ProFlow PF-GAC1, PF-AG1, 5 Technical Manual

© 2017 erie water treatment TM-EN-PF-GAC_AG-Rev2017.01
Technical Manual
WATER FILTER
Models: PF-GAC1
PF-AG1 PF-GAC1,5 PF-AG1,5
TABLE OF CONTENT & INSTALLATION RECORD
Page 2
Table of content & Installation record ..................................................................................Page 2
Warning & Safety instructions ..............................................................................................Page 3
Operating conditions & Requirements .................................................................................Page 4
Assembly..............................................................................................................................Page 5
Installation ...........................................................................................................................Page 6
Commissioning .....................................................................................................................Page 7
Electronic control panel .......................................................................................................Page 8
Maintenance ........................................................................................................................Page 10
Troubleshooting ...................................................................................................................Page 11
Electrical wiring diagrams ....................................................................................................Page 12
Default configuration parameter settings.............................................................................Page 13
Composition overview .........................................................................................................Page 14
Exploded view - PF-GAC1 & PF-AG1 - System .......................................................................Page 16
Exploded view - PF-GAC1 & PF-AG1 - Timer assembly ..........................................................Page 18
Exploded view - PF-GAC1 & PF-AG1 - Valve body .................................................................Page 20
Exploded view - PF-GAC1,5 & PF-AG1,5 - System .................................................................Page 22
Exploded view - PF-GAC1,5 & PF-AG1,5 - Timer assembly ....................................................Page 24
Exploded view - PF-GAC1,5 & PF-AG1,5 - Valve body ...........................................................Page 26
Exploded view - PF-GAC1,5 & PF-AG1,5 - Piston assembly ....................................................Page 28
Technical data - PF-GAC1 & PF-AG1 .....................................................................................Page 30
Technical data - PF-GAC1,5 & PF-AG1,5 ................................................................................Page 31
WARNING & SAFETY INSTRUCTIONS
Page 3
Before you begin the installation of the appliance, we advise you read
and carefully follow the instructions contained in this manual. It contains important information about safety, installation, use and maintenance of the product. The actual system that you have received, may differ from the pictures/illustrations/descriptions in these Instructions.
Failure to follow the instructions could cause personal injury or damage
to the appliance or property. Only when installed, commissioned and serviced correctly, the appliance will offer you many years of trouble-free operation.
The appliance is intended to ‘filter’ the water, meaning it will remove
specific undesired substances; it will not necessarily remove other contaminants present in the water. The appliance will not purify polluted water or make it safe to drink!
Installation of the appliance should only be undertaken by a competent
person, aware of the local codes in force. All plumbing and electrical connections must be done in accordance with local codes.
Before setting up the appliance, make sure to check it for any externally
visible damage; do not install or use when damaged.
Use a hand truck to transport the appliance. To prevent accident or
injury, do not hoist the appliance over your shoulder. Do not lay the appliance on its side.
Keep these Instructions in a safe place and ensure that new users are
familiar with the content.
The appliance is designed and manufactured in accordance with current
safety requirements and regulations. Incorrect repairs can result in unforeseen danger for the user, for which the manufacturer cannot be held responsible. Therefore repairs should only be undertaken by a competent technician, familiar and trained for this product.
In respect of the environment, this appliance should be disposed of in
accordance with Waste Electrical and Electronic Equipment requirements. Refer to national/local laws and codes for correct recycling of this appliance.
OPERATING CONDITIONS & REQUIREMENTS
Page 4
OPERATING PRESSURE MIN-MAX: 2,5-8,0 bar / 36-116 psi
low operating pressure may lead to insufficient backwash of the
filter media, resulting in an increase in pressure drop and/or a reduction of the filtration capacity during the service cycle.
if installed on a well, verify that the well pump is powerful
enough to provide sufficient flow rate for the backwash cycle.
check water pressure regularly; it may fluctuate severely
depending on the time of day, the day of the week or even the season of the year.
take into account that night time water pressure may be
considerably higher than day time water pressure.
install a pressure reducer ahead of the appliance if necessary. install a pressure booster, if it is likely that water pressure may
drop below the minimum.
OPERATING TEMPERATURE MIN-MAX: 4-48 °C / 39-120 °F
do not install the appliance in an environment where high
ambient temperatures (e.g. unvented boiler house) or freezing temperatures can occur.
the appliance cannot be exposed to outdoor elements, such as
direct sunlight or atmospheric precipitation.
do not install the appliance too close to a water heater; keep at
least 3 m (10 ft) of piping between the outlet of the appliance and the inlet of the water heater; water heaters can sometimes transmit heat back down the cold pipe into the appliance; always install a check valve at the outlet of the appliance.
ELECTRICAL CONNECTION:
this appliance only works on 24 VAC; always use it in
combination with the supplied transformer.
in case of damage to the power supply cable of the transformer,
immediately disconnect the transformer from the power outlet and replace the transformer.
make sure to plug the transformer into a power outlet, which is
installed in a dry location, with the proper rating and over­current protection.
ASSEMBLY
Page 5
CONTENT CHECK
Actual parts that you have received, may differ from the
pictures/illustrations in these Instructions!
For ease of transportation and installation, the filter
media may NOT loaded in the pressure tank, but delivered in separate bags of 1 cuft; it must be loaded on-site, after positioning of the pressure tank.
Check the content of the system, using the Composition Overview in these Instructions. Identify and lay-out the different components to facilitate the assembly.
SIMPLEX
Picture 1.a, 2.a, 3.a
A Simplex system consists of 1 single filter module (pressure tank, filter media, control valve).
During normal operation, the system delivers treated water. As soon as it initiates a regeneration, it automatically goes into bypass, guaranteeing uninterrupted supply of untreated water.
It is possible to install a so called Normally Open Service Valve (e.g. a solenoid operated diaphragm valve) in the outlet of the system, that is controlled by the electronic timer of the system; this Service Valve will be activated during the entire duration of the regeneration, to close-off the control valve's standard 'untreated water bypass during regeneration'.
MULTIPLEX PARALLEL
Picture 4
A Multiplex PARALLEL system consists of 2 or more Simplex systems, that:
- are hydraulically installed in parallel;
- are programmed for different times of regeneration;
- may have a so called Normally Open Service Valve (e.g. a solenoid operated diaphragm valve) in the outlet of each Simplex system, that is controlled by the electronic timer of each Simplex system; this Service Valve will be activated during the entire duration of the regeneration, to close-off the control valve's standard 'untreated water bypass during regeneration'.
During normal operation, all Simplex systems are in service, doubling/tripling/… the service flow rate!
In case of a power failure, all Service Valves will be deactivated, meaning the outlet of all Simplex systems will be open, guaranteeing uninterrupted supply of water.
FILTER MEDIA LOADING
1. Move the pressure tank to the correct installation location; position it on a flat and level surface. Make sure to leave enough space for ease of service.
2. Position the riser assembly upright and centred in the pressure tank; plug the top of the riser tube with a piece of tape or clean rag, to prevent filter media from entering the tube.
3. Place a funnel on the pressure tank opening and fill the pressure tank with filter media; make sure the riser assembly remains centered in the pressure tank.
4. Rinse the pressure tank opening to remove any grains of filter media from the threaded section.
5. Unplug the top of the riser tube.
CONTROL VALVE
only for PF-GAC1 & PF-AG1
1. Make sure the O-ring in the riser insert and the tank O­ring (around the threaded section of the control valve) are in the correct position.
2. Screw the top distributor onto the control valve.
3. Lubricate the threaded section of the pressure tank, the top of the riser tube and the tank O-ring of the control valve; use a silicon-based lubricant.
4. Lower the control valve straight down onto the riser tube, until the riser tube is correctly inserted in the riser insert; then push it down firmly and screw it onto the pressure tank.
only for PF-GAC1,5 & PF-AG1,5
Picture 5
1. On the brass valve seat: make sure the O-ring in the riser insert is in the correct
position;
install the top distributor and fix it by means of the 2
stainless steel screws;
install the tank O-ring in the groove on the flange
around the threaded section.
2. Lubricate the threaded section of the pressure tank, the top of the riser tube and the tank O-ring of the valve seat; use a silicon-based lubricant.
3. Lower the valve seat straight down onto the riser tube, until the riser tube is correctly inserted in the riser insert inside the valve seat; then push it down firmly and screw it onto the pressure tank.
4. Install the valve seat O-ring in the groove on the valve seat.
5. Install the control valve onto the valve seat; mind the alignment pin!
5. Bolt the control valve to the valve seat by means of the 4 stainless steel bolts; tighten firmly.
INSTALLATION
Page 6
INLET & OUTLET
We strongly recommend the use of flexible hoses to
connect the appliance to the water distribution system; use hoses with a large diameter in order to limit the pressure loss.
We strongly recommend the installation of a bypass
system (not included with this product!) to isolate the appliance from the water distribution system in case of repairs. It allows to turn off the water to the appliance, while maintaining full-flow (untreated) water supply to the user.
only for PF-GAC1 & PF-AG1: with factory bypass (optional)
Picture 1
= mains water supply (untreated water) = inlet of control valve (untreated water) = outlet of control valve (treated water) = application (treated water)
1. Screw the factory bypass onto the in/out ports on the control valve (&); make sure to install the gasket seals. Tighten the nuts firmly by hand.
2. Screw the connection kit with nuts onto the factory bypass (&); make sure to install the gasket seals. Tighten the nuts firmly by hand.
3. Connect the mains water supply to the adaptor on the inlet port of the factory bypass ().
4. Connect the application to the adaptor on the outlet port of the factory bypass ().
only for PF-GAC1 & PF-AG1:
with 3-valve connection kit (not included)
Picture 2
= inlet of control valve (untreated water) = outlet of control valve (treated water)
1. Install the 3-valve connection kit.
2. Screw the connection kit with nuts onto the in/out ports on the control valve (&); make sure to install the gasket seals. Tighten the nuts firmly by hand.
3. Connect the IN valve of the 3-valve connection kit to the adaptor on the in port of the control valve ().
4. Connect the OUT valve of the 3-valve connection kit to the adaptor on the out port of the control valve ().
5. Connect the mains water supply to the inlet of the 3-valve connection kit.
6. Connect the application to the outlet of the 3-valve connection kit.
only for PF-GAC1,5 & PF-AG1,5:
with 3-valve connection kit (not incl.)
Picture 3
= inlet of control valve (untreated water) = outlet of control valve (treated water)
1. Install the 3-valve connection kit.
2. Insert the adaptors in the in/out ports on the control valve (&); make sure not to damage the O-rings. Install the nuts and tighten them firmly by hand.
3. Connect the IN valve of the 3-valve connection kit to the adaptor on the in port of the control valve ().
4. Connect the OUT valve of the 3-valve connection kit to the adaptor on the out port of the control valve ().
5. Connect the mains water supply to the inlet of the 3-valve connection kit.
6. Connect the application to the outlet of the 3-valve connection kit.
DRAIN
We recommend the use of a stand pipe with P-trap. To prevent backflow from the sewerage system into the
appliance, always install and use an air gap (drain adaptor with air gap included with PF-GAC1 & PF-AG1), to connect the drain hose to the sewerage system.
Lay-out the drain hose in such a way that pressure loss
is minimized; avoid kinks and unnecessary elevations.
Make sure that the sewerage system is suitable for the
rinse water flow rate of the appliance.
only for PF-GAC1 & PF-AG1
Picture 6
1. Install the drain adaptor to the sewerage system; it fits over a 32 mm pipe or inside a 40 mm pipe adaptor. Ensure a permanent and watertight connection.
2. Connect a 13 mm hose to the drain connection of the control valve (); secure it by means of a clamp.
3. Run the drain hose to the drain adaptor and connect it to one of the hose barbs; secure it by means of a clamp. This drain line operates under pressure, so it may be installed higher than the appliance.
only for PF-GAC1,5 & PF-AG1,5
Picture 7
1. Connect a pipe to the 1” BSP Male drain connection of the control valve (); use an appropriate sealant.
2. Run the pipe to the sewerage system and connect it, ensuring sufficient air gap between the end of the pipe and the sewerage system. This drain line operates under pressure, so it may be installed higher than the appliance.
SERVICE VALVE (optional)
Picture 8
1. Plug the DIN plug on the connection cable of the Service Valve into the DIN socket at the back of the electronic timer head of the respective control valve ().
COMMISSIONING
Page 7
ELECTRICAL
1. Connect the appliances power cord to the transformers output.
2. Plug the transformer into an electrical outlet.
PRESSURIZING
1. Put the bypass system in 'bypass' position.
2. Make sure the electronic controller of the appliance is in service mode.
3. Open the mains water supply.
4. Open a cold treated water faucet nearby the appliance and let the water run for a few minutes until all air is purged and all foreign material that may have resulted from the installation is washed out; close the tap.
5. Gently pressurize the appliance, by putting it into service:
close the 'BYPASS' valve; open the 'OUT' valve; slowly open the 'IN' valve.
6. After 2-3 minutes, open a cold treated water faucet nearby the appliance and let the water run for a few minutes until all air is purged from the installation and the filter media is rinsed (it is normal for the rinse water to show some discoloration!); let the water run until the rinse water is clear; close the tap.
7. Check the appliance and all hydraulic connections for leaks.
ELECTRONIC CONTROL PANEL
1. Program the electronic controller.
INITIATE A REGENERATION
1. Manually initiate a regeneration, by pressing the scroll
button; the display will show:
2. Leave the appliance in this position; the count-down timer will count down to 0 sec and start a regeneration.
Regen in 10 sec
ELECTRONIC CONTROL PANEL
Page 8
Picture 9
symbol
button
function
SCROLL
to advance to the next
parameter
UP
to increase the value of the
parameter
DOWN
to decrease the value of the
parameter
POWER-UP
After power-up the display will show the installed software version for a period of 5 seconds.
POWER FAILURE
In the event of a power failure, the program will remain stored in the NOVRAM® during an undefined period, while an incorporated SuperCap will maintain the correct time of day during a period of several hours; consequently, in case of prolonged power failure, the time of day might not be maintained; if this happens, the time of day will be reset to 8:00 when the power supply is re-established, while the indication will flash, indicating that the time of day needs to be set.
When the power failure occurs during the execution of an automatic regeneration, the control valve will remain in its last position; when the power supply is re-established, the control valve will return to the service position, stay there for 60 sec. and restart a complete regeneration from the beginning.
TIMER FAILURE
In the event of a timer failure, the display will show the message:
If powering off/on the appliance doesn’t solve this problem, professional service is required.
MAINTENANCE REMINDER
Once the maintenance interval is reached, the display will intermittently show the message:
While the appliance will continue to operate normally, it is recommended to have preventive maintenance performed by a professional.
SERVICE MODE
In service mode the display shows the time of day and the number of days remaining until the next regeneration:
REGENERATION MODE
In regeneration mode the display shows the remaining regeneration time and the remaining cycle time:
The control valve can be reset to service mode at any time by pressing the scroll  button, as such manually advancing it through the regeneration cycles.
MANUAL REGENERATION
It is possible to manually initiate an immediate regeneration or a delayed regeneration (at the preprogrammed time of regeneration).
1. Press the scroll  button; the display will show:
If the control panel is left in this position, the
countdown timer will countdown to 0 sec and start an immediate regeneration.
To cancel this mode, press the scroll  button before
the countdown timer has reached 0 sec; the display will show:
If the control panel is left in this position, a delayed
regeneration will be started at the indicated
preprogrammed time of regeneration. To cancel this mode, press the scroll  button; the control panel will return to the service mode
HOLIDAY MODE
It is possible to put the appliance in holiday mode; this will prevent automatic regeneration from taking place, yet will ensure the appliance is automatically regenerated at the end of the holiday cycle.
1. Press the scroll  button repeatedly until the display
shows:
Press the up  or down button to activate the
holiday mode by setting the number of full days away
from home, or deactivate the holiday mode (OFF).
Once the control panel is back in service mode, the display will show:
The holiday mode is automatically cancelled when a
regeneration is manually initiated!
Service Required
Rgn:123 CycY:456
Maintenance Now
Regen in 10 sec
Regen @ 2:00
Holiday: OFF
8:01 Holiday
8:01 4 DAY REM
ELECTRONIC CONTROL PANEL
Page 9
PROGRAMMING INSTRUCTIONS -
BASIC SETTINGS
Before entering the programming mode, make sure that
the appliance is in the service mode.
In case no button is pressed in a period of 5 min, the
control panel will automatically return to the service mode; any changes made will NOT be saved!
1. Press the scroll  button; the display will show:
Press the up  or down button to set the
language.
2. Press the scroll  button again; the display will show:
Press the up  or down button to set the time of
day.
3. Press the scroll  button again; the display will show:
Press the up  or down button to set the number
of days between regenerations.
4. Press the scroll  button again; the display will show:
Press the up  or down button to save the settings
into the NOVRAM® and exit the programming mode.
The regeneration cycle is necessary to wash out
impurities that are captured in the filter media during the service cycle, and to prevent ‘caking’ of the filter media, which may result in an increase of pressure drop over the water filter. Typically a regeneration every 4 days should be sufficient. In case of high flow rates, excessive water usage or a high concentration of impurities in the incoming water, it may be necessary to lower the number of days between regenerations.
PROGRAMMING INSTRUCTIONS -
CONFIGURATION PARAMETERS
Before entering the programming mode, make sure that
the appliance is in the service mode.
All configuration parameters on this appliance have
been pre-programmed in the factory, to offer optimal performance in a wide range of applications and situations. Nevertheless it may be necessary or desirable to change any of these parameters, to further optimize the appliances performance or to adapt it to the specific requirements of the installation.
In case no button is pressed in a period of 5 min, the
control panel will automatically return to the service mode; any changes made will NOT be save!
1. Press the scroll  button and hold it for 5 sec until the
display shows:
2. Within 10 sec, press the up  button; the display will
show:
Press the up  or down button to set the units of
measure (Metric or US).
3. Press the scroll  button again; the display will show:
Press the up  or down button to activate the
maintenance reminder function by setting the
maintenance interval, or deactivate the maintenance
reminder function.
4. Press the scroll  button again; the display will show:
Press the up  or down button to set the length
of the regeneration cycle.
Press the scroll  button again to advance to the next
regeneration cycle.
Cycle 1
Backwash
Cycle 2
No function
Cycle 3
Fast rinse
Cycle 4
No function (PF
-
GAC1
,5 & PF
-
AG1,5)
5. Press the scroll  button again; the display will show:
Press the up  or down button to set the time of
regeneration.
6. Press the scroll  button again; the display will show:
Press the up  or down button to save the settings
into the NOVRAM® and exit the programming level.
Language:English
Set time: 8:01
Interval:4 Days
Cycle 1: XX min
System Check
Regen @ 0:00
Exit
Exit
MaintInt: 24mths
Units:Metric
MAINTENANCE
Page 10
RECOMMENDATION
Notwithstanding the reliability of the appliance, we strongly recommend to have it serviced and maintained on a regular basis by a competent and duly trained technician. He will be able to determine the appropriate maintenance interval for the appliance, depending on your specific application and the local operating conditions. The advantages of performing regular maintenance are: regular check of the local operating conditions (water
quality, pressure, etc);
regular control and adjustment of the settings of the
appliance, to guarantee it operates at maximum
efficiency; minimize the risk of unexpected break-down. Contact your dealer or installer for more information, or visit our website.
ROUTINE CHECKS
Regularly the user should perform a basic check to verify if the appliance is functioning correctly, on the basis of the following control points:
1. Check settings of electronic control panel.
2. Check water composition before/after appliance.
3. Check drain line from control valve; there shouldn’t be
any water flow (unless appliance is in regeneration).
4. Check appliance and surrounding area; there shouldn’t be
any water leakages.
BYPASSING THE APPLIANCE
Occasionally it may be necessary to put the appliance hydraulically in bypass, i.e. to isolate it from the water distribution system; f.e.:
in case of an urgent technical problem; when it is not necessary to supply treated water to the
application.
WITH FACTORY BYPASS (optional) (only for PF-GAC1 & PF-AG1)
Picture 10.a
SERVICE POSITION
= inlet valve to appliance is OPEN = outlet valve from appliance is OPEN
Picture 10.b
BYPASS POSITION
= inlet valve to appliance is CLOSED = outlet valve from appliance is CLOSED
Picture 10.c
MAINTENANCE POSITION
= inlet valve to appliance is OPEN = outlet valve from appliance is CLOSED
SANITIZING THE APPLIANCE
This appliance is manufactured from premium quality material and assembled in safe conditions to assure it is clean and sanitary. If installed and serviced correctly, this appliance will not infect or contaminate your water supply. However, as in any 'device' plumbed-in in your water distribution system, a proliferation of bacteria is possible, especially in case of 'stagnant water'. Therefore this appliance will automatically rinse the filter media periodically.
If the power supply to the appliance is disconnected for a longer period of time, we recommend, when the power supply is re-established, to manually initiate a complete regeneration.
Loading...
+ 22 hidden pages