Prolon Lonbox PSW5000 User Manual

Prolon Control Systems
Lonbox PSW5000 Users Manual
Switch interface for building automation
Prolon Control Systems
Lonbox PSW5000 Users Manual Page 2
Index
Index ............................................................................................................................................... 2
Overview ......................................................................................................................................... 3
Configuration .................................................................................................................................. 3
Functional Blocks ............................................................................................................................ 6
Node Object ................................................................................................................................ 6
Network Variables .................................................................................................................... 6
Configuration Properties ................................ .......................................................................... 6
Switch ......................................................................................................................................... 7
Network Variables .................................................................................................................... 7
Configuration Properties ................................ .......................................................................... 7
Scene Panel ................................................................................................................................ 8
Network Variables .................................................................................................................... 8
Configuration Properties ................................ .......................................................................... 8
Scene Controller .......................................................................................................................... 8
Network Variables .................................................................................................................... 9
Configuration Properties ................................ .......................................................................... 9
Switch Connection Information ...................................................................................................... 10
Mounting Instruction ............................................................................................................... 10
Technical Data .............................................................................................................................. 12
Models .......................................................................................................................................... 12
Prolon Control Systems
Lonbox PSW5000 Users Manual Page 3
Overview
The interface series PSW50xx is designed to be used in LonWorks based systems. The devices are used as an interface between one or more physical switches and a building automation installation. The normal function of the interface is to allow for manual operation of lights, sun blinds, ventilation etc.
The inputs can be assigned to operate the build-in LonMark Switch objects. It is possible to use 4 inputs to operate 4 separate light groups or to use all 4 inputs to operate one single light group with different functions.
The series consists of 5 models with different I / O configuration, the number of I / O in the various models is especially adapted to suit standard FUGA and OPUS switches.
The interfaces device uses LonWorks 2.0 technology. Software functions are according to the current LonMark standard, inputs control Switch 3200 or
Scene Panel 3250. In addition scenes can be configured with the build-in Scene Controllers. The device is very compact and designed to be placed behind the switch module when mounted in
or on a wall. In addition to the wires for connecting switches and indicators, the PSW50XX device has two wires
for TP/FT-10 network communication and two wires for connection of an external 24Vdc power supply, normally these two pairs are connected to a network cable. Only the communication and power wires should be run away from the device. The PSW50XX device should be combined with the switch interface into one unit; I/O is not designed to be wired away from the device.
It is possible to transmit the service pin message by activating inputs 1 and 2 simultaneously.
Configuration
The main configuration of the function of the interface is done through two configuration properties on the Node Object. The configuration is located on the Node Object because the configuration applies to the physical digital inputs and not the other function block (switch).
Using the node object UCPTdiAssignment each digital input is told which switch function block to apply its operation to. This means that for a 4 input module, the 4 inputs can operate 4 individual switch function blocks or all 4 digital inputs can be assigned to apply different actions to the same one switch function block.
In default configuration each input operates one function block. To change so that for example input 1 and 2 operates Switch[0] and inputs 3 and 4 operates
Switch[1] set UCPTdiAssignment to 0,0,1,1. When the 4 digital inputs has been assigned to a switch functional block, the operation or action
that the digital input will have is selected through the SCPTdiSwitchAction configuration property. Initially each digital input will work in the mode SWA_DIM_UP_DOWN_OFF_ON_LEVEL.
Prolon Control Systems
Lonbox PSW5000 Users Manual Page 4
The following table documents the different configuration modes that a digital input can be used in.
SWA_ACTIVE_ON
Used for toggle switch types When input is active the configured on level is transmitted. When input is passive OFF = 0% 0 is transmitted
SWA_ACTIVE_OFF
Used for toggle switch types When input is active OFF = 0% 0 is transmitted. When input is passive, the configured on level is transmitted.
SWA_ON_LEVEL
When activated the configured on level is transmitted.
SWA_ON_LAST
When activated, the last known on level is transmitted.
SWA_OFF
When activated, OFF 0% 0 is transmitted
SWA_AUTO
When activated an invalid switch value is transmitted 127.5% -1, this is used to reset manual override of a light controller.
SWA_DIM_UP
When pressed and as long as the switch is held active the switch level is dimmed up using configured step value.
SWA_DIM_DOWN
When pressed and as long as the switch is held active the switch level is dimmed down using configured step value.
SWA_DIM_UP_ON_LEVEL
If clicked configured on level is transmitted. If held active the switch level is dimmed up using configured
step value.
SWA_DIM_UP_ON_LAST
If clicked the last known on level is transmitted. If held active the switch level is dimmed up using configured
step value.
SWA_DIM_DOWN_OFF
If clicked, OFF 0% 0 is transmitted If held active the switch level is dimmed down using configured
step value.
SWA_DIM_UP_DOWN_OFF_ON_LEVEL
If clicked either OFF 0% 0 or configured on level is transmitted. If held active the switch level is dimmed up or down using configured step value.
SWA_DIM_UP_DOWN_OFF_ON_LAST
If clicked either OFF 0% 0 or last known on level is transmitted. If held active the switch level is dimmed up or down using configured step value.
SWA_TOGGLE
Toggles the switch level transmitted between off and configured on level.
SWA_SETTING_ON
When activated sends SET_ON with a setting level as configured in on level and a rotation of 0 (zero)
SWA_SETTING_OFF
When activated sends SET_OFF with a setting level as
Prolon Control Systems
Lonbox PSW5000 Users Manual Page 5
configured in on level and a rotation of 0 (zero)
SWA_SETTING_UP
If clicked sends a SET_UP with a level of 100%. When held sends SET_UP with a setting level as configured in on level and a rotation of 0 (zero). When released after being held sends SET_STOP.
SWA_SETTING_DOWN
If clicked sends a SET_DOWN with a level of 100%. When held sends SET_DOWN with a setting level as configured in on level and a rotation of 0 (zero). When released after being held sends SET_STOP.
SWA_SETTING_ROTATE_INC
When activated sends SET_DOWN with a setting level of 0 (zero) and a rotation level as configured in step value.
SWA_SETTING_ROTATE_DEC
When activated sends SET_UP with a setting level of 0 (zero) and a rotation level as configured in step value.
SWA_SETTING_STOP
When activated sends SET_STOP.
SWA_SETTING_NUL
When activated sends SET_NUL.
SWA_SETTING_OFF_ON
When input is activated SET_OFF is transmitted. When input is passivized SET_ON 100% is transmitted
SWA_SETTING_ON_SWITCH_UP
If clicked SET_ON is transmitted on the setting output. If held switch level is dimmed up with the configured step value.
SWA_SETTING_OFF_SWITCH_DOWN
If clicked SET_OFF is transmitted on the setting output. If held switch level is dimmed down with the configured step value.
SWA_SETTING_ON_OFF_SWITH_DIM
If clicked SET_ON or SET_OFF is transmitted. If held the switch level is dimmed up or down. When switch is
released the direction is changed.
SWA_SETTING_ON_UP
When clicked SET_ON is transmitted on the setting output. When held SET_UP is transmitted with setting value from
configured step value. When released SET_STOP is transmitted.
SWA_SETTING_OFF_DOWN
When clicked SET_OFF is transmitted on the setting output. When held SET_DOWN is transmitted with setting value from
configured step value. When released SET_STOP is transmitted.
Prolon Control Systems
Lonbox PSW5000 Users Manual Page 6
Functional Blocks
Node Object
Function block name: “Node” LonMark object type: 0 Number of blocks in device: 1 Principal network variable: nvoStatus (SNVT_obj_status)
Network Variables
nviRequest
LonMark network variable type name: SNVT_obj_request LonMark network variable type id: 92
nvoStatus
LonMark network variable type name: SNVT_obj_status LonMark network variable type id: 93
Configuration Properties
Major Device Version
LonMark configuration property type: 165 LonMark configuration property name: SCPTdevMajVer
As defined by the LonMark standard this constant configuration property defines the major version number of the device.
Devices with same major version number will have identical network interface. This means that if any changes are made to the device network interface, the major version number will be incremented.
Minor Device Version
LonMark configuration property type: 166 LonMark configuration property name: SCPTdevMinVer
As defined by the LonMark standard this constant configuration property defines the minor version number for the device.
Digital Input Assignment
LonMark configuration property type: 167 LonMark configuration property name: UCPTdiAssignment
Default value: 1,2,3,4,(5,6)
Digital Input Switch Action
LonMark configuration property type: 168 LonMark configuration property name: SCPTdiSwitchAction
Default value: SWA_DIM_UP_DOWN_OFF_ON_LEVEL
Prolon Control Systems
Lonbox PSW5000 Users Manual Page 7
Switch
Function block name: Switch LonMark object type: 3200 LonMark object name: SFPTswitch Number of blocks in device: 4-6 Principal network variable: nvoSwitch (SNVT_switch)
The switch function reflects the state of one or more connected switch button. Using the node object digital inputs can be assigned to the Switch function and the functionality can be configured.
The function or the switch object is described in detail in the configuration description.
Network Variables
nviSwitchFb
LonMark network variable type name: SNVT_switch LonMark network variable type id: 95
For correct dimming start point this feedback should be connected to the lamp actuator output. This will give information to the switch about lamp level when this is adjusted by another source, for example light controller or another manual switch. When a dimming sequence starts the initial output will be based on the last value received on the feedback or the last value that the switch has send.
nvoSwitch
LonMark network variable type name: SNVT_switch LonMark network variable type id: 95
The output will send the switch level when updated. See the configuration chapter for details on how the digital inputs will affect the switch output.
nvoSetting
LonMark network variable type name: SNVT_setting LonMark network variable type id: 117
The output will send the setting action and level when updated. See the configuration chapter for details on how the digital inputs will affect the setting output.
Configuration Properties
Step
LonMark configuration property type: 92 LonMark configuration property name: SCPTstep Applies to: Function Block
This configuration step size is used for dimming function of the switch. During dimming the step size is incremented or decremented on the output every 400 millisecond.
Default value: 2.5 %
Prolon Control Systems
Lonbox PSW5000 Users Manual Page 8
Maximum Ouput
LonMark configuration property type: 93 LonMark configuration property name: SCPTmaxOut Applies to: Function block
Default value: 100.0 %
Maximum Send Time
LonMark configuration property type: 49 LonMark configuration property name: UCPTturnOnLevel Applies to: Function block
Default value: 100.0 %.
Scene Panel
Function block name: “ScenePanel” LonMark object type: 3250 LonMark object name: SFPTscenePanel Number of blocks in device: 1 Principal network variable: nvoScene (SNVT_scene)
Network Variables
nvoScene
LonMark network variable type name: SNVT_scene LonMark network variable type id: 95
nviPreset
LonMark network variable type name: SNVT_preset LonMark network variable type id: 95
Configuration Properties
Switch scenes
LonMark configuration property type: 25 LonMark configuration property name: UCPTswitchScene Applies to: Function block
This configuration value is used to assign a scene number to each if the digital inputs on the switch interface. The value 0 (zero) will disable sending scene recall for a given input.
Default value: 1,2,3,4,(5,6)
Scene Controller
Function block name: SceneController LonMark object type: 20003 Number of blocks in device: 4-6 Principal network variable: nvoSceneValue (SNVT_switch)
Prolon Control Systems
Lonbox PSW5000 Users Manual Page 9
Network Variables
nviScene
LonMark network variable type name: SNVT_scene LonMark network variable type id: 115
nvoSceneValue
LonMark network variable type name: SNVT_switch LonMark network variable type id: 95
nviSetting
LonMark network variable type name: SNVT_setting LonMark network variable type id: 117
Configuration Properties
Scene Numbers
LonMark configuration property type: 10 LonMark configuration property name: UCPTsceneNumber Applies to: Function Block
The list of scene number that will trigger sending one of the values in the UCPTsceneValue list. The index of the scene number matches the index of the value, this means that it a scene recall is received for the scene number in UCPTsceneNumber table index 4 the matching value from the SCPTsceneValue table index 4 will be send.
Example: With the default configuration, if SC_RECALL 4 is received then the value 75% ON(1) will be transmitted on the output.
Default value: 1,2,3,4,5,6,7,8,9,10
Scene Values
LonMark configuration property type: 49 LonMark configuration property name: SCPTsceneValue Applies to: Function Block
The scene values defined for the scene numbers in the UCPTsceneNumber list. Default value: 0% OFF(0)
25% ON(1) 50% ON(1) 75% ON(1) 100% ON(1) 0% OFF(0) 0% OFF(0) 0% OFF (0) 0% OFF (0)
Prolon Control Systems
Lonbox PSW5000 Users Manual Page 10
Switch Connection Information
The following figures show the wire information for the different models available.
Mounting Instruction
The interface device is designed to be build directly together with a low voltage switch and LED indicator module. The input wires must not be extedended and the inputs and outputs should only be connected to switches or LED’s as shown below.
OBS: Activating switch 1&2 (DI1 + DI2) simultaneously will transmit a service-pin message to the network.
TP/FT-10
24 V d.c.
+
-
DI 1 DI 2 DI 3 DI 4
0 V
Svagstrømstryk
PSW5004
Figur 1 Lonbox PSW5004 - 4 indgange
+
-
DI 1 DI 2 DI 3 DI 4 DI 5 DI 6
0 V
Svagstrømstryk
PSW5006
TP/FT-10
24 V d.c.
Figur 2 Lonbox PSW5006 – 6 indgange
TP/FT-10
24 V d.c.
+
-
DI 1 DI 2 DI 3 DI 4
DO 1 DO 2
0 V
Svagstrømstryk
PSW5024
Figur 3 Lonbox PSW5024 - 4 indgange, 2 udgange
Prolon Control Systems
Lonbox PSW5000 Users Manual Page 11
+
-
DI 1 DI 2 DI 3 DI 4 DI 5
DI 6 DO 1 DO 2 DO 3
0 V
Svagstrømstryk
PSW5036
TP/FT-10
24 V d.c.
Figur 4 Lonbox PSW5036 - 6 indgange, 3 udgange
+
-
DI 1
DI 2
DI 3
DI 4
DO 1 DO 2 DO 3 DO 4
0 V
Svagstrømstryk
PSW5044
TP/FT-10
24 V d.c.
Figur 5 Lonbox PSW5044 - 4 indgange, 4 udgange
Prolon Control Systems
Lonbox PSW5000 Users Manual Page 12
Technical Data
Models
Interface
LonWorks 2.0
TP/FT-10 (bus eller fri)
Processor type
FT5000
Forsyning
24 V d.c.
Forbrug
Norm 15 mA @ 24 V d.c. Max. 25 mA @ 24 V d.c. (uden udgange)
Størrelse
32 * 35 * 15 mm
Kapslingsklasse
IP20
Drifttemperatur
-10 til 55 C
Opbevaringstemperatur
-20 til 70 C
Tilslutninger forsyning og bus
4 x 0.33
Tilslutning af svagstrømstryk
5..11 x 0.33
Indgange
Kontaktspænding
3,3 V d.c.
Pull-up
1 kOhm
Indgangsimpedans
10 kOhm
Strøm ved sluttet kontakt
3,3 mA
Udgange
Spænding
24 V d.c.
Max strøm
10 mA (240 mW)
Model / varenumre
EAN / GTIN koder
Lonbox PSW5004 4-in
5711536000383
Lonbox PSW5006 6-in
5711536000390
Lonbox PSW5024 2-out 4-in
5711536000406
Lonbox PSW5036 3-out 6-in
5711536000413
Lonbox PSW5044 4-out 4-in
5711536000420