13
Quick Reference Guide: Mode 4
PCS 3000 ULTRA FLOW
Troubleshooting
If you have a problem with the controller, try these
troubleshooting tips. If they don’t solve the problem,
call your PCS sales and service representative.
Controller Display Problems
Controller won’t turn on.
Controller Version 076-03 never sleeps. Display
should never be blank while controller is on.
1Turn power switch off and on. See page 3.
If display remains blank, go to step 2.
2 Check fuse. See page 15.
3 Check battery and wire connection. See page 15.
4 Check solar panel. See page 15.
Controller’s display is blank.
See above: “Controller won’t turn on.”
Controller’s display is scrambled.
Static electricity may have made controller lose its
place in program cycle.
● Reset controller: Turn power switch off and on.
Controller’s display shows Xs and Os.
See above: “Controller’s display is scrambled.”
Program Cycle Problems
Controller won’t run program cycle.
1 Check HIGH LINE CLOSE PRESSURE: SET 14.
Make sure pressure setting is above well’s:
▪ Expected casing peak pressure
▪ Normal high line pressure
2 Check calibration on transducers. Controller’s
display must show values for both casing and line
pressure. If necessary, recalibrate transducers. See
“Calibrating the Transducers” on page 7.
3 Check battery and wire connection. See page 15.
If battery voltage is low, controller closes motor
valve and shuts-in.
4 Check solenoid (shift valve). See page 15.
5 Check gas supply pressure to motor valve.
Recommended supply pressure is 35 psi. If supply
pressure is too low, it will not open motor valve.
Check filter and regulator(s) for debris and ice.
Controller won’t open motor valve.
See previous problem: “Controller won’t run program
cycle.”
CLOSE time goes directly to DELAY time (SALES).
Check controller’s Plunger Travel Time Reports.
● READ 06. If display shows PLT-0 A 00:00:00,
controller went through opening and closing part
of program even though plunger did not arrive.
Test 1: Check controller by disconnecting sensor.
● See page 15.
Test 2: Check plunger.
1 Check whether plunger is stuck in lubricator.
2 If plunger is not stuck in lubricator, go to Test 3.
Test 3: Look for wellhead electrical current.
1 Remove sensor from wellhead.
2Press OPEN. Controller should count down OPEN
time.
3 Hold sensor in your hand, and move steel wrench
through sensor band.
▪ If controller goes to DELAY time (SALES),
problem may be wellhead electrical current.
Go to step 4.
▪ If controller does not go to DELAY time (SALES),
problem should be sensor or sensor wire. Call
PCS sales and service representative.
4Wrap electrical tape on wellhead at location of
sensor to isolate it from possible wellhead electrical
current.
5 If electrical tape does not fix problem:
▪ Sensor or sensor wire may be defective, or
▪ Well may need a two-wire, 9 volt sensor or a
cathodic (PCS black lead) sensor.
Call PCS sales and service representative.
Short-term fix for sensor problem: Use CASING DROP
PRESSURE feature (see page 11).