Prolon T1100 User Manual

T1100
User Guide
Introduction
The T1100 digital thermostats are networkable, microprocessor-based thermostats designed for zoning applications. Proportional and integral (PI) control loops, working in conjunction with fully customizable outputs (1 analog / 1 digital) deliver accurate yet flexible control strategies. An auxiliary analog input is available for zone temperature averaging or as a radiant floor slab temperature input. Configuration, performed via a capacitive circular touch pad, is made easy through an intuitive menu system displayed on a backlit graphic LCD screen.
Installation
1. Open casing to remove back cover by pushing on the tab located underneath the thermostat. (Figure 1)
2. Pull wire(s) through central hole of back cover.
Ver. 5.1
3. Screw in the back cover to the wall.
4. Connect wires:
Pull out the screw terminal blocks. Remove 1 cm insulation from the end of
each wire.
Connect the wires to the terminal
blocks: see
Figure 2 for pin identification. Typical wiring examples can be found below.
Reinstall terminal blocks.
5. Reconnect top cover
Important: Do not install the thermostat under the following conditions:
x Any location exposed to direct sunlight x On an outside wall x Near an air discharge grill x In a location where vertical air circulation
is restricted
x Near a dimmer switch
Figure 1
Figure 2
1
Power source
The T1100 is powered by a 24 VAC power source connected using the "COM" pin and the "24 AC" pin (see Figure 3). The common for the power source is shared by the auxiliary analog input and the analog output.
Network Setup
The T1100 can work autonomously or networked. When networked, it will communicate in real-time with other ProLon controllers. The T1100 uses the Modbus RTU protocol over RS485. A unique network address must be assigned to each device on the network. For the T1100, this can be done through the menu system. The network connections are made using the “NETA” (+) and “NETB” (-) pins ( resistors can be activated or deactivated using jumpers on the back of the PCB (see and terminating resistors are used to improve signal quality in an RS485 network. For more information regarding application of network resistors or shielding, see the ProLon Network Guide.
Figure 4). Bias and terminating
Figure 5). Bias
L
120Vac24Vac
24 VAC
COM
1 2
3 4
Figure 3: Power Source
RS485
NET A (+) NET B (-)
Figure 4: Network Connection
1 2
3 4
Daisy Chain
Figure 5: Network Resistor Jumpers
N
2
Auxiliary Analog Input
The T1100 has an auxiliary analog input which can be used to connect another thermistor. The T1100 can be configured to use this alternate temperature reading for a variety of functions, including temperature averaging or radiant floor slab
AUX IN
COM
5 6
7 8 9
10
temperature. The alternate thermistor (10KΩ type 3) can be
connected to the auxiliary input using the “AUX IN” and “COM” pins (see
Figure 6: Auxiliary Input
Figure 6).
Outputs Specifications
The T1100 series thermostats contain a fully customizable Triac output and a 0­10VDC output to drive components. An integrated resettable fuse protects both outputs of the T1100 against current surges and short circuits. This protection will cut the current to the output as soon as an overload condition is detected. The fuse is round and yellow-colored which, upon a short circuit condition, will heat up and change to orange. When the faulty wiring or circuit is fixed, the fuse will automatically reset and allow current to flow through the output again.
Output Type Heating Cooling
Pas sive Sink Triac 10-30 V AC (dry c ontact)
Digital
Analog
On-or-Off Pulsed Max Current: 750 mA Modulat i ng Output On-or-Off Max Current: 40 mA Configurable si gnal:
- 0 to 10 VDC
- 2 to 10 VDC
- 0 to 5 VDC
Figure 7: Output Specifications
Valve Relay Triac
Modulat i ng V alve SCR Relay Triac
Valve Relay
Modulat i ng Valve Relay
3
Typical wiring of the Digital Output
The T1100 opens and closes a triac contact to allow an external source to power the load.
DO+ DO-
5 6
7
External Load
R
24 VAC
N
8 9
External
10
Figure 8: Typical wiring of digital output
Typical Wiring of the Analog Output
The T1100 provides the control signal to the load, which is powered externally or from the same power source as the T1100.
External
24 V
5
N
source
AO
COM
6 7 8
24 V
0-10v
Com
9
10
Figure 9: Typical wiring of analog output
Controlled
Load
4
Operation
The T1100 is controlled using the circular touch pad on the bottom half of the thermostat. The touch pad uses capacitive sensing technology to detect finger proximity. There are no moving parts to push or rotate. The T1100 is controlled using simple scrolling, tapping or holding motions, performed around the circle of the touch pad. The center of the circle is unused.
Hint Display
At the bottom of the screen, a circle representing the touch pad is displayed, with hints on how to navigate and modify settings, as well as providing feedback as you manipulate the touch pad. Hints are context-sensitive and will only display where logical.
Changing the setpoint
Tap here to
go BACK
FEEDBACK
The black arc follows your finger
22.8 ºC
Scroll clockwise or
counterclockwise
to adjust or navigate
Tap here to
ENTER
HINTS
Hold your finger over
highlighted areas to use
special features
5
Schedule Override
Navigating Menus
6
Menu Maps
Visualisation and Options Menu Map
Configuration Menu Map
7
Temperature Menu Map
Outputs Menu Map
8
Radiant Floor Menu Map
Network Menu Map
Visualisation Screen
9
Menu Guide
Section Description Min Max Default Units
1.1) Temp Unit Lets you select between Celsius or Fahrenheit temperature display.
1.2) Temp
Source
1.3) Sound This option lets you enable or disable audio
1.4) Backlight Auto: The backlight activates upon any user
Lets you decide how the zone temperature is determined:
Internal• (Only the onboard thermistor is used to calculate temperature) External• (The temperature reading is obtained from an external thermistor connected to the auxiliary input) Average• (The temperature reading is obtained from an average of both the internal thermistors reading and the reading obtained from the external thermistor connected to the auxiliary
input. ) NOTE: When an output is set to control a radiant floor, the external input is automatically dedicated to slab temperature sensing.
feedback from touchpad interaction.
interaction with the touchpad, and goes off after 60 seconds of inactivity. On: The backlight is permanently on. Off: the backlight is permanently off, regardless of user interaction.
-- Celsius-
- - Internal -
- - Enabled -
-- Auto-
1.5) Language This option changes the display language English
1.6) Restore Default
1.7) Reset Causes the thermostat to perform an
2.1) Device Type The type of thermostat being used. - - - -
Activating this option causes the thermostat to revert all configuration properties back to their factory defaults. cannot be undone.
electronic reset. All configuration properties remain saved, but any active overrides are lost.
-- --
WARNING: This
-- --
10
Section Description Min Max Default Units
2.2) Software Vers
2.3) Hardware
The current software version of the thermostat device type.
Physical version of the thermostat. - - - -
Vers
2.4) My Address This option lets you set the address of the thermostat on the network. Each device on a network must have a different address.
2.5) Name The name given to this zone. Can only be changed using Focus software.
temperature reading (regardless of source).
3.2) Morn
WarmUp Time
The duration that the outputs will be disabled after receiving a morning warm up command from the network master, unless the network master is using a longer period.
-- --
1 127 101 -
-- --
-15 15 0 °C3.1) Temp Calib This value will be added to the room
-27 27 0 °F 0 250 0 min
heating setpoint and the occupied cooling setpoint.
calculate the proportional component of the demand. Please refer to the following image.
Proportional
100%
2
Heating Setpoint
0%
Deadband
Proportional
0%
Cooling
Setpoint
2
100%
°C
4.3) Cool Int Defines the amount of time required for the cooling integral component of the demand to equalize the proportional component. Setting this value to zero removes the cooling integral component of the demand.
0.5 15 1 °C4.1) Deadband The deadband between the occupied
0.9 27 1.8 °F 0 10 3 °C4.2) Prop Band Defines the proportional band used to
0 18 5.4 °F
0 120 15 min
11
Section Description Min Max Default Units
4.4) Heat Int Defines the amount of time required for the heating integral component of the demand to equalize the proportional component. Setting this value to zero removes the cooling integral component of the demand.
During occupied mode, the thermostat will
Min
Max
Max
use this value as a low limit for the heating setpoint.
During occupied mode, the thermostat will use this value as a high limit for the heating setpoint.
use this value as a low limit for the cooling setpoint.
During occupied mode, the thermostat will use this value as a high limit for the cooling setpoint.
0 120 15 min
5 30 19 °C5.1) Heat SP
41 86 66.2 °F
6 44.5 25 °C5.2) Heat SP
42.8 112.1 77 °F
5.5 44 20 °C5.3) Cool SP Min During occupied mode, the thermostat will
41.9 111.2 68 °F
6.5 45 26 °C5.4) Cool SP
43.7 113 78.8 °F
0 20 3 °C6.1) Heat Offset During unoccupied mode, the active heating
setpoint is decreased by this amount.
0 36 5.4 °F 0 20 5 °C6.2) Cool Offset During unoccupied mode, the active cooling
setpoint is increased by this amount.
0 36 9 °F 5 30 15 °C6.3) Heat SP
41 86 59 °F
5.5 45 30 °C6.4) Cool SP Lim During unoccupied mode, the thermostat
41.9 113 86 °F 0 720 120 min
Lim
6.5) Unocc Overr Time
During unoccupied mode, the thermostat will use this value as a low limit for the heating setpoint.
will use this value as a high limit for the cooling setpoint.
The time spent in occupied mode once the thermostat is manually overridden from unoccupied mode.
12
Section Description Min Max Default Units
7.1) SP Mode Sets the digital output in heating or cooling mode.
7.2) Setpoint The desired setpoint for the digital output. Cannot be zero.
7.3)Ctrl Mode Sets the digital output in proportional or differential mode.
In proportional mode, the output is at 0% when the demand reaches the setpoint, and pulses proportionally as the demand increases, reaching 100% once the demand reaches the sum of the setpoint and the proportional band.
Proportional Band
0%
Output = 0%
Setpoint
Output = 100%
Demand
In differential mode, the output alternates between ON and OFF whenever the demand passes through a differential band centered on the setpoint.
Differential
- - HEAT -
5 95 50 %
-- DIFF-
Demand
OFF
Setpoint
7.4) Prop The proportional band used when the digital
ON
5 99 50 %
output Ctrl Mode is set to Proportional.
7.5) Diff The differential band used when the digital
8 99 40 %
output Ctrl Mode is set to Differential.
7.6) Rev Act When reverse acting is selected, the output
-- OFF­action will be inverted versus the output state. (If the output is indicating 100%, the contact will be open instead of closed.)
7.7) Override This option lets you manually override the
0 100 AUTO % digital output or set it back to automatic control.
13
Section Description Min Max Default Units
8.1) SP Mode Sets the analog output in heating or cooling mode.
8.2) Setpoint The desired setpoint for the analog output. Cannot be zero.
8.3) Ctrl Mode Sets the analog output in proportional or differential mode.
In proportional mode, the output is at 0% when the demand reaches the setpoint, and modulates (or pulses) proportionally as the demand increases, reaching 100% once the demand reaches the sum of the setpoint and the proportional band.
Proportional Band
0%
Output = 0%
Setpoint
Output = 100%
Demand
In differential mode, the output alternates between ON and OFF whenever the demand passes through a differential band centered on the setpoint.
Differential
- - HEAT -
1 95 25 %
-- PROP-
Demand
OFF
Setpoint
ON
8.4) Prop The proportional band used when the analog output Ctrl Mode is set to Proportional.
8.5) Diff The differential band used when the analog output Ctrl Mode is set to Differential.
8.6) Rev Act When reverse acting is selected, the analog output voltage will be inversely proportional to the output state.
8.7) Pulsed The analog output can be configured to pulse instead of modulate when used in Proportional mode.
5 99 75 %
8 99 40 %
-- OFF-
-- OFF-
14
Section Description Min Max Default Units
8.8) Range The analog output can be set to work over
- - 0-10V -
different voltage ranges:
0-10VDC
2-10VDC
0-5VDC
8.9) Override This option lets you manually override the
0 100 AUTO % analog output or set it back to automatic control.
9.1) Override This option lets you assign an output to
-- None­control the radiant floor system. It also gives access to the radiant floor menu.
Slab Temperature
5 30 27 °C10.1) Max Slab
Temp
Max
10.2) Min Slab Temp
Slab
Temperature
Setpoint
Min
Calculated
0% 100%
Output
Level
The Slab Temperature Setpoint is
41 86 80.6 °F
5 30 21 °C
determined using a scale defined by the minimum and maximum slab temperatures. The Calculated Output Level that
41 86 69.8 °F determines the Slab Temperature Setpoint is defined by the configuration of the output selected to control the radiant floor.
5 30 19 °C11.1) Min Slab
41 86 66.2 °F
Temp
When in unoccupied mode, the scale defined above is ignored, and the controller maintains this temperature in the slab.
15
Section Description Min Max Default Units
0 10 1 °C12.1)
Proportional
The output pulses at 50% of the cycle
0 18 1.8 °F
length when the slab temperature reaches the setpoint. The proportional band will increase or reduce the length of the pulse depending on the offset from the setpoint.
12.2) Integral Defined as the amount of time required to
0 600 60 min cause the pulse width to vary by 100% to compensate for a continual error of 1 °C.
13.1) Cycle Length
Cutoff
The amount of time of a total ON AND OFF cycle.
Above this temperature, the radiant floor output always remains deactivated. (There is a 2°C differential to allow for temperature
5 250 15 min
5 30 15 °C13.2) Outside
41 86 59 °F
fluctuations).
-15 15 0 °C13.3) Calibration This applies an offset to the slab
temperature reading, if required.
-27 -27 0 °F
14.1) GrpCode1 One of three control groups that this thermostat can belong to. Zero is ignored.
14.2) GrpCode2 One of three control groups that this thermostat can belong to. Zero is ignored.
14.3) GrpCode3 One of three control groups that this thermostat can belong to. Zero is ignored.
0 250 0 -
0 250 0 -
0 250 0 -
16
Section Description Min Max Default Units
14.4) GrpWght1 The weight of the thermostat in the group selected in GrpCode1.
14.5) GrpWght2 The weight of the thermostat in the group selected in GrpCode2.
14.6) GrpWght3 The weight of the thermostat in the group selected in GrpCode3.
14.7) Global
Wght
15.1) Baud Rate The baud rate used for serial
15.2) Parity The parity used for serial communication.
15.3) Stop Bits The number of stop bits used for serial
The weight of the thermostat in the global group.
communication.
None
Odd
Even
communication.
0 15 0 -
0 15 0 -
0 15 0 -
0 60 1 -
9600 115200 57600 bps
-- None-
12 1-
17
Specifications
Supply: 24 VAC ±10%, 50/60 Hz Microprocessor Power consumption: 5 VA max Inputs: 1 analog input (Thermistor 10K type3 /
dry contact), 10 bit resolution (1024 segments) Digital Output: Triac, 10-30 VAC sink, 750 mA
max (resettable fuse), ON/OFF or pulsed, heat/cool
Analog Output: 0-10 VDC, 40 mA max (resettable fuse), ON/OFF or pulsed, heat/cool
Screen: LCD 80x130 pixels with back lighting Interface: Circular capacitive touch pad Audible feedback: Yes
Flash Communication protocols: Modbus RTU (RS485), up to
127 devices. Baud rates: 9600, 19200, 38400, 57600, 76800, 115200 Connection: Screw-type terminal blocks (16 AWG max)
and RJ45 modular jack Dimensions: 82 mm x 126 mm ( 3.23" x 4.96" ) Weight: 0.1 kg (0.22 lb) Environment: 0-50 deg C (32-122 deg F) Mounting: Standard electrical box 2" x 4"
Dimensions
: Atmel 32 bits, 60 MHz, 256K Bytes
© Copyright 2010 ProLon. All rights reserved. No part of this document may be photocopied or reproduced by any means, or translated to another language without prior written consent of ProLon. All specifications are nominal and may change as design improvements are introduced. ProLon shall not be liable for damages resulting from misapplication or misuse of its products. All trademarks are the property of their respective owners.
18
Loading...