
AGP3300-U1-D24
Installation Guide
Caution
Be sure to read the “Warning/Caution
Information” on the attached sheet
before using the product.
Package Contents
(1) GP Unit (1)
(2) English and Japanese installation
Guides (1 of each) <This Guide>
(3) Warning/Caution Information (1)
(4) Installation Gasket (1, attached to th e
GP unit)
(5) Installation Fasteners (Set of 4)
(6) Power Connector (1)
(Attached to the GP unit)
(7) USB Cable Clamp (1 port) (1)
This unit has been carefully packed, with
special attention to quality. However,
should you find anything damaged or
missing, please contact your local GP
distributor immediately.
About the Manual
For detailed information on the GP3000
series, refer to the following manuals:
• GP3000 Series Hardware Manual
• Maintenance/Troubleshooting
• Device/PLC Connection Manual
The manuals can be selected from the
help menu of GP-Pro EX or downloaded
from Pro-face Home Page.
URL
http://www.pro-face.com/otasuke/
1

Part Names and Functions
Front
Rear
B
A
D
Right sideLeft side Bottom
F
G
E
H
I
J
C
Name Description
AStatus LED
Color Indicator
Green
Red
Orange
*1 When backlight replacement or repair of the GP is
required, please contact your local GP distributor.
Operation Mode
(Drawing)
OFFLINE
ON
In operation RUN
Flashing
In operation STOP
ON When power is turned on.
Flashing
In operation Major Error
ON Backlight burnout or GP malfuction
Flashing
Logic execution mode
(when logic is enabled)
-
During software startup
*1
B Expa nsion U n i t I n t e r f a c e (EXT) Used to connect an expansion unit that can transmit data.
Lit in green when the CF Card is inserted and the cover
is closed, or when the CF Card is being accessed.
C CF Card Access LED
D Ethernet Interface (LAN)
• Do not remove or insert the CF Card when the LED
lamp is on. Doing so may damage data on the CF
Card.
10BASE-T/100BASE-TX
This interface uses an RJ-45 type modular jack
connector (8 pins).
2

E Power Connector (Socket)
F USB Host Interface (USB)
G Serial Interface (COM1)
H Serial Interface (COM2)
ICF Card Cover
J DIP Switches
Complies with USB 1.1. Uses a “TYPE-A” connector.
Power supply voltage:DC5V
Output current:500mA (max.)
The maximum communication distance: 5m
D-sub 9-pin plug type. RS232C, RS422, and RS485
are switched by software.
D-sub 9-pin socket type. RS422 and RS485 are
supported.
Located inside the CF Card Cover.
±5%,
3

General Specifications
Electrical Specifications
Input Voltage DC24V
Rated Voltage DC19.2 to 28.8V
Allowable Voltage
Drop
Power Consumption 26W (max.)
Power Supply
In-Rush Current 30A (max.)
Voltage Endurance
Insulation Resistance DC500V 10MΩ (min.) (between charging and FG terminals)
Environmental Specifications
Surrounding Air
Temperature
Storage Temperature -20 to +60°C
Ambient Humidity
Physical
Storage Humidity
Dust 0.1mg/m
Pollution Degree For use in Pollution Degree 2 environment.
Structural Specifications
Grounding
*1
Structure
Installation
Cooling Method Natural air circulation
*1 The front face of the GP unit, installed in a solid panel, has been tested using conditions equivalent to
the standards shown in the specification. Even though the GP unit’s level of resistance is equivalent to
these standards, oils that should have no effect on the GP can possibly harm the unit. This can occur in
areas where either vaporized oils are present, or where low viscosity cutting oils are allowed to adhere
to the unit for long periods of time. If the GP’s front face protection sheet becomes peeled off, these
conditions can lead to the ingress of oil into the GP and separate protection measures are suggested.
Also, if non-approved oils are present, it may cause deformation or corrosion of the front panel’s plastic
cover. Therefore, prior to installing the GP be sure to confirm the type of conditions that will be present
in the GP’s operating environment.
If the installation gasket is used for a long period of time, or if the unit and its gasket are removed from
the panel, the original level of the protection cannot be guaranteed. To maintain the original protection
level, be sure to replace the installation gasket regularly.
5ms (max.)
AC1000V 20mA for 1 minute (between charging and FG terminals)
0 to 50°C
10 to 90% RH (Wet bulb temperature: 39°C max. - no
condensation.)
10 to 90% RH (Wet bulb temperature: 39°C max. - no
condensation.)
3
and below (non-conductive levels)
Grounding resistance of 100Ω, 2mm
country’s applicable standard.
(Same for FG and SG terminals)
Rating: IP65f NEMA #250 TYPE 1
(Front surface at panel embedding)
Feature size: All-in-one
Installation configuration: Panel embedding
2
or thicker wire, or your
4