.
With PID control (Identity code characteristics “control characteristic” = 2): The control variable output
resulting from the pause and the expiry of the time-delay td is reconciled jointly with the current
P-proportion and (if Ti is set > 0) with the newly established I-proportion.
Access Code
Access to the setting menu can be prevented by setting up an access code. The DULCOMETER® D1C
controller is supplied with the access code 5000 which permits free access to the setting menu. The
calibration menu remains freely accessible even if access to the setting menu is blocked by the code.
23
Page 24
9Fault / Remarks / Troubleshooting
* Depends on whether “alarm off” or “alarm on” in “General Settings”.
During servomotor setting
Position feed back wrong
Upper position <40 % max. value
Lower position >30 % range
Final value small
Direction check
Final value big
unsteady
Measured 40 mV > buffer
During checking sensorBasic loadStopNoNo error processing–