ProFlow PF-SOF1-SIM, PF-SOF1, 5-SIM, PF-SOF1-PRL, 5-PRL Technical Manual

...
© 2017 erie water treatment TM-EN-PF-SOF-Rev2017.01
Technical Manual
WATER SOFTENER
PF-SOF1-SIM
PF-SOF1-ALT
PF-SOF1-PRL
PF-SOF1,5-SIM
PF-SOF1,5-ALT
PF-SOF1,5-PRL
PF-BTA
TABLE OF CONTENT & INSTALLATION RECORD
Page 2
Table of content & Installation record ..................................................................................... Page 2
Warning & Safety instructions ................................................................................................. Page 3
Operating conditions & Requirements .................................................................................... Page 4
Assembly .................................................................................................................................. Page 5
Installation ............................................................................................................................... Page 7
Commissioning ......................................................................................................................... Page 9
Electronic control panel ........................................................................................................... Page 10
Maintenance ............................................................................................................................ Page 16
Troubleshooting ....................................................................................................................... Page 18
Electrical wiring diagrams ........................................................................................................ Page 20
Default configuration parameter settings - PF-SOF1 ............................................................... Page 21
Default configuration parameter settings - PF-SOF1,5 ............................................................ Page 22
Composition overview ............................................................................................................. Page 23
Exploded view - PF-SOF1-SIM .................................................................................................. Page 24
Exploded view - PF-SOF1-ALT & PF-SOF1-PRL ......................................................................... Page 26
Exploded view - PF-SOF1 - Timer assembly ............................................................................. Page 28
Exploded view - PF-SOF1 - Valve body ..................................................................................... Page 30
Exploded view - PF-SOF1,5-SIM ............................................................................................... Page 32
Exploded view - PF-SOF1,5-ALT & PF-SOF1,5-PRL ................................................................... Page 34
Exploded view - PF-SOF1,5 - Timer assembly .......................................................................... Page 36
Exploded view - PF-SOF1,5 - Valve body .................................................................................. Page 38
Exploded view - PF-SOF1,5 - Piston assembly.......................................................................... Page 40
Exploded view - PF-BTA-Simplex .............................................................................................. Page 42
Exploded view - PF-BTA-Duplex ............................................................................................... Page 43
Technical data - PF-SOF1 .......................................................................................................... Page 44
Technical data - PF-SOF1,5 ....................................................................................................... Page 46
Technical data - PF-BTA ............................................................................................................ Page 48
WARNING & SAFETY INSTRUCTIONS
Page 3
Before you begin the installation of the appliance, we advise you read
and carefully follow the instructions contained in this manual. It contains important information about safety, installation, use and maintenance of the product. The actual system that you have received, may differ from the pictures/illustrations/descriptions in these Instructions.
Failure to follow the instructions could cause personal injury or damage
to the appliance or property. Only when installed, commissioned and serviced correctly, the appliance will offer you many years of trouble-free operation.
The appliance is intended to 'soften' the water, meaning it will remove
hardness minerals; it will not necessarily remove other contaminants present in the water. The appliance will not purify polluted water or make it safe to drink!
Installation of the appliance should only be undertaken by a competent
person, aware of the local codes in force. All plumbing and electrical connections must be done in accordance with local codes.
Before setting up the appliance, make sure to check it for any externally
visible damage; do not install or use when damaged.
Use a hand truck to transport the appliance. To prevent accident or
injury, do not hoist the appliance over your shoulder. Do not lay the appliance on its side.
Keep these Instructions in a safe place and ensure that new users are
familiar with the content.
The appliance is designed and manufactured in accordance with current
safety requirements and regulations. Incorrect repairs can result in unforeseen danger for the user, for which the manufacturer cannot be held responsible. Therefore repairs should only be undertaken by a competent technician, familiar and trained for this product.
In respect of the environment, this appliance should be disposed of in
accordance with Waste Electrical and Electronic Equipment requirements. Refer to national/local laws and codes for correct recycling of this appliance.
OPERATING CONDITIONS & REQUIREMENTS
Page 4
OPERATING PRESSURE MIN-MAX: 1,4-8,0 bar / 20-116 psi
this appliance is configured to perform optimally at an
operating pressure of 3 bar (45 psi) ±½ bar (7 psi); in case of a lower or higher operating pressure the performance may be affected negatively!
check water pressure regularly; it may fluctuate severely
depending on the time of day, the day of the week or even the season of the year.
take into account that night time water pressure may be
considerably higher than day time water pressure.
install a pressure reducer ahead of the appliance if necessary. install a pressure booster, if it is likely that water pressure may
drop below the minimum.
OPERATING TEMPERATURE MIN-MAX: 2-48 °C / 35-120 °F
do not install the appliance in an environment where high
ambient temperatures (e.g. unvented boiler house) or freezing temperatures can occur.
the appliance cannot be exposed to outdoor elements, such as
direct sunlight or atmospheric precipitation.
do not install the appliance too close to a water heater; keep at
least 3 m (10 ft) of piping between the outlet of the appliance and the inlet of the water heater; water heaters can sometimes transmit heat back down the cold pipe into the appliance; always install a check valve at the outlet of the appliance.
ELECTRICAL CONNECTION:
this appliance only works on 24 VAC; always use it in
combination with the supplied transformer.
in case of damage to the power supply cable of the transformer,
immediately disconnect the transformer from the power outlet and replace the transformer.
make sure to plug the transformer into a power outlet, which is
installed in a dry location, with the proper rating and over­current protection.
ASSEMBLY
Page 5
CONTENT CHECK
Actual parts that you have received, may differ from the
pictures/illustrations in these Instructions!
For ease of transportation and installation, the softening
resin is NOT loaded in the pressure tank, but delivered in separate bags of 25 ltr; it must be loaded on-site, after positioning of the pressure tank.
Check the content of the system, using the Composition Overview in these Instructions. Identify and lay-out the different components to facilitate the assembly.
SIMPLEX
(PF-SOF1-SIM & PF-SOF1,5-SIM)
A Simplex system consists of 1 single softening module (pressure tank, resin, control valve and accessories).
During normal operation, the Simplex system delivers softened water. As soon as it initiates a regeneration, it
automatically goes into hard water bypass, guaranteeing uninterrupted supply of untreated water
It is possible to upgrade a Simplex system to a Duplex Parallel system, by adding a second Simplex system.
DUPLEX ALTERNATING
(PF-SOF1-ALT & PF-SOF1,5-ALT)
A Duplex ALTERNATING system consists of 2 Simplex systems, that:
- are hydraulically installed in parallel;
- are electronically interconnected by means of an
InterConnect cable;
- have a Normally Closed solenoid operated diaphragm
valve (so called Service Valve) in the outlet of each Simplex system; this Service Valve is controlled by the electronic timer of the Simplex system and is activated during the service cycle to open the outlet of the respective Simplex system;
- share 1 brine tank, that contains 2 brine valves.
During normal operation, only 1 of the 2 Simplex systems is in service, while the other one is regenerating or ‘in
standby’! As soon as the first Simplex system initiates a regeneration, the second system goes into service, guaranteeing uninterrupted supply of treated water. In case of a power failure, both Service Valves will be deactivated, meaning the outlet of both Simplex systems will be closed off, cutting off the water supply (potentially hard water!) to the application.
DUPLEX PARALLEL
(PF-SOF1-PRL & PF-SOF1,5-PRL)
A Duplex PARALLEL system consists of 2 Simplex systems, that:
- are hydraulically installed in parallel;
- are electronically interconnected by means of an
InterConnect cable;
- have a Normally Open solenoid operated diaphragm valve
(so called Service Valve) in the outlet of each Simplex system; this Service Valve is controlled by the electronic
timer of the Simplex system and is activated during the entire duration of the regeneration, to close-off the control valve's standard 'hard water bypass during regeneration';
- share 1 brine tank, that contains 2 brine valves.
During normal operation, both Simplex systems are in service, doubling the service flow rate! When one of the
Simplex systems initiates a regeneration, it immediately communicates it's status to the other Simplex system via the InterConnect cable, to make sure the other Simplex system remains in service, guaranteeing uninterrupted supply of treated water. In case of a power failure, both Service Valves will be deactivated, meaning the outlet of both Simplex systems will be open, guaranteeing uninterrupted supply of water.
For correct assembly, repeat the different assembly steps, until both Simplex systems are assembled and positioned correctly.
For large installations, with an important need for treated water, 2 or more Duplex systems can easily be installed in parallel hydraulically, to double/triple/... the flow rate and softening capacity.
RESIN LOADING
1. Move the pressure tank to the correct installation
location; position it on a flat and level surface. Make sure to leave enough space for ease of service.
2. Position the riser assembly upright and centred in the
pressure tank; plug the top of the riser tube with a piece of tape or clean rag, to prevent resin from entering the tube.
3. Add water to the pressure tank to a height of ±30 cm from
the bottom; this water will protect the bottom of the pressure tank and the bottom distributor, during filling of the pressure tank.
4. Place a funnel on the pressure tank opening and fill the
pressure tank with resin; make sure the riser assembly remains centered in the pressure tank.
5. Rinse the pressure tank opening to remove any resin
beads from the threaded section.
6. Unplug the top of the riser tube.
CONTROL VALVE
only for PF-SOF1
1. Make sure the O-ring in the riser insert and the tank O-
ring (around the threaded section of the control valve) are in the correct position.
2. Screw the top distributor onto the control valve.
3. Lubricate the threaded section of the pressure tank, the
top of the riser tube and the tank O-ring of the control valve; use a silicon-based lubricant.
4. Lower the control valve straight down onto the riser tube,
until the riser tube is correctly inserted in the riser insert; then push it down firmly and screw it onto the pressure tank.
ASSEMBLY
Page 6
only for PF-SOF1,5
Picture 1
1. On the brass valve seat: make sure the O-ring in the riser insert is in the correct
position;
install the top distributor and fix it by means of the 2
stainless steel screws;
install the tank O-ring in the groove on the flange
around the threaded section.
2. Lubricate the threaded section of the pressure tank, the top of the riser tube and the tank O-ring of the valve seat; use a silicon-based lubricant.
3. Lower the valve seat straight down onto the riser tube, until the riser tube is correctly inserted in the riser insert inside the valve seat; then push it down firmly and screw it onto the pressure tank.
4. Install the valve seat O-ring in the groove on the valve seat.
5. Install the control valve onto the valve seat; mind the alignment pin!
6. Bolt the control valve to the valve seat by means of the 4 stainless steel bolts; tighten firmly.
BRINE TANK ASSEMBLY (PF-BTA) (optional)
Picture 2&3
1. Move the brine tank to the correct installation location; position it on a flat and level surface. Make sure to leave enough space for ease of service.
2. Insert the polytube into the brine line connection on the control valve (); make sure to push the polytube in all the way; tighten the nut.
3. Remove the lid from the brine tank.
4. Remove the lid from the brine well.
5. Make sure the correct elbow connection is installed on the brine valve (⅜” for PF-SOF1 or ½” for PF-SOF1,5); replace if necessary.
6. Run the polytube from the control valve through the hole in the sidewall of the brine tank, to the inside of the brine tank.
7. Only for PF-SOF1,5: insert the reinforcement tube in the end of the ½” polytube.
8. Insert the polytube into the elbow connection on the brine valve; make sure to push the polytube in all the way.
9. Only for PF-SOF1,5: tighten the nut.
10. Install the lid on the brine well.
11. Add water to the brine tank to a height of ±10 cm from the bottom.
12. Add salt to the brine tank.
13. Install the lid on the brine tank.
INSTALLATION
Page 7
INLET & OUTLET
In case of high concentration of impurities in the inlet
water, we recommend the installation of a sediment filter, ahead of the appliance.
We strongly recommend the use of flexible hoses to
connect the appliance to the water distribution system; use hoses with a large diameter in order to limit the pressure loss.
We strongly recommend the installation of a bypass
system (not included with this product!) to isolate the appliance from the water distribution system in case of repairs. It allows to turn off the water to the appliance, while maintaining full-flow (untreated) water supply to the user.
only for PF-SOF1-SIM:
SIMPLEX with factory bypass (optional)
Picture 4
= mains water supply (untreated water) = inlet of control valve (untreated water) = outlet of control valve (treated water) = application (treated water)
1. Screw the factory bypass onto the in/out ports on the control valve (&); make sure to install the gasket seals. Tighten the nuts firmly by hand.
2. Screw the connection kit with nuts onto the factory bypass (&); make sure to install the gasket seals. Tighten the nuts firmly by hand.
3. Connect the mains water supply to the adaptor on the inlet port of the factory bypass ().
4. Connect the application to the adaptor on the outlet port of the factory bypass ().
only for PF-SOF1-SIM:
SIMPLEX with 3-valve connection kit (not included)
Picture 5
= inlet of control valve (untreated water) = outlet of control valve (treated water)
1. Install the 3-valve connection kit.
2. Screw the connection kit with nuts onto the in/out ports on the control valve (&); make sure to install the gasket seals. Tighten the nuts firmly by hand.
3. Connect the IN valve of the 3-valve connection kit to the adaptor on the in port of the control valve ().
4. Connect the OUT valve of the 3-valve connection kit to the adaptor on the out port of the control valve ().
5. Connect the mains water supply to the inlet of the 3-valve connection kit.
6. Connect the application to the outlet of the 3-valve connection kit.
only for PF-SOF1-ALT and PF-SOF1-PRL:
DUPLEX with multiple valve connection kit (not incl.)
Picture 6
= inlet of control valve (untreated water) = outlet of control valve (treated water) = Service Valve
1. Install the multiple valve connection kit.
2. Screw the connection kit with nuts onto the in/out ports
on the control valve (&); make sure to install the gasket seals. Tighten the nuts firmly by hand.
3. Screw the Service Valve () onto the adaptor at the out
port of the control valve (); make sure to respect the flow direction (see indication arrow on the bottom of the Service Valve); use an appropriate sealant.
4. Connect the IN valve of the multiple valve connection kit
to the adaptor on the in port of the control valve ().
5. Connect the OUT valve of the multiple valve connection
kit to the outlet of the Service Valve ().
6. Repeat steps 2-5 for both Simplex systems.
7. Connect the mains water supply to the inlet of the
multiple valve connection kit.
8. Connect the application to the outlet of the multiple valve
connection kit.
only for PF-SOF1,5-SIM:
SIMPLEX with 3-valve connection kit (not incl.)
Picture 7
= inlet of control valve (untreated water) = outlet of control valve (treated water) = PVC elbow = inlet of flow meter = outlet of flow meter
1. Install the 3-valve connection kit.
2. Insert the adaptors in the in/out ports on the control valve
(&); make sure not to damage the O-rings. Install the nuts and tighten them firmly by hand.
3. Screw the PVC elbow () onto the adaptor at the out port
of the control valve (); use an appropriate sealant.
4. Insert the adaptors in the in/out ports on the flow meter
(&); make sure not to damage the O-rings. Install the nuts and tighten them firmly by hand.
5. Screw the flow meter () into the PVC elbow (); make
sure to respect the flow direction (see indication arrow); use an appropriate sealant.
6. Connect the flow meter cable from the control valve to
the flow meter; secure it by means of the screw.
7. Connect the IN valve of the 3-valve connection kit to the
adaptor on the in port of the control valve ().
8. Connect the OUT valve of the 3-valve connection kit to the
adaptor on the out port of the flow meter ().
9. Connect the mains water supply to the inlet of the 3-valve
connection kit.
10. Connect the application to the outlet of the 3-valve
connection kit.
only for PF-SOF1,5-ALT and PF-SOF1,5-PRL:
DUPLEX with multiple valve connection kit (not incl.)
Picture 8
= inlet of control valve (untreated water) = outlet of control valve (treated water) = PVC elbow = inlet of flow meter = outlet of flow meter = Service Valve
1. Install the multiple valve connection kit.
2. Insert the adaptors in the in/out ports on the control valve
(&); make sure not to damage the O-rings. Install the nuts and tighten them firmly by hand.
INSTALLATION
Page 8
3. Screw the PVC elbow () onto the adaptor at the out port of the control valve (); use an appropriate sealant.
4. Insert the adaptors in the in/out ports on the flow meter (&); make sure not to damage the O-rings. Install the nuts and tighten them firmly by hand.
5. Screw the flow meter () into the PVC elbow (); make sure to respect the flow direction (see indication arrow); use an appropriate sealant.
6. Connect the flow meter cable from the control valve to the flow meter; secure it by means of the screw.
7. Screw the Service Valve () onto the adaptor on the out port of the flow meter (); make sure to respect the flow direction (see indication arrow on the bottom of the Service Valve); use an appropriate sealant.
8. Connect the IN valve of the multiple valve connection kit to the adaptor on the in port of the control valve ().
9. Connect the OUT valve of the multiple valve connection kit to the outlet of the Service Valve ().
10. Repeat steps 2-9 for both Simplex systems.
11. Connect the mains water supply to the inlet of the multiple valve connection kit.
12. Connect the application to the outlet of the multiple valve connection kit.
DRAIN
We recommend the use of a stand pipe with P-trap. To prevent backflow from the sewerage system into the
appliance, always install and use an air gap (drain adaptor with air gap included with PF-SOF1), to connect the drain hoses to the sewerage system.
Always use separate drain hoses for the control valve(s)
(discharge of rinse water) and the brine tank overflow.
Lay-out the drain hoses in such a way that pressure loss
is minimized; avoid kinks and unnecessary elevations.
Make sure that the sewerage system is suitable for the
rinse water flow rate of the appliance.
only for PF-SOF1
Picture 9
1. Install the drain adaptor to the sewerage system; it fits over a 32 mm pipe or inside a 40 mm pipe adaptor. Ensure a permanent and watertight connection.
2. Connect a 13 mm hose to the drain connection of the control valve (); secure it by means of a clamp.
3. Run the drain hose to the drain adaptor and connect it to one of the hose barbs; secure it by means of a clamp. This drain line operates under pressure, so it may be installed higher than the appliance.
4. For Duplex: repeat steps 1-3 for both Simplex systems.
only for PF-SOF1,5
Picture 10
1. Connect a pipe to the 1” BSP Male drain connection of the control valve (); use an appropriate sealant.
2. Run the pipe to the sewerage system and connect it, ensuring sufficient air gap between the end of the pipe and the sewerage system. This drain line operates under pressure, so it may be installed higher than the appliance.
3. For Duplex: repeat steps 1-2 for both Simplex systems.
PF-BTA: brine tank assembly (optional)
1. Install the air gap to the sewerage system; it fits over a
32 mm pipe or inside a 40 mm pipe adaptor. Ensure a permanent and watertight connection.
2. Connect a 13 mm hose to the overflow elbow on the brine
tank; secure it by means of a clamp.
3. Run the drain hose to the air gap and connect it to one of
the hose barbs; secure it by means of a clamp. This drain line does NOT operate under pressure, so it may NOT be installed higher than the brine tank.
SERVICE VALVES
(only for Duplex)
Picture 11
1. Plug the DIN plug on the connection cable of the Service
Valve into the DIN socket at the back of the electronic timer head of the respective control valve ().
COMMISSIONING
Page 9
ELECTRICAL
1. Connect the appliances power cord to the transformers output.
2. Plug the transformer into an electrical outlet.
PRESSURIZING
1. Put the bypass system in 'bypass' position.
2. Make sure the electronic controller(s) of the appliance is (are) in service mode.
3. Open the mains water supply.
4. Open a cold treated water faucet nearby the appliance and let the water run for a few minutes until all air is purged and all foreign material that may have resulted from the installation is washed out; close the tap.
5. Gently pressurize the appliance, by putting it into service:
close the 'BYPASS' valve; open the 'OUT' valve; slowly open the 'IN' valve.
6. After 2-3 minutes, open a cold treated water faucet nearby the appliance and let the water run for a few minutes until all air is purged from the installation and the resin bed is rinsed (it is normal for the rinse water to show some discoloration!); close the tap.
7. Check the appliance and all hydraulic connections for leaks.
8. For Duplex: repeat steps 5-7 for both Simplex systems.
ELECTRONIC CONTROL PANEL
1. Program the electronic controller.
2. For Duplex: repeat step 1 for both Simplex systems.
ADJUSTMENT RESIDUAL HARDNESS
(only for PF-SOF1)
In practice the residual hardness is influenced by the
inlet pressure, flow rate and hardness of the incoming untreated water. When adjusting the residual hardness, make sure these conditions are similar to the actual operating conditions.
ON CONTROL VALVE
Picture 12.a
1. Adjust the residual hardness of the water that leaves the softener, by means of the adjusting screw, incorporated at the right side of the control valve: to raise the residual hardness: turn the screw counter
clockwise;
to reduce the residual hardness: turn the screw
clockwise.
2. Measure the residual water hardness with a water hardness test kit; readjust if necessary.
WITH FACTORY BYPASS (optional)
Picture 12.b
1. Adjust the residual hardness of the water that leaves the softener, by means of the adjusting screw, incorporated in the 'outlet' valve of the factory bypass:
to raise the residual hardness: turn the screw counter
clockwise.
to reduce the residual hardness: turn the screw
clockwise.
2. Measure the residual water hardness with a water
hardness test kit; readjust if necessary.
INITIATE A REGENERATION
1. Manually initiate a regeneration, by pressing the scroll
button; the display will show:
2. Leave the appliance in this position; the count-down
timer will count down to 0 sec and start a regeneration; to save time you may skip, or terminate prematurely, the second cycle of the regeneration by pressing the scroll  button once, as soon as the display indicates that the system is in the second regeneration position.
3. For Duplex: repeat steps 1-2 for both Simplex systems.
INTERCONNECT CABLE
(only for Duplex)
Picture 13
1. Connect the control valves to each other by means of the
InterConnect cable; simply plug the DIN plugs on the InterConnect cable in the DIN sockets at the back of the electronic timer of each control valve ().
INITIATE ALTERNATING MODE
(only for Duplex Alternating)
1. On one of the 2 control valves, manually initiate a
regeneration, by pressing the scroll  button; the display will show:
2. Leave the appliance in this position; the count-down
timer will count down to 0 sec and start a regeneration.
3. Press the scroll
button repeatedly, to advance the control valve through the regeneration cycles and put it in Standby mode, until the display shows:
Regen in 10 sec
Regen in 10 sec
Stdby 1000 L -
ELECTRONIC CONTROL PANEL
Page 10
Picture 14
symbol
button
function
SCROLL
to advance to the next
parameter
UP
to increase the value of the
parameter
DOWN
to decrease the value of the
parameter
POWER-UP
After power-up the display will show the installed software version for a period of 5 seconds.
POWER FAILURE
In the event of a power failure, the program will remain stored in the NOVRAM® during an undefined period, while an incorporated SuperCap will maintain the correct time of day during a period of several hours; consequently, in case of prolonged power failure, the time of day might not be maintained; if this happens, the time of day will be reset to 8:00 when the power supply is re-established, while the indication will flash, indicating that the time of day needs to be set.
When the power failure occurs during the execution of an automatic regeneration, the control valve will remain in its last position; when the power supply is re-established, the control valve will return to the service position, stay there for 60 sec. and restart a complete regeneration from the beginning.
TIMER FAILURE
In the event of a timer failure, the display will show the message:
If powering off/on the appliance doesn’t solve this problem, professional service is required.
MAINTENANCE REMINDER
Once the maintenance interval is reached, the display will intermittently show the message:
While the appliance will continue to operate normally, it is recommended to have preventive maintenance performed by a professional.
SERVICE MODE
In service mode the display shows:
Simplex, Duplex Parallel: the time of day and the
remaining capacity:
Duplex Alternating: the systems status (Service or
Standby) and the remaining capacity:
REGENERATION MODE
In regeneration mode the display shows: Simplex, Duplex Parallel: the total remaining
regeneration time and remaining cycle time:
Duplex Alternating: the total remaining regeneration
time and remaining cycle time:
When the regeneration is finished, the system remains in Standby, until the other system starts a regeneration:
The control valve can be reset to service mode at any time by pressing the scroll  button, as such manually advancing it through the regeneration cycles.
CHECKING THE FLOW METER
In case of water usage, the remaining capacity counter in the service display will count back. This way the correct functioning of the water meter can be verified.
MANUAL REGENERATION
It is possible to manually initiate an immediate regeneration or a delayed regeneration (at the preprogrammed time of regeneration).
1. Press the scroll
button; the display will show:
If the control panel is left in this position, the
countdown timer will countdown to 0 sec and start an immediate regeneration.
To cancel this mode, press the scroll
button before the countdown timer has reached 0 sec; the display will show:
If the control panel is left in this position, a delayed
regeneration will be started at the indicated
preprogrammed time of regeneration.
To cancel this mode, press the scroll
button; the
control panel will return to the service mode.
Service Required
Rgn:123 CycY:456
8:01 1000L -
Srvc 1000L -
Stdby 1000L -
Rgn:123 CycY:456
Stdby 1000L -
Maintenance Now
Regen in 10 sec
Regen @ 2:00
ELECTRONIC CONTROL PANEL
Page 11
HOLIDAY MODE
It is possible to put the appliance in holiday mode; this will prevent automatic regeneration from taking place, yet will ensure the appliance is automatically regenerated at the end of the holiday cycle.
1. Press the scroll
button repeatedly until the display
shows:
Press the up
or down button to activate the
holiday mode by setting the number of full days away from home, or deactivate the holiday mode (OFF).
Once the control panel is back in service mode, the display
will show:
The holiday mode is automatically cancelled when a
regeneration is manually initiated!
PROGRAMMING INSTRUCTIONS -
BASIC SETTINGS
Before entering the programming mode, make sure that
the appliance is in the service mode.
In case no button is pressed in a period of 5 min, the
control panel will automatically return to the service mode; any changes made will NOT be saved!
1. Press the scroll
button and hold it for 2 sec until the
display shows:
Press the up
or down  button to set the
language.
2. Press the scroll
button again; the display will show
(does not apply to Duplex Alternating!):
Press the up
or down  button to set the time of
day.
3. Press the scroll
button again; the display will show:
Press the up
or down  button to set the unit of measure for water hardness. Make sure it is identical to the unit of measure of the water hardness test kit or water analysis report that is used to determine the hardness of the incoming untreated water!
4. Press the scroll
button again; the display will show:
Press the up
or down button to set the hardness
of the incoming untreated water.
5. Press the scroll
button again; the display will show:
Press the up
or down  button to save the settings
into the NOVRAM® and exit the programming mode.
Holiday: OFF
8:01 Holiday
Language:English
Set time: 8:01
Set Hardn: XX °f
HardUnit: °f
Exit
ELECTRONIC CONTROL PANEL
Page 12
PROGRAMMING INSTRUCTIONS -
CONFIGURATION PARAMETERS
Before entering the programming mode, make sure that
the appliance is in the service mode.
All configuration parameters on this appliance have
been pre-programmed in the factory, to offer optimal performance in a wide range of applications and situations. Nevertheless it may be necessary or desirable to change any of these parameters, to further optimize the appliances performance or to adapt it to the specific requirements of the installation. See table at the end of this manual for default configuration parameter settings.
In case no button is pressed in a period of 5 min, the
control panel will automatically return to the service mode; any changes made will NOT be saved!
only for PF-SOF1-SIM & PF-SOF1,5-SIM
1. Press the scroll
button and hold it for 6 sec until the
display shows:
2. Within 10 sec, press the up
button; the display will
show:
Press the up
or down  button to set the units of
measure (Metric or US).
3. Press the scroll
button again; the display will show:
Press the up
or down button to activate the
maintenance reminder function by setting the maintenance interval, or deactivate the maintenance reminder function.
4. Press the scroll
button again; the display will show:
Press the up
or down  button to set the
exchange capacity per litre of resin.
5. Press the scroll
button again; the display will show:
Press the up
or down  button to set the age correction factor (%/year) to compensate for capacity loss of the resin due to aging.
6. Press the scroll
button again; the display will show:
Press the up
or down  button to set the volume
of resin.
7. Press the scroll
button again; the display will show:
Press the up
or down  button to set the number
of days between regenerations.
8. Press the scroll
button again; the display will show:
Press the up
or down  button to set the length
of the regeneration cycle.
Press the scroll
button again to advance to the next
regeneration cycle.
Cycle 1
Backwash
Cycle 2
Brine draw/slow rinse
Cycle 3
Fast rinse/brine tank refill (PF-SOF1) Fast rinse (PF-SOF1,5)
Cycle 4
Brine tank refill (PF-SOF1,5)
9. Press the scroll
button again; the display will show:
Press the up
or down  button to set the
regeneration mode: Dlyd/Immd: when the remaining capacity equals
the reserve capacity, a delayed regeneration at the programmed time of regeneration is started; however when the remaining capacity equals 0 before the programmed time of regeneration is reached, an immediate regeneration is started.
Immediate: when the remaining capacity equals
0, an immediate regeneration is started.
Note: Delayed manual regeneration is not available when this regeneration mode is selected.
Delayed: when the remaining capacity equals the
reserve capacity, a delayed regeneration at the programmed time of regeneration is started.
10. Press the scroll
button again; the display will show
(only when the regeneration mode is set to ‘Delayed’ or ‘Dlyd/Immd’):
Press the up
or down  button to set the time of
regeneration.
11. Press the scroll
button again; the display will show
(only when the regeneration mode is set to ‘Dlyd’ or ‘Dlyd/Immd’):
Press the up
or down  button to set the reserve
capacity: Variable: the reserve capacity is calculated
automatically, based on the registered daily water usage.
Fxd: press the scroll
button again and press the
up  or down button to set the reserve capacity to a fixed amount.
Cycle 1: XX min
System Check
Regen @ 2:00
Resin:XXX liters
ExCap:5.5°f M3/L
Override: 7 days
Regen:Dlyd/Immd
Rsrv Variable
Units:Metric
MaintInt: 24mths
Age corr.: 2.0%
ELECTRONIC CONTROL PANEL
Page 13
12. Press the scroll
button again; the display will show:
Press the up
or down  button to save the program into the NOVRAM® and exit the programming level.
only for PF-SOF1-ALT & PF-SOF1,5-ALT
The 2 Simplex systems, that make up a Duplex system,
must be programmed individually; the program does NOT necessarily have to be the same on the 2 Simplex systems!
1. Press the scroll
button and hold it for 6 sec until the
display shows:
2. Within 10 sec, press the up
button; the display will
show:
Press the up
or down  button to set the units of
measure (Metric or US).
3. Press the scroll
button again; the display will show:
Press the up
or down button to activate the
maintenance reminder function by setting the maintenance interval, or deactivate the maintenance reminder function.
4. Press the scroll
button again; the display will show:
Press the up
or down  button to set the
exchange capacity per litre of resin.
5. Press the scroll
button again; the display will show:
Press the up
or down  button to set the age correction factor (%/year) to compensate for capacity loss of the resin due to aging.
6. Press the scroll
button again; the display will show:
Press the up
or down  button to set the volume
of resin.
7. Press the scroll
button again; the display will show:
Press the up
or down  button to set the number
of days between regenerations.
8. Press the scroll
button again; the display will show:
Press the up
or down  button to set the length
of the regeneration cycle.
Press the scroll
button again to advance to the next
regeneration cycle.
Exit
Cycle 1: XX min
System Check
Resin:XXX liters
ExCap:5.5°f M3/L
Units:Metric
MaintInt: 24mths
Age corr.: 2.0%
Override: 7 days
ELECTRONIC CONTROL PANEL
Page 14
Cycle 1
Backwash
Cycle 2
Brine draw/slow rinse
Cycle 3
Fast rinse/brine tank refill (PF-SOF1) Fast rinse (PF-SOF1,5)
Cycle 4
Brine tank refill (PF-SOF1,5)
9. Press the scroll
button again; the display will show:
Press the up
or down  button to save the program into the NOVRAM® and exit the programming level.
10. Repeat steps 1-9 for both Simplex systems.
only for PF-SOF1-PRL & PF-SOF1,5-PRL
The 2 Simplex systems, that make up a Duplex system,
must be programmed individually; the program does NOT necessarily have to be the same on the 2 Simplex systems!
1. Press the scroll
button and hold it for 6 sec until the
display shows:
2. Within 10 sec, press the up
button; the display will
show:
Press the up
or down  button to set the units of
measure (Metric or US).
3. Press the scroll
button again; the display will show:
Press the up
or down button to activate the
maintenance reminder function by setting the maintenance interval, or deactivate the maintenance reminder function.
4. Press the scroll
button again; the display will show:
Press the up
or down  button to set the
exchange capacity per litre of resin.
5. Press the scroll
button again; the display will show:
Press the up
or down  button to set the age
correction factor (%/year) to compensate for capacity loss of the resin due to aging.
6. Press the scroll
button again; the display will show:
Press the up
or down  button to set the volume
of resin.
7. Press the scroll
button again; the display will show:
Press the up
or down  button to set the number
of days between regenerations.
8. Press the scroll
button again; the display will show:
Press the up
or down  button to set the length
of the regeneration cycle.
Press the scroll
button again to advance to the next
regeneration cycle.
Cycle 1: XX min
System Check
Resin:XXX liters
ExCap:5.5°f M3/L
Override: 7 days
Exit
Units:Metric
MaintInt: 24mths
Age corr.: 2.0%
ELECTRONIC CONTROL PANEL
Page 15
Cycle 1
Backwash
Cycle 2
Brine draw/slow rinse
Cycle 3
Fast rinse/brine tank refill (PF-SOF1) Fast rinse (PF-SOF1,5)
Cycle 4
Brine tank refill (PF-SOF1,5)
9. Press the scroll
button again; the display will show:
Press the up
or down  button to set the
regeneration mode: Immediate: when the remaining capacity equals
0, an immediate regeneration is started.
Note: Delayed manual regeneration is not available when this regeneration mode is selected.
Dlyd/Immd: when the remaining capacity equals
the reserve capacity, a delayed regeneration at the programmed time of regeneration is started; however when the remaining capacity equals 0 before the programmed time of regeneration is reached, an immediate regeneration is started.
Delayed: when the remaining capacity equals the
reserve capacity, a delayed regeneration at the programmed time of regeneration is started.
10. Press the scroll
button again; the display will show (only when the regeneration mode is set to Delayed or Dlyd/Immd):
Press the up
or down  button to set the time of
regeneration.
11. Press the scroll
button again; the display will show (only when the regeneration mode is set to Delayed or Dlyd/Immd):
Press the up
or down  button to set the reserve
capacity: Variable: the reserve capacity is calculated
automatically, based on the registered daily water usage.
Fxd: press the scroll
button again and press the
up  or down button to set the reserve capacity to a fixed amount.
12. Press the scroll
button again; the display will show:
Press the up
or down  button to save the program into the NOVRAM® and exit the programming level.
13. Repeat steps 1-12 for both Simplex systems.
DIAGNOSTICS MODE
In the Diagnostics mode several operating parameters
can be consulted; particularly during a service intervention, these parameters can be helpful to identify the cause of a problem or malfunction.
Before entering the Diagnostics mode, make sure that
the appliance is in service mode.
In case no button is pressed in a period of 5 min, the
control panel will automatically return to the service mode!
Accessing the Diagnostics mode
1. Press the scroll
button and hold it for 6 sec until the
display shows:
2. Within 10 sec, press the down
button; the display will
show:
You are now in the Diagnostics mode. Press the scroll
button to advance to the next
diagnostics parameter.
Available diagnostics parameters
Regen X days ago: number of days since last
regeneration.
In Srvc: total number of days in service. # of Regens: number of regenerations since installation. TotVol: total volume of treated water since installation. LastRgn@: consumed capacity at last regeneration. InstFlow: instantaneous flow rate through appliance. AvgVol: calculated average daily water usage. Capacity: calculated capacity between regenerations. Hardness: setting of water hardness. Rsrv: setting of reserve capacity. Regen @: setting of time of regeneration. Override: setting of number of days between
regenerations.
Cycle X: setting of length of corresponding regeneration
cycle.
Units: control is programmed for Metric units. MTR: setting of the water meter. Capacity: control is programmed for hardness setting. Regen: setting of the regeneration mode. Valve Type: setting of valve type. MP Resets: number of resets of the microprocessor. Memory Reset: number of corrupt memory start-ups. EZRSDg: software version. CapToUse: remaining capacity.
Exiting the Diagnostics mode
1. Press the scroll
button repeatedly until the display
shows:
Press the up
or down  button to exit the
Diagnostics mode.
Regen XXdays ago
System Check
Exit
Regen:Immediate
Rsrv Variable
Regen @ 2:00
Exit
MAINTENANCE
Page 16
RECOMMENDATION
Notwithstanding the reliability of the appliance, we strongly recommend to have it serviced and maintained on a regular basis by a competent and duly trained technician. He will be able to determine the appropriate maintenance interval for the appliance, depending on your specific application and the local operating conditions. The advantages of performing regular maintenance are: regular check of the local operating conditions (water
quality, pressure, etc);
regular control and adjustment of the settings of the
appliance, to guarantee it operates at maximum efficiency;
minimize the risk of unexpected break-down. Contact your dealer or installer for more information, or visit our website.
ROUTINE CHECKS
Regularly the user should perform a basic check to verify if the appliance is functioning correctly, on the basis of the following control points:
1. Check settings of electronic control panel.
2. Measure water hardness before/after appliance.
3. Check drain line from control valve; there shouldn’t be
any water flow (unless appliance is in regeneration).
4. Check drain line from brine tank overflow; there shouldn’t
be any water flow.
5. Check appliance and surrounding area; there shouldn’t be
any water leakages.
BYPASSING THE APPLIANCE
Occasionally it may be necessary to put the appliance hydraulically in bypass, i.e. to isolate it from the water distribution system; f.e.:
in case of an urgent technical problem; when it is not necessary to supply treated water to the
application.
WITH FACTORY BYPASS (optional) (only for PF-SOF1)
Picture 15.a
SERVICE POSITION
= inlet valve to appliance is OPEN = outlet valve from appliance is OPEN
Picture 15.b
BYPASS POSITION
= inlet valve to appliance is CLOSED = outlet valve from appliance is CLOSED
Picture 15.c
MAINTENANCE POSITION
= inlet valve to appliance is OPEN = outlet valve from appliance is CLOSED
WATER CONDITIONER SALT
This appliance needs 'brine' for its periodic regenerations. This brine solution is made from water, that is automatically dosed in the brine tank by the control valve, and water conditioner salt. The user should make sure that the brine tank is always kept full of water conditioner salt. Therefore he should periodically check the salt level inside the brine tank and refill it if necessary. Simply lift the brine tank cover to check the salt level inside the brine tank.
Ideally the level of water conditioner salt inside the brine tank is kept between 1/3 and 2/3. A lower level of water conditioner salt can cause insufficient brine saturation, resulting in a loss of softening capacity. A higher level of water conditioner salt can cause salt bridging (hard crust or salt bridges in the brine tank). When you suspect salt bridging: carefully pound on the outside of the brine tank to break
loose the salt bridges;
using a broom (or like blunt tool) carefully push the salt to
break it apart;
pour warm water over the top of the salt to dissolve it.
RESIN CLEANER
Other contaminants (f.e. iron) present in the feed water can cause the resin bed to foul up, resulting in a loss of softening capacity. An approved resin cleaner can be used periodically to thoroughly clean the resin bed.
SANITIZING THE APPLIANCE
This appliance is manufactured from premium quality material and assembled in safe conditions to assure it is clean and sanitary. If installed and serviced correctly, this appliance will not infect or contaminate your water supply. However, as in any 'device' plumbed-in in your water distribution system, a proliferation of bacteria is possible, especially in case of 'stagnant water'. Therefore this appliance is equipped with a 'days override' feature, that will automatically rinse the resin bed periodically, even in case of low or absence of water usage.
If the power supply to the appliance is disconnected for a longer period of time, we recommend, when the power supply is re-established, to manually initiate a complete regeneration.
NORMALLY CLOSED SERVICE VALVES
(only for PF-SOF1-ALT & PF-SOF1,5-ALT)
Picture 16
= automatically operated = normally closed = manually operated = constantly open
The Normally Closed Service Valve in the outlet of each Simplex system will only be opened when it is powered. To manually open the Normally Closed Service Valve (f.e. in case of a power failure), simply turn the white solenoid coil counter clockwise.
Loading...
+ 36 hidden pages