Thank you for purchasing Pro-face's AGP-3300 Series Programmable Operator Interface (Hereafter referred to as the
“AGP unit”).
Before operating your AGP unit, be sure to read this manual to familiarize yourself with the AGP unit's operation procedures and features.
NOTICE
1.Copying this manual's contents, either in whole or in part, is prohibited without the express permission of Digital
Electronics Corporation, Japan.
2.The information contained in this manual is subject to change without notice.
3.If you should you find any errors or omissions in this document, please contact Digital Electronics Corporation to
report your findings.
4.Regardless of Clause 3 above, Digital Electronics Corporation shall not be held responsible for any damages,
losses or third-party damages resulting from the use of this product.
Product names used in this manual are the trademarks / regist ered trademarks of their respective owners.
All safety-related procedures stated in this document must be followed to operate the AGP correctly and safely. Be sure to
read this and any related documents thoroughly to understand the correct operation and functions of the AGP unit.
Safety Icons
Throughout this manual, these icons provide essential safety information for AGP operation procedures requiring special
attention. These icons indicate the following levels of danger:
Indicates situations where severe bodily injury, death or major equipment damage
can occur.
Indicates situations where slight bodily injury or minor equipment damage can
occur.
Indicates actions or procedures that should NOT be performed.
Indicates actions or procedures that MUST be performed to ensure correct unit
operation.
System Design
Do not create AGP touch panel switches that could possibly endanger the safety of personnel or equipment. A malfunction of the AGP unit, its I/O unit(s), cable(s), or other related equipment can cause unexpected output signals, leading to a serious accident. Be sure to design all important machine operation
switches so they are operated via a separate control system, and not via the AGP.
Do not create AGP touch panel switches to control machine safety operations, such as an emergency
stop switch. Install these switches as separate hardware switches, otherwise severe bodily injury or equipment damage can occur.
Be sure to design your system so that a communication fault between the AGP and its host controller will
not cause equipment to malfunction. This is to prevent any possibility of bodily injury or equipment damage.
Do not use the AGP as a warning device for critical alarms that can cause serious operator injury,
machine damage or can halt system operation. Critical alarm indicators and their control/activator units
must be designed using stand-alone hardware and/or mechanical interlocks.
2
Page 4
Do not use the AGP with aircraft control devices, aerospace equipment, central trunk data transmi ssion
(communication) devices, nuclear power control devices, or medical life support equipment, due to these
devices' inherent requirements of extremely high levels of safety and reliability.
Be sure to use redundant and/or failsafe system designs to ensure adequate levels of system reliability
and safety when using the AGP with transportation vehicles (trains, cars and ships), disaster and crime
prevention devices, various types of safety equipment, non-life support related medical devices, and other
similar equipment.
After the AGP unit's backlight burns out the touch panel is still active, unlike the AGP unit's "Standby
Mode". If the operator fails to notice that the backlight is burned out and touches the panel, a potentially
dangerous machine operation error can occur. Therefore, do not create AGP unit touch panel switches
that may cause injury and/or equipment damage. If your AGP unit's backlight suddenly turns OFF, use the
following steps to determine if the backlight is actually burned out.
1) If the AGP unit's "Backlight Control" is not set and the screen has gone blank, your backlight is burned out.
2) If the AGP unit's "Backlight Control" is set to Standby Mode and the screen has gone blank, and touching the screen or performing another input operation does not cause the display to reappear, your backlight is burned out.
To prevent an accidental machine operation error, Pro-face suggests you use the AGP unit's built-in burnout detection feature. This feature will automatically detect a backlight burnout and disable the touch
screen. (factory default setting is enabled).
SEE
4.1.1 Offline Settings
Backlight Control (page4-5)
Handling
Do not modify the AGP unit. Doing so may cause a fire or an electric shock.
Do not operate the AGP in an environment where flammable gases are present, since it may cause an
explosion.
Wiring
To prevent an electric shock be sure to disconnect your AGP unit's power cord from the power supply
before wiring the AGP.
Do not use voltage beyond the AGP unit's specified range. Doing so may cause a fire or an electric shock.
Maintenance
Do not connect or disconnect Host/PLC and AGP unit communication cables while the AGP is turned ON.
Do not replace the AGP unit's battery yourself. The AGP uses a lithium battery for backing up its internal
clock data and the battery may explode if it is replaced incorrectly. When replacement is required, please
contact your local AGP distributor.
3
Page 5
Installation
Be sure all cable connectors are securely attached to the AGP unit. A loose connection may cause incorrect input or output signals.
Wiring
Be sure to ground the AGP unit's FG wire separately from other equipment FG lines. Also, be sure to use
2
a grounding resistance of 100Ω or less and a 2mm
Be sure to use only the designated torque to tighten the AGP unit's terminal block screws. If these screws
are not tightened firmly, it may cause a short-circuit, fire or incorrect unit operation.
Be sure that metal particles and wiring debris do not fall inside the AGP unit. They can cause a fire, mal-
function or incorrect unit operation.
or thicker wire, or your country's applicable standard.
Maintenance
Be sure to turn the AGP unit's CF Card ACCESS switch OFF and confirm that the ACCESS lamp is not lit
prior to inserting or removing a CF Card. Otherwise, CF Card internal data may be damaged or lost.
Do not reset or turn the AGP OFF , or insert or remove the CF Card while the AGP unit's CF Card is being
accessed. Create special application screens to perform operations like turning power OFF, resetting the
AGP or inserting or removing the CF Card.
Unit Disposal
Be sure to dispose of the AGP according to your country's industrial waste disposal standards.
General Safety Precautions
Do not press on the AGP unit's display with excessive force or with a hard object, since it can damage the
display. Also, do not press on the touch panel with a pointed object, such as the tip of a mechanical pencil
or a screwdriver, since doing so can damage the touch panel.
Do not install the AGP where the ambient temperature exceeds the specified range. Doing so may cause
a unit malfunction.
To prevent abnormally high temperatures from occurring inside the AGP, do not restrict or block the AGP
unit's rear-face ventilation slots.
Do not operate the AGP in areas where large, sudden temperature changes can occur. These changes
can cause condensation to form inside the AGP, possibly causing it to malfunction.
Do not allow water, liquids or metal fragments to enter inside the AGP unit's case, since they can cause
either a malfunction or an electric shock. The allowable pollution degre e is 2.
4
Page 6
Do not operate or store the AGP in locations where it can be exposed to direct sunlight, high temperatures, excessive dust, moisture or vibration.
Do not operate or store the AGP where chemicals evaporate, or where chemicals are present in the air.
Do not use paint thinner or organic solvents to remove dirt or oil from the AGP unit's surface. Instead, use
a soft cloth moistened with a diluted neutral detergent.
Do not use or store the AGP in areas with direct sunlight, since the sun's ultraviolet rays may cause the
LCD's quality to deteriorate.
Do not store the AGP in an area where the temperature is lower than that recommended in the AGP unit's
specifications. Doing so may cause the LCD display's liquid to congeal, which can damage the LCD. Also,
if the storage area's temperature becomes higher than the specified level, the LCD's liquid may become
isotropic, causing irreversible damage to the LCD. Therefore, only store the AGP in areas where temperatures are within the AGP unit's specifications.
After turning OFF the AGP, be sure to wait a few seconds before turning it ON again. The AGP may not
operate correctly if it is restarted too quickly.
Due to the possibility of unexpected accidents, be sure to back up the AGP unit's screen data regularly.
LCD Panel Usage Precautions
• The LCD panel's liquid contains an irritant. If the panel is damaged and any of this liquid contacts your skin, immediately rinse the area with running water for at least 15 minutes. If the liquid gets in your eyes, immediately rinse your
eyes with running water for at least 15 minutes and consult a doctor.
• The AGP unit's LCD screen may show unevenness in the brightness of certain images or at some contrast settings.
This is an LCD characteristic and not a product defect.
• The AGP unit's LCD screen pixels may contain minute black and white-colored spots. This is an LCD characteristic
and not a product defect.
• The color displayed on the AGP unit's LCD screen may appear different when seen from outside the specified viewing
angle. This is an LCD characteristic and not a product defect.
• When the same image is displayed on the AGP unit's screen for a long period, an afterimage may appear when the
image is changed. If this happens, turn off the AGP, wait 10 seconds and then restart the unit. This is an LCD characteristic and not a product defect.
• T o preven t an afterimage:
• Set the AGP unit's display OFF feature when you plan to display the same screen image for a long period of time.
• Change the screen image periodically and try to not display the same image for a long period of time.
5
Page 7
Information Symbols
This manual uses the following icons:
Indicates a warning or a product limitation. Be sure to follow the instructions given with
this icon to ensure the safe operation of the AGP.
Screen EditorIndicates the Pro-Designer software (version 4.2 or higher).
PLCAbbreviation for Programmable Logic Controller.
*1Indicates useful or important supplemental info rma ti o n .
Contains additional or useful information.
SEE
Indicates pages containing related information.
6
Page 8
AGP-3300 Series Model Names
The term “AGP-3300” Series refers to the following AGP model numbers:
The following items are included in the AGP unit’s package. Before using the AGP, please check that all items listed here
are present.
AGP Unit (1) Installation Guide (1)
Installation
Guide
Installation Fasteners (4)Installation Gasket (1)
(Attached to the AGP unit)
Power Plug (1) USB Cable Clamp (1)
(Attached to the AGP unit)
USB Holder (1)
This unit has been carefully packed, with special attention to quality. However, should you find anything damaged or
missing, please contact your local AGP distributor immediately.
7
Page 9
UL/c-UL/CSA Approval
The AGP3300-L1-D24/AGP3300-S1-D24/AGP3300-T1-D24/AGP3301-L1-D24/AGP3301-S1-D24/AGP3302-B1-D24
are UL/c-UL/CSA listed products.
UL File No.E182139
These products conform to the following standards:
UL508
Industrial Control Equipment
UL1604
Electrical Equipment for use in Class I and II, Division 2, and Class III Hazardous (classified) locations.
CAN/CSA-C22.2 No.213-M1987
Safety Standard for Information Technology and Electrical Business Equipment
CAN/CSA-C22.2 No.14-95
Industrial Control Equipment
<Cautions>
Be aware of the following items when building the AGP into an end-use product:
• The AGP unit's rear face is not approved as an enclosure. When building the AGP unit into an end-use product, be sure
to use an enclosure that satisfies standards as the end-use product's overall enclosure.
• The AGP unit must be used indoors only.
• Install and operate the AGP with its front panel facing outwards.
• If the AGP is mounted so as to cool itself naturally , be sure to install it in a vertical panel. Also, insure that the AGP is
mounted at least 100 mm away from any other adjacent structures or machine parts. If these conditions are not met, the
heat generated by the AGP unit's internal components may cause it to fail to meet UL standards.
UL1604/CSA-C22.2, No.213 - Compliance and Handling Cautions
1. Power and input/output wiring must be in accordance with Class I, Division 2 wiring methods - Article 501-4(b) of
the National Electrical Code, NFPA 70 within the United States, and in accordance with Section 18-152 of the
Canadian Electrical Code for units installed within Canada.
2. Suitable for use in Class I, Division 2, Groups A, B, C, or D Hazardous Locations.
3. WARNING: Explosion hazard -substitution of components may impair compliance to Class I, Div ision 2.
4. WARNING: Explosion hazard -when in hazardous locations, turn the power OFF before replacing or wiring modules.
5. WARNING: Explosion hazard -confirm that the power supply has been turned OFF before disconnecting equip-
ment, or confirm that the location is not subject to the risk of explosion.
6. WARNING: Explosion hazard -do not connect/disconnect equipment unless area is known to be nonhazardous.
Port is for system setup and diagnostics.
8
Page 10
CE Marking
The AGP3300-L1-D24/AGP3300-S1-D24/AGP3300-T1-D24/AGP3301-L1-D24/AGP3301-S1-D24/AGP3302-B1-D24
units are CE marked, EMC compliant products. These units also conform to EN55011 Class A, EN61000-6-2 directives.
For detailed CE marking information, please contact your local AGP distributor.
6.3 Replacing the backlight...................................................................................6-4
Index
12
Page 14
1Introduction
1. System Design
2. Accessories
This chapter describes peripheral devices that can be connected to AGP Series units.
1-1
Page 15
AGP U n it
r
e)
e)
AGP-3300 Series User Manual
1.1System Design
AGP-3300/3301 Series Units
The following diagram illustrates the standard range of items that can be connected to AGP-3300/3301 Series units.
For host controller (PLC, etc.) connection information, refer to the “Pro-Design er External Device Drivers”.
Mitsubishi PLC A, QnA,
FX Series' 2 Port Adapter II
GP070-MD11
RS-422 Cable
(Prepared by user)
(11)
(11)
(11)
(8)
(8)
(8)
(8)
Host Controller
PLC etc.
RS-485
Isolation Unit
CA3-ISO485-01
9-pin-to-25-pin
RS422 Conversion Cable
CA3-CBLCBT422-01
Siemens COM Port
Conversion Adapter
CA3-ADPSEI-01
AGP Interfaces
(1) Ethernet (10BASE-T/100BASE-TX)
(Not available with AGP-3301 Series units)
(2) USB I/F
(3) CF Card
(4) Serial Interface (COM1) (RS-232C mode)
(5) Serial Interface (COM1) (RS-422 mode)
(6) Serial Interface (COM2)
RS-422 Cable
GP230-IS11-0
GP230-IS12-0
(9)
Siemens
RS-485 Cable
(Prepared by user)
MPI Cable
(Commercial type)
(10)
PLC Interfaces
(7) RS-232C Port
(8) RS-422 Port
(9) RS-485 Port
(10) MPI Port
(11) Programming Console Port
(Not available with AGP-3301 Series units)
(2) USB I/F
(3) CF Card
(4) Serial Interface (COM1) (RS-232C mode)
USB Port
PCMCIA Slot
Personal Computer
(Commercial type)
COM Port
Screen Editor
Software
Pro-Designer
*3
(version 4.2
or higher)
*1Must be MS-DOS NECPC-PR201/PL, EPSON ESC/P24-J84(C), HP Laser Jet PCL 4 command printer
or its equivalent. Printers with only Windows drivers cannot be used, however, printers using both Windows and DOS drivers may be used. For details, please contact your printer manufacturer or sales outlet.
*2For recommended units, refer to Page 1-8.
SEE
Recommended Units (page1-8)
*3Certain types and models of PCs cannot be used.
SEE
“Pro-Designer” Online Help
1-4
Page 18
Chapter 1 Introduction
AGP Unit
e)
e)
AGP-3302 Series Units
The following diagram illustrates the standard range of items that can be connected to AGP-3302 Series units. For
host controller (PLC, etc.) connection information, refer to the “Pro-Designer External Device Drivers”.
AGP RUN Mode Peripherals
(1)
(2)
(2)
RS-232C
Isola ti o n U nit
CA3-ISO232-01
USB-to-IEEE1284
Conversion Cable
(Commercial type)
USB Cable
FP-US00 or
commercial type
US B Hub (Commercial type)
Bar- Cod e R eader
(Commercial type)
RS-232C Cable
CA3-CBL232/5M-01
Mitsubishi PLC Q-Serie s Link Cable
CA3-CBLLNKMQ-01
*2
Bar- Cod e R eader
(Commercial typ
*1
Printer
(Commercial typ
(4)
(4)
(4)
Om r o n PLC SY S MAC Link Cable
CA3-CBLSYS-01
Mitsubishi PLC Q-Series Connection Cable
CA3-CBLQ-01
9-pin-to-25-pin RS232C
Conversion Cable
CA3-CBLCBT232-01
RS-232C Cable
GP410-IS00-0
(4)
(4)
1-5
Page 19
AGP-3300 Series User Manual
(3)
COM Port
Conversion
Adapter
CA3-ADPCOM-01
Mitsubishi PLC
FX-Series Connection Cable
CA3-CBLFX/1M-01
CA3-CBLFX/5M-01
Mitsubishi PLC
A-Series Connection Cable
CA3-CBLA-01
RS-422 Cable
CA3-CBL422/5M-01
AGP RS-422 Cable
CA3-CBL422-01
AGP 2 Port
Adapter Cable
CA3-MDCB11
AGP Multi-Link Cable
CA3-CBLMLT-01
Terminal Blo ck
Conversion Adapter
CA3-ADPTRM-01
Mitsubishi PLC A, QnA ,
FX Series' 2 Port Adapter II
GP070-MD11
RS-422 Cable
(Prepared by user)
(8)
(8)
(5)
(8)
(5)
(5)
(5)
Host Controller
PLC etc.
9-pin-to-25-pin
RS422 Conversion Cable
CA3-CBLCBT422-01
Siemens COM Port
Conversion Adapter
CA3-ADPSEI-01
AGP Interfaces
(1) USB I/F
(2) Serial Interface (COM1) (RS-232C mode)
(3) Serial Interface (COM2)
RS-422 Cable
GP230-IS11-0
GP230-IS12-0
(6)
Siemens
RS-485 Cable
(Prepared by user)
MPI Cable
(Commercia l type)
(7)
PLC Interfaces
(4) RS-232C Port
(5) RS-422 Port
(6) RS-485 Port
(7) MPI Port
(8) Programming Console Port
1-6
Page 20
AGP Edit Mode Peripherals
r
AGP Unit
Chapter 1 Introduction
(1)
(2)
USB Transf er Cable
CA3-USBCB-01
PC Connection
Cable for PS
PSP-CB01
USB Port
Personal Computer
(Commercial type)
COM Port
Screen Edito
Software
Pro-Designer
*3
(version 4.2
or higher)
AGP Interfaces
(1) USB Host
(2) Serial Interface (COM1)
*1Must be MS-DOS NECPC-PR201/PL, EPSON ESC/P24-J84(C), HP Laser Jet PCL 4 command printer
or its equivalent. Printers using only W indows driv ers cannot be used, however, printers using both Windows and DOS drivers may be used. For details, please contact your printer manufacturer or sales outlet.
*2For a list of recommended units, see Page 1-8.
SEE
Recommended Units (page1-8)
*3Certain types and models of PCs cannot be used.
SEE
Pro-Designer Online Help
1-7
Page 21
AGP-3300 Series User Manual
Recommended Units
The following table lists I/O devices that have been tested and confirmed to be compatible with AGP Series
units. If you connect a device that is not listed here, be sur e to test that your AGP operates normally prior to
using it in your system.
• Recommended units are subject to change without notice.
Serial Bar Code Readers (Connected via serial interface)
ManufacturerModelTypeRemarks
Aimex CorporationBR-530RSPen
OPT ElectronicsOPT-6125-RS
Symbol
Technologies,Inc.,
Denso Co.HC36IITR
Requires separately
sold BB-60 for power.
Touch Scanner
(Read Width: 65mm)
LS1902CLaser ScannerIncludes power supply.
Touch Scanner
(Read Width: 61mm)
Requires separately
sold DC5300T for
power.
Requires separately
sold P-200 unit for
power.
Also requires separately sold KRS-423XF1K (Sanwa Supply)
for connector cable.
USB Bar Code Readers (Support HID-type keyboards)
ManufacturerModelTypeRemarks
Aimex CorporationBR-530UKPen
OPT ElectronicsOPT-6125-USB
Denso Co.HC36TU-K
Touch Scanner
(Read Width: 65mm)
Touch Scanner
(Read Width: 61mm)
Power supply not
required.
Power supply not
required.
Power supply not
required.
1-8
Page 22
1.2Accessories
All accessories listed here are produced by Digital Electronics Corporation.
Disposable, dirt-resistant sheet for the AGP
unit’s screen. (5 sheets/set) (Hard type)
Maintenance Items
Product NameModel No.Description
Installation FastenerCA3-ATFALL-01Used to install the AGP into a solid panel.
Installation Gasket (6 inch)CA3-WPG6-01
Connector CoverCA3-BUSCVR-01Protects the AGP unit’s rear face connector.
Provides dust and moisture resistance when
AGP is installed into a solid panel.
1-10
Page 24
2Specifications
1. General Specifications
2. Functional Specifications
3. Interface Specifications
4. Part Names and Functions
5. Dimensions
This chapter describes the general, functional and interface specifications of the AGP as well as its part names
and dimensions.
2-1
Page 25
AGP-3300 Series User Manual
2.1General Specifications
2.1.1Electrical
Input VoltageDC 24V
Rated VoltageDC19.2V to DC28.8V
Power
Supply
Voltage EnduranceAC500V 20mA for 1 minute
Insulation ResistanceDC500V 100MΩ (min.)
Allowable Voltage Drop5ms (max.)10ms (max.)
Allowable Ripple Ratio5% (max.)
Power Consumption26W (max.)18W (max.)
In-Rush Current30A (max.)
2.1.2Environmental
Ambient Operating
Temperature
Storage Temperature-20°C to +60°C
Ambient Humidity
Physical
Dust0.1mg/m3 max. (non-conductive levels)
AGP-3300/3301
Series
0°C to +50°C
10%RH to 90%RH
(Wet bulb temperature: 39°C max. - no conden-
sation.)
AGP-3302 Series
*1
AtmosphereFree of corrosive gasses
Atmospheric
Endurance (AGP
Operation Altitude)
Mechanical
Electrical
*1Extended use in environments where ambient operating temperature is 40°C or higher may degrade the
display quality and result in decreased contrast.
Vibration Resistance
Impact Resistance
Noise Immunity
(via noise simulator)
Electrostatic Discharge Immunity
10Hz to 57Hz 0.075mm, 57Hz to 150Hz 9.8m/s
10Hz to 57Hz 0.035mm, 57Hz to 150Hz 4.9m/s
X, Y, Z directions for 10 times (80min.)
(147m/s
6kV (complies with EN 61000-4-2 Level 3)
800hPa to 1,114hPa
(2000m max.)
IEC61131-2 compliant
When vibration is NOT continuous
When vibration is continuous
IEC 61131-2 compliant
2
, X,Y,Z directions for 3 times)
Noise Voltage: 1,200Vp-p
Pulse Duration: 1µs
Rise Time: 1ns
2
2
2-2
Page 26
2.1.3Structural
Installation
Functional grounding: Grounding resistance of 100 Ω, 2mm
Grounding
thicker wire, or your country’s applicable standard. (Same for
FG and SG terminals)
Rating: Equivalent to IP65f NEMA #250 TYPE 4X/12
Structure
Cooling
Method
*1
(Front face of installed unit)
Natural air circulation
Weight1.0 kg [2.20 lb] max. (unit only)
Chapter 2 Specifications
2
or
External
Dimensions
W167.5mm [6.60 in] x H135mm [5.32 in] x D59.5mm [2.34 in]
*1The front face of the AGP unit, installed in a solid panel, has been tested using conditions equivalent to
the standards shown in the specification. Even though the AGP unit’ s level of resistance is equivalent to
these standards, oils that should have no effect on the AGP can possibly harm the unit. This can occur in
areas where either vaporized oils are present, or where low viscosity cutting oils are allowed to adhere to
the unit for long periods of time. If the AGP’s front face protection sheet becomes peeled off, these con ditions can lead to the ingress of oil into the AGP and separate protection measures are suggested. Also,
if non-approved oils are present, it may cause deformation or corrosion of the front panel’s plastic cover .
Therefore, prior to installing the AGP be sure to confirm the type of conditions that will be present in the
AGP’s operating environment. If the installation gasket is used for a long period of time, or if the unit
and its gasket are removed from the panel, the original level of the protection cannot be guaranteed. To
maintain the original protection level, be sur e to replace the installation gasket regularly.
2-3
Page 27
AGP-3300 Series User Manual
2.2Functional Specifications
2.2.1Display
AGP-3300T
TypeTFT color LCDSTN color LCD
ResolutionW320 x H240pixels
Dot PitchW0.36mm[0.01 in] x H0.36mm[0.01 in]
Effective Display AreaW115.2mm[4.54 in] x H86.4mm[3.40 in]
Color/Shade level65,536 colors4,096 colors16 gradations
Backlight
Brightness
Adjustment
Contrast AdjustmentNot available8 levels of adjustment via touch panel
Display Service Life
50,000hrs. or more
(at 25°C and continuous operation -
Backlight Service Life
Language Fonts
Character Sizes8X8, 8X16, 16X16 and 32X32 dot fonts
Font Sizes
8x8 dots40 Char. x 30 rows
Text
8x16 dots40 Char. x 15 rows
16x16 dots20 Char. x 15 rows
32x32 dots10 Char. x 7 rows
period until backlight brightness
decreases to 50%
or backlight starts
to flicker)
When replacement is required, contact your local AGP distributor.)
• The AGP’s internal clock has a slight error. At normal operating temperatures and conditions,
with the AGP operating from its lithium battery, the degree of error is 65 seconds per month.
Variations in operating conditions and battery life can cause this error to vary from -380 to +90
seconds per month. For systems where this degree of error will be a problem, the user should be
sure to monitor this error and make adjustments when required.
4.1.2 System Settings (page4-9)
Analog typing system
Resolution: 1024 x 1024
2-5
Page 29
AGP-3300 Series User Manual
2.2.4Interfaces
AGP-3300 Series
Serial Interface
Host
Interface
Network Interface
Expansion Bus Interface
USB Interface
Memory Card Interface
COM1: RS-232C/RS-422
Asynchronous transmission
Data Length: 7 or 8 bits
Parity: none/even/odd
Stop Bits: 1 or 2
Transmission Rate: 2400bps to 115200bps
Connector: D-sub 9-pin plug
COM2: RS-422 (RS-485)
Asynchronous transmission
Data Length: 7 or 8 bits
Parity: none/even/odd
Stop Bits: 1 or 2
Transmission Rate: 2400bps to 12Mbps
Connector: D-sub 9-pin socket
Ethernet
(IEEE802, 3u, 10BASE-T/100BASE-TX)
Connector: Modular jack (RJ-45)
S-GMU bus for expansion unit (External/internal)
USB 1.1 host I/F
Connector: USB TYPE-A x 1
Compact Flash
CF Card slot (TYPE-II)
AGP-3301 Series
COM1: RS-232C/RS-422
Asynchronous transmission
Data Length: 7 or 8 bits
Parity: none/even/odd
Stop Bits: 1 or 2
Transmission Rate: 2400bps to 115200bps
Host
Interface
Expansion Bus InterfaceS-GMU bus for expansion unit (External/internal)
USB Interface
Memory Card Interface
Serial Interface
Connector: D-sub 9-pin plug
COM2: RS-422 (RS-485)
Asynchronous transmission
Data Length: 7 or 8 bits
Parity: none/even/odd
Stop Bits: 1 or 2
Transmission Rate: 2400bps to 12Mbps
Connector: D-sub 9-pin socket
USB 1.1 host I/F
Connector: USB TYPE-A x 1
Compact Flash
CF Card slot (TYPE-II)
2-6
Page 30
AGP-3302 Series
COM1: RS-232C
Asynchronous transmission
Data Length: 7 or 8 bits
Parity: none/even/odd
Stop Bits: 1 or 2
Transmission Rate: 2400bps to 115.2Kbps
Host
Interface
Expansion Bus InterfaceS-GMU bus for expansion unit (External only)
Serial Interface
Connector: D-sub 9-pin plug
COM2: RS-422
Asynchronous transmission
Data Length: 7 or 8 bits
Parity: none/even/odd
Stop Bits: 1 or 2
Transmission Rate: 2400bps to 115.2Kbps
Connector: D-sub 9-pin plug
Chapter 2 Specifications
USB Interface
USB 1.1 host I/F
Connector: USB TYPE-A x 1
2-7
Page 31
AGP-3300 Series User Manual
2.3Interface Specifications
• The AGP unit’s serial port is not isolated. When the host (PLC) unit is also not
isolated, be sure to connect the #5 SG (Signal Ground) terminal to reduce the risk
of damaging the RS-232C/RS-422 circuit.
• Inside the AGP unit, the SG (Signal Ground) and FG (Frame Ground) terminals
are connected.
• When connecting an external device to the AGP using the SG terminal, be sure
to check that no short-circuit loop is created when you setup the system.
2.3.1Serial Interfaces
AGP-3300/3301 Series
Serial Interface (COM1)
This interface is used to connect an RS-232C or RS-422 (serial)
used.
*1
cable. A D-sub 9-pin plug connector is
Pin
Arrangement
5
1
Pin
Arrangement
5
1
Pin
No.
1CDInputCarrier Detect
2RD(RXD)InputReceive Data
3SD(TXD)OutputSend Data
4ER(DTR)OutputData Terminal Ready
9
5SG-Signal Ground
6DR(DSR)InputData Set Ready
6
7RS(RTS)OutputRequest to Send
8CS(CTS)InputSend Possible
9
ShellFG-Frame Ground (Common with SG)
Pin
No.
1RDAInputReceive Data A (+)
2RDBInputReceive Data B (-)
3SDAOutputSend Data A (+)
4ERAOutputData Terminal Ready A (+)
9
5SG-Signal Ground
6CSBInputSend Possible B (-)
6
7SDBOutputSend Data B (-)
8CSAInputSend Possible A (+)
9ERBOutputData Terminal Ready B (-)
ShellFG-Frame Ground (Common with SG)
Signal
Name
CI(RI)
/VCC
Signal
Name
DirectionMeaning
Input/-
DirectionMeaning
RS-232C
Called status display/+5V±5% Output 0.25A
RS-422
*2
2-8
Page 32
Chapter 2 Specifications
AGP Connector:XM2C-0942-502LX<OMRON Co.>
Recommended cable Connector: XM2D-0901<OMRON Co.>
Recommended cable Cover:XM2S-0913<OMRON Co.>
Jack Screw: XM2Z-0073<OMRON Co.>
#4-40 inch screws are used.
*1Communication method is switched via software.
*2The RI/VCC selection for Pin #9 is switched via software. The VCC output is not protected against
overcurrent. To prevent damage or a unit malfunction, use only the rated current.
Serial Interface (COM2)
This interface is used to connect an RS-422 (RS-485) serial cable. A D-sub 9-pin socket connector is used.
Pin
Arrangement
Pin #
Signal
Name
DirectionMeaning
RS-422
1TRMRX-T ermination (Receiver side: 100 Ω)
2RDAInputReceive Data A (+)
3SDAOutputSend Data A (+)
1
5
4RS(RTS)OutputRequest for Send
6
5SG-Signal Ground
6VCC-+5V±5% Output 0.25A
9
*1
7RDBInputReceive Data B (-)
8SDBOutputSend Data B (-)
9TRMTX-T ermination (Receiver side: 100 Ω)
ShellFG-Frame Ground (Common with SG)
AGP Connector:XM3B-0942-502LX<made by OMRON Corp.>
Recommended cable Connector: XM2A-0901<made by OMRON Corp.>
Recommended cable Cover:XM2S-0913<made by OMRON Corp.>
Jack Screw: XM2Z-0073<made by OMRON Corp.>
#4-40 inch screws are used.
*1The VCC output for Pin #6 is not protected against overcurrent. To prevent damage or a unit malfunc-
tion, use only the rated current.
2-9
Page 33
AGP-3300 Series User Manual
AGP-3302 Series
Serial Interface (COM1)
This interface is used to connect an RS-232C cable. A D-sub 9-pin plug connector is used.
1CDInputCarrier Detect
2RD(RXD)InputReceive Data
3SD(TXD)OutputSend Data
4ER(DTR)OutputData Terminal Ready
9
5SG-Signal Ground
6DR(DSR)InputData Set Ready
6
7RS(RTS)OutputRequest to Send
8CS(CTS)InputSend Possible
9
ShellFG-Frame Ground (Common with SG)
Signal
Name
CI(RI)
/VCC
DirectionMeaning
Input
/-
RS-232C
Called status display/+5V±5% Output 0.25A
*1
#4-40 inch screws are used.
*1RI/VCC selection for Pin #9 is switched via software. The VCC output is not protected against overcur-
rent. To prevent damage or unit malfunctions, use only the rated current.
2-10
Page 34
Chapter 2 Specifications
Serial Interface (COM2)
This interface is used to connect an RS-422 serial cable. A D-sub 9-pin socket connector is used.
Pin
Arrangement
5
1
AGP Connector: XM2C-0942-502LX <OMRON Co.>
Recommended cable Connector : XM2D-0901<OMRON Co.>
Recommended cable Cover: XM2S-0913<OMRON Co.>
Jack Screw: XM2Z-0073<OMRON Co.>
#4-40 inch screws are used.
Pin #
1RDAInputReceive Data A (+)
2RDBInputReceive Data B (-)
3SDAOutputSend Data A (+)
4E RAOutputData Terminal Ready A (+)
9
5SG-Signal Ground
6CSBInputSend Possible B (-)
6
7SDBOutputSend Data B (-)
8CSAInputSend Possible A (+)
9ERBOutputData Terminal Ready B (-)
ShellFG-Frame Ground (Common with SG)
Signal
Name
DirectionMeaning
RS-422
2-11
Page 35
AGP-3300 Series User Manual
2.4Part Names and Functions
The following images are of an AGP-3300 Series unit.
C
A,B
A: Display
The AGP monitor screen displays the screen setup
and corresponding host (PLC) data.
B: Touch Panel
Performs any screen change operations and sends
data to the PLC.
C: Status LED
This LED indicates the AGP’s status, e.g. power
Front
Back
input, firmware RUN status or backlight condition.
LEDAGP Status
Normal operation (power is
Green (lit)
Orange (lit)
(Green + red)
Orange
(blinking)
(Green + red)
D
E
Red (lit)When power is turned ON.
Not litPower is OFF.
D: Expansion Unit Interface
Connects expansion units with communication features.
E: CF Card Access Lamp
This LED shows the status of the CF Card access.
AGP-3302 Series units are not equipped with a CF
ON.) or OFFLINE operation.
Backlight burnout is
detected.
During software startup
2-12
Card interface.
Access LampIndicates
The CF Card is inserted
Green ON
Green OFF
and the CF Card Cover
is closed. Or, the CF
Card is being accessed.
The CF Card is not
inserted or is not being
accessed.
Page 36
Chapter 2 Specifications
F
Right Side
F: Ethernet Interface (10BASE-T/100BASE-TX)
The Ethernet transmission interface conforms to
IEEE802.3u (10BASE-T/100BASE-TX). An RJ-45
type modular jack connector (8-pole) is used. The
LED turns on or off to indicate the current status.
The AGP-3301/3302 Series does not include this
interface.
LEDIndicates
Green ONData transmission available
Green OFF
Yellow ON
Yellow OFFNo data transmission
H
G: Power Plug Connector
I
Connects the power cord.
No connection or subsequent transmission failure
Data transmission is occurring.
G
Left Side
K
With CF Card Cover open
J
H: USB Host Interface
Conforms to USB1.1. ( TYPE-A conn.) Connects a
data transfer cable or USB-compatible printer.
I: Serial Interface (COM1)
AGP-3300/3301 Series units:
RS-232C/RS-422 serial interface.
AGP-3302 Series units:
RS-232C serial interface.
L
J: Serial Interface (COM2)
AGP-3300/3301 Series units:
RS-422(RS-485) serial interface.
AGP-3302 Series units:
RS-422 serial interface.
K: CF Card Cover
Covers the CF Card Slot. This cover must be closed
when accessing the CF Card.
(AGP-3302 Series units are not equipped with a CF
Card socket.)
L: CF Card Socket
Insert the CF Card in this slot.
2-13
Page 37
AGP-3300 Series User Manual
(AGP-3302 Series units are not equipped with a CF
Card socket.)M: Dip Switches
Designate the CF Card’s serial settings. Factory settings are all OFF.
(AGP-3302 Series units have no CF Card socket.)
M
ON
2
1
4
3
Dip Switches
(Factory Settings)
Dip SwitchFunctionONOFFNote
CF Card Startup Settings
1
(Controls unit startup from the
CF Card.)
Startup from CF
Card is enabled.
Startup from CF
Card is disabled.
CF Card with startup
data required.
2OFF---
*1
3
COM1 (RS-232C)
Transfer Mode Set ti ng
This setting controls the
4
forced closing of the CF Card
cover.
COM1 (RS232C) Transfer
Mode is set.
Forced close
enabled.
Operation Mode
is set.
Forced close
disabled.
-
Used when CF Card
cover is damaged.
*1Communication with a PLC is disabled when DIP switch 3 is set to ON. DIP switch setup should be
completed before the AGP unit is turned on. Be sure to set DIP switch 3 to OFF after data transmission.
2-14
Page 38
2.5Dimensions
The following dimensions apply to all AGP Series units. (AGP-3300/3301/3302)
The dimensions of the AGP-3300, AGP-3301 and AGP-3302 are the same. The following drawings show the
AGP-3300.
2.5.1AGP-3300 Series External Dimensions
Unit: mm [in.]
155.5[6.12]
Top
167.5[6.60]
5[0.20]
Chapter 2 Specifications
59.5[2.34]
135[5.32]
Front
The following dimensions are with installation fasteners attached.
Unit: mm [in.]
65[2.56]
167.5[6.60]
146[5.75]
65[2.56]
Top
5[0.20]
123[4.84]
Side
59.5[2.34]
135[5.32]
Front
50[1.97]
Bottom
Side
50[1.97]
2-15
Page 39
AGP-3300 Series User Manual
The following drawing shows the AGP-3300 Series unit with cables.
Unit: mm [in.]
AGP-3301/3302 Series units
are not equipped with an
Ethernet interface.
Left
18[0.71]
25 [0.98]
• Depending on the type of connection cable used the dimensions shown above
will change. The dimensions given here are representative values and are
Top
BackRight
29[1.14]
intended for reference only.
2-16
Page 40
2.5.2Panel Cut Dimensions
Unit: mm [in.]
Chapter 2 Specifications
2.5.3Installation Fasteners
Unit: mm [in.]
+1
156 [6.14 ]
-0
+0.04
-0
under 4-R3
-0
+0.04
-0
+1
123.5 [ 4.86 ]
16 [0.63]
M6
∅10 [0.39]
11[0.43]
16.6 [0.65]
31 [1.22]
2-17
Page 41
AGP-3300 Series User Manual
Memo
2-18
Page 42
3Installation and
Wiring
1. Installation
2. Wiring Precautions
3. Ethernet Cable Connector
4. CF Card Insertion and Removal
5. Attaching the USB Cable Clamp
3-1
Page 43
AGP-3300 Series User Manual
3.1Installation
3.1.1Installation Procedures
Follow the steps given below when installing the AGP.
Check the Installation Gasket’s Seating
It is strongly recommended that you use the installation gasket, since it absorbs vibration in addition to repelling water.
Place the AGP on a level surface with the display panel facing downward. Check that the AGP’s installation
gasket is seated securely into the gasket’s groove, which runs around the perimeter of the panel’s frame.
For the procedure for attaching the installation gasket, refer to "6.1.2 Installation Gasket Check/Replacement."
• Before installing the AGP into a cabinet or panel, check that the installation gasket is securely attached to the unit.
• A gasket which has been used for a long period of time may have scratches or
dirt on it, and could have lost much of its dust and drip resistance. Be sure to
change the gasket periodically (or when scratches or dirt become visible).
• Be sure the gasket used is model CA3-WPG6-01.
• Be sure the gasket’s seam is not inserted into any of the unit’s corners, only in the
straight sections of the groove. Inserting it into a corner may lead to its eventually
tearing.
3-2
Page 44
Chapter 3 Installation and Wiring
Creating a Panel Cut
Create the correct sized opening required to install the AGP, using the installation dimensions given.
SEE
2.5.2 Panel Cut Dimensions (page2-17)
Panel
Panel Cut
Area
• Check that the installation panel or cabinet’s surface is flat, in good condition and has no jagged
edges. Also, if desired, metal reinforcing strips can be attached to the inside of the panel, near
the Panel Cut, to increase the panel’s strength.
• Panel thickness should be from 1.6mm [0.06in.] to 5.0mm [0.2 in.]. Decide the
panel’s thickness based on the level of panel strength required.
1.6mm [0.06in.] to 5mm [0.2 in.]
• For easier maintenance, operation, and improved ventilation, be sure to install
the AGP at least 100 mm [3.94 in.] away from adjacent structures and other
equipment.
Unit:mm [in.]
100
[3.94]
100
[3.94]
100 [3.94]
100
[3.94]
100 [3.94]
100 [3.94]
100 [3.94]
3-3
Page 45
AGP-3300 Series User Manual
• Be sure that the ambient operation temperature and the ambient humidity are
within their designated ranges. (Ambient operation temperature: 0 to 50°C, Ambient humidity: 10 to 90%RH, Wet bulb temperature: 39°C max.) When installing
the AGP on the panel of a cabinet or enclosure, “Ambient operation temperature”
indicates both the panel face and cabinet or enclosure’s internal temperature.
Panel
face
• Be sure that heat from surrounding equipment does not cause the AGP to exceed
its standard operating temperature.
• When installing the AGP in a slanted panel, the panel face should not incline
more than 30°.
Cabinet
interior
30° or less
• When installing the AGP in a slanted panel, and the panel face inclines more than
30°, the ambient temperature must not exceed 40 °C. You may need to use
forced air cooling (fan, A/C) to ensure the ambient operating temperature is 40 °C
or below.
• When installing the AGP vertically, position the unit so that the Power Input Terminal Block is also vertical.
3-4
Page 46
Installing the AGP
(1) Insert the AGP into the panel cut, as
shown.
(2) Insert the installation fasteners into the
AGP’s insertion slots, at the top and bottom of the unit. (total: 4 slots)
• Insert each installation fas-
Chapter 3 Installation and Wiring
tener securely into the
slot’s recess (shaded
area).
.
(3) Insert each of the fasteners shown below.
Be sure to pull the fastener back until it is
Slots
Installation Panel
Hook
flush with the rear of the attachment hole.
3-5
Page 47
AGP-3300 Series User Manual
(4) Use a Phillips screwdriver to tighten each
fastener screw and secure the AGP in
place.
• Tightening the screws with too much force can damage the AGP unit’s plastic
case.
• The necessary torque is 0.5 N
•m.
3-6
Page 48
3.2Wiring Precautions
7mm
3.2.1Connecting the Power Cord
To avoid an electric shock, prior to connecting the AGP unit's power cord terminals to the
power terminal block, confirm that the AGP unit's power supply is completely turned OFF,
via a breaker, or similar unit.
AGP3300-L1-D24/AGP3300-S1-D24/AGP3300-T1-D24/AGP3301-L1-D24/AGP3301-S1D24/AGP3302-B1-D24 units are designed to use only DC24V input. Any other power level
can damage both the AGP and the power supply.
Since there is no power switch on the AGP unit, be sure to attach a breaker- type swit ch to
its power cord.
When the FG terminal is connected, be sure the wire is grounded.
Chapter 3 Installation and Wiring
• When the FG terminal is connected, be sure the wire is grounded. Not grounding
the AGP unit will result in excess noise and vibration.
• The SG and FG terminals are connected internally in the AGP unit.
• When connecting the SG wire to another device, be sure that the design of the
system/connection does not produce a shorting loop.
Power Cord Specifications
Power Cord Diameter0.2 to 2.5 mm
Conductor TypeSimple or Twisted Wire
Conductor Length
• If the Conductor's end (individual) wires are not twisted correctly, the end wires
2
(0.0001 to 0.0097 inch2) (24 to 12 AWG)
may either short against each other, or against an electrode.
3-7
Page 49
AGP-3300 Series User Manual
n
Power Plug Specifications
+24V
+
Insertion Directio
-0V
-
FG
FG
+
-
FGGrounding Terminal connected to the AGP.
Left Side
Power
Connector
Power Plug
Wiring
When connecting the Power Cord, use the following items when performing wiring. (Items are made
by Phoenix Contact.) *
Recommended DriverSZF 1-0.6x3.5 (1204517)
AI 0.25-6BU (3201291)
AI 0.34-8TQ (3200865)
AI 0.5-8WH (3200014)
Recommended Pin Terminals
Recommended Pin
Terminal Crimp Tool
* For details, please contact your local Phoenix Contact distributor.
AI 0.75-8GY (3200519)
AI 1-8RD (3200030)
AI 1.5-8BK (3200043)
AI 2.5-8BU (3200522)
CRIMPFOX ZA3 (1201882)
3-8
Page 50
Chapter 3 Installation and Wiring
Connecting the AGP Power Cord
When connecting the power cord, be sure to follow the procedures given below.
(1) Confirm that the AGP unit’s Power Cord is unplugged from the power supply.
(2) Remove the power plug.
(3) Strip the power cord, twist the core wire ends and connect them to the power plug.
(4) Attach the power plug to the power connector.
• Use a flat-blade screwdriver (size: 0.6 x 3.5) to tighten the terminal screws.
The torque required to tighten these screws is 0.5 to 0.6 N
• Do not solder the cable connection.
• Be sure to twist the power cords, from the closer to the power plug.
• The power supply plug MSTB2, 5/3-ST-5, 08 is made by Phoenix Contact.
•m.
3-9
Page 51
AGP-3300 Series User Manual
3.2.2Connecting the Power Supply
• When supplying power to the AGP unit, please sepa-
Main Power
Main
Power
AGP Power
Power
Input/Output
AGP
Power
Power
Input/Output
Main
Circuit
AGP Unit
Input/Output
Unit
AGP Unit
Input/Output
Power
Input/Output
Power
Operation
Unit
rate the input/output and operation unit lines, as shown.
• To increase the noise resistance quality of the power
cable, simply twist each power wire end before attaching the Ring Terminal.
• The power supply cable must not be bundled or positioned close to main circuit lines (high voltage, high
current), or input/output signal lines.
• Connect a lightning surge absorber, as shown in the
diagram, to deal with power surges.
• To avoid excess noise, make the power cable as short
as possible.
E1
AGP Unit
FG
E2
Lightening Surge
Absorber
• Be sure to ground the surge
absorber (E1) separately from
the AGP unit (E2).
• Select a surge absorber that
has a maximum circuit voltage greater than that of the
peak voltage of the power
supply.
3-10
Page 52
3.2.3Grounding
Do not use common grounding, since it can lead to an accident or machine breakdown.
Chapter 3 Installation and Wiring
(a) Exclusive Grounding (BEST)
AGP Unit
(b) Common Grounding (OK)
AGP Unit
Other
Equipment
Other
Equipment
• When supplying power to the AGP unit, be sure to separate the input/output and power lines, as shown.
• Check that the grounding
resistance is less than 100Ω.
• FG and SG terminals are
internally connected in the
AGP.
• When connecting the SG line
to another device, be sure
that the design of the system/
connection does not produce
a shorting loop.
• The grounding wire should
have a cross sectional area
greater than 2mm
the connection point as close
to the AGP unit as possible,
and make the wire as short,
as possible. When using a
long grounding wire, replace
the thin wire with a thicker
wire, and place it in a duct.
2
. Create
(c) Common Grounding (Not OK)
AGP UnitOther
3.2.4I/O Signal Line Placement
•Input and output signal lines must be separated from the power control cables for operating circuits.
•If this is not possible, use a shielded cable and connect the shield to the AGP unit’s frame.
• If exclusive grounding is not possible, use a common
connection point. [diagram (b)]
• If the equipment does not function
Equipment
properly when grounded, disconnect
the ground wire from the FG terminal.
3-11
Page 53
AGP-3300 Series User Manual
3.3Ethernet Cable Connector
Use the following drawing to locate your AGP unit’s Ethernet connector. The AGP Ethernet interface is
IEEE802.3u compatible, and transmits data at 10Mbps or 100Mbps. (The Ethernet I/F is not equipped on the
AGP3301 Series.)
Ethernet Interface (10BASE-T/100BASE-TX)
Left Face (AGP-3300 Series unit)
• It is strongly recommended that your Ethernet network is installed by a trained engineer.
• 1:1 connections using a cross cable may not be possible depending on the type of personal computer and network card you are using. Make sure to use a hub for connection.
3-12
Page 54
3.4CF Card Insertion and Removal
CF Cards can only be used with AGP-3300/3301 Series units.
When using the AGP Unit and a CF Card, observe the following precautions:
Prior to inserting or removing a CF Card, be sure to turn the AGP unit’s CF Card ACCESS
switch OFF and to confirm that the ACCESS lamp is not lit. If you do not, CF Card internal
data may be damaged or lost.
While a CF Card is being accessed, NEVER turn OFF or reset the AGP , or insert or remove
the CF Card. Prior to performing these operations, create and use a special AGP application screen that will prevent access to the CF Card.
Prior to inserting a CF Card, familiarize yourself with the CF Card’s front and rear face orientation, as well as the CF Card connector’s position. If the CF Card is not correctly positioned when it is inserted into the Multi Unit, the CF Card’s internal data and the AGP unit
may be damaged or broken.
Chapter 3 Installation and Wiring
Be sure to use only CF Cards manufactured by the Digital Electronics Corporation. The CF
Card’s internal data may be damaged when using another manufacturer’s CF Card.
Once AGP data is lost, it cannot be recovered. Since accidental data loss can occur at any
time, be sure to back up all AGP screen and CF Card data regularly.
Be sure to follow the instructions given below to prevent the CF Card’s internal data from
being destroyed or a CF Card malfunction from occurring:
• DO NOT bend the CF Card.
• DO NOT drop or strike the CF Card against another object.
• Keep the CF Card dry.
• DO NOT touch the CF Card connectors.
• DO NOT disassemble or modify the CF Card.
Inserting the CF Card
Use the following steps to insert the CF Card in the AGP.
(1) Pull the CF Card Cover frontward and then open it upward.
3-13
Page 55
AGP-3300 Series User Manual
(2) Insert the CF Card in the CF Card Slot, until the eject button is pushed forward.
(3) Close the cover. (As shown.)
(4) Confirm that the CF Card Access LED turns ON.
• The AGP cannot access the CF Card if the CF Card cover is already opened. If, however , the CF
Card Cover is opened while the AGP is accessing the CF Card, access will not be interrupted.
Removing the CF Card
Simply reverse the steps shown in the previous “Inserting CF Card” explanation. Prior to pressing the eject
button to remove the CF Card, confirm that the CF Card Access LED is turned OFF.
Eject Button
3-14
Page 56
3.4.1CF Card Handling
The CF Card has a data overwrite limit of approximately 100,000 times. Therefore, be sure to back up all CF
Card data regularly to another storage media. (100,000 times assumes the over writing of 500KB of data in
DOS format.)
T w o methods are available for backing up data. After using either method (1) or method (2), use your PC to
save your data to the CF Card.
(1) If your PC is equipped with a PC Card Slot
To view CF Card data on a personal computer, first, insert the CF Card into a CF Card Adapter.
(2) If your PC is NOT equipped with a PC Card slot
Use a commercially available PC Card Reader, or a CF Card Reader.
Chapter 3 Installation and Wiring
3-15
Page 57
AGP-3300 Series User Manual
3.5Attaching the USB Cable Clamp
Attachment
(1) Insert the USB holder into the slot in front of the AGP unit’s USB port and pull it down and forward.
1
2
(2) Pass the band of the USB cable clamp through the bridge of the USB holder.
Bridge
USB Holder
(3) Insert the USB cable into the port. Fasten the band around the plug and secure it with the clamp
Clamp
USB Holder
USB Cable
3-16
Page 58
Release
Lower the tab and lift the clamp to release the plug
Chapter 3 Installation and Wiring
Tab
Clamp
3-17
Page 59
AGP-3300 Series User Manual
Memo
3-18
Page 60
4Settings
1. Types of Settings
4-1
Page 61
AGP-3300 Series User Manual
4.1Types of Settings
The AGP unit includes the [Settings] menu to specify various items necessary to use the AGP. You can display the [Settings] menu at two times: “When the AGP starts up” or “When Pro-Designer Runtime is activated.”
• Pro-Designer Runtime must be installed. For installation instructions, refer to Pro-Desig ner Ver.
4.2 or later software’s On-line Help.
When the AGP starts up
T ouch the upper left corner of the panel (the area within 40 pixels from top and left) within 10 seconds after
the AGP starts up.
When Pro-Designer Runtime is activated
T ouch either the upper right and lower left corners, or the upper left and lower right corners of the panel in this
order within one second.
(1)
(2)
(1)
(2)
4-2
Page 62
Chapter 4 Settings
[Settings] menu
The [Settings] menu has two tabs, [Offline] and [System]. Touch the desired tab to bring up those settings.
Offline
System
4-3
Page 63
AGP-3300 Series User Manual
4.1.1Offline Settings
When any [Offline] tab switches are touched, the following dialog will appear. Touching the [OK] key will
automatically restart the AGP and the corresponding setting screen will appear.
When a selection is set that cannot be used with an AGP-3300 Series unit, the following dialog appears.
Network
The following information explains how to enter the AGP unit’s network settings.
This cannot be set AGP-3301/3302 Series units.
• After making a change to the [Network] settings, be sure to restart the AGP unit. Touching the
[Network] screen’s [OK] key will automatically restart the AGP.
• Do not specify IP addresses which are already used by other AGP units or by the
host controller.
Settin g Procedure
(1) In the [Settings] menu, touch the [Offline] tab.
(2) Touch the [Network] icon.
(3) Touch/select ([IP Address], [Subnet Mask], or [Default Gateway]) and a keypad will appear .
To uch Buzzer
4-4
Page 64
Chapter 4 Settings
The following buzzer sound settings are available. The factory setting is [When Press Touch Object].
•NoneSelecting this will turn the buzzer off.
•When Press Touch ObjectThe buzzer will only sound when a Touch Object is touched.
•Press Anywhere On PanelYou cannot use this option with the AGP units.
Setting Procedure
(1) In the [Settings] menu, touch the [Offline] tab.
(2) Touch the [Buzzer] icon.
(3) Touch/select the desired buzzer mode.
Backlight Control
Two selections (modes) are available.
•Wait
To preserve the AGP unit’s display and extend the life of the backlight, the backlight can be set to automatically turn off after a designated period of inac tivity (idle time) elapses. The factory setting for this
item is [OFF].
•Enable Touch if Backlight is Off
This setting designates if the touch panel is enabled or disabled when a backlight burnout is detected.
When this feature is set to OFF, touch panel touch input is ignored, thereby preventing touch panel operation errors. The factory setting is [OFF]. (Checkbox is not set.)
4-5
Page 65
AGP-3300 Series User Manual
• Backlight burnout detection is performed via monitoring of the backlight’ s current consumption.
As a result, certain types of backlight failures cannot be detected.
Settin g Procedure
(1) In the [Settings] menu, touch the [Offline] tab.
(2) Touch the [Backlight] icon.
(3) To automatically turn the backlight of f aft er a specified peri od of time, tou ch the [Wait] selection and set
the “idle time” period.
Self Test
Performs the AGP unit’s self test. For detail s, see 5.2 SELF TEST.
OP. Switch
(This setting is disabled with AGP-3300 Series units.)
4-6
Page 66
Chapter 4 Settings
Pro-eView
Limits the access to Pro-eV iew.This setting is disabled with AGP-3301/3302 Series units. The default setting
is [Allow access from all IP].
• Only when Pro-Designer is set to [Use Pro-eView] are these settings enabled. For details, refer to
[Pro-Designer Online Help].
•Allow access from all IP
Access is not limited. Access from all IP addresses is granted.
•Allow access only entered IP
Only access from registered IP addresses is granted and access from other IP addresses is rejected.
•Reject access only entered IP
Only access from registered IP addresses is rejected and access from other IP addresses is granted.
Setting procedure
(1) In the [Settings] menu, touch the [Offline] tab.
(2) Touch the [Pro-eView] icon.
(3) Select the type of access limitation After selecting [Allow access only entered IP] or [Re ject acce ss only
entered IP], click the [List] key to go to the [List of entered IP address] screen and specify the IP
address(es) to register.
4-7
Page 67
AGP-3300 Series User Manual
When the [Add] button is touched, the IP address input sc reen appears. Touch the appro priate fields to d isplay
a keypad and enter setting values.
• You can specify either individual IP addresses (Case 1) or a range of IP addresses (Case 2).
Case 1Case 2
Option
Specifies the power supply setting for COM1 port. Select whether or not to use pin No. 9 in COM1 port to
supply power in RUN Mode.
• When [Power Supply for COM1 Port] is set to [On] and the checking jig is
attached to COM1 port, the SIO circuit may be damaged.
Settin g procedure
(1) In the [Settings] menu, touch the [Offline] tab.
(2) Touch the [Option] icon.
(3) Touch/select the desired power supply setting for COM1 port.
4-8
Page 68
4.1.2System Settings
Stylus
Calibrates the analog touch panel.
Chapter 4 Settings
Touch center of the cross.
Touch center of the cross.
Touch center of the cross.
Touch center of the cross.
Touch center of the cross.
Touch center of the cross.
• When you touch a location not near the + mark, the input is recognized as invalid and the calibration mode will not be properly completed. If all six touch inputs are recognized as valid, the
calibration mode finishes when the upper center cross is touched.
4-9
Page 69
AGP-3300 Series User Manual
Settin g procedure
(1) In the [Settings] menu, touch the [System] tab.
(2) Touch the [Stylus] icon.
(3) Touch the exact center of each + mark displayed on the screen. Continue touching it until the + mark
moves or disappears.
(4) When the + mark appears at a different location, touch the center of it in the same way.
(5) After all six + marks have been touched, calibration is completed and the [Settings] menu rappears
again.
Date/Time
Sets the AGP unit’s date and time.
Settin g procedure
(1) In the [Settings] menu, touch the [System] tab.
(2) Touch the [Date/Time] icon.
(3) Touch/select the Date or Time field to call up a data entry keypad. Use this keypad to enter all time set-
tings.
Restart System
Restarts the AGP.
Settin g procedure
(1) In the [Settings] menu, touch the [System] tab.
(2) Touch the [Restart] icon.
(3) Touch/select the [Restart] button to restart the AGP unit.
4-10
Page 70
Chapter 4 Settings
Language Selection
Designates the language used with the [System] and [Offline] tabs and User Applications.
The System Setting screen's language selection is [0 English] and others. Languages other than English must
be first set in Pro-Designer to be displayed as selections in this dialog box.
For User Applications, select the default language specified with the Pro-Designer software.
Setting procedure
(1) In the [Settings] menu, touch the [System] tab.
(2) Touch the [Language] icon.
(3) Touch/select the desired language for the [System] and [User Application] items.
4-11
Page 71
AGP-3300 Series User Manual
Version Information
Calls up the Pro-Designer runtime version and the current project’s version and build numbers.
Settin g procedure
(1) In the [Settings] menu, touch the [System] tab.
(2) Touch the [Ver. Info] icon.
4-12
Page 72
Memory
Displays the total amount of memory available and the amount of memory currently being used.
Setting procedure
(1) In the [Settings] menu, touch the [System] tab.
(2) Touch the [Memory] icon.
Chapter 4 Settings
Brightness
Adjusts the brightness and contrast of the screen.
•Brightness
Adjust the brightness (8 levels). Tou chi ng p incre ases the ba rs to the right, making the screen brighter.
Touching q decreases the bars to the left, making the screen darker.
•Contrast
Adjust the contrast ( 8 levels).(This setting is disabled with the AGP-3300T.) Touching p increases the
bars to the right, increasing the contrast. Touching q decreases the bars to the left, reducing the contrast.
Setting procedure
(1) In the [Settings] menu, touch the [System] tab.
(2) Touch the [Brightness] icon.
(3) Adjust the brightness and/or contrast.
4-13
Page 73
AGP-3300 Series User Manual
Option
This setting can only be selected when using a monochrome display (AGP-3300L/3301L/3302B only).
Selects whether or not to reverse the black and white areas on the screen.
Settin g procedure
(1) In the [Settings] menu, touch the [System] tab.
(2) Touch the [Option] icon.
(3) Touch/select whether or not to reverse the black and white areas on the screen.
4-14
Page 74
AGP-3300 Series User Manual
Memo
4-15
Page 75
AGP-3300 Series User Manual
4-16
Page 76
5Troubleshooting
1. Troubleshooting Checklists
2. SELF TEST
This section explains how to find and correct AGP unit problems.
The AGP unit can be connected to a wide range of devices, including a host (PLC), however, this manual can
not discuss every possible device, or problem. Therefore, regarding problems not directly related to the AGP
unit, refer to that device’s manual.
5-1
Page 77
AGP-3300 Series User Manual
5.1Troubleshooting Checklists
The primary AGP unit problems that occur are:
1) The panel display is blank.
2) Connected devices cannot be used.
When a problem occurs, be sure to first read each checklist item and follow the instructions given.
If this does not solve the problem, please contact your local AGP distributor.
TOUCH PANEL
For hardware and software problems, please contact your local AGP distributor.
5-2
Page 78
5.1.1No display
Use the flowchart below when the screen does not display when powering up, or if the screen turns OFF by
itself during RUN mode.
Chapter 5 Troubleshooting
No Screen Display
Yes
Are all
Pro-Designer screens
sent to the AGP unit?
Yes
Is the
[Initial Panel ID]
set up correctly in Pro-
Designer?
Yes
Is the AGP unit’s
status LED lit?
No
Is the voltage level within
the designated range?
No
No
No
Send the screen data to the AGP unit.
Set up [Initial Panel ID] and resend the screen
data.
Use the correct voltage.
SEE
2.1.1 Electrical (page2-2)
Turn the power supply OFF.
Are the power cable
terminals correctly
connected?
Turn the power supply ON.
Yes
Yes
No
Correct the power cable connection.
SEE
3.2 Wiring Precautions (page3-7)
5-3
Page 79
AGP-3300 Series User Manual
Is the Status LED’s orange
light ON?
No
Did the above procedure correct
the problem?
Yes
No
The backlight has burned out.
SEE
If not, →Hardware problem
6.3 Replacing the backlight (page6-4)
5-4
Page 80
5.1.2No AGP/Host Communication
When the AGP cannot communicate with the host PLC, follow the flowchart below to find the cause of the
problem and the solution.
Or, if an error message displays on the screen, check the error code to find the appropriate solution.
No PLC communication
Turn the power supply OFF.
Chapter 5 Troubleshooting
Are the power cable
terminals correctly
connected?
Yes
Is the correct Device/
PLC protocol and driver
information set up in Pro-
Designer?
Yes
Is the Device/PLC
cable connected correctly?
Yes
Did the above procedure correct
the problem?
No
No
No
No
Connect the terminals correctly.
SEE
Enter the correct protocol and driver information.
Refer to the Device/PLC’s manual and correctly connect the cable.
SEE
If not, →Hardware problem
3.2 Wiring Precautions (page3-7)
3.2 Wiring Precautions (page3-7)
5-5
Page 81
AGP-3300 Series User Manual
5.2SELF TEST
The AGP unit is equipped with a number of self diagnosis features that can be used to check its System and
Interfaces for possible problems.
5.2.1SELF TEST item list
The SELF TEST items are as follows:
• Char. Pattern• Disp. Pattern• Touch Panel
• COM 1
The following pages explain each item in detail.
*1These must be prepared by the user (cable, connector, etc.).
*1
5-6
• COM 2
*1
• Video Memory
Page 82
5.2.2SELF TEST - details
This section explains the SELF TEST selections.
Char. Pattern
Character pattern check of each font (Japanese, Korean, Taiwanese, Chinese and European languages).
Checks each language's font image.
For Korean, Taiwanese and Chinese, this check is available only for the fonts which the user has downloaded.
Disp. Pattern
Used when the device contents will not display correctly to check the drawing function.
Touch Panel
Touch Panel check. Checks if each touch cell highlights when pressed.
Chapter 5 Troubleshooting
COM1, COM2
Checks the RS-232C and RS-422 SIO lines for areas where communication problems develop. T o perf orm the
check, connect an SIO cable. If all is normal, [OK] displays; if there is a problem, an error message appears.
The SIO cable’s wiring is as shown below.
AGP-3300/3301 Series Units
COM1
RS-232C mode
CD
RD
SD
ER
SG
DR
RS
CS
1
2
3
4
5
6
7
8
COM1
RS-422 mode
RDA
SDA
SDB
RDB
CSB
ERB
CSA
ERA
1
3
7
2
6
9
8
4
RDA
SDA
RDB
SDB
COM2
2
3
7
8
9 RI
5-7
Page 83
AGP-3300 Series User Manual
AGP-330 2 Series
Checks the RS-232C and RS-422 SIO lines for communication problems. To perform the check, connecting
the SIO cable is necessary. If all is normal, OK displays; if there is a problem, an error message appears.
The SIO cable wiring is as shown below.
COM1
RS-232C mode
CD
RD
SD
ER
SG
DR
RS
CS
1
2
3
4
5
6
7
8
RDA
SDA
SDB
RDB
CSB
ERB
CSA
ERA
COM2
RS-422 mode
1
3
7
2
6
9
8
4
9 RI
Video Memory
This item is used to check video memory (memory used for screen display). Use this feature when your screen
display is not correct. This result of this test will be either [OK] (no problem) or [NG] (problem).
5-8
Page 84
6Maintenance
1. Regular Cleaning
2. Periodic Check Points
3. Replacing the backlight
This chapter explains cautions and inspection criteria that will ensure trouble-free use of the AGP.
6-1
Page 85
AGP-3300 Series User Manual
6.1Regular Cleaning
6.1.1Cleaning the Display
When the surface or frame of the display become dirty, soak a soft cloth in water with a neutral deter gent,
wring the cloth tightly, and wipe the display.
• Do not use paint thinner, organic solvents, or a strong acid compound to clean the
unit.
• Do not use hard or pointed objects to operate the touch-screen panel, since it can
damage the panel surface.
6.1.2Installation Gasket Check/Replacement
The installation gasket protects the AGP and improves its water resistance.
• A gasket which has been used for a long period of time may have scratches or
dirt on it, and could have lost much of its water resistance. Be sure to change the
gasket at least once a year, or when scratches or dirt become visible.
Installation Gasket Attachment Procedure
(1) Place the AGP on a flat, level surface facing the display face downwards.
(2) Remove the gasket from the AGP.
Gasket
6-2
Page 86
Chapter 6 Maintenance
(3) Attach the new gasket to the AGP. Be sure to insert the gasket into the AGP’s groove so that the gasket’ s
groove sides are vertical.
(4) Check that the gasket is attached correctly to the AGP.
• The gasket must be inserted correctly into the groove for the AGP’s moisture
resistance to be equivalent to IP65f.
• Be sure the gasket’s seam is not inserted into any of the unit’s corners, only in the
straight sections of the groove. Inserting it into a corner may lead to its eventually
tearing.
• The upper surface of the gasket should protrude approximately 2 mm out from
the groove. Be sure to check that the gasket is correctly inserted before installing
the AGP into a panel.
• To ensure stable resistance against dust and moisture, insert the gasket so that
the seam is at the bottom of the AGP unit.
Unit:mm [in.]
2.0 [0.08]
Seam
6-3
Page 87
AGP-3300 Series User Manual
6.2Periodic Check Points
T o keep your AGP unit in its best condition, please inspect the following points periodically.
AGP Operation Environment
•Is the operating temperature within the allowable range (0°C to 50°C)?
•Is the operating humidity within the specified range (10%RH to 90%RH, dry bulb temperature of 39°C or
less)?
•Is the operating atmosphere free of corrosive gasses?
Electrical Specifications
•Is the input voltage appropriate?
(DC19.2V to DC28.8V)
Related Items
•Are all power cords and cables connected properly? Have any become loose?
•Are all mounting brackets holding the unit securely?
•Are there many scratches or traces of dirt on the installation gasket?
6.3Replacing the backlight
The AGP’s backlight cannot be replaced by the user.
When the backlight needs to be replaced, please contact your local AGP distributor.