Prolon PL-RS, PL-T500, PL-T200, PL-T1000, PL-VC2000 Quick Start Manual

...
Page 1
QUICK START GUIDE
VAV CONTROLLERS & WALL SENSORS
www.proloncontrols.com | [email protected]
17 510 rue Charles, Suite 100, Mirabel, QC, J7J 1X9
REV 1.0
PL-QCK-WSENSOR/VC2000-EN
Page 2
Page 3
COM
THERM
COM
POT
(126 mm)
3.23”
(82 mm)
Room temperature
Setpoint (10K)
(82 mm)
Page 4
INT A (+)
INT B (-)
24VAC
COM
(126 mm)
3.23”
(82 mm)
Communication (RS485)
Power (2 VA max)
RJ45 connection
(to C1000)
(82 mm)
Page 5
INT A (+)
INT B (-)
24VAC
COM
3.23”
(82 mm)
Communication (RS485)
Power (2 VA max)
RJ45 connection
(to C1000)
(82 mm)
Page 6
24 VAC
Page 7
5
The sun icon is
OVERRIDE ACTIVE (Occupied mode)
unoccupied mode
Page 8
INT Port: Incoming Modbus RS485 communication from digital
sensor -OR- Remote computer with Prolon Focus software
Digital Input for night setback / Standby mode
Multi-function analog input
Common for all the inputs
Temperature setpoint (0-10K potentiometer)
Room temperature sensor (10K thermistor)
Output 5 (analog 0-10VDC) (Max Current: 40 mA)
Output 4 - Isolated or source, TRIAC 24 VAC
(max current: 300 mA)
Output 3 - Isolated or source, TRIAC 24 VAC
(max current: 300 mA)
Output 2 - Isolated or source, TRIAC 24 VAC
(max current: 300 mA)
Output 1 - Isolated or source, TRIAC 24 VAC
(max current: 300 mA)
Power source of the controller (24 VAC - Class 2)
NET Port: Incoming Modbus RS485 communication
- OR - BACnet MS/TP
Page 9
Service pin
General purpose analog input
(0-5 VDC, 4-20mA, 10K thermistor)
Supply / Radiant / Zone / Occupancy / Discharge
Digital sensor (T1000, T500 or T200) /
Remote computer with Focus
Analog output (0-10 VDC) (max current: 40 mA)
Network communication
Digital output - Isolated Triac
Dry contact (24 VAC) (max current: 750 mA)
Power source of the controller
(24 VAC - Class 2)
Airflow Sensor (PL-VC2000-PI)
Airflow sensors are only included in the PL-VC2000-PI
models only. Adding an airflow sensor to the Prolon VC2000
lets it regulate the airflow as well as temperature in a zone,
independently of the static pressure variations of the system.
The default flow sensor has a range of 0 to 2 in H20
(0 to 500 Pa). Depending on the flow cross used, this
translates to roughly 0-3500 ft/min.
Page 10
REV 1.0 / PL-QCK-WSENSOR/VC2000-EN18
Compliance
Technical Specications
Digital Sensor (PL-T1000)
• FCC Compliant to CFR47, Part 15, Subpart B, Class B
• Industry Canada (IC) Compliant to ICES-003, Issue 5: CAN ICES-3 (B) / NMB-3(B)
• RoHS Directive (2002/95/EC)
VAV Zone Controller (PL-C1000-VAV / PL-VC2000)
• cULus Listed; UL 916 Energy Management Equipment, File E364757, Vol.1
• CAN/CSA-C22.2 No. 2015-12, Signal Equipment
• FCC Compliant to CFR47, Part 15, Subpart B, Class B
• Industry Canada (IC) Compliant to ICES-003, Issue 5: CAN ICES-3 (B)/NMB-3(B)
• RoHS Directive (2002/95/EC)
FCC User Information
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Industry Canada
This Class (B) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment regulations.
Cet appareil numérique de la Classe (B) respecte toutes les exigences du Réglement sur le matériel brouilleur du Canada.
PL-RS / PL-T200
Supply: 24 VAC ±10%, 50/60 Hz Consumption: 2 VA max
PL-T500 / PL-T1000
Supply: 24 VAC ±10%, 50/60 Hz Consumption: 5 VA max
PL-C1000-VAV
Supply: 24 VAC ±10%, 50/60 Hz Consumption: 2 VA (Typ), 32 VA (Input)
PL-VC2000
Supply: 24 VAC ±10%, 50/60 Hz, Class 2 Consumption: 3 VA (Typ), 5 VA (Max), 24 VA (Input)